CPQUPS-MIB

File: CPQUPS-MIB.mib (24215 bytes)

Imported modules

CPQHOST-MIB RFC1155-SMI RFC1213-MIB
RFC-1212 RFC-1215

Imported symbols

compaq enterprises DisplayString
OBJECT-TYPE TRAP-TYPE sysName
cpqHoTrapFlags

Defined Types

CpqUpsOsCommonModuleEntry  
SEQUENCE    
  cpqUpsOsCommonModuleIndex INTEGER
  cpqUpsOsCommonModuleName DisplayString
  cpqUpsOsCommonModuleVersion DisplayString
  cpqUpsOsCommonModuleDate OCTET STRING
  cpqUpsOsCommonModulePurpose DisplayString

CpqUpsMemberEntry  
SEQUENCE    
  cpqUpsMemberIndex INTEGER
  cpqUpsMemberName DisplayString
  cpqUpsMemberCommunityStr DisplayString

Defined Values

cpqUps 1.3.6.1.4.1.232.12
OBJECT IDENTIFIER    

cpqUpsMibRev 1.3.6.1.4.1.232.12.1
OBJECT IDENTIFIER    

cpqUpsComponent 1.3.6.1.4.1.232.12.2
OBJECT IDENTIFIER    

cpqUpsInterface 1.3.6.1.4.1.232.12.2.1
OBJECT IDENTIFIER    

cpqUpsBasic 1.3.6.1.4.1.232.12.2.2
OBJECT IDENTIFIER    

cpqUpsFamily 1.3.6.1.4.1.232.12.2.3
OBJECT IDENTIFIER    

cpqUpsOsCommon 1.3.6.1.4.1.232.12.2.1.4
OBJECT IDENTIFIER    

cpqUpsMibRevMajor 1.3.6.1.4.1.232.12.1.1
The Major Revision level of the MIB. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information supported and/or the meaning of the supported information, correct interpretation of data may require a MIB document with the same major revision level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cpqUpsMibRevMinor 1.3.6.1.4.1.232.12.1.2
The Minor Revision level of the MIB. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

cpqUpsMibCondition 1.3.6.1.4.1.232.12.1.3
The overall condition. This object represents the overall status of the UPS system represented by this MIB.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4)  

cpqUpsOsCommonPollFreq 1.3.6.1.4.1.232.12.2.1.4.1
The Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (0) indicates that the Insight Agent retrieves the information upon request of a management station, it does not poll the device driver at a specific interval. If the poll frequency is zero (0) all attempts to write to this object will fail. If the poll frequency is non-zero, setting this value will change the polling frequency of the Insight Agent. Setting the poll frequency to zero (0) will always fail, an agent may also choose to fail any request to change the poll frequency to a value that would severely impact system performance.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

cpqUpsOsCommonModuleTable 1.3.6.1.4.1.232.12.2.1.4.2
A table of software modules/ that provide an interface to the device this MIB describes.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqUpsOsCommonModuleEntry

cpqUpsOsCommonModuleEntry 1.3.6.1.4.1.232.12.2.1.4.2.1
A description of a software module that provides an interface to the device this MIB describes.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqUpsOsCommonModuleEntry  

cpqUpsOsCommonModuleIndex 1.3.6.1.4.1.232.12.2.1.4.2.1.1
A unique index for this module description.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..255  

cpqUpsOsCommonModuleName 1.3.6.1.4.1.232.12.2.1.4.2.1.2
The module name.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsOsCommonModuleVersion 1.3.6.1.4.1.232.12.2.1.4.2.1.3
The module version in XX.YY format. Where XX is the major version number and YY is the minor version number. This field will be a null (size 0) string if the agent cannot provide the module version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..5)  

cpqUpsOsCommonModuleDate 1.3.6.1.4.1.232.12.2.1.4.2.1.4
The module date. field octets contents range ===== ====== ======= ===== 1 1-2 year 0..65536 2 3 month 1..12 3 4 day 1..31 4 5 hour 0..23 5 6 minute 0..59 6 7 second 0..60 (use 60 for leap-second) This field will be set to year = 0 if the agent cannot provide the module date. The hour, minute, and second field will be set to zero (0) if they are not relevant. The year field is set with the most significant octet first.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING Size(7)  

cpqUpsOsCommonModulePurpose 1.3.6.1.4.1.232.12.2.1.4.2.1.5
The purpose of the module described in this entry.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsLineStatus 1.3.6.1.4.1.232.12.2.2.1
The status of the AC line input to the UPS.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), failed(4)  

cpqUpsName 1.3.6.1.4.1.232.12.2.2.2
The UPS name (type).
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..20)  

cpqUpsEstimatedBatteryLife 1.3.6.1.4.1.232.12.2.2.3
The estimated time, in minutes, of battery power available. The value will be negative one (-1) if the agent is unable to determine this information. A UPS may not provide this information when AC power is available.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqUpsAutoShutdownDelay 1.3.6.1.4.1.232.12.2.2.4
The number of minutes of battery power remaining before the UPS driver will begin a graceful shutdown of the OS. A value of -1 indicates that no automatic shutdown will occur.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cpqUpsLaunchCommand 1.3.6.1.4.1.232.12.2.2.5
Application to launch for UPS support.
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING Size(0..250)  

cpqUpsAlarm 1.3.6.1.4.1.232.12.2.2.6
This variable contains the UPS alarm text.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..250)  

cpqUpsMemberTable 1.3.6.1.4.1.232.12.2.3.1
A table of entries that describes the family of rack-mounted servers that a single UPS supports.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqUpsMemberEntry

cpqUpsMemberEntry 1.3.6.1.4.1.232.12.2.3.1.1
A table of entries that describes the family of rack-mounted servers that a single UPS supports.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqUpsMemberEntry  

cpqUpsMemberIndex 1.3.6.1.4.1.232.12.2.3.1.1.1
A unique index for this module description.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..255  

cpqUpsMemberName 1.3.6.1.4.1.232.12.2.3.1.1.2
The name or address of one of the individual servers that is served by the rack-mounted UPS. Set cpqUpsMemberName to 0 to delete this row.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsMemberCommunityStr 1.3.6.1.4.1.232.12.2.3.1.1.3
The Community string for this individual server.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsAddMemberName 1.3.6.1.4.1.232.12.2.3.2
To add a row to the cpqUpsMemberTable, this variable must be set, followed immediately by the set of the cpqUpsAddMemberCommunityStr. Sets must occur in this order, or else a new row will not be added to the table.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsAddMemberCommunityStr 1.3.6.1.4.1.232.12.2.3.3
To add a row to the cpqUpsMemberTable, the cpqUpsAddMemberName must be set, followed immediately by a set of this variable. Sets must occur in this order, or else a new row will not be added to the cpqUpsMemberTable.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..255)  

cpqUpsLineFailed 12001
AC Line power failure. The UPS reports that the AC line power has failed.
TRAP-TYPE    

cpqUpsLineOk 12002
AC line power ok. The UPS reports that the AC line power has returned.
TRAP-TYPE    

cpqUpsShutdown 12003
UPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
TRAP-TYPE    

cpqUpsConfirmation 12004
Server now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
TRAP-TYPE    

cpqUpsBatteryLow 12005
UPS Battery Low. The server will soon lose power.
TRAP-TYPE    

cpqUps2LineFailed 12006
AC Line power failure. The UPS reports that the AC line power has failed.
TRAP-TYPE    

cpqUps2LineOk 12007
AC line power ok. The UPS reports that the AC line power has returned.
TRAP-TYPE    

cpqUps2Shutdown 12008
UPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
TRAP-TYPE    

cpqUps2Confirmation 12009
Server now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
TRAP-TYPE    

cpqUps2BatteryLow 12010
UPS Battery Low. The server will soon lose power.
TRAP-TYPE    

cpqUpsOverload 12011
The UPS has entered an overload condition. A failure may occur unless the overload is corrected.
TRAP-TYPE    

cpqUpsPendingBatteryFailure 12012
The UPS battery is about to fail. Replace as soon as possible.
TRAP-TYPE    

cpqUpsGenericCritical 12013
Generic UPS critical alarm.
TRAP-TYPE    

cpqUpsGenericInfo 12014
Generic UPS informational alarm.
TRAP-TYPE