DeltaUPS-MIB
File:
DeltaUPS-MIB.mib (46507 bytes)
Imported modules
Imported symbols
Defined Values
delta |
1.3.6.1.4.1.2254 |
OBJECT IDENTIFIER |
|
|
|
ups |
1.3.6.1.4.1.2254.2 |
OBJECT IDENTIFIER |
|
|
|
upsv4 |
1.3.6.1.4.1.2254.2.4 |
OBJECT IDENTIFIER |
|
|
|
dupsIdent |
1.3.6.1.4.1.2254.2.4.1 |
OBJECT IDENTIFIER |
|
|
|
dupsConfig |
1.3.6.1.4.1.2254.2.4.3 |
OBJECT IDENTIFIER |
|
|
|
dupsOutput |
1.3.6.1.4.1.2254.2.4.5 |
OBJECT IDENTIFIER |
|
|
|
dupsBypass |
1.3.6.1.4.1.2254.2.4.6 |
OBJECT IDENTIFIER |
|
|
|
dupsTest |
1.3.6.1.4.1.2254.2.4.8 |
OBJECT IDENTIFIER |
|
|
|
dupsAlarm |
1.3.6.1.4.1.2254.2.4.9 |
OBJECT IDENTIFIER |
|
|
|
dupsTraps |
1.3.6.1.4.1.2254.2.4.20 |
OBJECT IDENTIFIER |
|
|
|
dupsIdentModel |
1.3.6.1.4.1.2254.2.4.1.2 |
The UPS Model designation. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
dupsIdentUPSSoftwareVersion |
1.3.6.1.4.1.2254.2.4.1.3 |
The UPS firmware/software version(s). This variable
may or may not has the same value as
upsIdentAgentSoftwareVersion in some implementations. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
dupsIdentAgentSoftwareVersion |
1.3.6.1.4.1.2254.2.4.1.4 |
The UPS agent software version. This variable may or
may not has the same value as
upsIdentUPSSoftwareVersion in some implementations. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
dupsIdentName |
1.3.6.1.4.1.2254.2.4.1.5 |
A string identifying the UPS. This object should be
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
dupsAttachedDevices |
1.3.6.1.4.1.2254.2.4.1.6 |
A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
dupsRatingOutputVA |
1.3.6.1.4.1.2254.2.4.1.7 |
The magnitude of the nominal output VA rating. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRatingOutputVoltage |
1.3.6.1.4.1.2254.2.4.1.8 |
The magnitude of the nominal output voltage rating. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRatingOutputFrequency |
1.3.6.1.4.1.2254.2.4.1.9 |
The magnitude of the nominal output frequency rating. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRatingBatteryVoltage |
1.3.6.1.4.1.2254.2.4.1.12 |
The magnitude of the nominal battery voltage rating. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsLowTransferVoltUpBound |
1.3.6.1.4.1.2254.2.4.1.13 |
The minimum input line voltage upper bound allowed
before the UPS system transfers to battery backup. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsLowTransferVoltLowBound |
1.3.6.1.4.1.2254.2.4.1.14 |
The minimum input line voltage lower bound allowed
before the UPS system transfers to battery backup. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsHighTransferVoltUpBound |
1.3.6.1.4.1.2254.2.4.1.15 |
The maximum input line voltage upper bound allowed
before the UPS system transfers to battery backup. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsHighTransferVoltLowBound |
1.3.6.1.4.1.2254.2.4.1.16 |
The maximum input line voltage lower bound allowed
before the UPS system transfers to battery backup. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsLowBattTime |
1.3.6.1.4.1.2254.2.4.1.17 |
Minutes, time from low battery to low battery shutdown. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutletRelays |
1.3.6.1.4.1.2254.2.4.1.18 |
Number of outlet relay. If it is 0, the function is not
available for the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsType |
1.3.6.1.4.1.2254.2.4.1.19 |
Indicate the UPS type. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on-line(1), off-line(2), line-interactive(3), phase3(4), splite-phase(5) |
|
dupsShutdownType |
1.3.6.1.4.1.2254.2.4.2.1 |
This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
output(1), system(2) |
|
dupsAutoReboot |
1.3.6.1.4.1.2254.2.4.2.2 |
In backup mode, the UPS may shutdown normally by SDA command,
dry-contact remote shutdown signal or low battery shutdown.
This command is used to determine the unit should restart or
not next time when the power restores |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(2) |
|
dupsShutdownAction |
1.3.6.1.4.1.2254.2.4.2.3 |
If the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType after
the seconds. 0, aborted. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRestartAction |
1.3.6.1.4.1.2254.2.4.2.4 |
UPS will restart after the indicated number of minutes.
-1, aborted. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsSetOutletRelay |
1.3.6.1.4.1.2254.2.4.2.5 |
Indicate which outlet relay, from 1,2,3... . |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRelayOffDelay |
1.3.6.1.4.1.2254.2.4.2.6 |
Turn the relay off after the seconds. The relay was indicated
by SetOutletRelay. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsRelayOnDelay |
1.3.6.1.4.1.2254.2.4.2.7 |
Turn the relay on after the seconds. The relay was indicated
by SetOutletRelay. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsConfigBuzzerAlarm |
1.3.6.1.4.1.2254.2.4.3.1 |
UPS will keep silence but will alarm again when
next power event is occurred |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
alarm(1), silence(2) |
|
dupsConfigBuzzerState |
1.3.6.1.4.1.2254.2.4.3.2 |
If it is disabled then the UPS is always muted. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
enable(1), disable(2) |
|
dupsConfigSensitivity |
1.3.6.1.4.1.2254.2.4.3.3 |
The seneitivity of the UPS to utility line
abnormalities or noises. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), reduced(1), low(2) |
|
dupsConfigLowVoltageTransferPoint |
1.3.6.1.4.1.2254.2.4.3.4 |
The minimum input line voltage allowed before the UPS
system transfers to battery backup. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsConfigHighVoltageTransferPoint |
1.3.6.1.4.1.2254.2.4.3.5 |
The maximum line voltage allowed before the UPS
system transfers to battery backup. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsConfigShutdownOSDelay |
1.3.6.1.4.1.2254.2.4.3.6 |
The operating system shutdown delay time when the
input power fail. -1 will disable this option. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsConfigUPSBootDelay |
1.3.6.1.4.1.2254.2.4.3.7 |
Delay the UPS startup after power restores. The power
quality may not stable when power restores, this
feature let the UPS wait a period of time to startup
the system. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsConfigExternalBatteryPack |
1.3.6.1.4.1.2254.2.4.3.8 |
Indicate the number of external battery pack. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputSource |
1.3.6.1.4.1.2254.2.4.5.1 |
The present source of output power. The enumeration
none(7) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(0), battery(1), bypass(2), reducing(3), boosting(4), manualBypass(5), other(6), none(7) |
|
dupsOutputFrequency |
1.3.6.1.4.1.2254.2.4.5.2 |
The present output frequency in 1/10 Hz. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputNumLines |
1.3.6.1.4.1.2254.2.4.5.3 |
The number of output lines utilized in this device. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputVoltage1 |
1.3.6.1.4.1.2254.2.4.5.4 |
The Output line 1 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputCurrent1 |
1.3.6.1.4.1.2254.2.4.5.5 |
The Output line 1 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputPower1 |
1.3.6.1.4.1.2254.2.4.5.6 |
The Output line 1 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputLoad1 |
1.3.6.1.4.1.2254.2.4.5.7 |
The current UPS output line 1 load expressed in percent
of rated capacity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputVoltage2 |
1.3.6.1.4.1.2254.2.4.5.8 |
The Output line 2 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputCurrent2 |
1.3.6.1.4.1.2254.2.4.5.9 |
The Output line 2 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputPower2 |
1.3.6.1.4.1.2254.2.4.5.10 |
The Output line 2 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputLoad2 |
1.3.6.1.4.1.2254.2.4.5.11 |
The current UPS output line 2 load expressed in percent
of rated capacity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputVoltage3 |
1.3.6.1.4.1.2254.2.4.5.12 |
The Output line 3 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputCurrent3 |
1.3.6.1.4.1.2254.2.4.5.13 |
The Output line 3 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputPower3 |
1.3.6.1.4.1.2254.2.4.5.14 |
The Output line 3 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsOutputLoad3 |
1.3.6.1.4.1.2254.2.4.5.15 |
The current UPS output line 3 load expressed in percent
of rated capacity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassFrequency |
1.3.6.1.4.1.2254.2.4.6.1 |
The present bypass frequency in 1/10 Hz. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassNumLines |
1.3.6.1.4.1.2254.2.4.6.2 |
The number of bypass lines utilized in this device. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassVoltage1 |
1.3.6.1.4.1.2254.2.4.6.3 |
The bypass line 1 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassCurrent1 |
1.3.6.1.4.1.2254.2.4.6.4 |
The bypass line 1 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassPower1 |
1.3.6.1.4.1.2254.2.4.6.5 |
The bypass line 1 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassVoltage2 |
1.3.6.1.4.1.2254.2.4.6.6 |
The bypass line 2 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassCurrent2 |
1.3.6.1.4.1.2254.2.4.6.7 |
The bypass line 2 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassPower2 |
1.3.6.1.4.1.2254.2.4.6.8 |
The bypass line 2 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassVoltage3 |
1.3.6.1.4.1.2254.2.4.6.9 |
The bypass line 3 voltage of the UPS system in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassCurrent3 |
1.3.6.1.4.1.2254.2.4.6.10 |
The bypass line 3 current of the UPS system in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBypassPower3 |
1.3.6.1.4.1.2254.2.4.6.11 |
The bypass line 3 real power of the UPS system in watts. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBatteryCondiction |
1.3.6.1.4.1.2254.2.4.7.1 |
The indication of the capacity remaining in the UPS
system's batteries when AC normal. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
good(0), weak(1), replace(2) |
|
dupsBatteryStatus |
1.3.6.1.4.1.2254.2.4.7.2 |
The indication of the capacity remaining in the UPS
system's batteries when AC failed. A value of ok
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of low indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
depleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(0), low(1), depleted(2) |
|
dupsBatteryCharge |
1.3.6.1.4.1.2254.2.4.7.3 |
Tok_String |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
floating(0), charging(1), resting(2), discharging(3) |
|
dupsSecondsOnBattery |
1.3.6.1.4.1.2254.2.4.7.4 |
If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBatteryEstimatedTime |
1.3.6.1.4.1.2254.2.4.7.5 |
Estimated time from backup to low battery shutdown. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBatteryVoltage |
1.3.6.1.4.1.2254.2.4.7.6 |
The magnitude of the present battery voltage
in 1/10 V. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBatteryCurrent |
1.3.6.1.4.1.2254.2.4.7.7 |
The present battery current in 1/10 A. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsBatteryCapacity |
1.3.6.1.4.1.2254.2.4.7.8 |
An estimate of the battery charge remaining expressed
as a percent of full charge. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
dupsTemperature |
1.3.6.1.4.1.2254.2.4.7.9 |
The ambient temperature at or near the UPS Battery
casing. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsLastReplaceDate |
1.3.6.1.4.1.2254.2.4.7.10 |
The last battery replacement date. The format is YYYYMMDD. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..8) |
|
dupsNextReplaceDate |
1.3.6.1.4.1.2254.2.4.7.11 |
The next battery replacement date. The format is YYYYMMDD. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..8) |
|
dupsTestType |
1.3.6.1.4.1.2254.2.4.8.1 |
Perform the UPS Test procedure. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
abort(0), generalTest(1), batteryTest(2), testFor10sec(3), testUntilBattlow(4) |
|
dupsTestResultsSummary |
1.3.6.1.4.1.2254.2.4.8.2 |
The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
generalTestFail(3), and batteryTestFail(4) indicate that the
test completed either successfully, with a warning, or
with an error, respectively.Tests which have not yet
concluded are indicated by inProgress(2). The value
noTestsInitiated(0) indicates that no previous test
results are available. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
noTestsInitiated(0), donePass(1), inProgress(2), generalTestFail(3), batteryTestFail(4), deepBatteryTestFail(5) |
|
dupsTestResultsDetail |
1.3.6.1.4.1.2254.2.4.8.3 |
Additional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
dupsAlarmDisconnect |
1.3.6.1.4.1.2254.2.4.9.1 |
Does the UPS disconnect? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmPowerFail |
1.3.6.1.4.1.2254.2.4.9.2 |
Does the input power fail? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmBatteryLow |
1.3.6.1.4.1.2254.2.4.9.3 |
Are the UPS batteries low? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmLoadWarning |
1.3.6.1.4.1.2254.2.4.9.4 |
Does the UPS load percent over the load warning value? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmLoadSeverity |
1.3.6.1.4.1.2254.2.4.9.5 |
Does the UPS load percent over the load severity value? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmLoadOnBypass |
1.3.6.1.4.1.2254.2.4.9.6 |
Does the UPS load on bypass? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmUPSFault |
1.3.6.1.4.1.2254.2.4.9.7 |
Does the UPS general fail? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmBatteryGroundFault |
1.3.6.1.4.1.2254.2.4.9.8 |
Does the UPS battery ground fault? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmTestInProgress |
1.3.6.1.4.1.2254.2.4.9.9 |
Does the UPS test in progress? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmBatteryTestFail |
1.3.6.1.4.1.2254.2.4.9.10 |
Does the UPS test fail? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmFuseFailure |
1.3.6.1.4.1.2254.2.4.9.11 |
Does the UPS fuse failure? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOutputOverload |
1.3.6.1.4.1.2254.2.4.9.12 |
Does the UPS output overload? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOutputOverCurrent |
1.3.6.1.4.1.2254.2.4.9.13 |
Does the UPS output overcurrent? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmInverterAbnormal |
1.3.6.1.4.1.2254.2.4.9.14 |
Does the UPS inverter abnormal? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmRectifierAbnormal |
1.3.6.1.4.1.2254.2.4.9.15 |
Does the UPS rectifier abnormal? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmReserveAbnormal |
1.3.6.1.4.1.2254.2.4.9.16 |
Does the UPS reserve abnormal? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmLoadOnReserve |
1.3.6.1.4.1.2254.2.4.9.17 |
Does the UPS load on reserve? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOverTemperature |
1.3.6.1.4.1.2254.2.4.9.18 |
Does the UPS over heat? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOutputBad |
1.3.6.1.4.1.2254.2.4.9.19 |
Is the UPS output abnormal? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmBypassBad |
1.3.6.1.4.1.2254.2.4.9.20 |
Is the UPS bypass bad? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmUPSOff |
1.3.6.1.4.1.2254.2.4.9.21 |
Is the UPS in standby mode? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmChargerFail |
1.3.6.1.4.1.2254.2.4.9.22 |
Does the UPS charger fail? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmFanFail |
1.3.6.1.4.1.2254.2.4.9.23 |
Does the UPS fan fail? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEconomicMode |
1.3.6.1.4.1.2254.2.4.9.24 |
Indicates whether the UPS is in the economic mode. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOutputOff |
1.3.6.1.4.1.2254.2.4.9.25 |
Indicates whether the UPS output is turned off or not. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmSmartShutdown |
1.3.6.1.4.1.2254.2.4.9.26 |
Indicates whether the Smart Shutdown is in progress. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEmergencyPowerOff |
1.3.6.1.4.1.2254.2.4.9.27 |
UPS emergency power off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmUPSShutdown |
1.3.6.1.4.1.2254.2.4.9.28 |
UPS shutdown. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsEnvTemperature |
1.3.6.1.4.1.2254.2.4.10.1 |
The ambient environmental temperature. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsEnvHumidity |
1.3.6.1.4.1.2254.2.4.10.2 |
The environmental humidity. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsEnvSetTemperatureLimit |
1.3.6.1.4.1.2254.2.4.10.3 |
Alarm dupsAlarmOverTemperature on when the environmental
temperature over the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsEnvSetHumidityLimit |
1.3.6.1.4.1.2254.2.4.10.4 |
Alarm dupsAlarmOverHumidity on when the environmental
humidity over the value. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
dupsEnvSetEnvRelay1 |
1.3.6.1.4.1.2254.2.4.10.5 |
Tok_String |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normalOpen(0), normalClose(1) |
|
dupsEnvSetEnvRelay2 |
1.3.6.1.4.1.2254.2.4.10.6 |
Tok_String |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normalOpen(0), normalClose(1) |
|
dupsEnvSetEnvRelay3 |
1.3.6.1.4.1.2254.2.4.10.7 |
Tok_String |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normalOpen(0), normalClose(1) |
|
dupsEnvSetEnvRelay4 |
1.3.6.1.4.1.2254.2.4.10.8 |
Tok_String |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normalOpen(0), normalClose(1) |
|
dupsAlarmOverEnvTemperature |
1.3.6.1.4.1.2254.2.4.10.9 |
Does the environment over temperature? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmOverEnvHumidity |
1.3.6.1.4.1.2254.2.4.10.10 |
Does the environment over humidity? |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEnvRelay1 |
1.3.6.1.4.1.2254.2.4.10.11 |
Tok_String |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEnvRelay2 |
1.3.6.1.4.1.2254.2.4.10.12 |
Tok_String |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEnvRelay3 |
1.3.6.1.4.1.2254.2.4.10.13 |
Tok_String |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsAlarmEnvRelay4 |
1.3.6.1.4.1.2254.2.4.10.14 |
Tok_String |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
off(0), on(1) |
|
dupsPowerFail |
3 |
WARNING: Power failed! The UPS is operating on battery power. |
TRAP-TYPE |
|
|
|
dupsPowerRestored |
4 |
INFORMATION: Power restored! The utility power restored. |
TRAP-TYPE |
|
|
|
dupsLowBattery |
5 |
SEVER: The UPS batteries are low and will soon be exhausted. |
TRAP-TYPE |
|
|
|
dupsLoadWarning |
7 |
INFORMATION: Loading percent of the UPS over the Load Warning value. |
TRAP-TYPE |
|
|
|
dupsLoadSeverity |
9 |
Warning: Loading percent of the UPS over the Load Severity value. |
TRAP-TYPE |
|
|
|
dupsUPSFault |
13 |
SEVER: A general fault caused in the UPS. |
TRAP-TYPE |
|
|
|
dupsEnvRelay1Alarm |
37 |
INFORMATION: The environment relay1 is not in normal state. |
TRAP-TYPE |
|
|
|
dupsEnvRelay2Alarm |
39 |
INFORMATION: The environment relay2 is not in normal state. |
TRAP-TYPE |
|
|
|
dupsEnvRelay3Alarm |
41 |
INFORMATION: The environment relay3 is not in normal state. |
TRAP-TYPE |
|
|
|
dupsEnvRelay4Alarm |
43 |
INFORMATION: The environment relay4 is not in normal state. |
TRAP-TYPE |
|
|
|
dupsTestCompleted |
47 |
INFORMATION: This trap is sent upon completion of a UPS diagnostic test. |
TRAP-TYPE |
|
|
|
dupsEPOON |
48 |
INFORMATION: This trap is sent when emergency power off is on. |
TRAP-TYPE |
|
|
|
dupsEPOOFF |
49 |
INFORMATION: This trap is sent when UPS recover from emergency power off. |
TRAP-TYPE |
|
|
|