CPQRPM-MIB

File: CPQRPM-MIB.mib (85188 bytes)

Imported modules

CPQHOST-MIB RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

compaq DisplayString OBJECT-TYPE
TRAP-TYPE sysName

Defined Values

cpqRPM 1.3.6.1.4.1.232.154
OBJECT IDENTIFIER    

cpqRPMTrapInfo 1.3.6.1.4.1.232.154.1
OBJECT IDENTIFIER    

cpqRPMTraps 1.3.6.1.4.1.232.154.2
OBJECT IDENTIFIER    

cpqPMTraps 1.3.6.1.4.1.232.154.3
OBJECT IDENTIFIER    

cpqRPMTrapDescription 1.3.6.1.4.1.232.154.1.1
Text description of the event that caused the trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqRPMTrapDeviceId 1.3.6.1.4.1.232.154.1.2
A unique numeric identifier for the device that caused the trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2147483647  

cpqRPMTrapDeviceName 1.3.6.1.4.1.232.154.1.3
The text name for the device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cpqRPMTrapDeviceAddress 1.3.6.1.4.1.232.154.1.4
The hostname or ip address for the device.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..50)  

cpqRPMTrapType 1.3.6.1.4.1.232.154.1.5
Indicates the type of the event that caused the trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER system(1), event(2), change(3), power(4), environment(5)  

cpqRPMTrapSeverity 1.3.6.1.4.1.232.154.1.6
Indicates the severity of the event that caused the trap.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), information(2), normal(3), minor(4), major(5), critical(6)  

cpqRPMTrapCode 1.3.6.1.4.1.232.154.1.7
A unique identifier for the alarm.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2147483647  

cpqRPMTrapURL 1.3.6.1.4.1.232.154.1.8
The URL for the management software.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqRPMTrapDeviceConnected 1
A UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE    

cpqRPMTrapConnectionLost 2
A UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE    

cpqRPMTrapLookupFailed 3
CRPM failed to find an IP address for the device hostname.
TRAP-TYPE    

cpqRPMTrapConnectionFailed 4
CRPM failed to connect to a device.
TRAP-TYPE    

cpqRPMTrapDeviceSettingsChanged 5
Device settings have been changed by a user.
TRAP-TYPE    

cpqRPMTrapCMCTemp1BelowMin 10001
A CMC device is reporting temperature 1 below minimum threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp1AboveWarn 10002
A CMC device is reporting temperature 1 above warning threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp1AboveMax 10003
A CMC device is reporting temperature 1 above maximum threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp1Normal 10004
A CMC device is reporting temperature 1 has returned to a normal temperature.
TRAP-TYPE    

cpqRPMTrapCMCTemp2BelowMin 10005
A CMC device is reporting temperature 2 below minimum threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp2AboveWarn 10006
A CMC device is reporting temperature 2 above warning threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp2AboveMax 10007
A CMC device is reporting temperature 2 above maximum threshold.
TRAP-TYPE    

cpqRPMTrapCMCTemp2Normal 10008
A CMC device is reporting temperature 2 has returned to a normal temperature.
TRAP-TYPE    

cpqRPMTrapCMCVoltUnder 10011
A CMC device is reporting voltage below minimum threshold.
TRAP-TYPE    

cpqRPMTrapCMCVoltOver 10012
A CMC device is reporting voltage above maximum threshold.
TRAP-TYPE    

cpqRPMTrapCMCVoltNormal 10013
A CMC device is reporting voltage has returned to normal.
TRAP-TYPE    

cpqRPMTrapCMCHmdtUnder 10021
A CMC device is reporting humidity below minimum threshold.
TRAP-TYPE    

cpqRPMTrapCMCHmdtOver 10022
A CMC device is reporting humidity above maximum threshold.
TRAP-TYPE    

cpqRPMTrapCMCHmdtNormal 10023
A CMC device is reporting humidity has returned to normal.
TRAP-TYPE    

cpqRPMTrapCMCSmokeDetected 10031
A CMC device is reporting smoke detected.
TRAP-TYPE    

cpqRPMTrapCMCSmokeCleared 10032
A CMC device is reporting smoke cleared.
TRAP-TYPE    

cpqRPMTrapCMCShockDetected 10041
A CMC device is reporting shock detected.
TRAP-TYPE    

cpqRPMTrapCMCShockCleared 10042
A CMC device is reporting shock cleared.
TRAP-TYPE    

cpqRPMTrapCMCAux1Alarm 10051
A CMC device has entered an alarm condition for auxiliary input 1.
TRAP-TYPE    

cpqRPMTrapCMCAux1Cleared 10052
A CMC device is reporting auxiliary input 1 alarm cleared.
TRAP-TYPE    

cpqRPMTrapCMCAux2Alarm 10053
A CMC device has entered an alarm condition for auxiliary input 2.
TRAP-TYPE    

cpqRPMTrapCMCAux2Cleared 10054
A CMC device is reporting auxiliary input 2 alarm cleared.
TRAP-TYPE    

cpqRPMTrapCMCInput1Opened 10101
A CMC device is reporting input 1 has been opened.
TRAP-TYPE    

cpqRPMTrapCMCInput1Closed 10102
A CMC device is reporting input 1 has been closed.
TRAP-TYPE    

cpqRPMTrapCMCInput2Opened 10103
A CMC device is reporting input 2 has been opened.
TRAP-TYPE    

cpqRPMTrapCMCInput2Closed 10104
A CMC device is reporting input 2 has been closed.
TRAP-TYPE    

cpqRPMTrapCMCInput3Opened 10105
A CMC device is reporting input 3 has been opened.
TRAP-TYPE    

cpqRPMTrapCMCInput3Closed 10106
A CMC device is reporting input 3 has been closed.
TRAP-TYPE    

cpqRPMTrapCMCInput4Opened 10107
A CMC device is reporting input 4 has been opened.
TRAP-TYPE    

cpqRPMTrapCMCInput4Closed 10108
A CMC device is reporting input 4 has been closed.
TRAP-TYPE    

cpqRPMTrapCMCLockset1Unlocked 10111
A CMC device is reporting lockset 1 has been unlocked.
TRAP-TYPE    

cpqRPMTrapCMCLockset1FailedToLock 10112
A CMC device is reporting lockset 1 has failed to lock.
TRAP-TYPE    

cpqRPMTrapCMCLockset1Error 10113
A CMC device is reporting an error with lockset 1.
TRAP-TYPE    

cpqRPMTrapCMCLockset1Locked 10114
A CMC device is reporting lockset 1 has been locked.
TRAP-TYPE    

cpqRPMTrapCMCLockset2Unlocked 10116
A CMC device is reporting lockset 2 has been unlocked.
TRAP-TYPE    

cpqRPMTrapCMCLockset2FailedToLock 10117
A CMC device is reporting lockset 2 has failed to lock.
TRAP-TYPE    

cpqRPMTrapCMCLockset2Error 10118
A CMC device is reporting an error with lockset 2.
TRAP-TYPE    

cpqRPMTrapCMCLockset2Locked 10119
A CMC device is reporting lockset 2 has been locked.
TRAP-TYPE    

cpqRPMTrapCMCLockset1Normal 10134
A CMC device is reporting lockset 2 is normal.
TRAP-TYPE    

cpqRPMTrapCMCLockset2Normal 10135
A CMC device is reporting lockset 2 is normal.
TRAP-TYPE    

cpqRPMTrapUPSInputVoltageBelowMin 20001
A UPS device is reporting input voltage below minimum threshold.
TRAP-TYPE    

cpqRPMTrapUPSInputVoltageAboveMax 20002
A UPS device is reporting input voltage above maximum threshold.
TRAP-TYPE    

cpqRPMTrapUPSInputVoltageNormal 20003
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    

cpqRPMTrapUPSOutputVoltageBelowMin 20011
A UPS device is reporting output voltage below minimum threshold.
TRAP-TYPE    

cpqRPMTrapUPSOutputVoltageAboveMax 20012
A UPS device is reporting output voltage above maximum threshold.
TRAP-TYPE    

cpqRPMTrapUPSOutputVoltageNormal 21020
A UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSOutputOverload 20014
A UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE    

cpqRPMTrapUPSOutputOverloadCleared 20015
A UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE    

cpqRPMTrapUPSBatteryLow 21055
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    

cpqRPMTrapUPSBatteryLowCleared 21056
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    

cpqRPMTrapUPSBatteryDepleted 20022
A UPS device is a depleted battery.
TRAP-TYPE    

cpqRPMTrapUPSBatteryLevelNormal 20023
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    

cpqRPMTrapUPSOnBattery 21063
A UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    

cpqRPMTrapUPSOnBypass 20032
A UPS device is being bypassed.
TRAP-TYPE    

cpqRPMTrapUPSOnBuck 21029
A UPS device is reporting an On Buck condition due to the following. 1. Utility power has increased above recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE    

cpqRPMTrapUPSOnBoost 21031
A UPS device is reporting an On Boost condition due to the following. 1. Utility power has dropped below recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE    

cpqRPMTrapUPSOnUtilityPower 21064
A UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    

cpqRPMTrapUPSTemperatureLow 20101
A UPS device is reporting temperature blow minimum threshold.
TRAP-TYPE    

cpqRPMTrapUPSTemperatureHigh 20102
A UPS device is reporting temperature above maximum threshold.
TRAP-TYPE    

cpqRPMTrapUPSTemperatureNormal 20103
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    

cpqRPMTrapUPSInternalFailure 20111
A UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSInternalFailureCleared 20112
A UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSBatteryFailure 20121
A UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSBatteryFailureCleared 20122
A UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSDiagnosticTestFailed 20131
A UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSDiagnosticTestSucceeded 20132
A UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSInputUnderOverFreq 20141
Input (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation.
TRAP-TYPE    

cpqRPMTrapUPSInputUnderOverFreqCleared 20142
Measured input frequency is normal
TRAP-TYPE    

cpqRPMTrapUPSDCStartOccurred 29998
The UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
TRAP-TYPE    

cpqRPMTrapUPSDCStartOccurredCleared 29999
The UPS has been started on utility while AC input power is present.
TRAP-TYPE    

cpqRPMTrapUPSBypassNotAvailable 20161
A UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSBypassNotAvailableCleared 20162
A UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSUtilityFail 20171
Indicates that the utility input power is not within predetermined limits. This could be, but is not limited to, over voltage, under voltage, over frequency, under frequency or over current.
TRAP-TYPE    

cpqRPMTrapUPSUtilityFailCleared 20172
Indicates that the utility input power is within predetermined limits.
TRAP-TYPE    

cpqRPMTrapUPSUtilityNotPresent 20181
Indicates that the utility input is not present. This differs from alarm #57 in that the detected voltage is zero in this case.
TRAP-TYPE    

cpqRPMTrapUPSUtilityNotPresentCleared 20182
Indicates that the utility input is present.
TRAP-TYPE    

cpqRPMTrapUPSBypassManualTurnedOn 20191
The bypass has been given a manual turn on command.
TRAP-TYPE    

cpqRPMTrapUPSBypassManualTurnedOff 20192
The bypass has been given a manual turn off command.
TRAP-TYPE    

cpqRPMTrapUPSSiteWiringFault 20201
A UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE    

cpqRPMTrapUPSSiteWiringNormal 20202
A UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE    

cpqRPMtrapUPSBypassOffManual 21060
A UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    

cpqRPMtrapUPSBypassONManual 21059
A UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    

cppqRPMtrapUPSStartedOnBatteryCleared 20152
A UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    

cppqRPMtrapUPSStartedOnBattery 20151
A UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load.
TRAP-TYPE    

cpqRPMtrapUPSInputOutofRangeCleared 21022
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    

cpqRPMtrapUPSInputOutofRange 21021
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    

cpqRPMtrapUPSTemperatureOutOfRange 21007
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    

cpqRPMtrapUPSTemperatureOutOfRangeCleared 21008
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    

cpqRPMtrapUPSBypassOnAuto 21047
A UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    

cpqRPMtrapUPSBypassOnAutoCleared 21048
A UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    

cpqRPMtrapUPSOutputoutofRange 21019
A UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSBatteriesDisconnected 21053
A UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSBatteriesDisconnectedCleared 21054
A UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSBatteryDischarged 21057
A UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSBatteryDischargedCleared 21058
A UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE    

cpqRPMTrapUPSCheckBreaker 21041
A UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSCheckBreakerCleared 21042
A UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSEPOInitiated 21037
A UPS device is reporting an Emergency Power Off (EPO) command has been received to shutdown the UPS immediately with out delay. This command may come from a local control panel or from a remote source. Recommendations: 1. Turn the UPS on to reapply power to attached equipment.
TRAP-TYPE    

cpqRPMTrapUPSManualLoadDumped 21033
The UPS has been powered off with user interaction.
TRAP-TYPE    

cpqRPMTrapUPSManualLoadDumpedCleared 21034
The UPS has been powered off with user interaction.
TRAP-TYPE    

cpqRPMTrapUPSCabinetDoorOpen 21045
A UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSCabinetDoorOpenCleared 21046
A UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSFanFailure 21035
A UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSFanFailureCleared 21036
A UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE    

cpqRPMTrapUPSLossOfRedundancy 21023
A UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE    

cpqRPMTrapUPSLossOfRedundancyCleared 21024
A UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE    

cpqRPMTrapUPSShutdownImminent 21013
A UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    

cpqRPMTrapUPSShutdownImminentCleared 21014
A UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    

cpqRPMTrapUPSShutdownPending 21011
A UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    

cpqRPMTrapUPSShutdownPendingCleared 21012
A UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    

cpqRPMTestTrap 50001
This trap is sent to test SNMP setup.
TRAP-TYPE    

cpqPMTrapCritical 1
A critical alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    

cpqPMTrapWarning 2
A warning alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    

cpqPMTrapInformation 3
An information alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    

cpqPMTrapCleared 4
An alarm has cleared. Action: Check the Trap Details for more information.
TRAP-TYPE