CCPOWER-MIB
File:
CCPOWER-MIB.mib (52584 bytes)
Imported modules
Imported symbols
Defined Values
ccpower |
1.3.6.1.4.1.18642 |
OBJECT IDENTIFIER |
|
|
|
dcSystem |
1.3.6.1.4.1.18642.1 |
OBJECT IDENTIFIER |
|
|
|
settings |
1.3.6.1.4.1.18642.1.1.1 |
OBJECT IDENTIFIER |
|
|
|
floatVoltage |
1.3.6.1.4.1.18642.1.1.1.1 |
Rectifier DC Output Voltage.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
overloadCurrent |
1.3.6.1.4.1.18642.1.1.1.2 |
Current which when exceeded will cause an alarm.
Return value is XXXX representing XXXX amps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
highVoltageAlarm |
1.3.6.1.4.1.18642.1.1.1.3 |
Voltage which when exceeded will cause an alarm.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
lowVoltageAlarm |
1.3.6.1.4.1.18642.1.1.1.4 |
Voltage which when exceeded will cause an alarm.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect1Voltage |
1.3.6.1.4.1.18642.1.1.1.5 |
Voltage which when exceeded will cause a specific load to disconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect1Temperature |
1.3.6.1.4.1.18642.1.1.1.6 |
Temperature which when exceeded will cause a specific load to disconnect.
Return value is XX representing XX oC. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect1LoadShedSundayOff |
1.3.6.1.4.1.18642.1.1.1.7 |
Time on Sunday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedMondayOff |
1.3.6.1.4.1.18642.1.1.1.8 |
Time on Monday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedTuesdayOff |
1.3.6.1.4.1.18642.1.1.1.9 |
Time on Tuesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedWednesdayOff |
1.3.6.1.4.1.18642.1.1.1.10 |
Time on Wednesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedThursdayOff |
1.3.6.1.4.1.18642.1.1.1.11 |
Time on Thursday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedFridayOff |
1.3.6.1.4.1.18642.1.1.1.12 |
Time on Friday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1LoadShedSaturdayOff |
1.3.6.1.4.1.18642.1.1.1.13 |
Time on Saturday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2Voltage |
1.3.6.1.4.1.18642.1.1.1.14 |
Voltage which when exceeded will cause a specific load to disconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect2Temperature |
1.3.6.1.4.1.18642.1.1.1.15 |
Temperature which when exceeded will cause a specific load to disconnect.
Return value is XX representing XX oC. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect2LoadShedSundayOff |
1.3.6.1.4.1.18642.1.1.1.16 |
Time on Sunday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedMondayOff |
1.3.6.1.4.1.18642.1.1.1.17 |
Time on Monday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedTuesdayOff |
1.3.6.1.4.1.18642.1.1.1.18 |
Time on Tuesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedWednesdayOff |
1.3.6.1.4.1.18642.1.1.1.19 |
Time on Wednesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedThursdayOff |
1.3.6.1.4.1.18642.1.1.1.20 |
Time on Thursday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedFridayOff |
1.3.6.1.4.1.18642.1.1.1.21 |
Time on Friday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2LoadShedSaturdayOff |
1.3.6.1.4.1.18642.1.1.1.22 |
Time on Saturday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3Voltage |
1.3.6.1.4.1.18642.1.1.1.23 |
Voltage which when exceeded will cause a specific load to disconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect3Temperature |
1.3.6.1.4.1.18642.1.1.1.24 |
Temperature which when exceeded will cause a specific load to disconnect.
Return value is XX representing XX oC. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
disconnect3LoadShedSundayOff |
1.3.6.1.4.1.18642.1.1.1.25 |
Time on Sunday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedMondayOff |
1.3.6.1.4.1.18642.1.1.1.26 |
Time on Monday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedTuesdayOff |
1.3.6.1.4.1.18642.1.1.1.27 |
Time on Tuesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedWednesdayOff |
1.3.6.1.4.1.18642.1.1.1.28 |
Time on Wednesday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedThursdayOff |
1.3.6.1.4.1.18642.1.1.1.29 |
Time on Thursday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedFridayOff |
1.3.6.1.4.1.18642.1.1.1.30 |
Time on Friday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3LoadShedSaturdayOff |
1.3.6.1.4.1.18642.1.1.1.31 |
Time on Saturday which when reached will cause a specific load to disconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1Voltage |
1.3.6.1.4.1.18642.1.1.1.32 |
Voltage which when reached will cause a specific load to reconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
reconnect1LoadShedSundayOn |
1.3.6.1.4.1.18642.1.1.1.33 |
Time which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedMondayOn |
1.3.6.1.4.1.18642.1.1.1.34 |
Time on Monday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedTuesdayOn |
1.3.6.1.4.1.18642.1.1.1.35 |
Time on Tuesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedWednesdayOn |
1.3.6.1.4.1.18642.1.1.1.36 |
Time on Wednesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedThursdayOn |
1.3.6.1.4.1.18642.1.1.1.37 |
Time on Thursday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedFridayOn |
1.3.6.1.4.1.18642.1.1.1.38 |
Time on Friday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect1LoadShedSaturdayOn |
1.3.6.1.4.1.18642.1.1.1.39 |
Time on Saturday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2Voltage |
1.3.6.1.4.1.18642.1.1.1.40 |
Voltage which when reached will cause a specific load to reconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
reconnect2LoadShedSundayOn |
1.3.6.1.4.1.18642.1.1.1.41 |
Time on Sunday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedMondayOn |
1.3.6.1.4.1.18642.1.1.1.42 |
Time on Monday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedTuesdayOn |
1.3.6.1.4.1.18642.1.1.1.43 |
Time on Tuesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedWednesdayOn |
1.3.6.1.4.1.18642.1.1.1.44 |
Time on Wednesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedThursdayOn |
1.3.6.1.4.1.18642.1.1.1.45 |
Time on Thursday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedFridayOn |
1.3.6.1.4.1.18642.1.1.1.46 |
Time on Friday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2LoadShedSaturdayOn |
1.3.6.1.4.1.18642.1.1.1.47 |
Time on Saturday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3Voltage |
1.3.6.1.4.1.18642.1.1.1.48 |
Voltage which when reached will cause a specific load to reconnect.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
reconnect3LoadShedSundayOn |
1.3.6.1.4.1.18642.1.1.1.49 |
Time on Sunday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedMondayOn |
1.3.6.1.4.1.18642.1.1.1.50 |
Time on Monday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedTuesdayOn |
1.3.6.1.4.1.18642.1.1.1.51 |
Time on Tuesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedWednesdayOn |
1.3.6.1.4.1.18642.1.1.1.52 |
Time on Wednesday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedThursdayOn |
1.3.6.1.4.1.18642.1.1.1.53 |
Time on Thursday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedFridayOn |
1.3.6.1.4.1.18642.1.1.1.54 |
Time on Friday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3LoadShedSaturdayOn |
1.3.6.1.4.1.18642.1.1.1.55 |
Time on Saturday which when reached will cause a specific load to reconnect.
Return value is XX:XX representing HH:MM. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
equalizeTime |
1.3.6.1.4.1.18642.1.1.1.56 |
Number of hours the equalize voltage is to be applied.
Return value is XXX representing XX.X hours. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
equalizeVoltage |
1.3.6.1.4.1.18642.1.1.1.57 |
Equalize voltage to be applied.
Return value is XXX representing XX.X volts. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryResistancePercentChange |
1.3.6.1.4.1.18642.1.1.1.58 |
Resistance percentange change that when reached will cause an alarm.
Return value is XXX representing XXX %. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryResistanceTestInterval |
1.3.6.1.4.1.18642.1.1.1.59 |
Battery resistance test interval.
Return value is XX representing XX weeks. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
loadShedTimeControl |
1.3.6.1.4.1.18642.1.1.1.60 |
Load shed time control enabled/disabled status.
Return value: 1 = time control enabled, 2 = time control disabled. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enabled(1), disabled(2) |
|
batteryFloatCurrent |
1.3.6.1.4.1.18642.1.1.1.61 |
Battery float current.
Return value is XXX representing XXX amps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
rectifiers |
1.3.6.1.4.1.18642.1.2.1 |
OBJECT IDENTIFIER |
|
|
|
rectifierFloatVoltage |
1.3.6.1.4.1.18642.1.2.1.1 |
Rectifier float voltage.
Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
rectifierLoadCurrent |
1.3.6.1.4.1.18642.1.2.1.2 |
Rectifier DC load current.
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteries |
1.3.6.1.4.1.18642.1.2.2 |
OBJECT IDENTIFIER |
|
|
|
batteryCurrent |
1.3.6.1.4.1.18642.1.2.2.1 |
Battery current.
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTemperature |
1.3.6.1.4.1.18642.1.2.2.2 |
Battery temperature.
Return value is XX representing XX oC. Valid ranges are -40 to 99 oC. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryResistanceReference |
1.3.6.1.4.1.18642.1.2.2.3 |
Initial battery resistance.
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryResistanceReading |
1.3.6.1.4.1.18642.1.2.2.4 |
Last battery resistance reading.
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryResistanceChange |
1.3.6.1.4.1.18642.1.2.2.5 |
Percent change from last battery resistance reading.
Return value is XXX representing XXX %. Valid ranges are 001 to 999 %. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryCycles1 |
1.3.6.1.4.1.18642.1.2.2.6 |
Number of discharge/recharge cycles less than 1 minute.
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryCycles1to5 |
1.3.6.1.4.1.18642.1.2.2.7 |
Number of discharge/recharge cycles from 1 to 5 minutes.
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryCycles5to15 |
1.3.6.1.4.1.18642.1.2.2.8 |
Number of discharge/recharge cycles from 5 to 15 minutes.
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryCycles15 |
1.3.6.1.4.1.18642.1.2.2.9 |
Number of discharge/recharge cycles greater than 15 minutes.
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryCycles15LastDuration |
1.3.6.1.4.1.18642.1.2.2.11 |
Duration of batteryCycles15 last cycle.
Return value is XXXX representing XXXX minutes. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
batteryTestFault |
1.3.6.1.4.1.18642.1.2.2.12 |
Battery failure has occured during battery restistance test.
Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
abort1(1), abort2(2), abort3(3), none(4) |
|
floatVoltagePresets |
1.3.6.1.4.1.18642.1.2.3.1 |
Float voltage factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
highVoltageAlarmPresets |
1.3.6.1.4.1.18642.1.2.3.2 |
High voltage alarm factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
lowVoltageAlarmPresets |
1.3.6.1.4.1.18642.1.2.3.3 |
Low voltage alarm factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect1VoltagePresets |
1.3.6.1.4.1.18642.1.2.3.4 |
Disconnect voltage 1 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnectVoltage1Presets |
1.3.6.1.4.1.18642.1.2.3.13 |
Reconnect voltage 1 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect2VoltagePresets |
1.3.6.1.4.1.18642.1.2.3.14 |
Disconnect voltage 2 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect2VoltagePresets |
1.3.6.1.4.1.18642.1.2.3.23 |
Reconnect voltage 2 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
disconnect3VoltagePresets |
1.3.6.1.4.1.18642.1.2.3.24 |
Disconnect voltage 3 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
reconnect3VoltagePresets |
1.3.6.1.4.1.18642.1.2.3.33 |
Reconnect voltage 3 factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
overloadCurrentPresets |
1.3.6.1.4.1.18642.1.2.3.34 |
Overload current factory setting range.
Return value is XXXX amps min, XXXX amps max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
maximumCurrentPreset |
1.3.6.1.4.1.18642.1.2.3.35 |
Maximum current factory setting.
Return value is XXXX amps. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
batteryFloatCurrentPresets |
1.3.6.1.4.1.18642.1.2.3.36 |
Battery float current factory settings.
Return value is XXX amps min, XXX amps max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
equalizeTimePresets |
1.3.6.1.4.1.18642.1.2.3.37 |
Equalize time factory setting range.
Return value is 00.0 hours min, XX.X hours max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
equalizeVoltagePresets |
1.3.6.1.4.1.18642.1.2.3.38 |
Equalize voltage factory setting range.
Return value is XX.X volts min, XX.X volts max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
batteryResistancePresets |
1.3.6.1.4.1.18642.1.2.3.39 |
Battery resistance percent change factory setting range.
Return value is XXX % min, XXX % max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
batteryTestIntervalPresets |
1.3.6.1.4.1.18642.1.2.3.40 |
Battery resistance test interval factory setting range.
Return value is XX weeks min, XX weeks max. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
highVoltageAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.1 |
High voltage alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.2 |
Low voltage alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
overloadAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.3 |
Overload alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
breakerAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.4 |
Breaker alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
acFailureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.5 |
AC failure alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
fanFailureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.6 |
Fan failure alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
rectifierFailureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.7 |
Rectifier failure alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
majorAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.8 |
Major alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect1TemperatureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.9 |
Low voltage disconnect 1 high temperature alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect2TemperatureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.10 |
Low voltage disconnect 2 high temperature alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect3TemperatureAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.11 |
Low voltage disconnect 3 high temperature alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect1VoltageAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.12 |
Low voltage disconnect 1 low voltage alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect2VoltageAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.13 |
Low voltage disconnect 2 low voltage alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
lowVoltageDisconnect3VoltageAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.14 |
Low voltage disconnect 3 low voltage alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryResistanceAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.15 |
Battery resistance alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryCurrentAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.16 |
Battery resistance alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryTestAbortCondition1AlarmStatus |
1.3.6.1.4.1.18642.1.2.4.17 |
Battery test abort condition 1 alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryTestAbortCondition2AlarmStatus |
1.3.6.1.4.1.18642.1.2.4.18 |
Battery test abort condition 2 alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryTestAbortCondition3AlarmStatus |
1.3.6.1.4.1.18642.1.2.4.19 |
Battery test abort condition 3 alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
batteryDisconnectAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.20 |
Battery disconnect alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
fuseAlarmStatus |
1.3.6.1.4.1.18642.1.2.4.21 |
Fuse alarm status.
Return value 1 = alarm inactive, 2 = alarm active. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
inactive(1), active(2) |
|
highVoltageTrap |
4 |
Float voltage has exceeded preset value.
Return value: High voltage alarm XX.X volts. |
TRAP-TYPE |
|
|
|
lowVoltageTrap |
5 |
Float voltage is below preset value.
Return value: Low voltage alarm XX.X volts. |
TRAP-TYPE |
|
|
|
loadOverCurrentTrap |
6 |
Load current has exceeded preset value.
Return value: Load over current alarm XXXX amps. |
TRAP-TYPE |
|
|
|
batteryFloatCurrentTrap |
7 |
Battery float current has exceeded preset value.
Return value: Battery float current alarm XXXX amps. |
TRAP-TYPE |
|
|
|
loadDisconnect1VoltageTrap |
8 |
Load disconnect 1 voltage has dropped below preset value.
Return value: Load disconnect 1 voltage XX.X volts. |
TRAP-TYPE |
|
|
|
loadDisconnect2VoltageTrap |
9 |
Load disconnect 2 voltage has dropped below preset value.
Return value: Load disconnect 2 voltage XX.X volts. |
TRAP-TYPE |
|
|
|
loadDisconnect3VoltageTrap |
10 |
Load disconnect 3 voltage has dropped below preset value.
Return value: Load disconnect 3 voltage XX.X volts. |
TRAP-TYPE |
|
|
|
loadDisconnect1TemperatureTrap |
11 |
Load disconnect 1 temperature has exceeded preset value.
Return value: Load disconnect 1 temperature alarm XX oC. |
TRAP-TYPE |
|
|
|
loadDisconnect2TemperatureTrap |
12 |
Load disconnect 2 temperature has exceeded preset value.
Return value: Load disconnect 2 temperature alarm XX oC. |
TRAP-TYPE |
|
|
|
loadDisconnect3TemperatureTrap |
13 |
Load disconnect 3 temperature has exceeded preset value.
Return value: Load disconnect 3 temperature alarm XX oC. |
TRAP-TYPE |
|
|
|
fanFailureTrap |
15 |
Rectifier fan has failed.
Return value: Fan failure. |
TRAP-TYPE |
|
|
|
acFailureTrap |
16 |
Rectifier has lost AC input power.
Return value: AC failure. |
TRAP-TYPE |
|
|
|
majorFailureTrap |
17 |
Multiple failures of AC, rectififers, fans or a programmed alarm.
Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred. |
TRAP-TYPE |
|
|
|
batteryResistanceTrap |
18 |
Battery resistance has increased by a programmed percentage.
Return value: Battery resistance alarm X.XXXX ohms, XXX %. |
TRAP-TYPE |
|
|
|
batteryTestAbort1Trap |
19 |
Battery failure abort 1 has occured during battery resistance test.
Return value: Battery test failure: Abort 1. |
TRAP-TYPE |
|
|
|
batteryTestAbort2Trap |
20 |
Battery failure abort 2 has occured during battery resistance test.
Return value: Battery test failure: Abort 2. |
TRAP-TYPE |
|
|
|
batteryTestAbort3Trap |
21 |
Battery failure abort 3 has occured during battery resistance test.
Return value: Battery test failure: Abort 3. |
TRAP-TYPE |
|
|
|