CPQWCRM-MIB

File: CPQWCRM-MIB.mib (69247 bytes)

Imported modules

CPQHOST-MIB RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

compaq OBJECT-TYPE DisplayString
sysName sysDescr sysContact
sysLocation TRAP-TYPE

Defined Types

CpqWcrmInternalSensorEntry  
SEQUENCE    
  internalSensorIndex INTEGER
  internalSensorType INTEGER
  internalSensorText DisplayString Size(0..20)
  internalSensorStatus INTEGER
  internalSensorValue INTEGER
  internalSensorSetHigh INTEGER
  internalSensorSetLow INTEGER
  internalSensorSetWarn INTEGER

CpqWcrmInternalOutputEntry  
SEQUENCE    
  internalOutputIndex INTEGER
  internalOutputType INTEGER
  internalOutputText DisplayString Size(0..20)
  internalOutputStatus INTEGER
  internalOutputValue INTEGER
  internalOutputSet INTEGER
  internalOutputConfig INTEGER
  internalOutputDelay INTEGER
  internalOutputTimeoutAction INTEGER

CpqWcrmInternalMsgEntry  
SEQUENCE    
  internalMsgIndex INTEGER
  internalMsgText DisplayString Size(0..20)
  internalMsgStatus INTEGER
  internalMsgRelay INTEGER
  internalMsgBeeper INTEGER
  internalMsgTrap1 INTEGER
  internalMsgTrap2 INTEGER
  internalMsgTrap3 INTEGER
  internalMsgTrap4 INTEGER
  internalMsgReset INTEGER

CpqWcrmWaterCoolUnitSensorEntry  
SEQUENCE    
  waterCoolUnitSensorIndex INTEGER
  waterCoolUnitSensorType INTEGER
  waterCoolUnitSensorText DisplayString Size(0..20)
  waterCoolUnitSensorStatus INTEGER
  waterCoolUnitSensorValue INTEGER
  waterCoolUnitSensorSetHigh INTEGER
  waterCoolUnitSensorSetLow INTEGER
  waterCoolUnitSensorSetWarn INTEGER

CpqWcrmWaterCoolUnitOutputEntry  
SEQUENCE    
  waterCoolUnitOutputIndex INTEGER
  waterCoolUnitOutputType INTEGER
  waterCoolUnitOutputText DisplayString Size(0..20)
  waterCoolUnitOutputStatus INTEGER
  waterCoolUnitOutputValue INTEGER
  waterCoolUnitOutputSet INTEGER
  waterCoolUnitOutputConfig INTEGER
  waterCoolUnitOutputDelay INTEGER
  waterCoolUnitOutputTimeoutAction INTEGER

CpqWcrmWaterCoolUnitMsgEntry  
SEQUENCE    
  waterCoolUnitMsgIndex INTEGER
  waterCoolUnitMsgText DisplayString Size(0..20)
  waterCoolUnitMsgStatus INTEGER
  waterCoolUnitMsgRelay INTEGER
  waterCoolUnitMsgBeeper INTEGER
  waterCoolUnitMsgTrap1 INTEGER
  waterCoolUnitMsgTrap2 INTEGER
  waterCoolUnitMsgTrap3 INTEGER
  waterCoolUnitMsgTrap4 INTEGER
  waterCoolUnitMsgReset INTEGER

CpqWcrmTimerEntry  
SEQUENCE    
  cpqWcrmTimerIndex INTEGER
  cpqWcrmTimerStatus INTEGER
  cpqWcrmTimerDayOfWeek INTEGER
  cpqWcrmTimeOn DisplayString Size(0..5)
  cpqWcrmTimeOff DisplayString Size(0..5)
  cpqWcrmTimeControl INTEGER
  cpqWcrmTimerFunction INTEGER

CpqWcrmTrapTableEntry  
SEQUENCE    
  trapIndex INTEGER
  trapStatus INTEGER
  trapIPaddress DisplayString

Defined Values

cpqWcrm 1.3.6.1.4.1.232.167
OBJECT IDENTIFIER    

cpqWcrmMibRev 1.3.6.1.4.1.232.167.1
OBJECT IDENTIFIER    

cpqWcrmStatus 1.3.6.1.4.1.232.167.2
OBJECT IDENTIFIER    

cpqWcrmStatusSensorInternal 1.3.6.1.4.1.232.167.2.3
OBJECT IDENTIFIER    

cpqWcrmStatusInternalSensors 1.3.6.1.4.1.232.167.2.3.5
OBJECT IDENTIFIER    

cpqWcrmStatusInternalOutputs 1.3.6.1.4.1.232.167.2.3.6
OBJECT IDENTIFIER    

cpqWcrmStatusInternalMsg 1.3.6.1.4.1.232.167.2.3.7
OBJECT IDENTIFIER    

cpqWcrmStatusSensorWaterCoolUnit 1.3.6.1.4.1.232.167.2.4
OBJECT IDENTIFIER    

cpqWcrmStatusWaterCoolUnitSensors 1.3.6.1.4.1.232.167.2.4.5
OBJECT IDENTIFIER    

cpqWcrmStatusWaterCoolUnitOutputs 1.3.6.1.4.1.232.167.2.4.6
OBJECT IDENTIFIER    

cpqWcrmStatusWaterCoolUnitMsg 1.3.6.1.4.1.232.167.2.4.7
OBJECT IDENTIFIER    

cpqWcrmSetup 1.3.6.1.4.1.232.167.3
OBJECT IDENTIFIER    

cpqWcrmSetupGeneral 1.3.6.1.4.1.232.167.3.1
OBJECT IDENTIFIER    

cpqWcrmTimerTable1 1.3.6.1.4.1.232.167.3.1.8
OBJECT IDENTIFIER    

cpqWcrmTrapControl 1.3.6.1.4.1.232.167.4
OBJECT IDENTIFIER    

cpqWcrmTraps 1.3.6.1.4.1.232.167.4.7
OBJECT IDENTIFIER    

cpqWcrmControl 1.3.6.1.4.1.232.167.5
OBJECT IDENTIFIER    

cpqWcrmMibMajRev 1.3.6.1.4.1.232.167.1.1
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cpqWcrmMibMinRev 1.3.6.1.4.1.232.167.1.2
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

cpqWcrmMibCondition 1.3.6.1.4.1.232.167.1.3
The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on Environmental Controller) (4) a major problem (red LED on Environmental Controller) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on Environmental Controller)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4), configChanged(5)  

cpqWcrmStatusDeviceEnvironmentalController 1.3.6.1.4.1.232.167.2.1
General Status of Environmental Controller unit itself (1) failed (2) OK
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER failed(1), ok(2)  

cpqWcrmUnitsConnected 1.3.6.1.4.1.232.167.2.2
Number of sensor units connected to the Environmental Controller, Port 1 to 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmURL 1.3.6.1.4.1.232.167.2.7
URL of the management interface in the format http[s]://ipaddr[:port#][/page]
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..80)  

cpqWcrmInternalTypeOfDevice 1.3.6.1.4.1.232.167.2.3.1
Type of sensor unit connected to port 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitWcrm(2), unitIO(3)  

cpqWcrmInternalText 1.3.6.1.4.1.232.167.2.3.2
Descriptional text for sensor unit connected to port 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cpqWcrmInternalSerial 1.3.6.1.4.1.232.167.2.3.3
Serialnumber of sensor unit connected to port 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalStatus 1.3.6.1.4.1.232.167.2.3.4
General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), reset(4), timeout(5), detected(6), notAvail(7), lowPower(8)  

cpqWcrmInternalNumberOfSensors 1.3.6.1.4.1.232.167.2.3.5.1
Number of sensors connected to sensor unit 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalSensorTable 1.3.6.1.4.1.232.167.2.3.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalSensorEntry

cpqWcrmInternalSensorEntry 1.3.6.1.4.1.232.167.2.3.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmInternalSensorEntry  

internalSensorIndex 1.3.6.1.4.1.232.167.2.3.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

internalSensorType 1.3.6.1.4.1.232.167.2.3.5.2.1.2
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from Environmental Controller-FAS-Unit 20: leakage sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), voltOK(17), voltage(18), fanOK(19), leakage(20)  

internalSensorText 1.3.6.1.4.1.232.167.2.3.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

internalSensorStatus 1.3.6.1.4.1.232.167.2.3.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)  

internalSensorValue 1.3.6.1.4.1.232.167.2.3.5.2.1.5
Value of sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

internalSensorSetHigh 1.3.6.1.4.1.232.167.2.3.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

internalSensorSetLow 1.3.6.1.4.1.232.167.2.3.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

internalSensorSetWarn 1.3.6.1.4.1.232.167.2.3.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalNumberOfOutputs 1.3.6.1.4.1.232.167.2.3.6.1
Number of outputs available on internal sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalOutputTable 1.3.6.1.4.1.232.167.2.3.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalOutputEntry

cpqWcrmInternalOutputEntry 1.3.6.1.4.1.232.167.2.3.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmInternalOutputEntry  

internalOutputIndex 1.3.6.1.4.1.232.167.2.3.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

internalOutputType 1.3.6.1.4.1.232.167.2.3.6.2.1.2
Type of output which is connected to internal sensor to output[internalOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 6, universal relay output 5: output type 8, power output
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), universalOut(4), powerOut(5)  

internalOutputText 1.3.6.1.4.1.232.167.2.3.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

internalOutputStatus 1.3.6.1.4.1.232.167.2.3.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

internalOutputValue 1.3.6.1.4.1.232.167.2.3.6.2.1.5
Value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

internalOutputSet 1.3.6.1.4.1.232.167.2.3.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

internalOutputConfig 1.3.6.1.4.1.232.167.2.3.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

internalOutputDelay 1.3.6.1.4.1.232.167.2.3.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

internalOutputTimeoutAction 1.3.6.1.4.1.232.167.2.3.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cpqWcrmInternalNumberOfMsgs 1.3.6.1.4.1.232.167.2.3.7.1
Number of messages that can be created with internal sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalMsgTable 1.3.6.1.4.1.232.167.2.3.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalMsgEntry

cpqWcrmInternalMsgEntry 1.3.6.1.4.1.232.167.2.3.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmInternalMsgEntry  

internalMsgIndex 1.3.6.1.4.1.232.167.2.3.7.2.1.1
Index for the list of message entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

internalMsgText 1.3.6.1.4.1.232.167.2.3.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

internalMsgStatus 1.3.6.1.4.1.232.167.2.3.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to ON 10: output is set to OFF
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10)  

internalMsgRelay 1.3.6.1.4.1.232.167.2.3.7.2.1.4
Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgBeeper 1.3.6.1.4.1.232.167.2.3.7.2.1.5
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap1 1.3.6.1.4.1.232.167.2.3.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap2 1.3.6.1.4.1.232.167.2.3.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap3 1.3.6.1.4.1.232.167.2.3.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap4 1.3.6.1.4.1.232.167.2.3.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgReset 1.3.6.1.4.1.232.167.2.3.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

cpqWcrmWaterCoolUnitTypeOfDevice 1.3.6.1.4.1.232.167.2.4.1
Type of sensor unit connected to port 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), unitWcrm(2), unitIO(3)  

cpqWcrmWaterCoolUnitText 1.3.6.1.4.1.232.167.2.4.2
Descriptional text for sensor unit connected to port 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cpqWcrmWaterCoolUnitSerial 1.3.6.1.4.1.232.167.2.4.3
Serialnumber of sensor unit connected to port 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitStatus 1.3.6.1.4.1.232.167.2.4.4
General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), reset(4), timeout(5), detected(6), notAvail(7), lowPower(8)  

cpqWcrmWaterCoolUnitNumberOfSensors 1.3.6.1.4.1.232.167.2.4.5.1
Number of sensors connected to water cool unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitSensorTable 1.3.6.1.4.1.232.167.2.4.5.2
Headline of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitSensorEntry

cpqWcrmWaterCoolUnitSensorEntry 1.3.6.1.4.1.232.167.2.4.5.2.1
Entries of sensor table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitSensorEntry  

waterCoolUnitSensorIndex 1.3.6.1.4.1.232.167.2.4.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitSensorType 1.3.6.1.4.1.232.167.2.4.5.2.1.2
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: average temperature of air inlet to rack, average or max/min from each HEX 5: average temperature of air outlet from rack, average or max/min from each HEX 6: heatflow sensor 7: alarm: Bit 0: Leakage Bit 1: IIC Failure 8: warning: Bit 0..2: Fan Tach 1..3 Bit 3,4: Temp. sensor HEX1 In,Out Bit 5,6: Temp. sensor HEX2 In,Out Bit 7,8: Temp. sensor HEX3 In,Out Bit 9: Air temp. sensor Bit 10..12: IIC failure, HEX1..3 Bit 13: Waterflow low Bit 14,15: Watertemp. In,Out Bit 16: Waterflow sensor fail. Bit 17: Magnetic valve fail. Bit 18: Leakdetector fail. Bit 19: Uneven heat load Bit 20: Condensation Pump Cycles > Max Bit 21: Condensation Pump Running Time > Max 9: rpm speed of Fan1 10: rpm speed of Fan2 11: rpm speed of Fan3 12: fanSpeed setpoint, calculated from average temperatures 13: temperature air inlet to rack, HEX 1 14: temperature air outlet from rack, HEX 1 15: temperature air inlet to rack, HEX 1 16: temperature air outlet from rack, HEX 1 17: temperature air inlet to rack, HEX 1 18: temperature air outlet from rack, HEX 1 19: water temperature In 20: water temperature Out 21: water Flow 22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%) 23: status: Bit 0..Bit 2: fan module 1..3 available Bit 3: water module available 24: condensation pump number of seconds on counter (last operating time) 25: condensation pump on/off cycle counter 26: rpm speed of Fan4 27: rpm speed of Fan5 28: rpm speed of Fan6 29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2 30: water valve actual value (%)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), tempIn(4), tempOut(5), heatFlow(6), alarm(7), warning(8), rpmFan1(9), rpmFan2(10), rpmFan3(11), fanSpeed(12), tempIn1(13), tempOut1(14), tempIn2(15), tempOut2(16), tempIn3(17), tempOut3(18), tempWaterIn(19), tempWaterOut(20), waterFlow(21), valve(22), status(23), condensateDuration(24), condensateCycles(25), rpmFan4(26), rpmFan5(27), rpmFan6(28), transfSwitch(29), valveActValue(30)  

waterCoolUnitSensorText 1.3.6.1.4.1.232.167.2.4.5.2.1.3
Descriptional text for each sensor (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

waterCoolUnitSensorStatus 1.3.6.1.4.1.232.167.2.4.5.2.1.4
Actual status of the sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)  

waterCoolUnitSensorValue 1.3.6.1.4.1.232.167.2.4.5.2.1.5
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex) If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperature. If msg index = 2: This value represents the bit coded warning condition Bit 0: Top Fan Module Failed Bit 1: Middle Fan Module Failed Bit 2: Bottom Fan Module Failed Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed Bit 9: Air Temperature Sensor Failed Bit 10: Top Fan not installed Bit 11: Middle Fan not installed Bit 12: Bottom Fan not installed Bit 13: Waterflow low Bit 14: Water Unit Temperature Input Out of Range Bit 15: Water Unit Temperature Output Out of Range Bit 16: Waterflow Sensor Value Out of Range Bit 17: Water Valve Failed Bit 18: Leakdetector Failed Bit 19: Heat Load Warning Bit 20: The Condensation Pump has exceeded the max. number of cycles Bit 21: The Condensation Pump has exceeded the max. Running Time If msg index = 3: This value represents the bit coded alarm condition Bit 0: Leakage Detected Bit 1: Comm. Failure IIC
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetHigh 1.3.6.1.4.1.232.167.2.4.5.2.1.6
Value for high setpoint of sensor
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetLow 1.3.6.1.4.1.232.167.2.4.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetWarn 1.3.6.1.4.1.232.167.2.4.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitNumberOfOutputs 1.3.6.1.4.1.232.167.2.4.6.1
Number of outputs available on sensor water cool unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitOutputTable 1.3.6.1.4.1.232.167.2.4.6.2
Headline of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitOutputEntry

cpqWcrmWaterCoolUnitOutputEntry 1.3.6.1.4.1.232.167.2.4.6.2.1
Entries of output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitOutputEntry  

waterCoolUnitOutputIndex 1.3.6.1.4.1.232.167.2.4.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitOutputType 1.3.6.1.4.1.232.167.2.4.6.2.1.2
Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: water valve setpoint 5: water valve hysteresis 6: command for manual control 7: Flow Meter Model, 0=SIKA, 1=Chemline 8: minimum fan speed 9: min delta T, used for fan control 10: max delta T, used for fan control 11: specific heat capacity 12: setpoint heatload warning 13: setpoint Water Flow Loss Emergency Door Opening 14: setpoint High Temperature Emergency Door Opening 15: setpoint Condensation Pump Cycles (Warning) 16: setpoint Condensation Pump Running Time (Warning) 17: command for door opening, 0=lock door, 1=unlock door 18: KP parameter for PID controller 19: KI parameter for PID controller 20: KD parameter for PID controller 21: sampling time PID controller
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), setpoint(4), hysteresis(5), command(6), controlMode(7), fanSpeedMin(8), dTmin(9), dTmax(10), cpWatert(11), setHeatload(12), setEdoFlow(13), setEdoHeat(14), setCondCycles(15), setCondRun(16), doorControl(17), pidContrKP(18), pidContrKI(19), pidContrKD(20), pidSampleTime(21)  

waterCoolUnitOutputText 1.3.6.1.4.1.232.167.2.4.6.2.1.3
Descriptional text for each output (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

waterCoolUnitOutputStatus 1.3.6.1.4.1.232.167.2.4.6.2.1.4
Actual status of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

waterCoolUnitOutputValue 1.3.6.1.4.1.232.167.2.4.6.2.1.5
Signed value for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

waterCoolUnitOutputSet 1.3.6.1.4.1.232.167.2.4.6.2.1.6
Command for output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

waterCoolUnitOutputConfig 1.3.6.1.4.1.232.167.2.4.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

waterCoolUnitOutputDelay 1.3.6.1.4.1.232.167.2.4.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

waterCoolUnitOutputTimeoutAction 1.3.6.1.4.1.232.167.2.4.6.2.1.9
State for output if timeout (RS422) occurs
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cpqWcrmWaterCoolUnitNumberOfMsgs 1.3.6.1.4.1.232.167.2.4.7.1
Number of alarms that can be created with water cool unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitMsgTable 1.3.6.1.4.1.232.167.2.4.7.2
Headline of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitMsgEntry

cpqWcrmWaterCoolUnitMsgEntry 1.3.6.1.4.1.232.167.2.4.7.2.1
Entries of message table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitMsgEntry  

waterCoolUnitMsgIndex 1.3.6.1.4.1.232.167.2.4.7.2.1.1
Index for the list of alarm entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitMsgText 1.3.6.1.4.1.232.167.2.4.7.2.1.2
Descriptional text for each message (entry in the table)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..20)  

waterCoolUnitMsgStatus 1.3.6.1.4.1.232.167.2.4.7.2.1.3
Actual message status 4: OK 5: alarm 6: warning 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10)  

waterCoolUnitMsgRelay 1.3.6.1.4.1.232.167.2.4.7.2.1.4
Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgBeeper 1.3.6.1.4.1.232.167.2.4.7.2.1.5
Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap1 1.3.6.1.4.1.232.167.2.4.7.2.1.6
Trap receiver 1 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap2 1.3.6.1.4.1.232.167.2.4.7.2.1.7
Trap receiver 2 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap3 1.3.6.1.4.1.232.167.2.4.7.2.1.8
Trap receiver 3 activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap4 1.3.6.1.4.1.232.167.2.4.7.2.1.9
Trap receiver 4 and Event Logging activated
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgReset 1.3.6.1.4.1.232.167.2.4.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

cpqWcrmSetTempUnit 1.3.6.1.4.1.232.167.3.1.1
Unit of all temperature values and setpoints, Celsius or Fahrenheit
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

cpqWcrmSetBeeper 1.3.6.1.4.1.232.167.3.1.2
Audible alarm in Environmental Controller unit: (2): beeper is on (1): beeper is off (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(1), on(2)  

cpqWcrmResetRelay 1.3.6.1.4.1.232.167.3.1.3
Enable or disable acknowledging currently active alarm relay (with 'C' on Environmental Controller).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cpqWcrmLogicRelay 1.3.6.1.4.1.232.167.3.1.4
Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER closeAtAlarm(1), openAtAlarm(2), off(3)  

cpqWcrmWebAccess 1.3.6.1.4.1.232.167.3.1.5
Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER viewOnly(1), fullAccess(2), off(3)  

cpqWcrmSetupDate 1.3.6.1.4.1.232.167.3.1.6
actual Date in format DD.MM.YYYY
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cpqWcrmSetupTime 1.3.6.1.4.1.232.167.3.1.7
actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

cpqWcrmTimerNumber 1.3.6.1.4.1.232.167.3.1.8.1
Number of value-table entries=number of outlets available on this unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmTimerTable 1.3.6.1.4.1.232.167.3.1.8.2
Headline of status-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmTimerEntry

cpqWcrmTimerEntry 1.3.6.1.4.1.232.167.3.1.8.2.1
Entries of timer-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmTimerEntry  

cpqWcrmTimerIndex 1.3.6.1.4.1.232.167.3.1.8.2.1.1
Index for the list of timer entries. Its value ranges between 1 and the value of cpqWcrmTimerNumber.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cpqWcrmTimerStatus 1.3.6.1.4.1.232.167.3.1.8.2.1.2
Actual status of the timer
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER switchedOff(1), switchedOn(2), noTime(3)  

cpqWcrmTimerDayOfWeek 1.3.6.1.4.1.232.167.3.1.8.2.1.3
Selection of day of week for timer to switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat-sun(8), mon-fri(9), mon-sun(10)  

cpqWcrmTimeOn 1.3.6.1.4.1.232.167.3.1.8.2.1.4
Time to switch on current function, Format: HH:MM
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..5)  

cpqWcrmTimeOff 1.3.6.1.4.1.232.167.3.1.8.2.1.5
Time to switch off current function, Format: HH:MM
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..5)  

cpqWcrmTimeControl 1.3.6.1.4.1.232.167.3.1.8.2.1.6
Control via RTC
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cpqWcrmTimerFunction 1.3.6.1.4.1.232.167.3.1.8.2.1.7
Function which is controlled via timer 1-4: sending Traps to this Trap receiver will be disabled 5 - 8: scheduled alarm off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disTrapRec1(1), disTrapRec2(2), disTrapRec3(3), disTrapRec4(4), schedule1(5), schedule2(6), schedule3(7), schedule4(8)  

cpqWcrmSetFlowUnit 1.3.6.1.4.1.232.167.3.1.9
Unit of Water Flow, Liter/min or Gallon/min
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER literMin(1), gallonMin(2)  

cpqWcrmTraptableNumber 1.3.6.1.4.1.232.167.4.7.1
Number of trapTable entries. The number of trap-receiver
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqWcrmTrapTableTable 1.3.6.1.4.1.232.167.4.7.2
A list of trap-receiver entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmTrapTableEntry

cpqWcrmTrapTableEntry 1.3.6.1.4.1.232.167.4.7.2.1
Entries of trapTable
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqWcrmTrapTableEntry  

trapIndex 1.3.6.1.4.1.232.167.4.7.2.1.1
Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

trapStatus 1.3.6.1.4.1.232.167.4.7.2.1.2
Enable or disable trap receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

trapIPaddress 1.3.6.1.4.1.232.167.4.7.2.1.3
IP-address of trap-receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

cpqWcrmResetUnit 1.3.6.1.4.1.232.167.5.1
Command to reset (acknowledge) alarms of Environmental Controller unit. Setting to 'reset' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noReset' (1).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER noReset(1), reset(2)  

alarmSensorInternal 1
Internal Sensor Alarm
TRAP-TYPE    

alarmSensorWaterCoolUnit 2
Water Cool Unit Sensor Alarm
TRAP-TYPE    

alarmInternal 5
Internal Unit Alarm
TRAP-TYPE    

alarmWaterCoolUnit 6
Water Cool Unit System Alarm
TRAP-TYPE    

testTrap 10
Test trap sent to a trap receiver to check proper reception of traps
TRAP-TYPE