ELTEK-GENERIC-MIB

File: ELTEK-GENERIC-MIB.mib (46686 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC
ELTEK-COMMON-MIB

Imported symbols

NOTIFICATION-TYPE OBJECT-TYPE MODULE-IDENTITY
mib-2 enterprises Integer32
NOTIFICATION-GROUP DisplayString eltek

Defined Types

BatteryMidpointControlEntry  
SEQUENCE    
  midpointEnableID Integer32
  midpointEnable INTEGER

BatteryMidpointStatusEntry  
SEQUENCE    
  midpointStatusID Integer32
  midpointStatus INTEGER
  midpointDeltaVoltage Integer32

RectifierStatusEntry  
SEQUENCE    
  rectifierStatusID Integer32
  rectifierStatusStatus INTEGER
  rectifierStatusOutputCurrent Integer32
  rectifierStatusOutputVoltage Integer32
  rectifierStatusTemp Integer32
  rectifierStatusType DisplayString
  rectifierStatusSKU DisplayString
  rectifierStatusSerialNo DisplayString
  rectifierStatusRevisionLevel DisplayString

Defined Values

eltekPlant 1.3.6.1.4.1.12148.7
OBJECT IDENTIFIER    

controlSystem 1.3.6.1.4.1.12148.7.1
OBJECT IDENTIFIER    

systemTime 1.3.6.1.4.1.12148.7.1.1
OBJECT IDENTIFIER    

dcSystem 1.3.6.1.4.1.12148.7.2
OBJECT IDENTIFIER    

dcPlant 1.3.6.1.4.1.12148.7.2.1
OBJECT IDENTIFIER    

systemSiteInfo 1.3.6.1.4.1.12148.7.2.1.3
OBJECT IDENTIFIER    

battery 1.3.6.1.4.1.12148.7.3
OBJECT IDENTIFIER    

batteryLVD 1.3.6.1.4.1.12148.7.3.17
OBJECT IDENTIFIER    

batteryMidpoint 1.3.6.1.4.1.12148.7.3.18
OBJECT IDENTIFIER    

loadDistribution 1.3.6.1.4.1.12148.7.4
OBJECT IDENTIFIER    

loadDistributionLVDStatus 1.3.6.1.4.1.12148.7.4.3
OBJECT IDENTIFIER    

rectifier 1.3.6.1.4.1.12148.7.5
OBJECT IDENTIFIER    

rectifierStatus 1.3.6.1.4.1.12148.7.5.5
OBJECT IDENTIFIER    

acDistribution 1.3.6.1.4.1.12148.7.6
OBJECT IDENTIFIER    

alarmGroup 1.3.6.1.4.1.12148.7.7
OBJECT IDENTIFIER    

alarmWellknownAlarms 1.3.6.1.4.1.12148.7.7.1
OBJECT IDENTIFIER    

systemTimeTime 1.3.6.1.4.1.12148.7.1.1.1
The system date and time. Used for event timestamps and logging
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..255)  

systemInfoRefresh 1.3.6.1.4.1.12148.7.1.2
This object will re-initialize the agent, updating MIB data values.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), refreshdata(1)  

systemTrapRepeatRate 1.3.6.1.4.1.12148.7.1.3
This object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10  

systemSendOffTrap 1.3.6.1.4.1.12148.7.1.4
A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

systemSiteInfoCustomer 1.3.6.1.4.1.12148.7.2.1.3.1
The Customer name (as stored in the Smartpack Control Unit)
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoLocation 1.3.6.1.4.1.12148.7.2.1.3.2
The system/site Location details (as stored in the Smartpack Control Unit).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoMessage1 1.3.6.1.4.1.12148.7.2.1.3.3
The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoMessage2 1.3.6.1.4.1.12148.7.2.1.3.4
The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

systemSiteInfoInstalledDate 1.3.6.1.4.1.12148.7.2.1.3.5
The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemSiteInfoControllerType 1.3.6.1.4.1.12148.7.2.1.3.6
The system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER al175(0), al4000(1), al6000(2), enexus(3)  

systemSiteInfoSystemSeriaNum 1.3.6.1.4.1.12148.7.2.1.3.7
The serial number for the complete system
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemSiteInfoControllerSeriaNum 1.3.6.1.4.1.12148.7.2.1.3.8
The serial number for the system controller
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

systemNominalVoltage 1.3.6.1.4.1.12148.7.2.1.4
The nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER prs48v(0), prs24v(1), prs12v(2), prs26v(3), prs60v(4)  

systemOperationalStatus 1.3.6.1.4.1.12148.7.2.2
A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=battery test
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER floatvoltreg(0), floattempcomp(1), batteryboost(2), batterytest(3)  

batteryName 1.3.6.1.4.1.12148.7.3.1
A descriptive name of the battery installed in the system
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

batteryVoltage 1.3.6.1.4.1.12148.7.3.2
The measured battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..7500  

batteryCurrent 1.3.6.1.4.1.12148.7.3.3
The measured battery current.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

batteryTemp 1.3.6.1.4.1.12148.7.3.4
The battery temperature
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..9999  

batteryBreakerStatus 1.3.6.1.4.1.12148.7.3.5
The state of the battery fuse/breaker can be either closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

batteryChargeCurrentLimitCtrl 1.3.6.1.4.1.12148.7.3.6
Control field for the battery charge limitation feature; 0=inactive, 1=active.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER deactivate(0), activate(1)  

batteryChargeCurrentLimitValue 1.3.6.1.4.1.12148.7.3.7
Battery charging current limit value
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..2100  

batteryTempCompEnable 1.3.6.1.4.1.12148.7.3.8
Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryFloatVoltConfig 1.3.6.1.4.1.12148.7.3.9
The Voltage at which the DC System float charges.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryEqualizeVoltConfig 1.3.6.1.4.1.12148.7.3.10
The Voltage at which the DC System boost charges the batteries.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 4300..6000  

batteryHighMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.7.3.11
The High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryHighMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.7.3.12
The High Battery Voltage alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLowMajorAlarmVoltageConfig 1.3.6.1.4.1.12148.7.3.13
The Low Battery Voltage Alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryLowMinorAlarmVoltageConfig 1.3.6.1.4.1.12148.7.3.14
The Very Low Battery Voltage Alarm limit set voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryStartManualTest 1.3.6.1.4.1.12148.7.3.15
This pushbutton will start a manual battery test if otherwise the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), starttest(1), stoptest(2)  

batteryStartManualBoost 1.3.6.1.4.1.12148.7.3.16
This pushbutton will start a manual battery boost if otherwise the system allows it.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER pushbutton(0), startboost(1), stopboost(2)  

batteryLVDStatus 1.3.6.1.4.1.12148.7.3.17.1
Contactor is closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connect(0), disconnect(1), disable(2)  

batteryLVDDisconnectVoltage 1.3.6.1.4.1.12148.7.3.17.2
The Contactor Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

batteryLVDConnectVoltage 1.3.6.1.4.1.12148.7.3.17.3
The Contactor Reconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

batteryMidpointDeltaLimitVoltage 1.3.6.1.4.1.12148.7.3.18.1
The allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

batteryMidpointIndex 1.3.6.1.4.1.12148.7.3.18.2
An index of Battery Strings, for the batteryMidpointControlTable and batteryMidpointStatusTable arrays
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

batteryMidpointControlTable 1.3.6.1.4.1.12148.7.3.18.3
A table of settings related to Battery Symmetry (midpoint) Monitoring
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMidpointControlEntry

batteryMidpointControlEntry 1.3.6.1.4.1.12148.7.3.18.3.1
Settings related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMidpointControlEntry  

midpointEnableID 1.3.6.1.4.1.12148.7.3.18.3.1.1
The rectifier ID number of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

midpointEnable 1.3.6.1.4.1.12148.7.3.18.3.1.2
Enable (1) or Disable (0) the Battery Monitor channel which corresponds to the batteryMidpointIndex value
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

batteryMidpointStatusTable 1.3.6.1.4.1.12148.7.3.18.4
A table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    BatteryMidpointStatusEntry

batteryMidpointStatusEntry 1.3.6.1.4.1.12148.7.3.18.4.1
Values related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value
Status: current Access: not-accessible
OBJECT-TYPE    
  BatteryMidpointStatusEntry  

midpointStatusID 1.3.6.1.4.1.12148.7.3.18.4.1.1
The rectifier ID number of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..8  

midpointStatus 1.3.6.1.4.1.12148.7.3.18.4.1.2
Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex value
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER ok(0), alarm(1), disable(2)  

midpointDeltaVoltage 1.3.6.1.4.1.12148.7.3.18.4.1.3
The measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadDistributionCurrent 1.3.6.1.4.1.12148.7.4.1
The total load current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

loadDistributionBreakerStatus 1.3.6.1.4.1.12148.7.4.2
The state of the load fuse/breaker can be either closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER closed(0), open(1)  

loadLVD1EnableStatus 1.3.6.1.4.1.12148.7.4.3.1
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD1Status 1.3.6.1.4.1.12148.7.4.3.2
The A Bus (primary loads) Contactor is closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connect(0), disconnect(1), disable(2)  

loadLVD1ConnectVoltage 1.3.6.1.4.1.12148.7.4.3.3
The A Bus (primary loads) Contactor Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD1DisconnectVoltage 1.3.6.1.4.1.12148.7.4.3.4
The A Bus (primary loads) Contactor Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD2EnableStatus 1.3.6.1.4.1.12148.7.4.3.5
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD2Status 1.3.6.1.4.1.12148.7.4.3.6
The B Bus (secondary loads) Contactor is closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connect(0), disconnect(1), disable(2)  

loadLVD2ConnectVoltage 1.3.6.1.4.1.12148.7.4.3.7
The B Bus (secondary loads) Contactor Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD2DisconnectVoltage 1.3.6.1.4.1.12148.7.4.3.8
The B Bus (secondary loads) Contactor Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD3EnableStatus 1.3.6.1.4.1.12148.7.4.3.9
The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

loadLVD3Status 1.3.6.1.4.1.12148.7.4.3.10
The C Bus (critical loads) Contactor is closed(0) or open(1)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER connect(0), disconnect(1), disable(2)  

loadLVD3ConnectVoltage 1.3.6.1.4.1.12148.7.4.3.11
The C Bus (critical loads) Contactor Connect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

loadLVD3DisconnectVoltage 1.3.6.1.4.1.12148.7.4.3.12
The C Bus (critical loads) Contactor Disconnect Voltage
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..7200  

rectifierInstalledRectifiers 1.3.6.1.4.1.12148.7.5.1
The installed number of rectifiers for this DC Power System.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

rectifierRectifiersActive 1.3.6.1.4.1.12148.7.5.2
The actual number of active rectifiers in this DC Power System.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..101  

rectifierTotalCurrent 1.3.6.1.4.1.12148.7.5.3
The DC system's total available current
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

rectifierUtilization 1.3.6.1.4.1.12148.7.5.4
Utilization in % of available rectifier capacity
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..100  

rectifierStatusNoIndex 1.3.6.1.4.1.12148.7.5.5.1
A starting index for the rectifierStatusTable array
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 1..20  

rectifierStatusTable 1.3.6.1.4.1.12148.7.5.5.2
A table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RectifierStatusEntry

rectifierStatusEntry 1.3.6.1.4.1.12148.7.5.5.2.1
A row of rectifier status data corresponding to the rectifierStatusNoIndex value
Status: current Access: not-accessible
OBJECT-TYPE    
  RectifierStatusEntry  

rectifierStatusID 1.3.6.1.4.1.12148.7.5.5.2.1.1
The rectifier ID number of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..100  

rectifierStatusStatus 1.3.6.1.4.1.12148.7.5.5.2.1.2
The operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER absent(0), active(1), failed(2), walkin(3), disabledbycommand(4)  

rectifierStatusOutputCurrent 1.3.6.1.4.1.12148.7.5.5.2.1.3
The rectifier current of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusOutputVoltage 1.3.6.1.4.1.12148.7.5.5.2.1.4
The rectifier voltage of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusTemp 1.3.6.1.4.1.12148.7.5.5.2.1.5
The heatsink temperature of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..65535  

rectifierStatusType 1.3.6.1.4.1.12148.7.5.5.2.1.6
The rectifier article number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifierStatusSKU 1.3.6.1.4.1.12148.7.5.5.2.1.7
The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifierStatusSerialNo 1.3.6.1.4.1.12148.7.5.5.2.1.8
The rectifier serial number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

rectifierStatusRevisionLevel 1.3.6.1.4.1.12148.7.5.5.2.1.9
The rectifier version number string of the rectifier record.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

acVoltage1 1.3.6.1.4.1.12148.7.6.1
The AC Voltage of phase 1
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acVoltage2 1.3.6.1.4.1.12148.7.6.2
The AC Voltage of phase 2
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

acVoltage3 1.3.6.1.4.1.12148.7.6.3
The AC Voltage of phase 3
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

alarmMajorHighBattVolt 1.3.6.1.4.1.12148.7.7.1.1
The Very High Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorHighBattVolt 1.3.6.1.4.1.12148.7.7.1.2
The High Battery Voltage alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorLowBattVolt 1.3.6.1.4.1.12148.7.7.1.3
The Very Low Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorLowBattVolt 1.3.6.1.4.1.12148.7.7.1.4
The Low Battery Voltage Alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorBatteryHighTemp 1.3.6.1.4.1.12148.7.7.1.5
Temperature much too high alarm, or temperature compensation circuit / probe failure alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorBatteryHighTemp 1.3.6.1.4.1.12148.7.7.1.6
Temperature much too high alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryDisconnectOpen 1.3.6.1.4.1.12148.7.7.1.7
The Battery Disconnect Contactor alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD1open 1.3.6.1.4.1.12148.7.7.1.8
The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD2open 1.3.6.1.4.1.12148.7.7.1.9
The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmLVD3open 1.3.6.1.4.1.12148.7.7.1.10
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmACmains 1.3.6.1.4.1.12148.7.7.1.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryBreakerOpen 1.3.6.1.4.1.12148.7.7.1.12
Battery string disconnect breaker/fuse alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmDistributionBreakerOpen 1.3.6.1.4.1.12148.7.7.1.13
The Load Distribution breaker/fuse alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorRectifier 1.3.6.1.4.1.12148.7.7.1.14
This is a 'multiple rectifiers have failed' alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorRectifier 1.3.6.1.4.1.12148.7.7.1.15
This is a 'one rectifier has failed' alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMajorBatteryMidpoint 1.3.6.1.4.1.12148.7.7.1.16
Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmMinorBatteryMidpoint 1.3.6.1.4.1.12148.7.7.1.17
Battery Symmetry (midpoint) Delta Voltage out of limits alarm
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryLifeEnded 1.3.6.1.4.1.12148.7.7.1.18
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryTestmodeEntered 1.3.6.1.4.1.12148.7.7.1.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmBatteryBoostmodeEntered 1.3.6.1.4.1.12148.7.7.1.20
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable1 1.3.6.1.4.1.12148.7.7.1.21
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable2 1.3.6.1.4.1.12148.7.7.1.22
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable3 1.3.6.1.4.1.12148.7.7.1.23
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable4 1.3.6.1.4.1.12148.7.7.1.24
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable5 1.3.6.1.4.1.12148.7.7.1.25
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable6 1.3.6.1.4.1.12148.7.7.1.26
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable7 1.3.6.1.4.1.12148.7.7.1.27
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable8 1.3.6.1.4.1.12148.7.7.1.28
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable9 1.3.6.1.4.1.12148.7.7.1.29
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable10 1.3.6.1.4.1.12148.7.7.1.30
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable11 1.3.6.1.4.1.12148.7.7.1.31
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable12 1.3.6.1.4.1.12148.7.7.1.32
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable13 1.3.6.1.4.1.12148.7.7.1.33
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

alarmUserConfigurable14 1.3.6.1.4.1.12148.7.7.1.34
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normal(0), alarm(1)  

dcSystemTraps 1.3.6.1.4.1.12148.7.8
This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
Status: current Access: read-only
NOTIFICATION-GROUP    

alarmMajorHighBattVoltTrap 1.3.6.1.4.1.12148.7.8.1
The Very High Battery Voltage alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorHighBattVoltTrap 1.3.6.1.4.1.12148.7.8.2
The High Battery Voltage alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorLowBattVoltTrap 1.3.6.1.4.1.12148.7.8.3
The Very Low Battery Voltage Alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorLowBattVoltTrap 1.3.6.1.4.1.12148.7.8.4
The Low Battery Voltage Alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorBatteryHighTempTrap 1.3.6.1.4.1.12148.7.8.5
High Battery temperature alarm or Temperature Compensation circuit / probe failure alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorBatteryHighTempTrap 1.3.6.1.4.1.12148.7.8.6
High Battery temperature alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryDisconnectOpenTrap 1.3.6.1.4.1.12148.7.8.7
The Battery Disconnect Contactor alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD1openTrap 1.3.6.1.4.1.12148.7.8.8
The A Bus (primary loads) Contactor is open alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD2openTrap 1.3.6.1.4.1.12148.7.8.9
The B Bus (secondary loads) Contactor is open alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmLVD3openTrap 1.3.6.1.4.1.12148.7.8.10
The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmACmainsTrap 1.3.6.1.4.1.12148.7.8.11
The AC voltage has dropped below critical level, or one or more AC input phases was lost.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryBreakerOpenTrap 1.3.6.1.4.1.12148.7.8.12
Battery string disconnect breaker/fuse alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmDistributionBreakerOpenTrap 1.3.6.1.4.1.12148.7.8.13
The Load Distribution breaker/fuse alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorRectifierTrap 1.3.6.1.4.1.12148.7.8.14
This is a 'multiple rectifiers have failed' alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorRectifierTrap 1.3.6.1.4.1.12148.7.8.15
This is a 'one rectifier has failed' alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMajorBatteryMidpointTrap 1.3.6.1.4.1.12148.7.8.16
Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmMinorBatteryMidpointTrap 1.3.6.1.4.1.12148.7.8.17
Battery Symmetry (midpoint) Delta Voltage out of limits alarm
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryLifeEndedTrap 1.3.6.1.4.1.12148.7.8.18
The battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryTestmodeEnteredTrap 1.3.6.1.4.1.12148.7.8.19
The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmBatteryBoostmodeEnteredTrap 1.3.6.1.4.1.12148.7.8.20
The system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable1Trap 1.3.6.1.4.1.12148.7.8.21
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable2Trap 1.3.6.1.4.1.12148.7.8.22
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable3Trap 1.3.6.1.4.1.12148.7.8.23
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable4Trap 1.3.6.1.4.1.12148.7.8.24
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable5Trap 1.3.6.1.4.1.12148.7.8.25
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable6Trap 1.3.6.1.4.1.12148.7.8.26
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable7Trap 1.3.6.1.4.1.12148.7.8.27
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable8Trap 1.3.6.1.4.1.12148.7.8.28
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable9Trap 1.3.6.1.4.1.12148.7.8.29
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable10Trap 1.3.6.1.4.1.12148.7.8.30
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable11Trap 1.3.6.1.4.1.12148.7.8.31
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable12Trap 1.3.6.1.4.1.12148.7.8.32
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable13Trap 1.3.6.1.4.1.12148.7.8.33
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmUserConfigurable14Trap 1.3.6.1.4.1.12148.7.8.34
Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.
Status: current Access: read-only
NOTIFICATION-TYPE