DataAire-dap4-al-MIB
File:
DataAire-dap4-al-MIB.mib (76424 bytes)
Imported modules
Imported symbols
Defined Values
dap4-alMIB |
1.3.6.1.4.1.9839.2.1 |
This is the MIB module for the dap4_al device. |
MODULE-IDENTITY |
|
|
|
carel |
1.3.6.1.4.1.9839 |
OBJECT IDENTIFIER |
|
|
|
systm |
1.3.6.1.4.1.9839.1 |
OBJECT IDENTIFIER |
|
|
|
agentRelease |
1.3.6.1.4.1.9839.1.1 |
Release of the Agent. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
agentCode |
1.3.6.1.4.1.9839.1.2 |
Code of the Agent. 2=pCOWeb. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pCOId1-Status |
1.3.6.1.4.1.9839.2.0.10.1 |
Status of pCOId1. 0=Offline, 1=Init, 2=Online |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pCOId1-ErrorsNumber |
1.3.6.1.4.1.9839.2.0.11.1 |
Number of Communication Errors from pCOId1 to pCOWeb. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
dehum-on |
1.3.6.1.4.1.9839.2.1.1.1 |
Dehumidify mode is running |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
hum-on |
1.3.6.1.4.1.9839.2.1.1.2 |
Humidifier is running |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
engy-on |
1.3.6.1.4.1.9839.2.1.1.3 |
Energy saver is running |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cool-inhibit |
1.3.6.1.4.1.9839.2.1.1.4 |
Cooling inhibit from Zone Master |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
heat-held |
1.3.6.1.4.1.9839.2.1.1.5 |
Heat inhibited due to alarm condition |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
humidifier-inhibit |
1.3.6.1.4.1.9839.2.1.1.6 |
Humidifier stopped due to alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
dehum-inhibit |
1.3.6.1.4.1.9839.2.1.1.7 |
Dehum is inhibited |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
floor-wtr-alm |
1.3.6.1.4.1.9839.2.1.1.9 |
Water under floor alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
air-flow-alm |
1.3.6.1.4.1.9839.2.1.1.10 |
No air flow alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
filter-alm |
1.3.6.1.4.1.9839.2.1.1.11 |
Dirty filter from digital input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
humidifier-alm |
1.3.6.1.4.1.9839.2.1.1.12 |
Alarm from humidifier digital input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
firestat-alm |
1.3.6.1.4.1.9839.2.1.1.13 |
Temperature of return air above firestat alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
shortcycle-alm |
1.3.6.1.4.1.9839.2.1.1.14 |
One or more comps has short cycled |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
humidity-fail |
1.3.6.1.4.1.9839.2.1.1.15 |
Sensor is out of range |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
ret-air-fail |
1.3.6.1.4.1.9839.2.1.1.16 |
Sensor is out of range |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
maint-alm |
1.3.6.1.4.1.9839.2.1.1.17 |
Maintenance Schedule Due alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
c1-hp-alm |
1.3.6.1.4.1.9839.2.1.1.18 |
High pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
c1-lp-alm |
1.3.6.1.4.1.9839.2.1.1.19 |
Low pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
c2-hp-alm |
1.3.6.1.4.1.9839.2.1.1.20 |
High pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
c2-lp-alm |
1.3.6.1.4.1.9839.2.1.1.21 |
Low pressure alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
smoke-alm |
1.3.6.1.4.1.9839.2.1.1.22 |
Smoke detected from digital input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
wtr-flow-alm |
1.3.6.1.4.1.9839.2.1.1.23 |
No water flow alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
disch-air-fail |
1.3.6.1.4.1.9839.2.1.1.24 |
Sensor is out of range |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
ra-tmp-hi-alm |
1.3.6.1.4.1.9839.2.1.1.25 |
Temperature of return air above alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
ra-tmp-lo-alm |
1.3.6.1.4.1.9839.2.1.1.26 |
Temperature of return air below alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
hum-hi-alm |
1.3.6.1.4.1.9839.2.1.1.27 |
Humidity above alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
hum-lo-alm |
1.3.6.1.4.1.9839.2.1.1.28 |
Humidity below alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
fan-overload |
1.3.6.1.4.1.9839.2.1.1.29 |
Fan overload |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
stdby-pump-on |
1.3.6.1.4.1.9839.2.1.1.30 |
Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cust-msg-sw1 |
1.3.6.1.4.1.9839.2.1.1.31 |
Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cust-msg-sw2 |
1.3.6.1.4.1.9839.2.1.1.32 |
Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cust-msg-sw3 |
1.3.6.1.4.1.9839.2.1.1.33 |
Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cust-msg-sw4 |
1.3.6.1.4.1.9839.2.1.1.34 |
Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
humsw-inhibit |
1.3.6.1.4.1.9839.2.1.1.35 |
Humidifier stopped due to custom alarm switch |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
heat-inhibit |
1.3.6.1.4.1.9839.2.1.1.36 |
Heat inhibited due to custom switch alarm condition |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
rht-hum-inhibit |
1.3.6.1.4.1.9839.2.1.1.37 |
Reheat and humidification inhibited from operation |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
disch-tmp-lo-alm |
1.3.6.1.4.1.9839.2.1.1.38 |
Temperature of discharge air below alarm set point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
override-alm |
1.3.6.1.4.1.9839.2.1.1.39 |
Manual override: Check bypass switches - Standard alarm. Manual override switch is on |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
condensation-alm |
1.3.6.1.4.1.9839.2.1.1.40 |
High condensation from digital input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
unit-in-standby |
1.3.6.1.4.1.9839.2.1.1.41 |
Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
cw-sns-fail |
1.3.6.1.4.1.9839.2.1.1.42 |
Sensor is out of range |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
humsw-chk-cyl |
1.3.6.1.4.1.9839.2.1.1.43 |
Humidifier stopped due to custom alarm switch |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
bms-cooling-inhibit |
1.3.6.1.4.1.9839.2.1.1.44 |
Cooling operation inhibited by BMS |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
bms-heat-inhibit |
1.3.6.1.4.1.9839.2.1.1.45 |
Heat inhibited due to bms |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
bms-dehum-inhibit |
1.3.6.1.4.1.9839.2.1.1.47 |
Dehumidify mode inhibited by bms |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
fan-inhibit-bms |
1.3.6.1.4.1.9839.2.1.1.48 |
Inhibit fan by bms |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
hum-expect |
1.3.6.1.4.1.9839.2.1.1.49 |
Reduces control humidity cycling |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
usashr-f-c |
1.3.6.1.4.1.9839.2.1.1.50 |
Temperature Mode 0=_C 1=_F |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
lead-comp |
1.3.6.1.4.1.9839.2.1.1.52 |
Lead compressor select 0= C1, 1= C2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
wtrvlv-dir |
1.3.6.1.4.1.9839.2.1.1.53 |
Water valve direct or reverse acting |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
ups-on-alm |
1.3.6.1.4.1.9839.2.1.1.54 |
Alarm: UPS power on: Check main power -Optional alarm. External alarm input required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
pwrup-alm |
1.3.6.1.4.1.9839.2.1.1.55 |
Loss of power requires manual reset of alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
seetag-cust-alm1 |
1.3.6.1.4.1.9839.2.1.1.56 |
Local alarm #1: See tag inside door =Optional alarm. External alarm input required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
seetag-cust-alm2 |
1.3.6.1.4.1.9839.2.1.1.57 |
Local alarm #2: See tag inside door =Optional alarm. External alarm input required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
seetag-cust-alm3 |
1.3.6.1.4.1.9839.2.1.1.58 |
Local alarm #3: See tag inside door =Optional alarm. External alarm input required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
seetag-cust-alm4 |
1.3.6.1.4.1.9839.2.1.1.59 |
Local alarm #4: See tag inside door =Optional alarm. External alarm input required |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
shortcycle-alm-en |
1.3.6.1.4.1.9839.2.1.1.60 |
Enable short cycle alarm of the compressors |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
superv-off |
1.3.6.1.4.1.9839.2.1.1.61 |
Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
bms-heartbeat |
1.3.6.1.4.1.9839.2.1.1.62 |
Bms heartbeat - pCO looks for update every 10 minutes |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1 |
|
ret-air-tmp |
1.3.6.1.4.1.9839.2.1.2.1 |
Temperature of return air |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
temp-setpoint |
1.3.6.1.4.1.9839.2.1.2.4 |
Temperature setpoint |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-9999..9999 |
|
temp-deadband |
1.3.6.1.4.1.9839.2.1.2.5 |
Amount from setpoint before a comp is staged on |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
humidity-ain-offs |
1.3.6.1.4.1.9839.2.1.2.6 |
Humidity Sensor Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
return-ain-offs |
1.3.6.1.4.1.9839.2.1.2.7 |
Return Temperature Sensor Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cw-tmp |
1.3.6.1.4.1.9839.2.1.2.8 |
Temperature of chilled water |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
disch-air-tmp |
1.3.6.1.4.1.9839.2.1.2.9 |
Temperature of discharge air |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
discharge-ain-offs |
1.3.6.1.4.1.9839.2.1.2.10 |
Discharge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cw-ain-offs |
1.3.6.1.4.1.9839.2.1.2.11 |
Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
engsaver-setpoint |
1.3.6.1.4.1.9839.2.1.2.12 |
Temperature setpoint where chilled water will is requested |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-9999..9999 |
|
opt1-analog |
1.3.6.1.4.1.9839.2.1.2.13 |
Value of the analog input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt2-analog |
1.3.6.1.4.1.9839.2.1.2.14 |
Value of the analog input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt3-analog |
1.3.6.1.4.1.9839.2.1.2.15 |
Value of the analog input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt4-analog |
1.3.6.1.4.1.9839.2.1.2.16 |
Value of the analog input |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-1-y1 |
1.3.6.1.4.1.9839.2.1.2.17 |
Analog Sensor 1 Minimum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-1-y2 |
1.3.6.1.4.1.9839.2.1.2.18 |
Analog Sensor 1 Maximum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-1-ain-offs |
1.3.6.1.4.1.9839.2.1.2.19 |
Analog Sensor 1 Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-2-y1 |
1.3.6.1.4.1.9839.2.1.2.20 |
Analog Sensor 2 Minimum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-2-y2 |
1.3.6.1.4.1.9839.2.1.2.21 |
Analog Sensor 2 Maximum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-2-ain-offs |
1.3.6.1.4.1.9839.2.1.2.22 |
Analog Sensor 2 Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-3-y1 |
1.3.6.1.4.1.9839.2.1.2.23 |
Analog Sensor 3 Minimum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-3-y2 |
1.3.6.1.4.1.9839.2.1.2.24 |
Analog Sensor 3 Maximum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-3-ain-offs |
1.3.6.1.4.1.9839.2.1.2.25 |
Analog Sensor 3 Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-4-y1 |
1.3.6.1.4.1.9839.2.1.2.26 |
Analog Sensor 4 Minimum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-4-y2 |
1.3.6.1.4.1.9839.2.1.2.27 |
Analog Sensor 4 Maximum Value |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-4-ain-offs |
1.3.6.1.4.1.9839.2.1.2.28 |
Analog Sensor 4 Calibration |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
disch-air-lo-sp |
1.3.6.1.4.1.9839.2.1.3.1 |
Lower Limit alarm of discharge air temp |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32767..32767 |
|
humidity-dis |
1.3.6.1.4.1.9839.2.1.3.2 |
Relative humidity displayed as xx% |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-999..999 |
|
stages-on |
1.3.6.1.4.1.9839.2.1.3.3 |
Cooling Stages On, DX only |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32767..32767 |
|
heaters-on |
1.3.6.1.4.1.9839.2.1.3.4 |
Number of heat stages running |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
comp-duty |
1.3.6.1.4.1.9839.2.1.3.7 |
Cooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
heat-duty |
1.3.6.1.4.1.9839.2.1.3.8 |
Heating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
hum-duty |
1.3.6.1.4.1.9839.2.1.3.9 |
Humidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
c1-hours-h |
1.3.6.1.4.1.9839.2.1.3.10 |
Compressor 1 Runtime -This point applies to DX unit with one compressor -high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c1-hours-l |
1.3.6.1.4.1.9839.2.1.3.11 |
Compressor 1 Runtime -This point applies to DX unit with one compressor -low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c2-hours-h |
1.3.6.1.4.1.9839.2.1.3.12 |
Compressor 2 Runtime -This point applies to DX unit with dual compressor - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c2-hours-l |
1.3.6.1.4.1.9839.2.1.3.13 |
Compressor 2 Runtime -This point applies to DX unit with dual compressor - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
ht1-hours-h |
1.3.6.1.4.1.9839.2.1.3.14 |
Heater 1 Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
ht1-hours-l |
1.3.6.1.4.1.9839.2.1.3.15 |
Heater 1 Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
current-second |
1.3.6.1.4.1.9839.2.1.3.16 |
Current second |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..59 |
|
current-minute |
1.3.6.1.4.1.9839.2.1.3.17 |
Current minute |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..59 |
|
current-hour |
1.3.6.1.4.1.9839.2.1.3.18 |
Current hour |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..23 |
|
current-day |
1.3.6.1.4.1.9839.2.1.3.19 |
Current day |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..31 |
|
current-month |
1.3.6.1.4.1.9839.2.1.3.20 |
Current month |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..12 |
|
current-year |
1.3.6.1.4.1.9839.2.1.3.21 |
Current year |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
firestat-sp |
1.3.6.1.4.1.9839.2.1.3.22 |
Alarm settting of return air temp to determine there is a fire |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
hum-hi-sp |
1.3.6.1.4.1.9839.2.1.3.23 |
Humidity upper limit alarm |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
ret-air-hi-sp |
1.3.6.1.4.1.9839.2.1.3.24 |
Upper limit alarm of return air temp |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
hum-lo-sp |
1.3.6.1.4.1.9839.2.1.3.25 |
Humidity lower limit alarm |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
ret-air-lo-sp |
1.3.6.1.4.1.9839.2.1.3.26 |
Lower limit alarm of return air temp |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
hum-deadband |
1.3.6.1.4.1.9839.2.1.3.27 |
amount hum must change from setpoint before acting |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
hum-setpoint |
1.3.6.1.4.1.9839.2.1.3.28 |
humidity setpoint |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
start-dly |
1.3.6.1.4.1.9839.2.1.3.29 |
Time before the system starts up |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..600 |
|
alm1-del |
1.3.6.1.4.1.9839.2.1.3.30 |
Optional Alarm 1 Delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
alm2-del |
1.3.6.1.4.1.9839.2.1.3.31 |
Optional Alarm 2 Delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
alm3-del |
1.3.6.1.4.1.9839.2.1.3.32 |
Optional Alarm 3 Delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
alarm1-txt |
1.3.6.1.4.1.9839.2.1.3.33 |
Message on optional alarm screen, some also add function |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..16 |
|
alarm2-txt |
1.3.6.1.4.1.9839.2.1.3.34 |
Message on optional alarm screen, some also add function |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..16 |
|
alarm3-txt |
1.3.6.1.4.1.9839.2.1.3.35 |
Message on optional alarm screen, some also add function |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..16 |
|
alarm4-txt |
1.3.6.1.4.1.9839.2.1.3.36 |
Message on optional alarm screen, some also add function |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..16 |
|
comp-sel |
1.3.6.1.4.1.9839.2.1.3.37 |
Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..5 |
|
dehum-mode |
1.3.6.1.4.1.9839.2.1.3.38 |
0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
reheat-sel |
1.3.6.1.4.1.9839.2.1.3.39 |
Number of heat stages |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..3 |
|
hum-sel |
1.3.6.1.4.1.9839.2.1.3.40 |
0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
powerup-sel |
1.3.6.1.4.1.9839.2.1.3.42 |
0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..2 |
|
buzzer-select |
1.3.6.1.4.1.9839.2.1.3.43 |
0=None, 1=short beeps, 2=long beep, 3=Constant |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..3 |
|
cw-disp |
1.3.6.1.4.1.9839.2.1.3.44 |
% of 10volts of analog output #1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
wtrvlv-duty |
1.3.6.1.4.1.9839.2.1.3.45 |
Chilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
hum-hours-h |
1.3.6.1.4.1.9839.2.1.3.46 |
Humidifier Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
hum-hours-l |
1.3.6.1.4.1.9839.2.1.3.47 |
Humidifier Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
blower-hours-h |
1.3.6.1.4.1.9839.2.1.3.48 |
Blower Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
blower-hours-l |
1.3.6.1.4.1.9839.2.1.3.49 |
Blower Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
alm4-del |
1.3.6.1.4.1.9839.2.1.3.50 |
Optional Alarm 4 Delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
assist-sel |
1.3.6.1.4.1.9839.2.1.3.51 |
0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4... |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..5 |
|
wtrvlv-sel |
1.3.6.1.4.1.9839.2.1.3.52 |
Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
wtrvlv-volts-sel |
1.3.6.1.4.1.9839.2.1.3.53 |
Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..4 |
|
hum-volts |
1.3.6.1.4.1.9839.2.1.3.54 |
% of 10volts of analog output #2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..999 |
|
dehum-hours-h |
1.3.6.1.4.1.9839.2.1.3.55 |
Dehumidifier Runtime - High |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
dehum-hours-l |
1.3.6.1.4.1.9839.2.1.3.56 |
Dehumidifier Runtime - Low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
autoflush-dly |
1.3.6.1.4.1.9839.2.1.3.58 |
Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..99 |
|
y4-out |
1.3.6.1.4.1.9839.2.1.3.59 |
Value sent to optional analog output#1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
y5-out |
1.3.6.1.4.1.9839.2.1.3.60 |
Value sent to optional analog output#2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
air-flow |
1.3.6.1.4.1.9839.2.1.3.61 |
Current Fan Airflow - Based on calculated Pressure Diff formula |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-snsr1-name |
1.3.6.1.4.1.9839.2.1.3.62 |
Name of the sensor |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-1-ain-type |
1.3.6.1.4.1.9839.2.1.3.63 |
Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9 |
|
opt-snsr2-name |
1.3.6.1.4.1.9839.2.1.3.64 |
Name of the sensor |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-2-ain-type |
1.3.6.1.4.1.9839.2.1.3.65 |
Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9 |
|
opt-snsr3-name |
1.3.6.1.4.1.9839.2.1.3.66 |
Name of the sensor |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-3-ain-type |
1.3.6.1.4.1.9839.2.1.3.67 |
Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9 |
|
opt-snsr4-name |
1.3.6.1.4.1.9839.2.1.3.68 |
Name of the sensor |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
opt-sns-4-ain-type |
1.3.6.1.4.1.9839.2.1.3.69 |
Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..9 |
|
cw-fan-speed-bms |
1.3.6.1.4.1.9839.2.1.3.70 |
CW Fan speed (%) sent via BMS |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..100 |
|
dx-fan-speed-bms |
1.3.6.1.4.1.9839.2.1.3.71 |
DX Fan speed (%) sent via BMS |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..100 |
|
fan-speed-max |
1.3.6.1.4.1.9839.2.1.3.72 |
Maximum Fan speed (% of output) modulation. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
70..100 |
|
fan-speed-min |
1.3.6.1.4.1.9839.2.1.3.73 |
Minimum Fan speed (% of output) modulation from pressure. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
40..100 |
|
fan-pr-sp |
1.3.6.1.4.1.9839.2.1.3.74 |
Fan pressure setpoint (0.01 inches of water) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..1001 |
|
fan-pr-band |
1.3.6.1.4.1.9839.2.1.3.75 |
Fan pressure band (0.01 inches of water) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..100 |
|
fan-af-max |
1.3.6.1.4.1.9839.2.1.3.76 |
Maximum air flow limit of setpoint from BMS or valve modulation. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
fan-af-min |
1.3.6.1.4.1.9839.2.1.3.77 |
Minimum air flow limit of setpoint from BMS or valve modulation. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
fan-kfactor |
1.3.6.1.4.1.9839.2.1.3.78 |
Fan K Factor |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
100..500 |
|
num-fans |
1.3.6.1.4.1.9839.2.1.3.79 |
Number of fans installed in this unit |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..3 |
|
ht2-hours-h |
1.3.6.1.4.1.9839.2.1.3.81 |
Heater 2 Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
ht2-hours-l |
1.3.6.1.4.1.9839.2.1.3.82 |
Heater 2 Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
ht3-hours-h |
1.3.6.1.4.1.9839.2.1.3.83 |
Heater 3 Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
ht3-hours-l |
1.3.6.1.4.1.9839.2.1.3.84 |
Heater 3 Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
engy-hours-h |
1.3.6.1.4.1.9839.2.1.3.85 |
Energy Saver Runtime - This optional point applies to energy saver units only -high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
engy-hours-l |
1.3.6.1.4.1.9839.2.1.3.86 |
Energy Saver Runtime - This optional point applies to energy saver units only - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cw-hours-h |
1.3.6.1.4.1.9839.2.1.3.87 |
Chilled Water Runtime - This applies to chilled water units only - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cw-hours-l |
1.3.6.1.4.1.9839.2.1.3.88 |
Chilled Water Runtime - This applies to chilled water units only - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c3-hours-h |
1.3.6.1.4.1.9839.2.1.3.89 |
Compressor 3 Runtime - This applies when unit has four stages tandem compressors - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c3-hours-l |
1.3.6.1.4.1.9839.2.1.3.90 |
Compressor 3 Runtime - This applies when unit has four stages tandem compressors - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c4-hours-l |
1.3.6.1.4.1.9839.2.1.3.91 |
Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
c4-hours-h |
1.3.6.1.4.1.9839.2.1.3.92 |
Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cond-hours-h |
1.3.6.1.4.1.9839.2.1.3.93 |
Condenser Runtime - high |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
cond-hours-l |
1.3.6.1.4.1.9839.2.1.3.94 |
Condenser Runtime - low |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|
dx-fan-speed |
1.3.6.1.4.1.9839.2.1.3.95 |
Fan speed (% of output) when compressor cooling. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
60..100 |
|
cw-fan-speed |
1.3.6.1.4.1.9839.2.1.3.96 |
Fan speed (% of output) when cold water cooling. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
60..100 |
|
fan-af-dx-sp |
1.3.6.1.4.1.9839.2.1.3.97 |
Fan air flow setpoint for DX unit (cfm) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
fan-af-cw-sp |
1.3.6.1.4.1.9839.2.1.3.98 |
Fan air flow setpoint for CW unit (cfm) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..32000 |
|
zm-airflow-sp |
1.3.6.1.4.1.9839.2.1.3.99 |
Zone Airflow Setpoint kcfm |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
-32768..32767 |
|