PowerSupplyState  
INTEGER statePowerOn(1), statePowerOff(2), powerNotInstaled(9999)    

SerialPortSpeed  
INTEGER speed300bps(300), speed600bps(600), speed1200bps(1200), speed2400bps(2400), speed4800bps(4800), speed9600bps(9600), speed19200bps(19200), speed38400bps(38400), speed57600bps(57600), speed115200bps(115200), speed230400bps(230400), speed460800bps(460800)    

SerialPortSignalState  
INTEGER up(1), down(2)    

SerialPortPinOut  
INTEGER cyclades(1), cisco(2), rs422(3), rs485(4), auto(5)    

AcsActiveSessionsTableEntry  
SEQUENCE    
  acsActiveSessionsTableIndex InterfaceIndexOrZero
  acsActiveSessionsTableUser DisplayString
  acsActiveSessionsTableGroup DisplayString
  acsActiveSessionsTableType DisplayString
  acsActiveSessionsTableConnection DisplayString
  acsActiveSessionsTableSessionTime DisplayString
  acsActiveSessionsTableFrom DisplayString
  acsActiveSessionsTableKill INTEGER

AcsSerialPortTableEntry  
SEQUENCE    
  acsSerialPortTableNumber Integer32
  acsSerialPortTableDeviceName DisplayString
  acsSerialPortTableStatus INTEGER
  acsSerialPortTableName DisplayString
  acsSerialPortTableProfile INTEGER
  acsSerialPortTablePinOut SerialPortPinOut
  acsSerialPortTableComSpeed SerialPortSpeed
  acsSerialPortTableComParity INTEGER
  acsSerialPortTableComDataSize Integer32
  acsSerialPortTableComStopBits Integer32
  acsSerialPortTableComFlowControl INTEGER
  acsSerialPortTableSignalStateDTR SerialPortSignalState
  acsSerialPortTableSignalStateDCD SerialPortSignalState
  acsSerialPortTableSignalStateRTS SerialPortSignalState
  acsSerialPortTableSignalStateCTS SerialPortSignalState
  acsSerialPortTableTxBytes Integer32
  acsSerialPortTableRxBytes Integer32
  acsSerialPortTableFrameError Integer32
  acsSerialPortTableParityError Integer32
  acsSerialPortTableBreak Integer32
  acsSerialPortTableOverrun Integer32

AcsPowerMgmtSerialTableEntry  
SEQUENCE    
  acsPowerMgmtSerialTableIndex InterfaceIndex
  acsPowerMgmtSerialTablePortNumber Integer32
  acsPowerMgmtSerialTableDeviceName DisplayString
  acsPowerMgmtSerialTableNumberPDUs Integer32
  acsPowerMgmtSerialTableNumberUPS Integer32

AcsPowerMgmtPDUTableEntry  
SEQUENCE    
  acsPowerMgmtPDUTablePortNumber InterfaceIndex
  acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero
  acsPowerMgmtPDUTablePduId DisplayString
  acsPowerMgmtPDUTablePortName DisplayString
  acsPowerMgmtPDUTableModel DisplayString
  acsPowerMgmtPDUTableVendor DisplayString
  acsPowerMgmtPDUTableFirmwareVersion DisplayString
  acsPowerMgmtPDUTableNumberOfOutlets Integer32
  acsPowerMgmtPDUTableCurrentNOS Integer32
  acsPowerMgmtPDUTableCurrent1Value Integer32
  acsPowerMgmtPDUTableCurrent1Max Integer32
  acsPowerMgmtPDUTableCurrent2Value Integer32
  acsPowerMgmtPDUTableCurrent2Max Integer32
  acsPowerMgmtPDUTableCurrent3Value Integer32
  acsPowerMgmtPDUTableCurrent3Max Integer32
  acsPowerMgmtPDUTableTemperatureNOS Integer32
  acsPowerMgmtPDUTableTemperature1Value Integer32
  acsPowerMgmtPDUTableTemperature1Max Integer32
  acsPowerMgmtPDUTableTemperature2Value Integer32
  acsPowerMgmtPDUTableTemperature2Max Integer32
  acsPowerMgmtPDUTableTemperature3Value Integer32
  acsPowerMgmtPDUTableTemperature3Max Integer32
  acsPowerMgmtPDUTableHumidityNOS Integer32
  acsPowerMgmtPDUTableHumidity1Value Integer32
  acsPowerMgmtPDUTableHumidity1Max Integer32
  acsPowerMgmtPDUTableHumidity2Value Integer32
  acsPowerMgmtPDUTableHumidity2Max Integer32
  acsPowerMgmtPDUTableHumidity3Value Integer32
  acsPowerMgmtPDUTableHumidity3Max Integer32
  acsPowerMgmtPDUTableVoltageNOS Integer32
  acsPowerMgmtPDUTableVoltage1Value Integer32
  acsPowerMgmtPDUTableVoltage1Max Integer32
  acsPowerMgmtPDUTableVoltage2Value Integer32
  acsPowerMgmtPDUTableVoltage2Max Integer32
  acsPowerMgmtPDUTableVoltage3Value Integer32
  acsPowerMgmtPDUTableVoltage3Max Integer32
  acsPowerMgmtPDUTableNumberOfPhases Integer32
  acsPowerMgmtPDUTableNumberOfBanks Integer32
  acsPowerMgmtPDUTableCurrentValue Integer32
  acsPowerMgmtPDUTableCurrentMax Integer32
  acsPowerMgmtPDUTableCurrentMin Integer32
  acsPowerMgmtPDUTableCurrentAvg Integer32
  acsPowerMgmtPDUTableCurrentReset INTEGER
  acsPowerMgmtPDUTableVoltageType INTEGER
  acsPowerMgmtPDUTableVoltageValue Integer32
  acsPowerMgmtPDUTableVoltageMax Integer32
  acsPowerMgmtPDUTableVoltageMin Integer32
  acsPowerMgmtPDUTableVoltageAvg Integer32
  acsPowerMgmtPDUTableVoltageReset INTEGER
  acsPowerMgmtPDUTablePowerType INTEGER
  acsPowerMgmtPDUTablePowerValue Integer32
  acsPowerMgmtPDUTablePowerMax Integer32
  acsPowerMgmtPDUTablePowerMin Integer32
  acsPowerMgmtPDUTablePowerAvg Integer32
  acsPowerMgmtPDUTablePowerReset INTEGER
  acsPowerMgmtPDUTablePowerFactorType INTEGER
  acsPowerMgmtPDUTablePowerFactorValue Integer32
  acsPowerMgmtPDUTablePowerFactorMax Integer32
  acsPowerMgmtPDUTablePowerFactorMin Integer32
  acsPowerMgmtPDUTablePowerFactorAvg Integer32
  acsPowerMgmtPDUTablePowerFactorReset INTEGER
  acsPowerMgmtPDUTableAlarm INTEGER
  acsPowerMgmtPDUTableEnvSensors Integer32

AcsPowerMgmtOutletsTableEntry  
SEQUENCE    
  acsPowerMgmtOutletsTablePortNumber InterfaceIndex
  acsPowerMgmtOutletsTablePduNumber InterfaceIndex
  acsPowerMgmtOutletsTableNumber InterfaceIndex
  acsPowerMgmtOutletsTableName DisplayString
  acsPowerMgmtOutletsTableStatus INTEGER
  acsPowerMgmtOutletsTablePowerControl INTEGER
  acsPowerMgmtOutletsTablePortName DisplayString
  acsPowerMgmtOutletsTablePduId DisplayString

AcsPowerMgmtGroupTableEntry  
SEQUENCE    
  acsPowerMgmtGroupTableIndex InterfaceIndexOrZero
  acsPowerMgmtGroupTableName DisplayString
  acsPowerMgmtGroupTableStatus INTEGER
  acsPowerMgmtGroupTablePowerControl INTEGER

AcsPowerMgmtPhasesTableEntry  
SEQUENCE    
  acsPowerMgmtPhasesTablePortNumber InterfaceIndex
  acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero
  acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero
  acsPowerMgmtPhasesTablePhaseName DisplayString
  acsPowerMgmtPhasesTablePduId DisplayString
  acsPowerMgmtPhasesTablePortName DisplayString
  acsPowerMgmtPhasesTableCurrentValue Integer32
  acsPowerMgmtPhasesTableCurrentMax Integer32
  acsPowerMgmtPhasesTableCurrentMin Integer32
  acsPowerMgmtPhasesTableCurrentAvg Integer32
  acsPowerMgmtPhasesTableCurrentReset INTEGER
  acsPowerMgmtPhasesTableVoltageType INTEGER
  acsPowerMgmtPhasesTableVoltageValue Integer32
  acsPowerMgmtPhasesTableVoltageMax Integer32
  acsPowerMgmtPhasesTableVoltageMin Integer32
  acsPowerMgmtPhasesTableVoltageAvg Integer32
  acsPowerMgmtPhasesTableVoltageReset INTEGER
  acsPowerMgmtPhasesTablePowerType INTEGER
  acsPowerMgmtPhasesTablePowerValue Integer32
  acsPowerMgmtPhasesTablePowerMax Integer32
  acsPowerMgmtPhasesTablePowerMin Integer32
  acsPowerMgmtPhasesTablePowerAvg Integer32
  acsPowerMgmtPhasesTablePowerReset INTEGER
  acsPowerMgmtPhasesTablePowerFactorType INTEGER
  acsPowerMgmtPhasesTablePowerFactorValue Integer32
  acsPowerMgmtPhasesTablePowerFactorMax Integer32
  acsPowerMgmtPhasesTablePowerFactorMin Integer32
  acsPowerMgmtPhasesTablePowerFactorAvg Integer32
  acsPowerMgmtPhasesTablePowerFactorReset INTEGER
  acsPowerMgmtPhasesTableAlarm INTEGER

AcsPowerMgmtBanksTableEntry  
SEQUENCE    
  acsPowerMgmtBanksTablePortNumber InterfaceIndex
  acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero
  acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero
  acsPowerMgmtBanksTableBankName DisplayString
  acsPowerMgmtBanksTablePduId DisplayString
  acsPowerMgmtBanksTablePortName DisplayString
  acsPowerMgmtBanksTableCurrentValue Integer32
  acsPowerMgmtBanksTableCurrentMax Integer32
  acsPowerMgmtBanksTableCurrentMin Integer32
  acsPowerMgmtBanksTableCurrentAvg Integer32
  acsPowerMgmtBanksTableCurrentReset INTEGER
  acsPowerMgmtBanksTableVoltageType INTEGER
  acsPowerMgmtBanksTableVoltageValue Integer32
  acsPowerMgmtBanksTableVoltageMax Integer32
  acsPowerMgmtBanksTableVoltageMin Integer32
  acsPowerMgmtBanksTableVoltageAvg Integer32
  acsPowerMgmtBanksTableVoltageReset INTEGER
  acsPowerMgmtBanksTablePowerType INTEGER
  acsPowerMgmtBanksTablePowerValue Integer32
  acsPowerMgmtBanksTablePowerMax Integer32
  acsPowerMgmtBanksTablePowerMin Integer32
  acsPowerMgmtBanksTablePowerAvg Integer32
  acsPowerMgmtBanksTablePowerReset INTEGER
  acsPowerMgmtBanksTablePowerFactorType INTEGER
  acsPowerMgmtBanksTablePowerFactorValue Integer32
  acsPowerMgmtBanksTablePowerFactorMax Integer32
  acsPowerMgmtBanksTablePowerFactorMin Integer32
  acsPowerMgmtBanksTablePowerFactorAvg Integer32
  acsPowerMgmtBanksTablePowerFactorReset INTEGER
  acsPowerMgmtBanksTableAlarm INTEGER

AcsPowerMgmtEnvMonTableEntry  
SEQUENCE    
  acsPowerMgmtEnvMonTablePortNumber InterfaceIndex
  acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero
  acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero
  acsPowerMgmtEnvMonTableName DisplayString
  acsPowerMgmtEnvMonTablePduId DisplayString
  acsPowerMgmtEnvMonTablePortName DisplayString
  acsPowerMgmtEnvMonTableType INTEGER
  acsPowerMgmtEnvMonTableStatus INTEGER
  acsPowerMgmtEnvMonTableValue Integer32
  acsPowerMgmtEnvMonTableMaxValue Integer32

AcsPowerMgmtOutElecMonTableEntry  
SEQUENCE    
  acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex
  acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex
  acsPowerMgmtOutElecMonTableNumber InterfaceIndex
  acsPowerMgmtOutElecMonTableCurrentValue Integer32
  acsPowerMgmtOutElecMonTableCurrentMax Integer32
  acsPowerMgmtOutElecMonTableCurrentMin Integer32
  acsPowerMgmtOutElecMonTableCurrentAvg Integer32
  acsPowerMgmtOutElecMonTableCurrentReset INTEGER
  acsPowerMgmtOutElecMonTablePowerValue Integer32
  acsPowerMgmtOutElecMonTablePowerMax Integer32
  acsPowerMgmtOutElecMonTablePowerMin Integer32
  acsPowerMgmtOutElecMonTablePowerAvg Integer32
  acsPowerMgmtOutElecMonTablePowerReset INTEGER
  acsPowerMgmtOutElecMonTableVoltageValue Integer32
  acsPowerMgmtOutElecMonTableVoltageMax Integer32
  acsPowerMgmtOutElecMonTableVoltageMin Integer32
  acsPowerMgmtOutElecMonTableVoltageAvg Integer32
  acsPowerMgmtOutElecMonTableVoltageReset INTEGER
  acsPowerMgmtOutElecMonTablePowerFactorValue Integer32
  acsPowerMgmtOutElecMonTablePowerFactorMax Integer32
  acsPowerMgmtOutElecMonTablePowerFactorMin Integer32
  acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32
  acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER
  acsPowerMgmtOutElecMonTableAlarm INTEGER

AcsPowerMgmtUPSTableEntry  
SEQUENCE    
  acsPowerMgmtUPSTablePortNumber InterfaceIndex
  acsPowerMgmtUPSTableUpsIndex InterfaceIndexOrZero
  acsPowerMgmtUPSTableUpsId DisplayString
  acsPowerMgmtUPSTablePortName DisplayString
  acsPowerMgmtUPSTableModel DisplayString
  acsPowerMgmtUPSTableVendor DisplayString
  acsPowerMgmtUPSTableFirmwareVersion DisplayString
  acsPowerMgmtUPSTableAgentFirmwareVersion DisplayString
  acsPowerMgmtUPSTableSystemStatus DisplayString
  acsPowerMgmtUPSTableInputBlackOutCount Integer32
  acsPowerMgmtUPSTableInputBrownOutCount Integer32
  acsPowerMgmtUPSTableInletAirTemperature DisplayString
  acsPowerMgmtUPSTableNumberOutletGroups Integer32
  acsPowerMgmtUPSTableUPSSerialNumber DisplayString
  acsPowerMgmtUPSTableUPSManufactureDate DisplayString
  acsPowerMgmtUPSTableAutoRestartDelay Integer32
  acsPowerMgmtUPSTableAutoRestartControl INTEGER
  acsPowerMgmtUPSTableAudibleAlarmControl INTEGER
  acsPowerMgmtUPSTableSilenceAlarm Integer32
  acsPowerMgmtUPSTableInverterState DisplayString
  acsPowerMgmtUPSTableDCConverterStatus DisplayString
  acsPowerMgmtUPSTableShutdownReason DisplayString
  acsPowerMgmtUPSTableUPSTopology DisplayString
  acsPowerMgmtUPSTableBypassInverterInputConfig DisplayString

AcsPowerMgmtUPSInputTableEntry  
SEQUENCE    
  acsPowerMgmtUPSInputTablePortNumber InterfaceIndex
  acsPowerMgmtUPSInputTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSInputTableFrequency DisplayString
  acsPowerMgmtUPSInputTableRMSVoltageL1N DisplayString
  acsPowerMgmtUPSInputTableRMSVoltageL1L2 DisplayString
  acsPowerMgmtUPSInputTableRMSVoltageL2N DisplayString
  acsPowerMgmtUPSInputTableRMSCurrentL1 DisplayString
  acsPowerMgmtUPSInputTableRMSCurrentL2 DisplayString
  acsPowerMgmtUPSInputTableMaxVoltageL1N DisplayString
  acsPowerMgmtUPSInputTableMinVoltageL1N DisplayString
  acsPowerMgmtUPSInputTableMaxVoltageL2N DisplayString
  acsPowerMgmtUPSInputTableMinVoltageL2N DisplayString
  acsPowerMgmtUPSInputTableNominalVoltage DisplayString
  acsPowerMgmtUPSInputTableNominalFrequency DisplayString
  acsPowerMgmtUPSInputTableNominalCurrent DisplayString

AcsPowerMgmtUPSBypassTableEntry  
SEQUENCE    
  acsPowerMgmtUPSBypassTablePortNumber InterfaceIndex
  acsPowerMgmtUPSBypassTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSBypassTableRMSVoltageL1N DisplayString
  acsPowerMgmtUPSBypassTableRMSVoltageL1L2 DisplayString
  acsPowerMgmtUPSBypassTableRMSVoltageL2N DisplayString
  acsPowerMgmtUPSBypassTableRMSCurrent DisplayString
  acsPowerMgmtUPSBypassTableRMSCurrentL2 DisplayString
  acsPowerMgmtUPSBypassTableInputFrequency DisplayString
  acsPowerMgmtUPSBypassTableNominalVoltage DisplayString

AcsPowerMgmtUPSBatteryTableEntry  
SEQUENCE    
  acsPowerMgmtUPSBatteryTablePortNumber InterfaceIndex
  acsPowerMgmtUPSBatteryTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSBatteryTableDCBusVoltage DisplayString
  acsPowerMgmtUPSBatteryTableTimeRemaining DisplayString
  acsPowerMgmtUPSBatteryTablePercentageCharge DisplayString
  acsPowerMgmtUPSBatteryTableChargeStatus DisplayString
  acsPowerMgmtUPSBatteryTableLowBatteryWarningTime INTEGER
  acsPowerMgmtUPSBatteryTableTestResult DisplayString
  acsPowerMgmtUPSBatteryTableDCBusNominalVoltage DisplayString
  acsPowerMgmtUPSBatteryTableNominalBatteryCapacity DisplayString
  acsPowerMgmtUPSBatteryTableBatteryFloatVoltage DisplayString
  acsPowerMgmtUPSBatteryTableBatteryCabinetType DisplayString
  acsPowerMgmtUPSBatteryTableBatteryNumberOfEBC DisplayString
  acsPowerMgmtUPSBatteryTableBatteryRating DisplayString
  acsPowerMgmtUPSBatteryTableBatteryDischargeTime DisplayString
  acsPowerMgmtUPSBatteryTableBatteryChargeCompensating DisplayString
  acsPowerMgmtUPSBatteryTableBatteryChargerState DisplayString
  acsPowerMgmtUPSBatteryTableStartBatteryTest INTEGER
  acsPowerMgmtUPSBatteryTableBatteryStatus DisplayString

AcsPowerMgmtUPSOutputTableEntry  
SEQUENCE    
  acsPowerMgmtUPSOutputTablePortNumber InterfaceIndex
  acsPowerMgmtUPSOutputTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSOutputTableApparentPower DisplayString
  acsPowerMgmtUPSOutputTableFrequency DisplayString
  acsPowerMgmtUPSOutputTablePercentPower DisplayString
  acsPowerMgmtUPSOutputTablePercentPowerL1 DisplayString
  acsPowerMgmtUPSOutputTablePercentPowerL2 DisplayString
  acsPowerMgmtUPSOutputTablePower DisplayString
  acsPowerMgmtUPSOutputTableRMSCurrentL1 DisplayString
  acsPowerMgmtUPSOutputTableRMSCurrentL2 DisplayString
  acsPowerMgmtUPSOutputTableRMSVoltageL1N DisplayString
  acsPowerMgmtUPSOutputTableRMSVoltageL2N DisplayString
  acsPowerMgmtUPSOutputTableRMSVoltageL1L2 DisplayString
  acsPowerMgmtUPSOutputOffDelay INTEGER
  acsPowerMgmtUPSOutputOnDelay INTEGER
  acsPowerMgmtUPSOutputCycleDelay INTEGER
  acsPowerMgmtUPSOutputTableMaxVoltageL1 DisplayString
  acsPowerMgmtUPSOutputTableMinVoltageL1 DisplayString
  acsPowerMgmtUPSOutputTableMaxVoltageL2 DisplayString
  acsPowerMgmtUPSOutputTableMinVoltageL2 DisplayString
  acsPowerMgmtUPSOutputTableNominalVoltage DisplayString
  acsPowerMgmtUPSOutputTablePowerNominalFrequency DisplayString
  acsPowerMgmtUPSOutputTablePowerApparentPowerRating DisplayString
  acsPowerMgmtUPSOutputTablePowerNominalPowerFactor DisplayString
  acsPowerMgmtUPSOutputTablePowerPowerFactorCorrection DisplayString
  acsPowerMgmtUPSOutputTablePowerL1 DisplayString
  acsPowerMgmtUPSOutputTablePowerL2 DisplayString
  acsPowerMgmtUPSOutputTableApparentPowerL1 DisplayString
  acsPowerMgmtUPSOutputTableApparentPowerL2 DisplayString

AcsPowerMgmtUPSEcoModeTableEntry  
SEQUENCE    
  acsPowerMgmtUPSEcoModeTablePortNumber InterfaceIndex
  acsPowerMgmtUPSEcoModeTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSEcoModeTableStatus DisplayString
  acsPowerMgmtUPSEcoModeTableStateControl INTEGER

AcsPowerMgmtUPSOutletGroupTableEntry  
SEQUENCE    
  acsPowerMgmtUPSOutletGroupTablePortNumber InterfaceIndex
  acsPowerMgmtUPSOutletGroupTableUpsIndex InterfaceIndex
  acsPowerMgmtUPSOutletGroupTableNumber InterfaceIndex
  acsPowerMgmtUPSOutletGroupTableLabel DisplayString
  acsPowerMgmtUPSOutletGroupTableState DisplayString
  acsPowerMgmtUPSOutletGroupTablePowerControl INTEGER

Defined Values

acs 1.3.6.1.4.1.10418.26
This module defines the MIB extensions to ACS80xx products.
MODULE-IDENTITY    

acsProducts 1.3.6.1.4.1.10418.26.1
OBJECT IDENTIFIER    

acsManagement 1.3.6.1.4.1.10418.26.2
OBJECT IDENTIFIER    

acs8048 1.3.6.1.4.1.10418.26.1.1
OBJECT IDENTIFIER    

acs8032 1.3.6.1.4.1.10418.26.1.2
OBJECT IDENTIFIER    

acs8016 1.3.6.1.4.1.10418.26.1.3
OBJECT IDENTIFIER    

acs8008 1.3.6.1.4.1.10418.26.1.4
OBJECT IDENTIFIER    

acs808 1.3.6.1.4.1.10418.26.1.5
OBJECT IDENTIFIER    

acs804 1.3.6.1.4.1.10418.26.1.6
OBJECT IDENTIFIER    

acs802 1.3.6.1.4.1.10418.26.1.7
OBJECT IDENTIFIER    

acsAppliance 1.3.6.1.4.1.10418.26.2.1
OBJECT IDENTIFIER    

acsSessions 1.3.6.1.4.1.10418.26.2.2
OBJECT IDENTIFIER    

acsSerialPort 1.3.6.1.4.1.10418.26.2.3
OBJECT IDENTIFIER    

acsPowerMgmt 1.3.6.1.4.1.10418.26.2.5
OBJECT IDENTIFIER    

acsTrapObject 1.3.6.1.4.1.10418.26.2.6
OBJECT IDENTIFIER    

acsHostName 1.3.6.1.4.1.10418.26.2.1.1
The appliance name
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsProductModel 1.3.6.1.4.1.10418.26.2.1.2
The appliance product model
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

acsPartNumber 1.3.6.1.4.1.10418.26.2.1.3
The part number of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsSerialNumber 1.3.6.1.4.1.10418.26.2.1.4
The serial number of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsEIDNumber 1.3.6.1.4.1.10418.26.2.1.5
The electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsBootcodeVersion 1.3.6.1.4.1.10418.26.2.1.6
The version of the bootcode of this appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsFirmwareVersion 1.3.6.1.4.1.10418.26.2.1.7
The version of the firmware of this appliance.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsPowerSupply 1.3.6.1.4.1.10418.26.2.1.8
It gives information about Power Supply of this appliance
Status: current Access: read-only
OBJECT-IDENTITY    

acsPowerSupplyNumber 1.3.6.1.4.1.10418.26.2.1.8.1
Number of the power supplies of this appliance
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerSupplyStatePw1 1.3.6.1.4.1.10418.26.2.1.8.2
State of the first power supply
Status: current Access: read-only
OBJECT-TYPE    
  PowerSupplyState  

acsPowerSupplyStatePw2 1.3.6.1.4.1.10418.26.2.1.8.3
State of the second power supply
Status: current Access: read-only
OBJECT-TYPE    
  PowerSupplyState  

acsReboot 1.3.6.1.4.1.10418.26.2.1.9
A set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately reboots.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reboot(2)  

acsActiveSessionsNumberOfSession 1.3.6.1.4.1.10418.26.2.2.1
Number of active sessions.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsActiveSessionsTable 1.3.6.1.4.1.10418.26.2.2.2
This table contains the list of active sessions.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsActiveSessionsTableEntry

acsActiveSessionsTableEntry 1.3.6.1.4.1.10418.26.2.2.2.1
each entry has the information about the active session
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsActiveSessionsTableEntry  

acsActiveSessionsTableIndex 1.3.6.1.4.1.10418.26.2.2.2.1.1
A unique index representing an entry in this table.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsActiveSessionsTableUser 1.3.6.1.4.1.10418.26.2.2.2.1.2
The name of the user that opens this session.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableGroup 1.3.6.1.4.1.10418.26.2.2.2.1.3
The name of the group that the user belongs to.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableType 1.3.6.1.4.1.10418.26.2.2.2.1.4
The session type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableConnection 1.3.6.1.4.1.10418.26.2.2.2.1.5
Connection type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableSessionTime 1.3.6.1.4.1.10418.26.2.2.2.1.6
Time of the session
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableFrom 1.3.6.1.4.1.10418.26.2.2.2.1.7
The source IP address of the session.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

acsActiveSessionsTableKill 1.3.6.1.4.1.10418.26.2.2.2.1.8
A set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immediately kills the session.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), killSession(2)  

acsSerialPortNumberOfPorts 1.3.6.1.4.1.10418.26.2.3.1
Number of Serial Ports (physical serial port plus Aux Port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTable 1.3.6.1.4.1.10418.26.2.3.2
This table contains information about serial ports.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsSerialPortTableEntry

acsSerialPortTableEntry 1.3.6.1.4.1.10418.26.2.3.2.1
each entry has the information about specific serial port.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsSerialPortTableEntry  

acsSerialPortTableNumber 1.3.6.1.4.1.10418.26.2.3.2.1.1
A unique index representing an entry in this table. It is the number of the serial port. For AUX port, the number will be the number of physical serial ports plus 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..49  

acsSerialPortTableDeviceName 1.3.6.1.4.1.10418.26.2.3.2.1.2
The associated device name for the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..25)  

acsSerialPortTableStatus 1.3.6.1.4.1.10418.26.2.3.2.1.3
The status of the serial port: disabled(1) = it was configured as disable. idle(2) = there is not any session opened in this port. inUse(3) = there is session(s) opened in this port.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(1), idle(2), inUse(3)  

acsSerialPortTableName 1.3.6.1.4.1.10418.26.2.3.2.1.4
Name associated with this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..25)  

acsSerialPortTableProfile 1.3.6.1.4.1.10418.26.2.3.2.1.5
Configured profile for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER casProfile(1), tsProfile(2), dialInProfile(3), powerProfile(4)  

acsSerialPortTablePinOut 1.3.6.1.4.1.10418.26.2.3.2.1.6
RJ45 Pin-out configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortPinOut  

acsSerialPortTableComSpeed 1.3.6.1.4.1.10418.26.2.3.2.1.7
Speed configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortSpeed  

acsSerialPortTableComParity 1.3.6.1.4.1.10418.26.2.3.2.1.8
Parity configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none(1), odd(2), even(3)  

acsSerialPortTableComDataSize 1.3.6.1.4.1.10418.26.2.3.2.1.9
Data Size configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableComStopBits 1.3.6.1.4.1.10418.26.2.3.2.1.10
Number of Stop Bits configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableComFlowControl 1.3.6.1.4.1.10418.26.2.3.2.1.11
Flow Control configured for this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none(1), hardware(2), software(3)  

acsSerialPortTableSignalStateDTR 1.3.6.1.4.1.10418.26.2.3.2.1.12
State of the DTR RS-232C signal.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortSignalState  

acsSerialPortTableSignalStateDCD 1.3.6.1.4.1.10418.26.2.3.2.1.13
State of the DCD RS-232C signal.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortSignalState  

acsSerialPortTableSignalStateRTS 1.3.6.1.4.1.10418.26.2.3.2.1.14
State of the RTS RS-232C signal.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortSignalState  

acsSerialPortTableSignalStateCTS 1.3.6.1.4.1.10418.26.2.3.2.1.15
State of the CTS RS-232C signal.
Status: current Access: read-only
OBJECT-TYPE    
  SerialPortSignalState  

acsSerialPortTableTxBytes 1.3.6.1.4.1.10418.26.2.3.2.1.16
The number of transmited bytes by the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableRxBytes 1.3.6.1.4.1.10418.26.2.3.2.1.17
The number of received bytes by the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableFrameError 1.3.6.1.4.1.10418.26.2.3.2.1.18
The number of frame error detected in the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableParityError 1.3.6.1.4.1.10418.26.2.3.2.1.19
The number of parity error detected in the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableBreak 1.3.6.1.4.1.10418.26.2.3.2.1.20
The number of break detected in the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsSerialPortTableOverrun 1.3.6.1.4.1.10418.26.2.3.2.1.21
The number of overrun error detected in the serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtNumSerialPorts 1.3.6.1.4.1.10418.26.2.5.1
The number of Serial Ports that has PDU connected on the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtSerialTable 1.3.6.1.4.1.10418.26.2.5.2
Information about each serial port thas has PDU connect.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtSerialTableEntry

acsPowerMgmtSerialTableEntry 1.3.6.1.4.1.10418.26.2.5.2.1
Information about each serial port thas has PDU connect.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtSerialTableEntry  

acsPowerMgmtSerialTableIndex 1.3.6.1.4.1.10418.26.2.5.2.1.1
The index of the register.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtSerialTablePortNumber 1.3.6.1.4.1.10418.26.2.5.2.1.2
The number of the serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtSerialTableDeviceName 1.3.6.1.4.1.10418.26.2.5.2.1.3
The device name of this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtSerialTableNumberPDUs 1.3.6.1.4.1.10418.26.2.5.2.1.4
Total number of units connected in this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtSerialTableNumberUPS 1.3.6.1.4.1.10418.26.2.5.2.1.5
Total number of UPS devices connected to this serial port.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTable 1.3.6.1.4.1.10418.26.2.5.3
This table contains the list of detected PDUs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtPDUTableEntry

acsPowerMgmtPDUTableEntry 1.3.6.1.4.1.10418.26.2.5.3.1
each entry has the information about the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtPDUTableEntry  

acsPowerMgmtPDUTablePortNumber 1.3.6.1.4.1.10418.26.2.5.3.1.1
Number of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtPDUTablePduIndex 1.3.6.1.4.1.10418.26.2.5.3.1.2
A PDU position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtPDUTablePduId 1.3.6.1.4.1.10418.26.2.5.3.1.3
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPDUTablePortName 1.3.6.1.4.1.10418.26.2.5.3.1.4
Name of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPDUTableModel 1.3.6.1.4.1.10418.26.2.5.3.1.5
Model of the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPDUTableVendor 1.3.6.1.4.1.10418.26.2.5.3.1.6
Vendor of the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPDUTableFirmwareVersion 1.3.6.1.4.1.10418.26.2.5.3.1.7
Version of the PDU firmware.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPDUTableNumberOfOutlets 1.3.6.1.4.1.10418.26.2.5.3.1.8
Number of outlets of the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentNOS 1.3.6.1.4.1.10418.26.2.5.3.1.9
Number of current sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent1Value 1.3.6.1.4.1.10418.26.2.5.3.1.10
Current of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.)
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent1Max 1.3.6.1.4.1.10418.26.2.5.3.1.11
Maximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent2Value 1.3.6.1.4.1.10418.26.2.5.3.1.12
Current of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.)
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent2Max 1.3.6.1.4.1.10418.26.2.5.3.1.13
Maximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent3Value 1.3.6.1.4.1.10418.26.2.5.3.1.14
Current of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.)
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrent3Max 1.3.6.1.4.1.10418.26.2.5.3.1.15
Maximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperatureNOS 1.3.6.1.4.1.10418.26.2.5.3.1.16
Number of temperature sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature1Value 1.3.6.1.4.1.10418.26.2.5.3.1.17
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature1Max 1.3.6.1.4.1.10418.26.2.5.3.1.18
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature2Value 1.3.6.1.4.1.10418.26.2.5.3.1.19
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature2Max 1.3.6.1.4.1.10418.26.2.5.3.1.20
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature3Value 1.3.6.1.4.1.10418.26.2.5.3.1.21
Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableTemperature3Max 1.3.6.1.4.1.10418.26.2.5.3.1.22
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidityNOS 1.3.6.1.4.1.10418.26.2.5.3.1.23
Number of humidity sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity1Value 1.3.6.1.4.1.10418.26.2.5.3.1.24
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity1Max 1.3.6.1.4.1.10418.26.2.5.3.1.25
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity2Value 1.3.6.1.4.1.10418.26.2.5.3.1.26
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity2Max 1.3.6.1.4.1.10418.26.2.5.3.1.27
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity3Value 1.3.6.1.4.1.10418.26.2.5.3.1.28
Humidity of this PM unit . If the humidity measurement is not installed this value will be 0.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableHumidity3Max 1.3.6.1.4.1.10418.26.2.5.3.1.29
Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltageNOS 1.3.6.1.4.1.10418.26.2.5.3.1.30
Number of voltage sensors in the PDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage1Value 1.3.6.1.4.1.10418.26.2.5.3.1.31
Voltage of this sensor in this PDU unit.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage1Max 1.3.6.1.4.1.10418.26.2.5.3.1.32
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage2Value 1.3.6.1.4.1.10418.26.2.5.3.1.33
Voltage of this sensor in this PDU unit.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage2Max 1.3.6.1.4.1.10418.26.2.5.3.1.34
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage3Value 1.3.6.1.4.1.10418.26.2.5.3.1.35
Voltage of this sensor in this PDU unit.
Status: obsolete Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltage3Max 1.3.6.1.4.1.10418.26.2.5.3.1.36
Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage.
Status: obsolete Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableNumberOfPhases 1.3.6.1.4.1.10418.26.2.5.3.1.37
Number of phases of this PDU unit.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER single-phase(0), three-phase(3)  

acsPowerMgmtPDUTableNumberOfBanks 1.3.6.1.4.1.10418.26.2.5.3.1.38
Number of banks of this PDU unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentValue 1.3.6.1.4.1.10418.26.2.5.3.1.39
Actual value of current sensor in this PDU.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentMax 1.3.6.1.4.1.10418.26.2.5.3.1.40
Max detected value of current sensor in this PDU.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentMin 1.3.6.1.4.1.10418.26.2.5.3.1.41
Min detected value of current sensor in this PDU.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentAvg 1.3.6.1.4.1.10418.26.2.5.3.1.42
Average value for current sensor in this PDU.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableCurrentReset 1.3.6.1.4.1.10418.26.2.5.3.1.43
Reset max, min and avg values of current.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPDUTableVoltageType 1.3.6.1.4.1.10418.26.2.5.3.1.44
Type of voltage values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPDUTableVoltageValue 1.3.6.1.4.1.10418.26.2.5.3.1.45
Actual value of voltage sensor in this PDU unit.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltageMax 1.3.6.1.4.1.10418.26.2.5.3.1.46
Max detected value of voltage sensor in this PDU unit.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltageMin 1.3.6.1.4.1.10418.26.2.5.3.1.47
Min detected value of voltage sensor in this PDU unit.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltageAvg 1.3.6.1.4.1.10418.26.2.5.3.1.48
Average value for voltage sensor in this PDU unit.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTableVoltageReset 1.3.6.1.4.1.10418.26.2.5.3.1.49
Reset max, min and avg values of voltage.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPDUTablePowerType 1.3.6.1.4.1.10418.26.2.5.3.1.50
Type of power consumption values.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPDUTablePowerValue 1.3.6.1.4.1.10418.26.2.5.3.1.51
Actual value of power consumption in this PDU unit.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerMax 1.3.6.1.4.1.10418.26.2.5.3.1.52
Max detected value of power consumption in this PDU unit.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerMin 1.3.6.1.4.1.10418.26.2.5.3.1.53
Min detected value of power consumption in this PDU unit.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerAvg 1.3.6.1.4.1.10418.26.2.5.3.1.54
Average value for power consumption in this PDU unit.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerReset 1.3.6.1.4.1.10418.26.2.5.3.1.55
Reset max, min and avg values of power consumption.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPDUTablePowerFactorType 1.3.6.1.4.1.10418.26.2.5.3.1.56
Type of power factor values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPDUTablePowerFactorValue 1.3.6.1.4.1.10418.26.2.5.3.1.57
Actual value of power factor in this PDU unit.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerFactorMax 1.3.6.1.4.1.10418.26.2.5.3.1.58
Max detected value of power factor in this PDU unit.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerFactorMin 1.3.6.1.4.1.10418.26.2.5.3.1.59
Min detected value of power factor in this PDU unit.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerFactorAvg 1.3.6.1.4.1.10418.26.2.5.3.1.60
Average value for power factor in this PDU unit.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPDUTablePowerFactorReset 1.3.6.1.4.1.10418.26.2.5.3.1.61
Reset max, min and avg values of power factor.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPDUTableAlarm 1.3.6.1.4.1.10418.26.2.5.3.1.62
Show the PDU alarm status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

acsPowerMgmtPDUTableEnvSensors 1.3.6.1.4.1.10418.26.2.5.3.1.63
Number of environmental sensor in this PDU.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtTotalNumberOfOutlets 1.3.6.1.4.1.10418.26.2.5.4
Number of outlets managed by the appliance.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutletsTable 1.3.6.1.4.1.10418.26.2.5.5
This table contains the information about outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtOutletsTableEntry

acsPowerMgmtOutletsTableEntry 1.3.6.1.4.1.10418.26.2.5.5.1
each entry has the information about the outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtOutletsTableEntry  

acsPowerMgmtOutletsTablePortNumber 1.3.6.1.4.1.10418.26.2.5.5.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutletsTablePduNumber 1.3.6.1.4.1.10418.26.2.5.5.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutletsTableNumber 1.3.6.1.4.1.10418.26.2.5.5.1.3
Number of the outlet in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutletsTableName 1.3.6.1.4.1.10418.26.2.5.5.1.4
Name of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtOutletsTableStatus 1.3.6.1.4.1.10418.26.2.5.5.1.5
Status of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

acsPowerMgmtOutletsTablePowerControl 1.3.6.1.4.1.10418.26.2.5.5.1.6
A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. powerLock(5)= when SET the power lock command is sent to PDU. powerUnlock(6)=when SET the power unlock command is sent to PDU. The powerLock and powerUnlock are valid only for Cyclades-PM PDUs
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4), powerLock(5), powerUnlock(6)  

acsPowerMgmtOutletsTablePortName 1.3.6.1.4.1.10418.26.2.5.5.1.7
Serial Port Name where the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtOutletsTablePduId 1.3.6.1.4.1.10418.26.2.5.5.1.8
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtNumberOfOutletGroup 1.3.6.1.4.1.10418.26.2.5.6
Number of configured group of outlets.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtGroupTable 1.3.6.1.4.1.10418.26.2.5.7
This table contains the information about group of outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtGroupTableEntry

acsPowerMgmtGroupTableEntry 1.3.6.1.4.1.10418.26.2.5.7.1
each entry has the information about group of outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtGroupTableEntry  

acsPowerMgmtGroupTableIndex 1.3.6.1.4.1.10418.26.2.5.7.1.1
Index of the group.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtGroupTableName 1.3.6.1.4.1.10418.26.2.5.7.1.2
Name of the group of outlets.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtGroupTableStatus 1.3.6.1.4.1.10418.26.2.5.7.1.3
Status of the group of outlet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2)  

acsPowerMgmtGroupTablePowerControl 1.3.6.1.4.1.10418.26.2.5.7.1.4
A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4)  

acsPowerMgmtPhasesTable 1.3.6.1.4.1.10418.26.2.5.8
This table contains data monitoring of each detected phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtPhasesTableEntry

acsPowerMgmtPhasesTableEntry 1.3.6.1.4.1.10418.26.2.5.8.1
each entry has the data monitoring about phases.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtPhasesTableEntry  

acsPowerMgmtPhasesTablePortNumber 1.3.6.1.4.1.10418.26.2.5.8.1.1
Number of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtPhasesTablePduIndex 1.3.6.1.4.1.10418.26.2.5.8.1.2
A PDU position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtPhasesTablePhaseIndex 1.3.6.1.4.1.10418.26.2.5.8.1.3
phase index in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtPhasesTablePhaseName 1.3.6.1.4.1.10418.26.2.5.8.1.4
phase name in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPhasesTablePduId 1.3.6.1.4.1.10418.26.2.5.8.1.5
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPhasesTablePortName 1.3.6.1.4.1.10418.26.2.5.8.1.6
Name of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtPhasesTableCurrentValue 1.3.6.1.4.1.10418.26.2.5.8.1.7
Actual value of current sensor in this phase.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableCurrentMax 1.3.6.1.4.1.10418.26.2.5.8.1.8
Max detected value of current sensor in this phase.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableCurrentMin 1.3.6.1.4.1.10418.26.2.5.8.1.9
Min detected value of current sensor in this phase.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableCurrentAvg 1.3.6.1.4.1.10418.26.2.5.8.1.10
Average value for current sensor in this phase.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableCurrentReset 1.3.6.1.4.1.10418.26.2.5.8.1.11
Reset max, min and avg values of current.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPhasesTableVoltageType 1.3.6.1.4.1.10418.26.2.5.8.1.12
Type of voltage values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPhasesTableVoltageValue 1.3.6.1.4.1.10418.26.2.5.8.1.13
Actual value of voltage sensor in this phase.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableVoltageMax 1.3.6.1.4.1.10418.26.2.5.8.1.14
Max detected value of voltage sensor in this phase.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableVoltageMin 1.3.6.1.4.1.10418.26.2.5.8.1.15
Min detected value of voltage sensor in this phase.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableVoltageAvg 1.3.6.1.4.1.10418.26.2.5.8.1.16
Average value for voltage sensor in this phase.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTableVoltageReset 1.3.6.1.4.1.10418.26.2.5.8.1.17
Reset max, min and avg values of voltage.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPhasesTablePowerType 1.3.6.1.4.1.10418.26.2.5.8.1.18
Type of power consumption values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPhasesTablePowerValue 1.3.6.1.4.1.10418.26.2.5.8.1.19
Actual value of power consumption in this phase.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerMax 1.3.6.1.4.1.10418.26.2.5.8.1.20
Max detected value of power consumption in this phase.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerMin 1.3.6.1.4.1.10418.26.2.5.8.1.21
Min detected value of power consumption in this phase.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerAvg 1.3.6.1.4.1.10418.26.2.5.8.1.22
Average value for power consumption in this phase.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerReset 1.3.6.1.4.1.10418.26.2.5.8.1.23
Reset max, min and avg values of power consumption.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPhasesTablePowerFactorType 1.3.6.1.4.1.10418.26.2.5.8.1.24
Type of power factor values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtPhasesTablePowerFactorValue 1.3.6.1.4.1.10418.26.2.5.8.1.25
Actual value of power factor in this phase.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerFactorMax 1.3.6.1.4.1.10418.26.2.5.8.1.26
Max detected value of power factor in this phase.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerFactorMin 1.3.6.1.4.1.10418.26.2.5.8.1.27
Min detected value of power factor in this phase.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerFactorAvg 1.3.6.1.4.1.10418.26.2.5.8.1.28
Average value for power factor in this phase.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtPhasesTablePowerFactorReset 1.3.6.1.4.1.10418.26.2.5.8.1.29
Reset max, min and avg values of power factor.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtPhasesTableAlarm 1.3.6.1.4.1.10418.26.2.5.8.1.30
Show the phase alarm status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

acsPowerMgmtBanksTable 1.3.6.1.4.1.10418.26.2.5.9
This table contains data monitoring of each detected bank.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtBanksTableEntry

acsPowerMgmtBanksTableEntry 1.3.6.1.4.1.10418.26.2.5.9.1
each entry has the data monitoring about bank.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtBanksTableEntry  

acsPowerMgmtBanksTablePortNumber 1.3.6.1.4.1.10418.26.2.5.9.1.1
Number of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtBanksTablePduIndex 1.3.6.1.4.1.10418.26.2.5.9.1.2
A PDU position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtBanksTableBankIndex 1.3.6.1.4.1.10418.26.2.5.9.1.3
Bank index in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtBanksTableBankName 1.3.6.1.4.1.10418.26.2.5.9.1.4
Bank name in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtBanksTablePduId 1.3.6.1.4.1.10418.26.2.5.9.1.5
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtBanksTablePortName 1.3.6.1.4.1.10418.26.2.5.9.1.6
Name of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtBanksTableCurrentValue 1.3.6.1.4.1.10418.26.2.5.9.1.7
Actual value of current sensor in this bank.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableCurrentMax 1.3.6.1.4.1.10418.26.2.5.9.1.8
Max detected value of current sensor in this bank.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableCurrentMin 1.3.6.1.4.1.10418.26.2.5.9.1.9
Min detected value of current sensor in this bank.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableCurrentAvg 1.3.6.1.4.1.10418.26.2.5.9.1.10
Average value for current sensor in this bank.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableCurrentReset 1.3.6.1.4.1.10418.26.2.5.9.1.11
Reset max, min and avg values of current.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtBanksTableVoltageType 1.3.6.1.4.1.10418.26.2.5.9.1.12
Type of voltage values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtBanksTableVoltageValue 1.3.6.1.4.1.10418.26.2.5.9.1.13
Actual value of voltage sensor in this bank.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableVoltageMax 1.3.6.1.4.1.10418.26.2.5.9.1.14
Max detected value of voltage sensor in this bank.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableVoltageMin 1.3.6.1.4.1.10418.26.2.5.9.1.15
Min detected value of voltage sensor in this bank.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableVoltageAvg 1.3.6.1.4.1.10418.26.2.5.9.1.16
Average value for voltage sensor in this bank.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTableVoltageReset 1.3.6.1.4.1.10418.26.2.5.9.1.17
Reset max, min and avg values of voltage.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtBanksTablePowerType 1.3.6.1.4.1.10418.26.2.5.9.1.18
Type of power consumption values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtBanksTablePowerValue 1.3.6.1.4.1.10418.26.2.5.9.1.19
Actual value of power consumption in this bank.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerMax 1.3.6.1.4.1.10418.26.2.5.9.1.20
Max detected value of power consumption in this bank.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerMin 1.3.6.1.4.1.10418.26.2.5.9.1.21
Min detected value of power consumption in this bank.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerAvg 1.3.6.1.4.1.10418.26.2.5.9.1.22
Average value for power consumption in this bank.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerReset 1.3.6.1.4.1.10418.26.2.5.9.1.23
Reset max, min and avg values of power consumption.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtBanksTablePowerFactorType 1.3.6.1.4.1.10418.26.2.5.9.1.24
Type of power factor values.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER none-sensor(0), estimated(1), read(2)  

acsPowerMgmtBanksTablePowerFactorValue 1.3.6.1.4.1.10418.26.2.5.9.1.25
Actual value of power factor in this bank.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerFactorMax 1.3.6.1.4.1.10418.26.2.5.9.1.26
Max detected value of power factor in this bank.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerFactorMin 1.3.6.1.4.1.10418.26.2.5.9.1.27
Min detected value of power factor in this bank.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerFactorAvg 1.3.6.1.4.1.10418.26.2.5.9.1.28
Average value for power factor in this bank.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtBanksTablePowerFactorReset 1.3.6.1.4.1.10418.26.2.5.9.1.29
Reset max, min and avg values of power factor.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER no-action(1), reset(2)  

acsPowerMgmtBanksTableAlarm 1.3.6.1.4.1.10418.26.2.5.9.1.30
Show the bank alarm status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

acsPowerMgmtEnvMonTable 1.3.6.1.4.1.10418.26.2.5.10
This table contains data monitoring of each detected environmental sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtEnvMonTableEntry

acsPowerMgmtEnvMonTableEntry 1.3.6.1.4.1.10418.26.2.5.10.1
each entry has the data monitoring about environmental sensors.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtEnvMonTableEntry  

acsPowerMgmtEnvMonTablePortNumber 1.3.6.1.4.1.10418.26.2.5.10.1.1
Number of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtEnvMonTablePduIndex 1.3.6.1.4.1.10418.26.2.5.10.1.2
A PDU position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtEnvMonTableIndex 1.3.6.1.4.1.10418.26.2.5.10.1.3
envmon sensor index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtEnvMonTableName 1.3.6.1.4.1.10418.26.2.5.10.1.4
envmon sensor name.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtEnvMonTablePduId 1.3.6.1.4.1.10418.26.2.5.10.1.5
PDU identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtEnvMonTablePortName 1.3.6.1.4.1.10418.26.2.5.10.1.6
Name of serial port when the PDU is connected.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtEnvMonTableType 1.3.6.1.4.1.10418.26.2.5.10.1.7
The type of environmental monitor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER temp-internal(1), temperature(2), humidity(3), air-flow(4), smoke(5), dry-contact(6), water-level(7), motion(8), unplugged(9), unknown(10), air-pressure(11), vibration(12), vibration-contact(13), leak(14), door-contact(15)  

acsPowerMgmtEnvMonTableStatus 1.3.6.1.4.1.10418.26.2.5.10.1.8
Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor, Door-Contact. For Door-Contact, normal(1) = closed, triggered(2) = opened.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), triggered(2), not-applicable(3)  

acsPowerMgmtEnvMonTableValue 1.3.6.1.4.1.10418.26.2.5.10.1.9
Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtEnvMonTableMaxValue 1.3.6.1.4.1.10418.26.2.5.10.1.10
Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTable 1.3.6.1.4.1.10418.26.2.5.11
This table contains the information about data monitoring of outlets.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtOutElecMonTableEntry

acsPowerMgmtOutElecMonTableEntry 1.3.6.1.4.1.10418.26.2.5.11.1
each entry has the information about the outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtOutElecMonTableEntry  

acsPowerMgmtOutElecMonTablePortNumber 1.3.6.1.4.1.10418.26.2.5.11.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutElecMonTablePduNumber 1.3.6.1.4.1.10418.26.2.5.11.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutElecMonTableNumber 1.3.6.1.4.1.10418.26.2.5.11.1.3
Number of the outlet in the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtOutElecMonTableCurrentValue 1.3.6.1.4.1.10418.26.2.5.11.1.4
Actual value of outlet current sensor.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableCurrentMax 1.3.6.1.4.1.10418.26.2.5.11.1.5
Max detected value of outlet current sensor.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableCurrentMin 1.3.6.1.4.1.10418.26.2.5.11.1.6
Min detected value of outlet current sensor.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableCurrentAvg 1.3.6.1.4.1.10418.26.2.5.11.1.7
Average value for outlet current sensor.( A x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableCurrentReset 1.3.6.1.4.1.10418.26.2.5.11.1.8
Reset max, min and avertage values of outlet current.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

acsPowerMgmtOutElecMonTablePowerValue 1.3.6.1.4.1.10418.26.2.5.11.1.9
Actual value of outlet power comsumption sensor.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerMax 1.3.6.1.4.1.10418.26.2.5.11.1.10
Max detected value of outlet power comsumption sensor.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerMin 1.3.6.1.4.1.10418.26.2.5.11.1.11
Min detected value of outlet power comsumption sensor.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerAvg 1.3.6.1.4.1.10418.26.2.5.11.1.12
Average value for outlet power comsumption sensor.( W x 10 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerReset 1.3.6.1.4.1.10418.26.2.5.11.1.13
Reset max, min and avertage values of outlet power comsumption.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

acsPowerMgmtOutElecMonTableVoltageValue 1.3.6.1.4.1.10418.26.2.5.11.1.14
Actual value of outlet voltage sensor.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableVoltageMax 1.3.6.1.4.1.10418.26.2.5.11.1.15
Max detected value of outlet voltage sensor.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableVoltageMin 1.3.6.1.4.1.10418.26.2.5.11.1.16
Min detected value of outlet voltage sensor.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableVoltageAvg 1.3.6.1.4.1.10418.26.2.5.11.1.17
Average value for outlet voltage sensor.( V )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTableVoltageReset 1.3.6.1.4.1.10418.26.2.5.11.1.18
Reset max, min and avertage values of outlet voltage.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

acsPowerMgmtOutElecMonTablePowerFactorValue 1.3.6.1.4.1.10418.26.2.5.11.1.19
Actual value of outlet power-factor sensor.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerFactorMax 1.3.6.1.4.1.10418.26.2.5.11.1.20
Max detected value of outlet power-factor sensor.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerFactorMin 1.3.6.1.4.1.10418.26.2.5.11.1.21
Min detected value of outlet power-factor sensor.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerFactorAvg 1.3.6.1.4.1.10418.26.2.5.11.1.22
Average value for outlet power-factor sensor.( PF x 100 )
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtOutElecMonTablePowerFactorReset 1.3.6.1.4.1.10418.26.2.5.11.1.23
Reset max, min and avertage values of outlet power-factor.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), reset(2)  

acsPowerMgmtOutElecMonTableAlarm 1.3.6.1.4.1.10418.26.2.5.11.1.24
Show the outlet alarm status.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)  

acsPowerMgmtUPSTable 1.3.6.1.4.1.10418.26.2.5.12
This table contains the list of detected UPSs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSTableEntry

acsPowerMgmtUPSTableEntry 1.3.6.1.4.1.10418.26.2.5.12.1
Each entry has the information about the UPS.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSTableEntry  

acsPowerMgmtUPSTablePortNumber 1.3.6.1.4.1.10418.26.2.5.12.1.1
Number of serial port when the UPS is connected.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.12.1.2
A UPS position in the chain.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndexOrZero  

acsPowerMgmtUPSTableUpsId 1.3.6.1.4.1.10418.26.2.5.12.1.3
UPS identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTablePortName 1.3.6.1.4.1.10418.26.2.5.12.1.4
Name of serial port or IP address if network device
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableModel 1.3.6.1.4.1.10418.26.2.5.12.1.5
Model of the UPS.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableVendor 1.3.6.1.4.1.10418.26.2.5.12.1.6
Vendor of the UPS.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableFirmwareVersion 1.3.6.1.4.1.10418.26.2.5.12.1.7
Version of the UPS firmware.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableAgentFirmwareVersion 1.3.6.1.4.1.10418.26.2.5.12.1.8
Firmware version of the agent card.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableSystemStatus 1.3.6.1.4.1.10418.26.2.5.12.1.9
System Status of the UPS.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableInputBlackOutCount 1.3.6.1.4.1.10418.26.2.5.12.1.10
The number of occurrences, since the last reset, where the input was not qualified to provide power to the system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtUPSTableInputBrownOutCount 1.3.6.1.4.1.10418.26.2.5.12.1.11
The number of occurrences, since the last reset, where the system input voltage has fallen below a pre-determined threshold for a specified amount of time.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtUPSTableInletAirTemperature 1.3.6.1.4.1.10418.26.2.5.12.1.12
Temperature of the inlet air.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableNumberOutletGroups 1.3.6.1.4.1.10418.26.2.5.12.1.13
The number of Outlet Groups on this UPS
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acsPowerMgmtUPSTableUPSSerialNumber 1.3.6.1.4.1.10418.26.2.5.12.1.14
System serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableUPSManufactureDate 1.3.6.1.4.1.10418.26.2.5.12.1.15
Manufacturing date of the system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableAutoRestartDelay 1.3.6.1.4.1.10418.26.2.5.12.1.16
If power is lost, the control will delay this amount of time after power is restored before restarting the unit.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

acsPowerMgmtUPSTableAutoRestartControl 1.3.6.1.4.1.10418.26.2.5.12.1.17
When set to enabled, the UPS will automatically restart the load when utility power is restored after a battery discharge.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

acsPowerMgmtUPSTableAudibleAlarmControl 1.3.6.1.4.1.10418.26.2.5.12.1.18
Audible alarm control.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2)  

acsPowerMgmtUPSTableSilenceAlarm 1.3.6.1.4.1.10418.26.2.5.12.1.19
Silence audible alarm.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(0), silenceAlarm(1)  

acsPowerMgmtUPSTableInverterState 1.3.6.1.4.1.10418.26.2.5.12.1.20
Inverter on/off state.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableDCConverterStatus 1.3.6.1.4.1.10418.26.2.5.12.1.21
The operating state of the dc converter.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableShutdownReason 1.3.6.1.4.1.10418.26.2.5.12.1.22
The reason for the most recent shutdown.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableUPSTopology 1.3.6.1.4.1.10418.26.2.5.12.1.23
UPS Topology.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSTableBypassInverterInputConfig 1.3.6.1.4.1.10418.26.2.5.12.1.24
Input source configuration for the bypass and inverter.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTable 1.3.6.1.4.1.10418.26.2.5.13
This table contains the information about UPS inputs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSInputTableEntry

acsPowerMgmtUPSInputTableEntry 1.3.6.1.4.1.10418.26.2.5.13.1
each entry has the information about the UPS inputs.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSInputTableEntry  

acsPowerMgmtUPSInputTablePortNumber 1.3.6.1.4.1.10418.26.2.5.13.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSInputTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.13.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSInputTableFrequency 1.3.6.1.4.1.10418.26.2.5.13.1.3
Input Frequency.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableRMSVoltageL1N 1.3.6.1.4.1.10418.26.2.5.13.1.4
RMS Voltage L1-N.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableRMSVoltageL1L2 1.3.6.1.4.1.10418.26.2.5.13.1.5
RMS Voltage L1L2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableRMSVoltageL2N 1.3.6.1.4.1.10418.26.2.5.13.1.6
RMS Voltage L2N.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableRMSCurrentL1 1.3.6.1.4.1.10418.26.2.5.13.1.7
RMS Current for L1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableRMSCurrentL2 1.3.6.1.4.1.10418.26.2.5.13.1.8
RMS Current for L2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableMaxVoltageL1N 1.3.6.1.4.1.10418.26.2.5.13.1.9
Input Max Voltage measurement for Line L1-N since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableMinVoltageL1N 1.3.6.1.4.1.10418.26.2.5.13.1.10
Input Min Voltage measurement for Line L1-N since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableMaxVoltageL2N 1.3.6.1.4.1.10418.26.2.5.13.1.11
Input Max Voltage measurement for Line L2-N since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableMinVoltageL2N 1.3.6.1.4.1.10418.26.2.5.13.1.12
Input Min Voltage measurement for Line L1-N since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableNominalVoltage 1.3.6.1.4.1.10418.26.2.5.13.1.13
Input nominal voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableNominalFrequency 1.3.6.1.4.1.10418.26.2.5.13.1.14
Input nominal frequency.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSInputTableNominalCurrent 1.3.6.1.4.1.10418.26.2.5.13.1.15
Input nominal current.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTable 1.3.6.1.4.1.10418.26.2.5.14
This table contains the information about UPS bypass.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSBypassTableEntry

acsPowerMgmtUPSBypassTableEntry 1.3.6.1.4.1.10418.26.2.5.14.1
each entry has the information about the UPS bypass.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSBypassTableEntry  

acsPowerMgmtUPSBypassTablePortNumber 1.3.6.1.4.1.10418.26.2.5.14.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSBypassTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.14.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSBypassTableRMSVoltageL1N 1.3.6.1.4.1.10418.26.2.5.14.1.3
RMS Voltage L1N.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableRMSVoltageL1L2 1.3.6.1.4.1.10418.26.2.5.14.1.4
RMS Voltage L1L2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableRMSVoltageL2N 1.3.6.1.4.1.10418.26.2.5.14.1.5
RMS Voltage L2N.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableRMSCurrent 1.3.6.1.4.1.10418.26.2.5.14.1.6
RMS Current.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableRMSCurrentL2 1.3.6.1.4.1.10418.26.2.5.14.1.7
RMS Current.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableInputFrequency 1.3.6.1.4.1.10418.26.2.5.14.1.8
Bypass Input Frequency.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBypassTableNominalVoltage 1.3.6.1.4.1.10418.26.2.5.14.1.9
Bypass Nominal Voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTable 1.3.6.1.4.1.10418.26.2.5.15
This table contains the information about UPS battery.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSBatteryTableEntry

acsPowerMgmtUPSBatteryTableEntry 1.3.6.1.4.1.10418.26.2.5.15.1
each entry has the information about the UPS bypass.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSBatteryTableEntry  

acsPowerMgmtUPSBatteryTablePortNumber 1.3.6.1.4.1.10418.26.2.5.15.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSBatteryTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.15.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSBatteryTableDCBusVoltage 1.3.6.1.4.1.10418.26.2.5.15.1.3
DC Bus Voltage
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableTimeRemaining 1.3.6.1.4.1.10418.26.2.5.15.1.4
The calculated available time on battery.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTablePercentageCharge 1.3.6.1.4.1.10418.26.2.5.15.1.5
Battery Percentage Charge.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableChargeStatus 1.3.6.1.4.1.10418.26.2.5.15.1.6
Battery Charge Status.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableLowBatteryWarningTime 1.3.6.1.4.1.10418.26.2.5.15.1.7
When battery time remaining falls to, or below, this value (minutes) the low battery alarm is activated.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 2..30  

acsPowerMgmtUPSBatteryTableTestResult 1.3.6.1.4.1.10418.26.2.5.15.1.8
The outcome of the previous battery test.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableDCBusNominalVoltage 1.3.6.1.4.1.10418.26.2.5.15.1.9
Battery DC Bus Nominal Voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableNominalBatteryCapacity 1.3.6.1.4.1.10418.26.2.5.15.1.10
Nominal Battery Capacity.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryFloatVoltage 1.3.6.1.4.1.10418.26.2.5.15.1.11
Battery Float Voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryCabinetType 1.3.6.1.4.1.10418.26.2.5.15.1.12
Battery Cabinet Type.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryNumberOfEBC 1.3.6.1.4.1.10418.26.2.5.15.1.13
Number of Extended Battery Cabinets installed.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryRating 1.3.6.1.4.1.10418.26.2.5.15.1.14
Battery Rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryDischargeTime 1.3.6.1.4.1.10418.26.2.5.15.1.15
Time on battery operation for this discharge
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryChargeCompensating 1.3.6.1.4.1.10418.26.2.5.15.1.16
Battery charge algorithm changed due to battery temperature.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableBatteryChargerState 1.3.6.1.4.1.10418.26.2.5.15.1.17
Battery charger state.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSBatteryTableStartBatteryTest 1.3.6.1.4.1.10418.26.2.5.15.1.18
Command to initate a manual battery test.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), start(2)  

acsPowerMgmtUPSBatteryTableBatteryStatus 1.3.6.1.4.1.10418.26.2.5.15.1.19
Battery Status.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTable 1.3.6.1.4.1.10418.26.2.5.16
This table contains the information about UPS output.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSOutputTableEntry

acsPowerMgmtUPSOutputTableEntry 1.3.6.1.4.1.10418.26.2.5.16.1
Each entry has the information about the UPS output.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSOutputTableEntry  

acsPowerMgmtUPSOutputTablePortNumber 1.3.6.1.4.1.10418.26.2.5.16.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSOutputTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.16.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSOutputTableApparentPower 1.3.6.1.4.1.10418.26.2.5.16.1.3
DC Bus Voltage
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableFrequency 1.3.6.1.4.1.10418.26.2.5.16.1.4
Output frequency.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePercentPower 1.3.6.1.4.1.10418.26.2.5.16.1.5
The system output power as a percentage of the rated capacity.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePercentPowerL1 1.3.6.1.4.1.10418.26.2.5.16.1.6
The system output power on line L1 as a percentage of the rated capacity.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePercentPowerL2 1.3.6.1.4.1.10418.26.2.5.16.1.7
The system output power on line L2 as a percentage of the rated capacity.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePower 1.3.6.1.4.1.10418.26.2.5.16.1.8
The sum total power of all system output phases.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableRMSCurrentL1 1.3.6.1.4.1.10418.26.2.5.16.1.9
System output RMS current for line L1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableRMSCurrentL2 1.3.6.1.4.1.10418.26.2.5.16.1.10
System output RMS current for line L2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableRMSVoltageL1N 1.3.6.1.4.1.10418.26.2.5.16.1.11
The system output RMS voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableRMSVoltageL2N 1.3.6.1.4.1.10418.26.2.5.16.1.12
The system output RMS voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableRMSVoltageL1L2 1.3.6.1.4.1.10418.26.2.5.16.1.13
The system output RMS voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputOffDelay 1.3.6.1.4.1.10418.26.2.5.16.1.14
Turns the UPS output off after the number of seconds specified. When a value is written to this object the output will be turned off after the specified time has elapsed and the output will remain off.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..300  

acsPowerMgmtUPSOutputOnDelay 1.3.6.1.4.1.10418.26.2.5.16.1.15
Turns the UPS output on after the number of seconds specified. When a value is written to this object the output will be turned on after the specified time has elapsed.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..300  

acsPowerMgmtUPSOutputCycleDelay 1.3.6.1.4.1.10418.26.2.5.16.1.16
Turns the UPS off and then back on after the number of seconds specified. When a value is written to this object the output will turned off immediately and then turned back on after the specified time has elapsed.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..300  

acsPowerMgmtUPSOutputTableMaxVoltageL1 1.3.6.1.4.1.10418.26.2.5.16.1.17
The maximum system output voltage measurement for line 1 since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableMinVoltageL1 1.3.6.1.4.1.10418.26.2.5.16.1.18
The minimum system output voltage measurement for line 1 since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableMaxVoltageL2 1.3.6.1.4.1.10418.26.2.5.16.1.19
The maximum system output voltage measurement for line 21 since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableMinVoltageL2 1.3.6.1.4.1.10418.26.2.5.16.1.20
The minimum system output voltage measurement for line 2 since the last reset.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableNominalVoltage 1.3.6.1.4.1.10418.26.2.5.16.1.21
The nominal (or rated) system output voltage.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerNominalFrequency 1.3.6.1.4.1.10418.26.2.5.16.1.22
The nominal (or rated) system output frequency.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerApparentPowerRating 1.3.6.1.4.1.10418.26.2.5.16.1.23
Output apparent power rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerNominalPowerFactor 1.3.6.1.4.1.10418.26.2.5.16.1.24
The nominal (or rated) system power factor.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerPowerFactorCorrection 1.3.6.1.4.1.10418.26.2.5.16.1.25
The state of the power factor correction circuitry of the system.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerL1 1.3.6.1.4.1.10418.26.2.5.16.1.26
The system output power on line 1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTablePowerL2 1.3.6.1.4.1.10418.26.2.5.16.1.27
The system output power on line 2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableApparentPowerL1 1.3.6.1.4.1.10418.26.2.5.16.1.28
The system output apparent power on line 1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutputTableApparentPowerL2 1.3.6.1.4.1.10418.26.2.5.16.1.29
The system output apparent power on line 2.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSEcoModeTable 1.3.6.1.4.1.10418.26.2.5.17
This table contains the information about UPS ECO Mode.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSEcoModeTableEntry

acsPowerMgmtUPSEcoModeTableEntry 1.3.6.1.4.1.10418.26.2.5.17.1
each entry has the information about the UPS ECO Mode.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSEcoModeTableEntry  

acsPowerMgmtUPSEcoModeTablePortNumber 1.3.6.1.4.1.10418.26.2.5.17.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSEcoModeTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.17.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSEcoModeTableStatus 1.3.6.1.4.1.10418.26.2.5.17.1.3
Current ECO Mode Status.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSEcoModeTableStateControl 1.3.6.1.4.1.10418.26.2.5.17.1.4
Enable or disable ECO mode.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), enable(2), disable(3)  

acsPowerMgmtUPSOutletGroupTable 1.3.6.1.4.1.10418.26.2.5.18
This table contains the UPS Outlet Group Information.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcsPowerMgmtUPSOutletGroupTableEntry

acsPowerMgmtUPSOutletGroupTableEntry 1.3.6.1.4.1.10418.26.2.5.18.1
Each entry has the UPS outlet group information.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcsPowerMgmtUPSOutletGroupTableEntry  

acsPowerMgmtUPSOutletGroupTablePortNumber 1.3.6.1.4.1.10418.26.2.5.18.1.1
Serial Port number.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSOutletGroupTableUpsIndex 1.3.6.1.4.1.10418.26.2.5.18.1.2
Index.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSOutletGroupTableNumber 1.3.6.1.4.1.10418.26.2.5.18.1.3
Number of the outletgroup in the UPS.
Status: current Access: read-only
OBJECT-TYPE    
  InterfaceIndex  

acsPowerMgmtUPSOutletGroupTableLabel 1.3.6.1.4.1.10418.26.2.5.18.1.4
User-defined label for the outlet group.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutletGroupTableState 1.3.6.1.4.1.10418.26.2.5.18.1.5
User-defined label for the outlet group.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

acsPowerMgmtUPSOutletGroupTablePowerControl 1.3.6.1.4.1.10418.26.2.5.18.1.6
A set value of power(2-6) will send command to the UPS. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to UPS. powerOff(3) = when SET the power Off command is sent to UPS. powerCycle(4)=when SET the power cycle command is sent to UPS.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noAction(1), powerOn(2), powerOff(3), powerCycle(4)