CAREL-ug40cdz-MIB

File: CAREL-ug40cdz-MIB.mib (56893 bytes)

Imported modules

SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI
RFC1213-MIB

Imported symbols

OBJECT-GROUP sysContact sysName
sysLocation enterprises MODULE-IDENTITY
OBJECT-TYPE Integer32 DisplayString

Defined Values

ug40cdzMIB 1.3.6.1.4.1.9839.2.1
This is the MIB module for the UG40 Close Control Uniflair device.
MODULE-IDENTITY    

carel 1.3.6.1.4.1.9839
OBJECT IDENTIFIER    

systm 1.3.6.1.4.1.9839.1
OBJECT IDENTIFIER    

agentRelease 1.3.6.1.4.1.9839.1.1
Release of the Agent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

agentCode 1.3.6.1.4.1.9839.1.2
Code of the Agent. 1=WebGate
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

instruments 1.3.6.1.4.1.9839.2
OBJECT IDENTIFIER    

webGateInfo 1.3.6.1.4.1.9839.2.0
OBJECT IDENTIFIER    

agentParameters 1.3.6.1.4.1.9839.2.0.1
OBJECT IDENTIFIER    

netSize 1.3.6.1.4.1.9839.2.0.1.1
Network size. It corresponds to the number of units connected to the WebGate.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..16  

baudRate 1.3.6.1.4.1.9839.2.0.1.2
Baudrate of the Carel network.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1200 | 2400 | 4800 | 9600 | 19200  

unitTypeGroup 1.3.6.1.4.1.9839.2.0.2
OBJECT IDENTIFIER    

unit1-Type 1.3.6.1.4.1.9839.2.0.2.1
Type of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

unitCodeGroup 1.3.6.1.4.1.9839.2.0.3
OBJECT IDENTIFIER    

unit1-Code 1.3.6.1.4.1.9839.2.0.3.1
Code of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.4
OBJECT IDENTIFIER    

unit1-SoftwareRelease 1.3.6.1.4.1.9839.2.0.4.1
Software release of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitMinSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.5
OBJECT IDENTIFIER    

unit1-MinSoftwareRelease 1.3.6.1.4.1.9839.2.0.5.1
Minimum software release of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitMaxSoftwareReleaseGroup 1.3.6.1.4.1.9839.2.0.6
OBJECT IDENTIFIER    

unit1-MaxSoftwareRelease 1.3.6.1.4.1.9839.2.0.6.1
Maximum software release of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitNoAnswerCounterGroup 1.3.6.1.4.1.9839.2.0.7
OBJECT IDENTIFIER    

unit1-NoAnswerCounter 1.3.6.1.4.1.9839.2.0.7.1
No answer counter of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitErrorChecksumCounterGroup 1.3.6.1.4.1.9839.2.0.8
OBJECT IDENTIFIER    

unit1-ErrorChecksumCounter 1.3.6.1.4.1.9839.2.0.8.1
Error checksum counter of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

unitTimeoutCounterGroup 1.3.6.1.4.1.9839.2.0.9
OBJECT IDENTIFIER    

unit1-TimeoutCounter 1.3.6.1.4.1.9839.2.0.9.1
Timeout counter of the unit having serial address 1.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

digitalObjects 1.3.6.1.4.1.9839.2.1.1
OBJECT IDENTIFIER    

systemOn 1.3.6.1.4.1.9839.2.1.1.1
System On (Fan)
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

compressore1 1.3.6.1.4.1.9839.2.1.1.2
Compressor 1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

compressore2 1.3.6.1.4.1.9839.2.1.1.3
Compressor 2
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

compressore3 1.3.6.1.4.1.9839.2.1.1.4
Compressor 3
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

compressore4 1.3.6.1.4.1.9839.2.1.1.5
Compressor 4
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

heating1 1.3.6.1.4.1.9839.2.1.1.6
Heating 1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

heating2 1.3.6.1.4.1.9839.2.1.1.7
Heating 2
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

hotGasCoil 1.3.6.1.4.1.9839.2.1.1.9
Hot Gas Coil
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

dehumidification 1.3.6.1.4.1.9839.2.1.1.10
Dehumidification
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

humidification 1.3.6.1.4.1.9839.2.1.1.11
Humidification
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

emerg 1.3.6.1.4.1.9839.2.1.1.12
Main Power Loss
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmAccess 1.3.6.1.4.1.9839.2.1.1.20
Tampering Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRoomHT 1.3.6.1.4.1.9839.2.1.1.21
Alarm: Room High Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRoomLT 1.3.6.1.4.1.9839.2.1.1.22
Alarm: Room Low Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRoomHH 1.3.6.1.4.1.9839.2.1.1.23
Alarm: Room High Humidity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRoomLH 1.3.6.1.4.1.9839.2.1.1.24
Alarm: Room Low Humidity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRoomEAP 1.3.6.1.4.1.9839.2.1.1.25
Room T+H Limits by External Sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmFilter 1.3.6.1.4.1.9839.2.1.1.26
Alarm: Clogged Filter
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmFlood 1.3.6.1.4.1.9839.2.1.1.27
Alarm: Water Leakage Detected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmAirFlow 1.3.6.1.4.1.9839.2.1.1.28
Alarm: Loss of Air Flow
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHeater 1.3.6.1.4.1.9839.2.1.1.29
Alarm: Heater Overheating
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHP1 1.3.6.1.4.1.9839.2.1.1.30
Alarm: Circuit 1 High Pressure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHP2 1.3.6.1.4.1.9839.2.1.1.31
Alarm: Circuit 1 High Pressure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmLP1 1.3.6.1.4.1.9839.2.1.1.32
Alarm: Circuit 1 Low Pressure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmLP2 1.3.6.1.4.1.9839.2.1.1.33
Alarm: Circuit 2 Low Pressure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmEXV1 1.3.6.1.4.1.9839.2.1.1.34
Alarm: Circuit 1 Electronic Valve Failure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmEXV2 1.3.6.1.4.1.9839.2.1.1.35
Alarm: Circuit 2 Electronic Valve Failure
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmPSE 1.3.6.1.4.1.9839.2.1.1.36
Alarm: Wrong Phase Sequence
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmSmokeFire 1.3.6.1.4.1.9839.2.1.1.37
Alarm: SMOKE-FIRE DETECTED
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmLAN 1.3.6.1.4.1.9839.2.1.1.38
Interrupted LAN Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHUHC 1.3.6.1.4.1.9839.2.1.1.39
Alarm: Humidifier High Current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHUPL 1.3.6.1.4.1.9839.2.1.1.40
Alarm: Humidifier Power Loss
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHUWL 1.3.6.1.4.1.9839.2.1.1.41
Alarm: Humidifier Water Loss
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWDHT 1.3.6.1.4.1.9839.2.1.1.42
Alarm: CW Temperature too High for Dehumidification
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWF 1.3.6.1.4.1.9839.2.1.1.43
Alarm: CW Valve Failure or Water Flow too Low
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWFF 1.3.6.1.4.1.9839.2.1.1.44
Alarm: Loss of Water Flow
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWHT 1.3.6.1.4.1.9839.2.1.1.45
Alarm: High Chilled Water Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRTS 1.3.6.1.4.1.9839.2.1.1.46
Alarm: Room Temp. Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHWS 1.3.6.1.4.1.9839.2.1.1.47
Alarm: Hot Water Temp. Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWS 1.3.6.1.4.1.9839.2.1.1.48
Alarm: Chilled Water Temp. Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmOTS 1.3.6.1.4.1.9839.2.1.1.49
Alarm: Outdoor Temperature Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmDTS 1.3.6.1.4.1.9839.2.1.1.50
Alarm: Delivery Air Temp. Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmRHS 1.3.6.1.4.1.9839.2.1.1.51
Alarm: Room Humidity Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmCWOTS 1.3.6.1.4.1.9839.2.1.1.52
Alarm: Chilled Water Outlet T. Sensor Failed/Disconnected
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmC1Hours 1.3.6.1.4.1.9839.2.1.1.53
ServiceAlarm: Compressor 1 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmC2Hours 1.3.6.1.4.1.9839.2.1.1.54
ServiceAlarm: Compressor 2 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmC3Hours 1.3.6.1.4.1.9839.2.1.1.55
ServiceAlarm: Compressor 3 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmC4Hours 1.3.6.1.4.1.9839.2.1.1.56
ServiceAlarm: Compressor 4 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmFilterHours 1.3.6.1.4.1.9839.2.1.1.57
ServiceAlarm: Air Filter hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHeat1Hours 1.3.6.1.4.1.9839.2.1.1.58
ServiceAlarm: Heater 1 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHeat2Hours 1.3.6.1.4.1.9839.2.1.1.59
ServiceAlarm: Heater 1 hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHumHours 1.3.6.1.4.1.9839.2.1.1.60
ServiceAlarm: Humidifier hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmUnitHours 1.3.6.1.4.1.9839.2.1.1.61
ServiceAlarm: Unit hour counter threshold
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmDI2 1.3.6.1.4.1.9839.2.1.1.62
Alarm by Digital Input 2
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmDI4 1.3.6.1.4.1.9839.2.1.1.63
Alarm by Digital Input 4
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmDI6 1.3.6.1.4.1.9839.2.1.1.64
Alarm by Digital Input 6
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmHum 1.3.6.1.4.1.9839.2.1.1.65
Humidifier General Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmGeneral 1.3.6.1.4.1.9839.2.1.1.66
General Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarm2ndLevel 1.3.6.1.4.1.9839.2.1.1.67
Standby Unit Switchover Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmA 1.3.6.1.4.1.9839.2.1.1.68
Type A Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmB 1.3.6.1.4.1.9839.2.1.1.69
Type B Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

alarmC 1.3.6.1.4.1.9839.2.1.1.70
Type C Alarm
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

selDXCW 1.3.6.1.4.1.9839.2.1.1.71
DX/CW Switch on TC Units
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

selSW 1.3.6.1.4.1.9839.2.1.1.72
Summer/Winter Switchover
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

systemOnOff 1.3.6.1.4.1.9839.2.1.1.75
System On-Off
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetAlarm 1.3.6.1.4.1.9839.2.1.1.76
Alarm Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrsFilt 1.3.6.1.4.1.9839.2.1.1.77
Filter Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrC1 1.3.6.1.4.1.9839.2.1.1.78
Compressor 1 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrC2 1.3.6.1.4.1.9839.2.1.1.79
Compressor 2 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrC3 1.3.6.1.4.1.9839.2.1.1.80
Compressor 3 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrC4 1.3.6.1.4.1.9839.2.1.1.81
Compressor 4 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStC1 1.3.6.1.4.1.9839.2.1.1.82
Compressor 1 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStC2 1.3.6.1.4.1.9839.2.1.1.83
Compressor 2 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStC3 1.3.6.1.4.1.9839.2.1.1.84
Compressor 3 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStC4 1.3.6.1.4.1.9839.2.1.1.85
Compressor 4 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrH1 1.3.6.1.4.1.9839.2.1.1.86
Heater 1 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrH2 1.3.6.1.4.1.9839.2.1.1.87
Heater 2 Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStH1 1.3.6.1.4.1.9839.2.1.1.88
Heater 1 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStH2 1.3.6.1.4.1.9839.2.1.1.89
Heater 2 Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrHU 1.3.6.1.4.1.9839.2.1.1.90
Humidifier Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetStHU 1.3.6.1.4.1.9839.2.1.1.91
Humidifier Starting Counter Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

resetHrACU 1.3.6.1.4.1.9839.2.1.1.92
Unit Run Hours Reset
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

sleepmode 1.3.6.1.4.1.9839.2.1.1.95
Setback Mode (Sleep Mode)
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

smtest 1.3.6.1.4.1.9839.2.1.1.96
Sleep Mode Test
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

enablemeanT 1.3.6.1.4.1.9839.2.1.1.97
Local/Mean Usage of Values
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1  

analogObjects 1.3.6.1.4.1.9839.2.1.2
OBJECT IDENTIFIER    

roomTemp 1.3.6.1.4.1.9839.2.1.2.1
Room Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

outdoorTemp 1.3.6.1.4.1.9839.2.1.2.2
Ambient Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

deliveryTemp 1.3.6.1.4.1.9839.2.1.2.3
Delivery Air Temperature
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

cwTemp 1.3.6.1.4.1.9839.2.1.2.4
Chilled Water Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

hwTemp 1.3.6.1.4.1.9839.2.1.2.5
Hot Water Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

roomRH 1.3.6.1.4.1.9839.2.1.2.6
Room Relative Humidity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

cwoTemp 1.3.6.1.4.1.9839.2.1.2.7
Chilled Water Outlet Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

evapPress1 1.3.6.1.4.1.9839.2.1.2.8
Circuit 1 Evaporating Pressure
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

evapPress2 1.3.6.1.4.1.9839.2.1.2.9
Circuit 2 Evaporating Pressure
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

suctTemp1 1.3.6.1.4.1.9839.2.1.2.10
Circuit 1 Suction Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

suctTemp2 1.3.6.1.4.1.9839.2.1.2.11
Circuit 2 Suction Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

evapTemp1 1.3.6.1.4.1.9839.2.1.2.12
Circuit 1 Evap.Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

evapTemp2 1.3.6.1.4.1.9839.2.1.2.13
Circuit 2 Evap.Temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

ssh1 1.3.6.1.4.1.9839.2.1.2.14
Circuit 1 Superheat
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

ssh2 1.3.6.1.4.1.9839.2.1.2.15
Circuit 2 Superheat
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

coolRamp 1.3.6.1.4.1.9839.2.1.2.16
Cooling Valve Ramp
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

heatRamp 1.3.6.1.4.1.9839.2.1.2.17
Heating Valve Ramp
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

fanSpeed 1.3.6.1.4.1.9839.2.1.2.18
Evapor. Fan Speed
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

coolSetP 1.3.6.1.4.1.9839.2.1.2.20
Cooling Set Point
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

coolDiff 1.3.6.1.4.1.9839.2.1.2.21
Cooling Prop.Band
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

cool2SetP 1.3.6.1.4.1.9839.2.1.2.22
Cooling 2nd Set Point
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

heatSetP 1.3.6.1.4.1.9839.2.1.2.23
Heating Set point
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

heat2SetP 1.3.6.1.4.1.9839.2.1.2.24
Heating 2nd Set point
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

heatDiff 1.3.6.1.4.1.9839.2.1.2.25
Heating Prop.Band
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

thrsHT 1.3.6.1.4.1.9839.2.1.2.26
High Room Temperature Alarm Threshold
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

thrsLT 1.3.6.1.4.1.9839.2.1.2.27
Low Room Temperature Alarm Threshold
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

smCoolSetp 1.3.6.1.4.1.9839.2.1.2.28
Setback Mode: Cooling Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

smHeatSetp 1.3.6.1.4.1.9839.2.1.2.29
Setback Mode: Heating Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

cwDehumSetp 1.3.6.1.4.1.9839.2.1.2.30
CW Setpoint to Start Dehumidification
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

cwHtThrsh 1.3.6.1.4.1.9839.2.1.2.31
CW High Temperature Alarm Threshold
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

cwModeSetp 1.3.6.1.4.1.9839.2.1.2.32
CW Setpoint to start CW Operating Mode (Only TC Units)
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

radcoolSpES 1.3.6.1.4.1.9839.2.1.2.33
Radcooler Setpoint in Energy Saving Mode
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

radcoolSpDX 1.3.6.1.4.1.9839.2.1.2.34
Radcooler Setpoint in DX Mode
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

delTempLimit 1.3.6.1.4.1.9839.2.1.2.35
Delivery Temperature Low Limit Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

dtAutChgMLT 1.3.6.1.4.1.9839.2.1.2.36
Delta Temperature for Automatic Mean/Local Changeover
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

integerObjects 1.3.6.1.4.1.9839.2.1.3
OBJECT IDENTIFIER    

filterWorkH 1.3.6.1.4.1.9839.2.1.3.1
Air Filter Working Houres
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

unitWorkH 1.3.6.1.4.1.9839.2.1.3.2
Unit Working Houres
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

compr1WorkH 1.3.6.1.4.1.9839.2.1.3.3
Compressor 1 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

compr2WorkH 1.3.6.1.4.1.9839.2.1.3.4
Compressor 2 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

compr3WorkH 1.3.6.1.4.1.9839.2.1.3.5
Compressor 3 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

compr4WorkH 1.3.6.1.4.1.9839.2.1.3.6
Compressor 4 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

heat1WorkH 1.3.6.1.4.1.9839.2.1.3.7
Heater 1 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

heat2WorkH 1.3.6.1.4.1.9839.2.1.3.8
Heater 2 Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

humiWorkH 1.3.6.1.4.1.9839.2.1.3.9
Humidifier Run Hours
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

dehumPband 1.3.6.1.4.1.9839.2.1.3.12
Dehumidification Prop.Band
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

humidPband 1.3.6.1.4.1.9839.2.1.3.13
Humidification Prop.Band
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

hhAlarmThrsh 1.3.6.1.4.1.9839.2.1.3.14
High Humidity Alarm Threshold
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

lhAlarmThrsh 1.3.6.1.4.1.9839.2.1.3.15
Low Humidity Alarm Threshold
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

dehumSetp 1.3.6.1.4.1.9839.2.1.3.16
Dehumidification Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

smDehumSetp 1.3.6.1.4.1.9839.2.1.3.17
Setback Mode: Dehumidification Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

humidSetp 1.3.6.1.4.1.9839.2.1.3.18
Humidification Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

smHumidSetp 1.3.6.1.4.1.9839.2.1.3.19
Setback Mode: Humidification Setpoint
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

pwOnDelay 1.3.6.1.4.1.9839.2.1.3.20
Restart Delay
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

regulDelay 1.3.6.1.4.1.9839.2.1.3.21
Regulation Start Transitory
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

lowPdelay 1.3.6.1.4.1.9839.2.1.3.22
Low Pressure Delay
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

thAlarmdelay 1.3.6.1.4.1.9839.2.1.3.23
Temp./Humid.Limits Alarm Delay
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

regExcTime 1.3.6.1.4.1.9839.2.1.3.24
Anti-Hunting Constant
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

stdbyTime 1.3.6.1.4.1.9839.2.1.3.25
Stand-by Cycle Base Time
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

lanUnit 1.3.6.1.4.1.9839.2.1.3.27
Number of LAN Units
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

smCycleTime 1.3.6.1.4.1.9839.2.1.3.28
Sleep Mode Testing Cycle Time
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -32767..32767  

exv1steps 1.3.6.1.4.1.9839.2.1.3.29
Circuit 1 EXV Valve Position
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767  

exv2steps 1.3.6.1.4.1.9839.2.1.3.30
Circuit 2 EXV Valve Position
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -32767..32767