ENLOGIC-PDU-MIB

File: ENLOGIC-PDU-MIB.mib (149341 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC
INET-ADDRESS-MIB RFC1213-MIB

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises Integer32 Unsigned32
IpAddress MODULE-COMPLIANCE OBJECT-GROUP
NOTIFICATION-GROUP TEXTUAL-CONVENTION DisplayString
MacAddress TruthValue InetAddressType
InetAddress sysContact sysName
sysLocation

Defined Types

PduNamePlateEntry  
SEQUENCE    
  pduNamePlateIndex Integer32
  pduNamePlateName DisplayString
  pduNamePlateLocation DisplayString
  pduNamePlateInetAddressType InetAddressType
  pduNamePlateIPAddress InetAddress
  pduNamePlateInetNetMask InetAddress
  pduNamePlateInetGateway InetAddress
  pduNamePlateMACAddress MacAddress
  pduNamePlateUTCTimeOffset DisplayString
  pduNamePlateModelNumber DisplayString
  pduNamePlateSerialNumber DisplayString
  pduNamePlateDateofManufacture DisplayString
  pduNamePlateFirmwareVersion DisplayString
  pduNamePlateFirmwareVersionTimeStamp DisplayString
  pduNamePlateType INTEGER

PduUnitConfigEntry  
SEQUENCE    
  pduUnitConfigIndex Integer32
  pduUnitConfigName DisplayString
  pduUnitConfigLocation DisplayString
  pduUnitConfigDisplayOrientation INTEGER
  pduUnitConfigColdstartDelay Unsigned32
  pduUnitConfigGlobalOutletStateOnStartup INTEGER
  pduUnitConfigLowerCriticalThreshold Unsigned32
  pduUnitConfigLowerWarningThreshold Unsigned32
  pduUnitConfigUpperCriticalThreshold Unsigned32
  pduUnitConfigUpperWarningThreshold Unsigned32
  pduUnitConfigAlarmResetThreshold Unsigned32
  pduUnitConfigAlarmStateChangeDelay Unsigned32
  pduUnitConfigEnabledThresholds BITS
  pduUnitConfigPeakPowerReset INTEGER
  pduUnitConfigEnergyReset INTEGER
  pduUnitConfigOutletPeakPowerReset INTEGER
  pduUnitConfigOutletEnergyReset INTEGER
  pduUnitConfigUsb INTEGER
  pduUnitConfigSsh INTEGER
  pduUnitConfigResetNetworkManagementCard INTEGER
  pduUnitConfigDaisyChainState INTEGER

PduUnitPropertiesEntry  
SEQUENCE    
  pduUnitPropertiesIndex Integer32
  pduUnitPropertiesName DisplayString
  pduUnitPropertiesOutletCount Integer32
  pduUnitPropertiesSwitchedOutletCount Integer32
  pduUnitPropertiesMeteredOutletCount Integer32
  pduUnitPropertiesInputPhaseCount Integer32
  pduUnitPropertiesCircuitBreakerCount Integer32
  pduUnitPropertiesMaxExternalSensorCount Integer32
  pduUnitPropertiesConnExternalSensorCount Integer32
  pduUnitPropertiesRatedVoltage DisplayString
  pduUnitPropertiesRatedMaxCurrent DisplayString
  pduUnitPropertiesRatedFrequency DisplayString
  pduUnitPropertiesRatedPower DisplayString
  pduUnitPropertiesOrientation INTEGER
  pduUnitPropertiesOutletLayout INTEGER
  pduUnitPropertiesDaisyChainMemberType INTEGER
  pduUnitPropertiesServerCount Integer32

PduUnitStatusEntry  
SEQUENCE    
  pduUnitStatusIndex Integer32
  pduUnitStatusName DisplayString
  pduUnitStatusLoadState INTEGER
  pduUnitStatusActivePower Integer32
  pduUnitStatusApparentPower Integer32
  pduUnitStatusPeakPower Integer32
  pduUnitStatusPeakPowerTimestamp DisplayString
  pduUnitStatusPeakPowerStartTime DisplayString
  pduUnitStatusEnergy Integer32
  pduUnitStatusResettableEnergy Integer32
  pduUnitStatusEnergyStartTime DisplayString
  pduUnitStatusOutletsEnergyStartTime DisplayString

PduInputPhaseConfigEntry  
SEQUENCE    
  pduInputPhaseConfigIndex Integer32
  pduInputPhaseConfigCount Integer32
  pduInputPhaseConfigOverloadRestriction INTEGER
  pduInputPhaseConfigCurrentLowerCriticalThreshold Unsigned32
  pduInputPhaseConfigCurrentLowerWarningThreshold Unsigned32
  pduInputPhaseConfigCurrentUpperCriticalThreshold Unsigned32
  pduInputPhaseConfigCurrentUpperWarningThreshold Unsigned32
  pduInputPhaseConfigVoltageLowerCriticalThreshold Unsigned32
  pduInputPhaseConfigVoltageLowerWarningThreshold Unsigned32
  pduInputPhaseConfigVoltageUpperCriticalThreshold Unsigned32
  pduInputPhaseConfigVoltageUpperWarningThreshold Unsigned32
  pduInputPhaseConfigCurrentAlarmResetThreshold Unsigned32
  pduInputPhaseConfigCurrentAlarmStateChangeDelay Integer32
  pduInputPhaseConfigCurrentEnabledThresholds BITS
  pduInputPhaseConfigVoltageAlarmResetThreshold Unsigned32
  pduInputPhaseConfigVoltageAlarmStateChangeDelay Integer32
  pduInputPhaseConfigVoltageEnabledThresholds BITS

PduInputPhasePropertiesEntry  
SEQUENCE    
  pduInputPhasePropertiesIndex Integer32
  pduInputPhasePropertiesCount Integer32

PduInputPhaseStatusEntry  
SEQUENCE    
  pduInputPhaseStatusIndex Integer32
  pduInputPhaseStatusCount Integer32
  pduInputPhaseStatusCurrentState INTEGER
  pduInputPhaseStatusVoltageState INTEGER
  pduInputPhaseStatusCurrent Integer32
  pduInputPhaseStatusVoltage Integer32
  pduInputPhaseStatusActivePower Integer32
  pduInputPhaseStatusApparentPower Integer32
  pduInputPhaseStatusPowerFactor Integer32

PduCircuitBreakerConfigEntry  
SEQUENCE    
  pduCircuitBreakerConfigIndex Integer32
  pduCircuitBreakerConfigCount Integer32
  pduCircuitBreakerName DisplayString
  pduCircuitBreakerConfigOverloadRestriction INTEGER
  pduCircuitBreakerConfigLowerCriticalThreshold Unsigned32
  pduCircuitBreakerConfigLowerWarningThreshold Unsigned32
  pduCircuitBreakerConfigUpperCriticalThreshold Unsigned32
  pduCircuitBreakerConfigUpperWarningThreshold Unsigned32
  pduCircuitBreakerConfigAlarmResetThreshold Unsigned32
  pduCircuitBreakerConfigAlarmStateChangeDelay Unsigned32
  pduCircuitBreakerConfigEnabledThresholds BITS

PduCircuitBreakerPropertiesEntry  
SEQUENCE    
  pduCircuitBreakerPropertiesIndex Integer32
  pduCircuitBreakerPropertiesCount Integer32
  pduCircuitBreakerPropertiesInputLayout INTEGER

PduCircuitBreakerStatusEntry  
SEQUENCE    
  pduCircuitBreakerStatusIndex Integer32
  pduCircuitBreakerStatusCount Integer32
  pduCircuitBreakerLabel DisplayString
  pduCircuitBreakerStatusLoadState INTEGER
  pduCircuitBreakerStatusCurrent Integer32

PduOutletSwitchedConfigEntry  
SEQUENCE    
  pduOutletSwitchedConfigIndex Integer32
  pduOutletSwitchedName DisplayString
  pduOutletSwitchedStateOnStartup INTEGER
  pduOutletSwitchedConfigPowerOnTime Integer32
  pduOutletSwitchedConfigPowerOffTime Integer32
  pduOutletSwitchedConfigRebootDuration Integer32

PduOutletSwitchedPropertiesEntry  
SEQUENCE    
  pduOutletSwitchedPropertiesIndex Integer32
  pduOutletSwitchedPropertiesNumber Integer32
  pduOutletSwitchedPropertiesName DisplayString
  pduOutletSwitchedPropertiesInputPhaseLayout INTEGER
  pduOutletSwitchedPropertiesCircuitBreaker Integer32

PduOutletSwitchedStatusEntry  
SEQUENCE    
  pduOutletSwitchedStatusIndex Integer32
  pduOutletSwitchedStatusNumber Integer32
  pduOutletSwitchedStatusName DisplayString
  pduOutletSwitchedStatusState INTEGER

PduOutletSwitchedControlEntry  
SEQUENCE    
  pduOutletSwitchedControlIndex Integer32
  pduOutletSwitchedControlNumber Integer32
  pduOutletSwitchedControlName DisplayString
  pduOutletSwitchedControlCommand INTEGER

PduOutletMeteredConfigEntry  
SEQUENCE    
  pduOutletMeteredConfigIndex Integer32
  pduOutletMeteredName DisplayString
  pduOutletMeteredConfigLowerCriticalThreshold Unsigned32
  pduOutletMeteredConfigLowerWarningThreshold Unsigned32
  pduOutletMeteredConfigUpperCriticalThreshold Unsigned32
  pduOutletMeteredConfigUpperWarningThreshold Unsigned32
  pduOutletMeteredConfigAlarmResetThreshold Unsigned32
  pduOutletMeteredConfigAlarmStateChangeDelay Unsigned32
  pduOutletMeteredConfigEnabledThresholds BITS

PduOutletMeteredPropertiesEntry  
SEQUENCE    
  pduOutletMeteredPropertiesIndex Integer32
  pduOutletMeteredPropertiesNumber Integer32
  pduOutletMeteredPropertiesName DisplayString
  pduOutletMeteredPropertiesInputPhaseLayout INTEGER
  pduOutletMeteredPropertiesCircuitBreaker Integer32
  pduOutletMeteredPropertiesPowerRating Integer32

PduOutletMeteredStatusEntry  
SEQUENCE    
  pduOutletMeteredStatusIndex Integer32
  pduOutletMeteredStatusNumber Integer32
  pduOutletMeteredStatusName DisplayString
  pduOutletMeteredStatusLoadState INTEGER
  pduOutletMeteredStatusCurrent Integer32
  pduOutletMeteredStatusActivePower Integer32
  pduOutletMeteredStatusPowerFactor Integer32
  pduOutletMeteredStatusPeakPower Integer32
  pduOutletMeteredStatusPeakPowerTimeStamp DisplayString
  pduOutletMeteredStatusPeakPowerStartTime DisplayString
  pduOutletMeteredStatusResettableEnergy Integer32

PduExternalSensorNamePlateEntry  
SEQUENCE    
  pduExternalSensorNamePlateIndex Integer32
  pduExternalSensorNamePlateName DisplayString
  pduExternalSensorNamePlateDescription DisplayString
  pduExternalSensorNamePlateLocation DisplayString
  pduExternalSensorNamePlateSerialNumber DisplayString
  pduExternalSensorNamePlateType INTEGER
  pduExternalSensorNamePlateUnits INTEGER
  pduExternalSensorNamePlateIdentifier Integer32

PduExternalSensorConfigEntry  
SEQUENCE    
  pduExternalSensorConfigIndex Integer32
  pduExternalSensorConfigLowerCriticalThreshold Unsigned32
  pduExternalSensorConfigLowerWarningThreshold Unsigned32
  pduExternalSensorConfigUpperCriticalThreshold Unsigned32
  pduExternalSensorConfigUpperWarningThreshold Unsigned32
  pduExternalSensorConfigAlarmResetThreshold Unsigned32
  pduExternalSensorConfigAlarmStateChangeDelay Unsigned32
  pduExternalSensorConfigEnabledThresholds BITS
  pduExternalSensorConfigAlarmState INTEGER

PduExternalSensorStatusEntry  
SEQUENCE    
  pduExternalSensorStatusIndex Integer32
  pduExternalSensorStatusName DisplayString
  pduExternalSensorStatusAisle INTEGER
  pduExternalSensorStatusCommStatus INTEGER
  pduExternalSensorStatusState INTEGER
  pduExternalSensorStatusValue Integer32
  pduExternalSensorStatusTimeStamp DisplayString
  pduExternalSensorStatusHighPrecisionValue Integer32

PduServerPingEntry  
SEQUENCE    
  pduServerPingIndex Integer32
  pduServerPingServerIPAddress DisplayString
  pduServerPingEnabled INTEGER

PduUnitSmartCabinetEntry  
SEQUENCE    
  pduUnitSmartCabinetIndex Integer32
  pduUnitSmartCabinetCardUserName DisplayString
  pduUnitSmartCabinetCardID Integer32
  pduUnitSmartCabinetTimestamp DisplayString
  pduUnitSmartCabinetDoor Integer32

TrapsInfoEntry  
SEQUENCE    
  trapsInfoIndex Integer32
  userName DisplayString
  userUpdated DisplayString
  firmwareVersion DisplayString
  roleUpdated DisplayString
  smtpRecipients DisplayString
  smtpServer DisplayString

EspNamePlateEntry  
SEQUENCE    
  espNamePlateIndex Integer32
  espNamePlateName DisplayString
  espNamePlateLocation DisplayString
  espNamePlateInetAddressType InetAddressType
  espNamePlateIPAddress InetAddress
  espNamePlateInetNetMask InetAddress
  espNamePlateInetGateway InetAddress
  espNamePlateMACAddress MacAddress
  espNamePlateUTCTimeOffset DisplayString
  espNamePlateModelNumber DisplayString
  espNamePlateSerialNumber DisplayString
  espNamePlateDateofManufacture DisplayString
  espNamePlateFirmwareVersion DisplayString
  espNamePlateFirmwareVersionTimeStamp DisplayString
  espNamePlateType INTEGER

EspUnitConfigEntry  
SEQUENCE    
  espUnitConfigIndex Integer32
  espUnitConfigName DisplayString
  espUnitConfigLocation DisplayString
  espUnitConfigEnergyReset INTEGER
  espUnitConfigResetNetworkManagementCard INTEGER

EspUnitPropertiesEntry  
SEQUENCE    
  espUnitPropertiesIndex Integer32
  espUnitPropertiesName DisplayString
  espUnitPropertiesOutletCount Integer32
  espUnitPropertiesSwitchedOutletCount Integer32
  espUnitPropertiesMeteredOutletCount Integer32
  espUnitPropertiesInputPhaseCount Integer32
  espUnitPropertiesCircuitBreakerCount Integer32
  espUnitPropertiesMaxExternalSensorCount Integer32
  espUnitPropertiesConnExternalSensorCount Integer32
  espUnitPropertiesRatedVoltage DisplayString
  espUnitPropertiesRatedMaxCurrent DisplayString
  espUnitPropertiesRatedFrequency DisplayString
  espUnitPropertiesRatedPower DisplayString

EspUnitStatusEntry  
SEQUENCE    
  espUnitStatusIndex Integer32
  espUnitStatusName DisplayString
  espUnitStatusLoadState INTEGER
  espUnitStatusActivePower Integer32
  espUnitStatusApparentPower Integer32
  espUnitStatusEnergy Integer32
  espUnitStatusResettableEnergy Integer32
  espUnitStatusEnergyStartTime DisplayString

EspInputPhaseConfigEntry  
SEQUENCE    
  espInputPhaseConfigIndex Integer32
  espInputPhaseConfigCount Integer32

EspInputPhaseStatusEntry  
SEQUENCE    
  espInputPhaseStatusIndex Integer32
  espInputPhaseStatusCount Integer32
  espInputPhaseStatusCurrentState INTEGER
  espInputPhaseStatusVoltageState INTEGER
  espInputPhaseStatusCurrent Integer32
  espInputPhaseStatusVoltage Integer32
  espInputPhaseStatusActivePower Integer32
  espInputPhaseStatusApparentPower Integer32
  espInputPhaseStatusPowerFactor Integer32

EspCircuitBreakerConfigEntry  
SEQUENCE    
  espCircuitBreakerConfigIndex Integer32
  espCircuitBreakerConfigCount Integer32
  espCircuitBreakerName DisplayString

EspCircuitBreakerPropertiesEntry  
SEQUENCE    
  espCircuitBreakerPropertiesIndex Integer32
  espCircuitBreakerPropertiesCount Integer32
  espCircuitBreakerPropertiesInputLayout INTEGER

EspCircuitBreakerStatusEntry  
SEQUENCE    
  espCircuitBreakerStatusIndex Integer32
  espCircuitBreakerStatusCount Integer32
  espCircuitBreakerLabel DisplayString
  espCircuitBreakerStatusLoadState INTEGER
  espCircuitBreakerStatusCurrent Integer32

EspExternalSensorNamePlateEntry  
SEQUENCE    
  espExternalSensorNamePlateIndex Integer32
  espExternalSensorNamePlateName DisplayString
  espExternalSensorNamePlateSerialNumber DisplayString
  espExternalSensorNamePlateType INTEGER
  espExternalSensorNamePlateUnits INTEGER

EspExternalSensorConfigEntry  
SEQUENCE    
  espExternalSensorConfigIndex Integer32
  espExternalSensorConfigAlarmState INTEGER

EspExternalSensorStatusEntry  
SEQUENCE    
  espExternalSensorStatusIndex Integer32
  espExternalSensorStatusName DisplayString
  espExternalSensorStatusAisle INTEGER
  espExternalSensorStatusCommStatus INTEGER
  espExternalSensorStatusState INTEGER
  espExternalSensorStatusValue Integer32
  espExternalSensorStatusHighPrecisionValue Integer32

Defined Values

enlogic 1.3.6.1.4.1.38446
This MIB describes the SNMP functions of the Enlogic PDU.
MODULE-IDENTITY    

pdu 1.3.6.1.4.1.38446.1
OBJECT IDENTIFIER    

pduNamePlate 1.3.6.1.4.1.38446.1.1
OBJECT IDENTIFIER    

pduUnit 1.3.6.1.4.1.38446.1.2
OBJECT IDENTIFIER    

pduInputPhase 1.3.6.1.4.1.38446.1.3
OBJECT IDENTIFIER    

pduCircuitBreaker 1.3.6.1.4.1.38446.1.4
OBJECT IDENTIFIER    

pduOutlet 1.3.6.1.4.1.38446.1.5
OBJECT IDENTIFIER    

pduExternalSensor 1.3.6.1.4.1.38446.1.6
OBJECT IDENTIFIER    

pduServerPing 1.3.6.1.4.1.38446.1.7
OBJECT IDENTIFIER    

pduSmartCabinet 1.3.6.1.4.1.38446.1.8
OBJECT IDENTIFIER    

pduTraps 1.3.6.1.4.1.38446.1.9
OBJECT IDENTIFIER    

pduNamePlateTableSize 1.3.6.1.4.1.38446.1.1.1
The total number of PDUs
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduNamePlateTable 1.3.6.1.4.1.38446.1.1.2
A table of PDU nameplate data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduNamePlateEntry

pduNamePlateEntry 1.3.6.1.4.1.38446.1.1.2.1
Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduNamePlateEntry  

pduNamePlateIndex 1.3.6.1.4.1.38446.1.1.2.1.1
The index of the PDU nameplate table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduNamePlateName 1.3.6.1.4.1.38446.1.1.2.1.2
A user-defined string identifying the PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateLocation 1.3.6.1.4.1.38446.1.1.2.1.3
A user-defined string identifying the location of PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateInetAddressType 1.3.6.1.4.1.38446.1.1.2.1.4
The type of address format
Status: current Access: read-only
OBJECT-TYPE    
  InetAddressType  

pduNamePlateIPAddress 1.3.6.1.4.1.38446.1.1.2.1.5
The current IP address. A value of 0.0.0.0 indicates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

pduNamePlateInetNetMask 1.3.6.1.4.1.38446.1.1.2.1.6
The current netmask. A value of 0.0.0.0 indiates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

pduNamePlateInetGateway 1.3.6.1.4.1.38446.1.1.2.1.7
The current gateway. A value of 0.0.0.0 indicates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

pduNamePlateMACAddress 1.3.6.1.4.1.38446.1.1.2.1.8
The assigned MAC address for the PDU
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

pduNamePlateUTCTimeOffset 1.3.6.1.4.1.38446.1.1.2.1.9
The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateModelNumber 1.3.6.1.4.1.38446.1.1.2.1.10
The PDU model number
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateSerialNumber 1.3.6.1.4.1.38446.1.1.2.1.11
The PDU serial number
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateDateofManufacture 1.3.6.1.4.1.38446.1.1.2.1.12
The date the PDU was manufactured in mm/dd/yyyy format
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateFirmwareVersion 1.3.6.1.4.1.38446.1.1.2.1.13
The PDU firmware version
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateFirmwareVersionTimeStamp 1.3.6.1.4.1.38446.1.1.2.1.14
Timestamp of when the PDU firmware was last updated
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduNamePlateType 1.3.6.1.4.1.38446.1.1.2.1.15
The type of Unit, PDU or Inline Meter
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER pdu(0), inlineMeter(1)  

pduUnitTableSize 1.3.6.1.4.1.38446.1.2.1
The number of units.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduUnitConfigTable 1.3.6.1.4.1.38446.1.2.2
A table of PDU configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduUnitConfigEntry

pduUnitConfigEntry 1.3.6.1.4.1.38446.1.2.2.1
Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize
Status: current Access: not-accessible
OBJECT-TYPE    
  PduUnitConfigEntry  

pduUnitConfigIndex 1.3.6.1.4.1.38446.1.2.2.1.1
The index of the PDU Unit Config Entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduUnitConfigName 1.3.6.1.4.1.38446.1.2.2.1.2
A user-defined string identifying the PDU
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduUnitConfigLocation 1.3.6.1.4.1.38446.1.2.2.1.3
A user-defined string identifying the location of the PDU
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduUnitConfigDisplayOrientation 1.3.6.1.4.1.38446.1.2.2.1.4
Indicates the intended physical orientation of the oLED display displayNormal (1) indicates normal orientation. displayReverse (2) indicates upside down orientation
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER displayNormal(1), displayReverse(2)  

pduUnitConfigColdstartDelay 1.3.6.1.4.1.38446.1.2.2.1.5
The amount of time, specified in seconds, between when power is provided to the PDU and when the PDU start providing basic master power to the outlets
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32 0..3600  

pduUnitConfigGlobalOutletStateOnStartup 1.3.6.1.4.1.38446.1.2.2.1.6
The outlet state on device startup; applies to all outlets unless overridden at the outlet level
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1), lastKnownState(2)  

pduUnitConfigLowerCriticalThreshold 1.3.6.1.4.1.38446.1.2.2.1.7
User-defined lower critical unit active power alarm threshold measured in Watts
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigLowerWarningThreshold 1.3.6.1.4.1.38446.1.2.2.1.8
User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigUpperCriticalThreshold 1.3.6.1.4.1.38446.1.2.2.1.9
User-defined upper critical unit active power alarm threshold measured in Watts
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigUpperWarningThreshold 1.3.6.1.4.1.38446.1.2.2.1.10
User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigAlarmResetThreshold 1.3.6.1.4.1.38446.1.2.2.1.11
The hysteresis used for deassertions in Watts
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.2.2.1.12
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduUnitConfigEnabledThresholds 1.3.6.1.4.1.38446.1.2.2.1.13
A bit string indicating which alarm thresholds are enabled
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

pduUnitConfigPeakPowerReset 1.3.6.1.4.1.38446.1.2.2.1.14
Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2)  

pduUnitConfigEnergyReset 1.3.6.1.4.1.38446.1.2.2.1.15
Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2), notSupported(3)  

pduUnitConfigOutletPeakPowerReset 1.3.6.1.4.1.38446.1.2.2.1.16
Setting this OID to reset (2) will cause the outlet peak power meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2), notSupported(3)  

pduUnitConfigOutletEnergyReset 1.3.6.1.4.1.38446.1.2.2.1.17
Setting this OID to reset (2) will cause the outlet energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2), notSupported(3)  

pduUnitConfigUsb 1.3.6.1.4.1.38446.1.2.2.1.18
Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

pduUnitConfigSsh 1.3.6.1.4.1.38446.1.2.2.1.19
Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

pduUnitConfigResetNetworkManagementCard 1.3.6.1.4.1.38446.1.2.2.1.20
Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(0), reset(1)  

pduUnitConfigDaisyChainState 1.3.6.1.4.1.38446.1.2.2.1.21
Setting this OID to daisychain(0) will enable daisychain mode.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER daisychain(0)  

pduUnitPropertiesTable 1.3.6.1.4.1.38446.1.2.3
A table of PDU properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduUnitPropertiesEntry

pduUnitPropertiesEntry 1.3.6.1.4.1.38446.1.2.3.1
A unit properties entry containing objects for a particular unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduUnitPropertiesEntry  

pduUnitPropertiesIndex 1.3.6.1.4.1.38446.1.2.3.1.1
The index of the PDU properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduUnitPropertiesName 1.3.6.1.4.1.38446.1.2.3.1.2
A user-defined string identifying the PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitPropertiesOutletCount 1.3.6.1.4.1.38446.1.2.3.1.3
The total number of outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduUnitPropertiesSwitchedOutletCount 1.3.6.1.4.1.38446.1.2.3.1.4
The total number of switched outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduUnitPropertiesMeteredOutletCount 1.3.6.1.4.1.38446.1.2.3.1.5
The total number of metered outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduUnitPropertiesInputPhaseCount 1.3.6.1.4.1.38446.1.2.3.1.6
The total number of phases on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduUnitPropertiesCircuitBreakerCount 1.3.6.1.4.1.38446.1.2.3.1.7
The total number of circuit breaker on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduUnitPropertiesMaxExternalSensorCount 1.3.6.1.4.1.38446.1.2.3.1.8
The maximum number of external sensors that can be connected to the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduUnitPropertiesConnExternalSensorCount 1.3.6.1.4.1.38446.1.2.3.1.9
The current number of external sensors connected to the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduUnitPropertiesRatedVoltage 1.3.6.1.4.1.38446.1.2.3.1.10
The PDU voltage rating in Volts
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitPropertiesRatedMaxCurrent 1.3.6.1.4.1.38446.1.2.3.1.11
The PDU current rating in Amps
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitPropertiesRatedFrequency 1.3.6.1.4.1.38446.1.2.3.1.12
The PDU frequency rating in Hz
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitPropertiesRatedPower 1.3.6.1.4.1.38446.1.2.3.1.13
The PDU VA (VoltAmps) rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitPropertiesOrientation 1.3.6.1.4.1.38446.1.2.3.1.14
The PDU orientation
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER horizontal(1), vertical(2)  

pduUnitPropertiesOutletLayout 1.3.6.1.4.1.38446.1.2.3.1.15
The outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9):
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER seqPhaseToNuetral(1), seqPhaseToPhase(2), seqPhToNeu21PhToPh(3), seqPhToPhGrouped(4), seqPhToNGrouped(5), seqPToN1516PToPGrouped(6), seqPhToPh2xGrouped(7), seqPhToN2xGrouped(8), seqNotApplicable(9)  

pduUnitPropertiesDaisyChainMemberType 1.3.6.1.4.1.38446.1.2.3.1.16
The daisy-chain member type
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER standalone(1), parent(2), child(3)  

pduUnitPropertiesServerCount 1.3.6.1.4.1.38446.1.2.3.1.17
The number of servers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduUnitStatusTable 1.3.6.1.4.1.38446.1.2.4
A table of PDU status information
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduUnitStatusEntry

pduUnitStatusEntry 1.3.6.1.4.1.38446.1.2.4.1
Status information from the PDU being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduUnitStatusEntry  

pduUnitStatusIndex 1.3.6.1.4.1.38446.1.2.4.1.1
The index of the PDU status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduUnitStatusName 1.3.6.1.4.1.38446.1.2.4.1.2
A user-defined string identifying the PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitStatusLoadState 1.3.6.1.4.1.38446.1.2.4.1.3
Returns the present load status of the PDU based on Active Power.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

pduUnitStatusActivePower 1.3.6.1.4.1.38446.1.2.4.1.4
Returns power consumption, in Watts(W), of the PDU being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitStatusApparentPower 1.3.6.1.4.1.38446.1.2.4.1.5
Returns power consumption, in Volt-Amps(VA) of the PDU load being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitStatusPeakPower 1.3.6.1.4.1.38446.1.2.4.1.6
Returns peak power consumption, in Watts(W), of the PDU being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitStatusPeakPowerTimestamp 1.3.6.1.4.1.38446.1.2.4.1.7
Indicates the date and time that peak power consumption occurred
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitStatusPeakPowerStartTime 1.3.6.1.4.1.38446.1.2.4.1.8
Indicates the date and time of the last device peak power reset
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitStatusEnergy 1.3.6.1.4.1.38446.1.2.4.1.9
Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitStatusResettableEnergy 1.3.6.1.4.1.38446.1.2.4.1.10
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitStatusEnergyStartTime 1.3.6.1.4.1.38446.1.2.4.1.11
Indicates the date and time of the last device energy meter reset
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitStatusOutletsEnergyStartTime 1.3.6.1.4.1.38446.1.2.4.1.12
Indicates the date and time of the last outlets energy meter reset
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduInputPhaseTableSize 1.3.6.1.4.1.38446.1.3.1
The number of PDU Input Phases
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseConfigTable 1.3.6.1.4.1.38446.1.3.2
A table of PDU Input Phase configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduInputPhaseConfigEntry

pduInputPhaseConfigEntry 1.3.6.1.4.1.38446.1.3.2.1
An input phase entry containing objects for a particular input phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduInputPhaseConfigEntry  

pduInputPhaseConfigIndex 1.3.6.1.4.1.38446.1.3.2.1.1
The index of the PDU Input Phase configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseConfigCount 1.3.6.1.4.1.38446.1.3.2.1.2
The total number of Input Phases
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseConfigOverloadRestriction 1.3.6.1.4.1.38446.1.3.2.1.3
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER alwaysAllowTurnOn(1), restrictOnUpperWarning(2), restrictOnUpperCritical(3), notSupported(4)  

pduInputPhaseConfigCurrentLowerCriticalThreshold 1.3.6.1.4.1.38446.1.3.2.1.4
User-defined lower critical input phase current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigCurrentLowerWarningThreshold 1.3.6.1.4.1.38446.1.3.2.1.5
User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigCurrentUpperCriticalThreshold 1.3.6.1.4.1.38446.1.3.2.1.6
User-defined upper critical input phase current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigCurrentUpperWarningThreshold 1.3.6.1.4.1.38446.1.3.2.1.7
User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigVoltageLowerCriticalThreshold 1.3.6.1.4.1.38446.1.3.2.1.8
User-defined lower critical input phase voltage alarm threshold in Volts(V).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigVoltageLowerWarningThreshold 1.3.6.1.4.1.38446.1.3.2.1.9
User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigVoltageUpperCriticalThreshold 1.3.6.1.4.1.38446.1.3.2.1.10
User-defined upper critical input phase voltage alarm threshold in Volts(V).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigVoltageUpperWarningThreshold 1.3.6.1.4.1.38446.1.3.2.1.11
User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigCurrentAlarmResetThreshold 1.3.6.1.4.1.38446.1.3.2.1.12
The hysteresis used for current alarm deassertions in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigCurrentAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.3.2.1.13
The delay measured in samples before a current state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduInputPhaseConfigCurrentEnabledThresholds 1.3.6.1.4.1.38446.1.3.2.1.14
A bit string indicating which current alarm thresholds are enabled.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

pduInputPhaseConfigVoltageAlarmResetThreshold 1.3.6.1.4.1.38446.1.3.2.1.15
The hysteresis used for voltage alarm deassertions in Volts(V).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduInputPhaseConfigVoltageAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.3.2.1.16
The delay measured in samples before a voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduInputPhaseConfigVoltageEnabledThresholds 1.3.6.1.4.1.38446.1.3.2.1.17
A bit string indicating which voltage alarm thresholds are enabled.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

pduInputPhasePropertiesTable 1.3.6.1.4.1.38446.1.3.3
A table of PDU Input Phase properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduInputPhasePropertiesEntry

pduInputPhasePropertiesEntry 1.3.6.1.4.1.38446.1.3.3.1
An input phase properties entry containing objects for a particular input phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduInputPhasePropertiesEntry  

pduInputPhasePropertiesIndex 1.3.6.1.4.1.38446.1.3.3.1.1
The index of the PDU Input Phase status entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhasePropertiesCount 1.3.6.1.4.1.38446.1.3.3.1.2
The numeric Input Phase ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseStatusTable 1.3.6.1.4.1.38446.1.3.4
A table of PDU Input Phase status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduInputPhaseStatusEntry

pduInputPhaseStatusEntry 1.3.6.1.4.1.38446.1.3.4.1
An input phase status entry containing objects for a particular input phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduInputPhaseStatusEntry  

pduInputPhaseStatusIndex 1.3.6.1.4.1.38446.1.3.4.1.1
The index of the PDU Input Phase status entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseStatusCount 1.3.6.1.4.1.38446.1.3.4.1.2
The numeric Input Phase ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduInputPhaseStatusCurrentState 1.3.6.1.4.1.38446.1.3.4.1.3
Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

pduInputPhaseStatusVoltageState 1.3.6.1.4.1.38446.1.3.4.1.4
Indicates the present voltage status of the PDU Input Phase being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

pduInputPhaseStatusCurrent 1.3.6.1.4.1.38446.1.3.4.1.5
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduInputPhaseStatusVoltage 1.3.6.1.4.1.38446.1.3.4.1.6
Returns the voltage, in Volts(V), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduInputPhaseStatusActivePower 1.3.6.1.4.1.38446.1.3.4.1.7
Returns power consumption, in Watts(W), consumed on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduInputPhaseStatusApparentPower 1.3.6.1.4.1.38446.1.3.4.1.8
Returns power consumption, in Volt-Amps(VA), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduInputPhaseStatusPowerFactor 1.3.6.1.4.1.38446.1.3.4.1.9
Returns the ratio of active to apparent power of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduCircuitBreakerTableSize 1.3.6.1.4.1.38446.1.4.1
The number of PDU Circuit Breakers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduCircuitBreakerConfigTable 1.3.6.1.4.1.38446.1.4.2
A table of PDU Circuit Breaker configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduCircuitBreakerConfigEntry

pduCircuitBreakerConfigEntry 1.3.6.1.4.1.38446.1.4.2.1
A circuit breaker configuration entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduCircuitBreakerConfigEntry  

pduCircuitBreakerConfigIndex 1.3.6.1.4.1.38446.1.4.2.1.1
The index of the PDU Circuit Breaker configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduCircuitBreakerConfigCount 1.3.6.1.4.1.38446.1.4.2.1.2
The number of circuit breakers on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduCircuitBreakerName 1.3.6.1.4.1.38446.1.4.2.1.3
The label of the circuit breaker
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduCircuitBreakerConfigOverloadRestriction 1.3.6.1.4.1.38446.1.4.2.1.4
This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER alwaysAllowTurnOn(1), restrictOnUpperWarning(2), restrictOnUpperCritical(3), notSupported(4)  

pduCircuitBreakerConfigLowerCriticalThreshold 1.3.6.1.4.1.38446.1.4.2.1.5
User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigLowerWarningThreshold 1.3.6.1.4.1.38446.1.4.2.1.6
User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigUpperCriticalThreshold 1.3.6.1.4.1.38446.1.4.2.1.7
User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigUpperWarningThreshold 1.3.6.1.4.1.38446.1.4.2.1.8
User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigAlarmResetThreshold 1.3.6.1.4.1.38446.1.4.2.1.9
The hysteresis used for deassertions in hundredths of Amps(A).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.4.2.1.10
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduCircuitBreakerConfigEnabledThresholds 1.3.6.1.4.1.38446.1.4.2.1.11
A bit string indicating which alarm thresholds are enabled.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

pduCircuitBreakerPropertiesTable 1.3.6.1.4.1.38446.1.4.3
A table of PDU circuit breaker properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduCircuitBreakerPropertiesEntry

pduCircuitBreakerPropertiesEntry 1.3.6.1.4.1.38446.1.4.3.1
A circuit breaker properties entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduCircuitBreakerPropertiesEntry  

pduCircuitBreakerPropertiesIndex 1.3.6.1.4.1.38446.1.4.3.1.1
The index of the PDU Circuit Breaker properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduCircuitBreakerPropertiesCount 1.3.6.1.4.1.38446.1.4.3.1.2
The number of Circuit Breakers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduCircuitBreakerPropertiesInputLayout 1.3.6.1.4.1.38446.1.4.3.1.3
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)  

pduCircuitBreakerStatusTable 1.3.6.1.4.1.38446.1.4.4
A table of PDU circuit breaker status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduCircuitBreakerStatusEntry

pduCircuitBreakerStatusEntry 1.3.6.1.4.1.38446.1.4.4.1
A circuit breaker status entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduCircuitBreakerStatusEntry  

pduCircuitBreakerStatusIndex 1.3.6.1.4.1.38446.1.4.4.1.1
The index of the PDU Circuit Breaker status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduCircuitBreakerStatusCount 1.3.6.1.4.1.38446.1.4.4.1.2
The number of Circuit Breakers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduCircuitBreakerLabel 1.3.6.1.4.1.38446.1.4.4.1.3
The label on the PDU identifying the circuit breaker
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduCircuitBreakerStatusLoadState 1.3.6.1.4.1.38446.1.4.4.1.4
Indicates the present load status of the PDU Circuit Breaker being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5), off(6)  

pduCircuitBreakerStatusCurrent 1.3.6.1.4.1.38446.1.4.4.1.5
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletSwitchedTableSize 1.3.6.1.4.1.38446.1.5.1
The number of PDU Outlets
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedConfigTable 1.3.6.1.4.1.38446.1.5.2
A table of PDU Switched Outlet configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletSwitchedConfigEntry

pduOutletSwitchedConfigEntry 1.3.6.1.4.1.38446.1.5.2.1
An outlet configuration entry containing objects for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletSwitchedConfigEntry  

pduOutletSwitchedConfigIndex 1.3.6.1.4.1.38446.1.5.2.1.1
The index of the PDU Switched Outlet configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedName 1.3.6.1.4.1.38446.1.5.2.1.2
The user-defined name for the Switched Outlet
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduOutletSwitchedStateOnStartup 1.3.6.1.4.1.38446.1.5.2.1.3
The outlet state on device startup; overrides the global value pduUnitConfigGlobalOutletStateOnStartup.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1), lastKnownState(2)  

pduOutletSwitchedConfigPowerOnTime 1.3.6.1.4.1.38446.1.5.2.1.4
The amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing power
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduOutletSwitchedConfigPowerOffTime 1.3.6.1.4.1.38446.1.5.2.1.5
The amount of time, in seconds, this outlet will delay powering off
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduOutletSwitchedConfigRebootDuration 1.3.6.1.4.1.38446.1.5.2.1.6
The amount of time, in seconds, this outlet will remain in powered off state before returning to power on state during a reboot action.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduOutletSwitchedPropertiesTable 1.3.6.1.4.1.38446.1.5.3
A table of PDU Switched Outlet properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletSwitchedPropertiesEntry

pduOutletSwitchedPropertiesEntry 1.3.6.1.4.1.38446.1.5.3.1
An outlet properties entry containing objects for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletSwitchedPropertiesEntry  

pduOutletSwitchedPropertiesIndex 1.3.6.1.4.1.38446.1.5.3.1.1
The index of the PDU Switched Outlet properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedPropertiesNumber 1.3.6.1.4.1.38446.1.5.3.1.2
The numeric Switched Outlet ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedPropertiesName 1.3.6.1.4.1.38446.1.5.3.1.3
The user-defined switched outlet ID string
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletSwitchedPropertiesInputPhaseLayout 1.3.6.1.4.1.38446.1.5.3.1.4
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Phase1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)  

pduOutletSwitchedPropertiesCircuitBreaker 1.3.6.1.4.1.38446.1.5.3.1.5
The numeric Circuit Breaker ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedStatusTable 1.3.6.1.4.1.38446.1.5.4
A table of PDU Switched Outlet status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletSwitchedStatusEntry

pduOutletSwitchedStatusEntry 1.3.6.1.4.1.38446.1.5.4.1
Status data from the PDU Switched Outlet being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletSwitchedStatusEntry  

pduOutletSwitchedStatusIndex 1.3.6.1.4.1.38446.1.5.4.1.1
The index of the PDU Switched Outlet status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedStatusNumber 1.3.6.1.4.1.38446.1.5.4.1.2
The numeric Switched Outlet ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedStatusName 1.3.6.1.4.1.38446.1.5.4.1.3
The user-defined switched outlet ID string
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletSwitchedStatusState 1.3.6.1.4.1.38446.1.5.4.1.4
Indicates the present switch state of the PDU switched outlet being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

pduOutletSwitchedControlTable 1.3.6.1.4.1.38446.1.5.5
A table of PDU Switched Outlet status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletSwitchedControlEntry

pduOutletSwitchedControlEntry 1.3.6.1.4.1.38446.1.5.5.1
Status data from the PDU Switched Outlet being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletSwitchedControlEntry  

pduOutletSwitchedControlIndex 1.3.6.1.4.1.38446.1.5.5.1.1
The index to the PDU switched outlet control data table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedControlNumber 1.3.6.1.4.1.38446.1.5.5.1.2
The numeric Switched Outlet ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletSwitchedControlName 1.3.6.1.4.1.38446.1.5.5.1.3
The user-defined switched outlet ID string
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletSwitchedControlCommand 1.3.6.1.4.1.38446.1.5.5.1.4
Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER immediateOff(1), immediateOn(2), delayedOff(3), delayedOn(4), immediateReboot(5), delayedReboot(6), outletUnknown(7)  

pduOutletMeteredTableSize 1.3.6.1.4.1.38446.1.5.6
The number of PDU Outlets
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredConfigTable 1.3.6.1.4.1.38446.1.5.7
A table of PDU Metered Outlet configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletMeteredConfigEntry

pduOutletMeteredConfigEntry 1.3.6.1.4.1.38446.1.5.7.1
An outlet configuration entry containing objects for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletMeteredConfigEntry  

pduOutletMeteredConfigIndex 1.3.6.1.4.1.38446.1.5.7.1.1
The index of the PDU Metered Outlet configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredName 1.3.6.1.4.1.38446.1.5.7.1.2
The user-defined name for the Metered Outlet
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduOutletMeteredConfigLowerCriticalThreshold 1.3.6.1.4.1.38446.1.5.7.1.3
User-defined lower critical outlet active power alarm threshold in Watts(W).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigLowerWarningThreshold 1.3.6.1.4.1.38446.1.5.7.1.4
User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigUpperCriticalThreshold 1.3.6.1.4.1.38446.1.5.7.1.5
User-defined upper critical outlet active power alarm threshold in Watts(W).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigUpperWarningThreshold 1.3.6.1.4.1.38446.1.5.7.1.6
User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigAlarmResetThreshold 1.3.6.1.4.1.38446.1.5.7.1.7
The hysteresis used for deassertions in Watts(W).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.5.7.1.8
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutletMeteredConfigEnabledThresholds 1.3.6.1.4.1.38446.1.5.7.1.9
A bit string indicating which alarm thresholds are enabled.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3)  

pduOutletMeteredPropertiesTable 1.3.6.1.4.1.38446.1.5.8
A table of PDU Metered Outlet properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletMeteredPropertiesEntry

pduOutletMeteredPropertiesEntry 1.3.6.1.4.1.38446.1.5.8.1
Configuration data from the PDU Metered Outlet being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletMeteredPropertiesEntry  

pduOutletMeteredPropertiesIndex 1.3.6.1.4.1.38446.1.5.8.1.1
The index of the PDU Metered Outlet properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredPropertiesNumber 1.3.6.1.4.1.38446.1.5.8.1.2
The numeric Metered Outlet ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredPropertiesName 1.3.6.1.4.1.38446.1.5.8.1.3
The user-defined Metered outlet ID string
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletMeteredPropertiesInputPhaseLayout 1.3.6.1.4.1.38446.1.5.8.1.4
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Phase1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)  

pduOutletMeteredPropertiesCircuitBreaker 1.3.6.1.4.1.38446.1.5.8.1.5
The numeric Circuit Breaker ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredPropertiesPowerRating 1.3.6.1.4.1.38446.1.5.8.1.6
Maximum power rating of the PDU metered outlet
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletMeteredStatusTable 1.3.6.1.4.1.38446.1.5.9
A table of PDU Metered Outlet status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutletMeteredStatusEntry

pduOutletMeteredStatusEntry 1.3.6.1.4.1.38446.1.5.9.1
Status data from the PDU Metered Outlet being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutletMeteredStatusEntry  

pduOutletMeteredStatusIndex 1.3.6.1.4.1.38446.1.5.9.1.1
The index of the PDU Metered Outlet status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredStatusNumber 1.3.6.1.4.1.38446.1.5.9.1.2
The numeric Metered Outlet ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduOutletMeteredStatusName 1.3.6.1.4.1.38446.1.5.9.1.3
The user-defined Metered outlet ID string
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletMeteredStatusLoadState 1.3.6.1.4.1.38446.1.5.9.1.4
Returns the present load status of the PDU metered outlet being queried.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

pduOutletMeteredStatusCurrent 1.3.6.1.4.1.38446.1.5.9.1.5
Returns the current draw, in hundredths of Amps(A), of the load on the PDU outlet being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletMeteredStatusActivePower 1.3.6.1.4.1.38446.1.5.9.1.6
Returns the power draw, in Watts(W), of the load on the PDU outlet being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletMeteredStatusPowerFactor 1.3.6.1.4.1.38446.1.5.9.1.7
Returns the ratio of active to apparent power of the PDU Outlet being queried
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletMeteredStatusPeakPower 1.3.6.1.4.1.38446.1.5.9.1.8
Returns peak power consumption, in Watts(W), of the Rack PDU outlet being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduOutletMeteredStatusPeakPowerTimeStamp 1.3.6.1.4.1.38446.1.5.9.1.9
Indicates the date and time that this metered outlet's peak power consumption occurred
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletMeteredStatusPeakPowerStartTime 1.3.6.1.4.1.38446.1.5.9.1.10
Indicates the start date and time that this metered outlet began recording peak power observations
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduOutletMeteredStatusResettableEnergy 1.3.6.1.4.1.38446.1.5.9.1.11
A user resettable energy meter measuring outlet load energy consumption in tenths of Kilowatt-Hours(kWh).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduExternalSensorTableSize 1.3.6.1.4.1.38446.1.6.1
The total number of External Sensors
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

pduExternalSensorNamePlateTable 1.3.6.1.4.1.38446.1.6.2
A table of PDU ExternalSensorNamePlate data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduExternalSensorNamePlateEntry

pduExternalSensorNamePlateEntry 1.3.6.1.4.1.38446.1.6.2.1
External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of pduExternalSensorNamePlateTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduExternalSensorNamePlateEntry  

pduExternalSensorNamePlateIndex 1.3.6.1.4.1.38446.1.6.2.1.1
The index of the PDU External Sensor status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

pduExternalSensorNamePlateName 1.3.6.1.4.1.38446.1.6.2.1.2
A user-defined string identifying the external sensor
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduExternalSensorNamePlateDescription 1.3.6.1.4.1.38446.1.6.2.1.3
A user-defined description of the external sensor
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduExternalSensorNamePlateLocation 1.3.6.1.4.1.38446.1.6.2.1.4
A user-defined string identifying the location of the PDU
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduExternalSensorNamePlateSerialNumber 1.3.6.1.4.1.38446.1.6.2.1.5
The serial number of the external sensor being queried
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduExternalSensorNamePlateType 1.3.6.1.4.1.38446.1.6.2.1.6
The type of external sensor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER temperature(1), humidity(2), doorSwitch(3), dryContact(4), spotFluid(5), ropeFluid(6), smoke(7), beacon(8), airVelocity(9), modbusAdapter(17), hidAdapter(18)  

pduExternalSensorNamePlateUnits 1.3.6.1.4.1.38446.1.6.2.1.7
The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER logic(0), degreeC(1), degreeF(2), percent(3), mps(4)  

pduExternalSensorNamePlateIdentifier 1.3.6.1.4.1.38446.1.6.2.1.8
Unique identifier of the external sensor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduExternalSensorConfigTable 1.3.6.1.4.1.38446.1.6.3
A table of PDU External Sensor configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduExternalSensorConfigEntry

pduExternalSensorConfigEntry 1.3.6.1.4.1.38446.1.6.3.1
Configuration data from the PDU External Sensor being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduExternalSensorConfigEntry  

pduExternalSensorConfigIndex 1.3.6.1.4.1.38446.1.6.3.1.1
The index of the PDU External Sensor configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

pduExternalSensorConfigLowerCriticalThreshold 1.3.6.1.4.1.38446.1.6.3.1.2
User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigLowerWarningThreshold 1.3.6.1.4.1.38446.1.6.3.1.3
User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigUpperCriticalThreshold 1.3.6.1.4.1.38446.1.6.3.1.4
User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigUpperWarningThreshold 1.3.6.1.4.1.38446.1.6.3.1.5
User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigAlarmResetThreshold 1.3.6.1.4.1.38446.1.6.3.1.6
The hysteresis used for deassertions.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigAlarmStateChangeDelay 1.3.6.1.4.1.38446.1.6.3.1.7
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduExternalSensorConfigEnabledThresholds 1.3.6.1.4.1.38446.1.6.3.1.8
A bit string indicating which alarm thresholds are enabled.
Status: current Access: read-write
OBJECT-TYPE    
  BITS lowerCritical(0), lowerWarning(1), upperWarning(2), upperCritical(3), binarySensorAlarm(4)  

pduExternalSensorConfigAlarmState 1.3.6.1.4.1.38446.1.6.3.1.9
User defined alarm state of external sensor
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(0)  

pduExternalSensorStatusTable 1.3.6.1.4.1.38446.1.6.4
A table of PDU External Sensor status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduExternalSensorStatusEntry

pduExternalSensorStatusEntry 1.3.6.1.4.1.38446.1.6.4.1
Status data from the PDU External Sensor being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  PduExternalSensorStatusEntry  

pduExternalSensorStatusIndex 1.3.6.1.4.1.38446.1.6.4.1.1
The index of the PDU External Sensor status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

pduExternalSensorStatusName 1.3.6.1.4.1.38446.1.6.4.1.2
The user-defined name for the External Sensor
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduExternalSensorStatusAisle 1.3.6.1.4.1.38446.1.6.4.1.3
Indicates whether the external sensor is in a hot or cold aisle
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER hotAisle(1), coldAisle(2)  

pduExternalSensorStatusCommStatus 1.3.6.1.4.1.38446.1.6.4.1.4
The communications status of the sensor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notInstalled(1), commsOk(2), commsLost(3)  

pduExternalSensorStatusState 1.3.6.1.4.1.38446.1.6.4.1.5
This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notPresent(0), alarmed(1), normal(2), belowLowerCritical(3), belowLowerWarning(4), aboveUpperWarning(5), aboveUpperCritical(6)  

pduExternalSensorStatusValue 1.3.6.1.4.1.38446.1.6.4.1.6
Sensor reading in pduExternalSensorConfigUnits value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduExternalSensorStatusTimeStamp 1.3.6.1.4.1.38446.1.6.4.1.7
The sensor reading timestamp.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduExternalSensorStatusHighPrecisionValue 1.3.6.1.4.1.38446.1.6.4.1.8
Temperature sensor reading in tenths of pduExternalSensorConfigUnits value. This OID is applied to temperature sensor only
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduServerPingTableSize 1.3.6.1.4.1.38446.1.7.1
The total number of Servers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduServerPingTable 1.3.6.1.4.1.38446.1.7.2
A table of Server Ping data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduServerPingEntry

pduServerPingEntry 1.3.6.1.4.1.38446.1.7.2.1
Server Ping data from the server being queried. The number of entries equals the value of pduServerPingTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduServerPingEntry  

pduServerPingIndex 1.3.6.1.4.1.38446.1.7.2.1.1
The index of the PDU pduServerPing table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

pduServerPingServerIPAddress 1.3.6.1.4.1.38446.1.7.2.1.2
The IP Address/host name of the server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduServerPingEnabled 1.3.6.1.4.1.38446.1.7.2.1.3
Is ping enabled for this server?
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER false(0), true(1)  

pduUnitSmartCabinetTableSize 1.3.6.1.4.1.38446.1.8.1
The total number of Smart Cabinet Configuration
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

pduUnitSmartCabinetTable 1.3.6.1.4.1.38446.1.8.2
A table of Smart Cabinet information
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduUnitSmartCabinetEntry

pduUnitSmartCabinetEntry 1.3.6.1.4.1.38446.1.8.2.1
Information of Smart Cabinet
Status: current Access: not-accessible
OBJECT-TYPE    
  PduUnitSmartCabinetEntry  

pduUnitSmartCabinetIndex 1.3.6.1.4.1.38446.1.8.2.1.1
The index of the PDU Smart Cabinet table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

pduUnitSmartCabinetCardUserName 1.3.6.1.4.1.38446.1.8.2.1.2
User name of ID card
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitSmartCabinetCardID 1.3.6.1.4.1.38446.1.8.2.1.3
Card ID.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduUnitSmartCabinetTimestamp 1.3.6.1.4.1.38446.1.8.2.1.4
Indicates the date and time of information update
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduUnitSmartCabinetDoor 1.3.6.1.4.1.38446.1.8.2.1.5
Aisle of Smart Cabinet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER hotAisle(1), coldAisle(2)  

pduUnitSmartCabinetControl 1.3.6.1.4.1.38446.1.8.3
OBJECT IDENTIFIER    

pduUnitSmartCabinetControlUserName 1.3.6.1.4.1.38446.1.8.3.1
User name of ID card
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduUnitSmartCabinetControlCardID 1.3.6.1.4.1.38446.1.8.3.2
Card ID.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduUnitSmartCabinetControlTimestamp 1.3.6.1.4.1.38446.1.8.3.3
Indicates the date and time of information update
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

pduUnitSmartCabinetControlDoor 1.3.6.1.4.1.38446.1.8.3.4
Aisle of Smart Cabinet.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER hotAisle(1), coldAisle(2)  

pduUnitSmartCabinetCardIDEdit 1.3.6.1.4.1.38446.1.8.3.5
Smart Cabinet edit CardID
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER grant(0), remove(1)  

pduUnitSmartCabinetColdAisleLockState 1.3.6.1.4.1.38446.1.8.3.6
Smart Cabinet ColdAisle lock state
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unlock(0), lock(1), notPresent(2)  

pduUnitSmartCabinetHotAisleLockState 1.3.6.1.4.1.38446.1.8.3.7
Smart Cabinet HotAisle lock state
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unlock(0), lock(1), notPresent(2)  

trapsInfo 1.3.6.1.4.1.38446.1.9.1
OBJECT IDENTIFIER    

trapsInfoTable 1.3.6.1.4.1.38446.1.9.1.1
A list of Trap Information entries. The number of entries are given by the value of pduUnitTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TrapsInfoEntry

trapsInfoEntry 1.3.6.1.4.1.38446.1.9.1.1.1
An entry containing objects used in traps
Status: current Access: not-accessible
OBJECT-TYPE    
  TrapsInfoEntry  

trapsInfoIndex 1.3.6.1.4.1.38446.1.9.1.1.1.1
The index of the traps table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

userName 1.3.6.1.4.1.38446.1.9.1.1.1.2
The user currently logged in.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

userUpdated 1.3.6.1.4.1.38446.1.9.1.1.1.3
The user added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

firmwareVersion 1.3.6.1.4.1.38446.1.9.1.1.1.4
The version of Firmware.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

roleUpdated 1.3.6.1.4.1.38446.1.9.1.1.1.5
The role added, deleted, or modified.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpRecipients 1.3.6.1.4.1.38446.1.9.1.1.1.6
Comma separated list of SMTP recipients
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

smtpServer 1.3.6.1.4.1.38446.1.9.1.1.1.7
The IP address/host name of the SMTP server
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

pduIndex 1.3.6.1.4.1.38446.1.9.1.2
A unique value for PDU. Its value ranges between 1 and the value of PDU count
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

externalSensorIndex 1.3.6.1.4.1.38446.1.9.1.3
A unique value for each sensor. Its value ranges between 1 and the value of external sensor count.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

serverPing 1.3.6.1.4.1.38446.1.9.1.4
Whether server ping has been enabled or disabled and whether the server is reachable or not reachable
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER pingEnable(1), pingDisable(2), serverReachable(3), serverNotReachable(4)  

usbDevice 1.3.6.1.4.1.38446.1.9.1.5
Whether a USB device has been connected or disconnected
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER connected(1), disconnected(2)  

errorDescription 1.3.6.1.4.1.38446.1.9.1.6
Description of the Error
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

daisyChain 1.3.6.1.4.1.38446.1.9.1.7
Whether a daisy chain member has been connected or disconnected
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER connected(1), disconnected(2)  

systemCommunication 1.3.6.1.4.1.38446.1.9.1.8
Whether the Network management card has lost contact with daisy a chain member.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER ok(1), lost(2)  

networkCardStart 1.3.6.1.4.1.38446.1.9.2
The network card has started
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

networkCardReset 1.3.6.1.4.1.38446.1.9.3
The network card was reset via the web or command line interface.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userLogin 1.3.6.1.4.1.38446.1.9.4
A user logged in
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userLogoff 1.3.6.1.4.1.38446.1.9.5
A user logged off
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userAuthenticationFailed 1.3.6.1.4.1.38446.1.9.6
A user authentication attempt failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userSessionTimeout 1.3.6.1.4.1.38446.1.9.7
A user session timed out
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userAdded 1.3.6.1.4.1.38446.1.9.8
A user account was added to system.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userModified 1.3.6.1.4.1.38446.1.9.9
A user account was modified.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userDeleted 1.3.6.1.4.1.38446.1.9.10
A user account was deleted.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleAdded 1.3.6.1.4.1.38446.1.9.11
A user role was added.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleModified 1.3.6.1.4.1.38446.1.9.12
A user role was modified.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

roleDeleted 1.3.6.1.4.1.38446.1.9.13
A user role was deleted.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

firmwareUpdateStarted 1.3.6.1.4.1.38446.1.9.14
A firmware update has started.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

firmwareUpdateCompleted 1.3.6.1.4.1.38446.1.9.15
The firmware update has completed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userBlocked 1.3.6.1.4.1.38446.1.9.16
A user is blocked.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

outletControl 1.3.6.1.4.1.38446.1.9.17
Outlet control operation applied.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

userPasswordChange 1.3.6.1.4.1.38446.1.9.18
A user password was changed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

passwordSettingsChange 1.3.6.1.4.1.38446.1.9.19
One or more password policy settings were changed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

logFileCleared 1.3.6.1.4.1.38446.1.9.21
The log file has been cleared.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduConfigurationFileImported 1.3.6.1.4.1.38446.1.9.22
PDU configuration file was imported.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduConfigurationFileExported 1.3.6.1.4.1.38446.1.9.23
PDU configuration file was exported
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduUnitActivePowerStateChange 1.3.6.1.4.1.38446.1.9.24
PDU unit active power state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduInputphaseVoltageStateChange 1.3.6.1.4.1.38446.1.9.25
PDU input phase voltage state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduInputphaseCurrentStateChange 1.3.6.1.4.1.38446.1.9.26
PDU input phase Current state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduCircuitBreakerCurrentStateChange 1.3.6.1.4.1.38446.1.9.27
PDU Circuit Breaker Current state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduOutletActivePowerStateChange 1.3.6.1.4.1.38446.1.9.28
PDU Metered Outlet Active Power state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduExternalSensorStateChange 1.3.6.1.4.1.38446.1.9.29
PDU External Sensor state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smtpTransmissionFailure 1.3.6.1.4.1.38446.1.9.30
SMTP message transmission failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

ldapError 1.3.6.1.4.1.38446.1.9.31
A LDAP error occurred
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

firmwareUpdateFailed 1.3.6.1.4.1.38446.1.9.32
A firmware update has failed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

serverPingState 1.3.6.1.4.1.38446.1.9.33
The Ping feature has been enabled.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

bootloaderState 1.3.6.1.4.1.38446.1.9.34
Enter into Bootloader mode
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

daisyChainState 1.3.6.1.4.1.38446.1.9.35
A daisy chain member has been connected or disconnected.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

systemInternalCommunicationLost 1.3.6.1.4.1.38446.1.9.36
Network management card has lost contaction with internal boards.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smartCabinetLockUnlocked 1.3.6.1.4.1.38446.1.9.37
The Cabinet lock is unlocked.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smartCabinetLockLocked 1.3.6.1.4.1.38446.1.9.38
The Cabinet lock is locked
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smartCabinetSwapCard 1.3.6.1.4.1.38446.1.9.39
Card is swapped
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smartCabinetLockerLockDoorOpen 1.3.6.1.4.1.38446.1.9.40
Locker locked but door open
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

smartCabinetLockerUnlockDoorClose 1.3.6.1.4.1.38446.1.9.41
Locker unlocked but door close
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

systemReboot 1.3.6.1.4.1.38446.1.9.50
System has rebooted
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

esp 1.3.6.1.4.1.38446.2
OBJECT IDENTIFIER    

espNamePlate 1.3.6.1.4.1.38446.2.1
OBJECT IDENTIFIER    

espUnit 1.3.6.1.4.1.38446.2.2
OBJECT IDENTIFIER    

espInputPhase 1.3.6.1.4.1.38446.2.3
OBJECT IDENTIFIER    

espCircuitBreaker 1.3.6.1.4.1.38446.2.4
OBJECT IDENTIFIER    

espExternalSensor 1.3.6.1.4.1.38446.2.6
OBJECT IDENTIFIER    

espTraps 1.3.6.1.4.1.38446.2.9
OBJECT IDENTIFIER    

espNamePlateTable 1.3.6.1.4.1.38446.2.1.2
A table of es PDU nameplate data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspNamePlateEntry

espNamePlateEntry 1.3.6.1.4.1.38446.2.1.2.1
Nameplate data from the PDU being queried. The numbers of entries equals the value of espNamePlateTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspNamePlateEntry  

espNamePlateIndex 1.3.6.1.4.1.38446.2.1.2.1.1
The index of the es PDU nameplate table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espNamePlateName 1.3.6.1.4.1.38446.2.1.2.1.2
A user-defined string identifying the es PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateLocation 1.3.6.1.4.1.38446.2.1.2.1.3
A user-defined string identifying the location of PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateInetAddressType 1.3.6.1.4.1.38446.2.1.2.1.4
The type of address format
Status: current Access: read-only
OBJECT-TYPE    
  InetAddressType  

espNamePlateIPAddress 1.3.6.1.4.1.38446.2.1.2.1.5
The current IP address. A value of 0.0.0.0 indicates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

espNamePlateInetNetMask 1.3.6.1.4.1.38446.2.1.2.1.6
The current netmask. A value of 0.0.0.0 indiates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

espNamePlateInetGateway 1.3.6.1.4.1.38446.2.1.2.1.7
The current gateway. A value of 0.0.0.0 indicates an error or an unset option
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

espNamePlateMACAddress 1.3.6.1.4.1.38446.2.1.2.1.8
The assigned MAC address for the PDU
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

espNamePlateUTCTimeOffset 1.3.6.1.4.1.38446.2.1.2.1.9
The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateModelNumber 1.3.6.1.4.1.38446.2.1.2.1.10
The PDU model number
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateSerialNumber 1.3.6.1.4.1.38446.2.1.2.1.11
The PDU serial number
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateDateofManufacture 1.3.6.1.4.1.38446.2.1.2.1.12
The date the PDU was manufactured in mm/dd/yyyy format
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateFirmwareVersion 1.3.6.1.4.1.38446.2.1.2.1.13
The PDU firmware version
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateFirmwareVersionTimeStamp 1.3.6.1.4.1.38446.2.1.2.1.14
Timestamp of when the PDU firmware was last updated
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espNamePlateType 1.3.6.1.4.1.38446.2.1.2.1.15
The type of Unit, PDU or Inline Meter
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER pdu(0), inlineMeter(1)  

espUnitConfigTable 1.3.6.1.4.1.38446.2.2.2
A table of PDU configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspUnitConfigEntry

espUnitConfigEntry 1.3.6.1.4.1.38446.2.2.2.1
Configuration data from the PDU being queried. The number of entries equals the value of espUnitTableSize
Status: current Access: not-accessible
OBJECT-TYPE    
  EspUnitConfigEntry  

espUnitConfigIndex 1.3.6.1.4.1.38446.2.2.2.1.1
The index of the PDU Unit Config Entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espUnitConfigName 1.3.6.1.4.1.38446.2.2.2.1.2
A user-defined string identifying the PDU
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

espUnitConfigLocation 1.3.6.1.4.1.38446.2.2.2.1.3
A user-defined string identifying the location of the PDU
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

espUnitConfigEnergyReset 1.3.6.1.4.1.38446.2.2.2.1.15
Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(1), reset(2), notSupported(3)  

espUnitConfigResetNetworkManagementCard 1.3.6.1.4.1.38446.2.2.2.1.20
Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOperation(0), reset(1)  

espUnitPropertiesTable 1.3.6.1.4.1.38446.2.2.3
A table of PDU properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspUnitPropertiesEntry

espUnitPropertiesEntry 1.3.6.1.4.1.38446.2.2.3.1
A unit properties entry containing objects for a particular unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspUnitPropertiesEntry  

espUnitPropertiesIndex 1.3.6.1.4.1.38446.2.2.3.1.1
The index of the PDU properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espUnitPropertiesName 1.3.6.1.4.1.38446.2.2.3.1.2
A user-defined string identifying the PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitPropertiesOutletCount 1.3.6.1.4.1.38446.2.2.3.1.3
The total number of outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espUnitPropertiesSwitchedOutletCount 1.3.6.1.4.1.38446.2.2.3.1.4
The total number of switched outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espUnitPropertiesMeteredOutletCount 1.3.6.1.4.1.38446.2.2.3.1.5
The total number of metered outlets on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espUnitPropertiesInputPhaseCount 1.3.6.1.4.1.38446.2.2.3.1.6
The total number of phases on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espUnitPropertiesCircuitBreakerCount 1.3.6.1.4.1.38446.2.2.3.1.7
The total number of circuit breaker on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espUnitPropertiesMaxExternalSensorCount 1.3.6.1.4.1.38446.2.2.3.1.8
The maximum number of external sensors that can be connected to the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espUnitPropertiesConnExternalSensorCount 1.3.6.1.4.1.38446.2.2.3.1.9
The current number of external sensors connected to the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espUnitPropertiesRatedVoltage 1.3.6.1.4.1.38446.2.2.3.1.10
The PDU voltage rating in Volts
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitPropertiesRatedMaxCurrent 1.3.6.1.4.1.38446.2.2.3.1.11
The PDU current rating in Amps
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitPropertiesRatedFrequency 1.3.6.1.4.1.38446.2.2.3.1.12
The PDU frequency rating in Hz
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitPropertiesRatedPower 1.3.6.1.4.1.38446.2.2.3.1.13
The PDU VA (VoltAmps) rating.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitStatusTable 1.3.6.1.4.1.38446.2.2.4
A table of PDU status information
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspUnitStatusEntry

espUnitStatusEntry 1.3.6.1.4.1.38446.2.2.4.1
Status information from the PDU being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  EspUnitStatusEntry  

espUnitStatusIndex 1.3.6.1.4.1.38446.2.2.4.1.1
The index of the PDU status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espUnitStatusName 1.3.6.1.4.1.38446.2.2.4.1.2
A user-defined string identifying the PDU
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espUnitStatusLoadState 1.3.6.1.4.1.38446.2.2.4.1.3
Returns the present load status of the PDU based on Active Power.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

espUnitStatusActivePower 1.3.6.1.4.1.38446.2.2.4.1.4
Returns power consumption, in Watts(W), of the PDU being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espUnitStatusApparentPower 1.3.6.1.4.1.38446.2.2.4.1.5
Returns power consumption, in Volt-Amps(VA) of the PDU load being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espUnitStatusEnergy 1.3.6.1.4.1.38446.2.2.4.1.9
Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espUnitStatusResettableEnergy 1.3.6.1.4.1.38446.2.2.4.1.10
A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espUnitStatusEnergyStartTime 1.3.6.1.4.1.38446.2.2.4.1.11
Indicates the date and time of the last device energy meter reset
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espInputPhaseConfigTable 1.3.6.1.4.1.38446.2.3.2
A table of PDU Input Phase configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspInputPhaseConfigEntry

espInputPhaseConfigEntry 1.3.6.1.4.1.38446.2.3.2.1
An input phase entry containing objects for a particular input phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspInputPhaseConfigEntry  

espInputPhaseConfigIndex 1.3.6.1.4.1.38446.2.3.2.1.1
The index of the PDU Input Phase configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espInputPhaseConfigCount 1.3.6.1.4.1.38446.2.3.2.1.2
The total number of Input Phases
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espInputPhaseStatusTable 1.3.6.1.4.1.38446.2.3.4
A table of PDU Input Phase status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspInputPhaseStatusEntry

espInputPhaseStatusEntry 1.3.6.1.4.1.38446.2.3.4.1
An input phase status entry containing objects for a particular input phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspInputPhaseStatusEntry  

espInputPhaseStatusIndex 1.3.6.1.4.1.38446.2.3.4.1.1
The index of the PDU Input Phase status entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espInputPhaseStatusCount 1.3.6.1.4.1.38446.2.3.4.1.2
The numeric Input Phase ID
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 1..256  

espInputPhaseStatusCurrentState 1.3.6.1.4.1.38446.2.3.4.1.3
Indicates the present current status of the PDU Input Phase being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

espInputPhaseStatusVoltageState 1.3.6.1.4.1.38446.2.3.4.1.4
Indicates the present voltage status of the PDU Input Phase being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5)  

espInputPhaseStatusCurrent 1.3.6.1.4.1.38446.2.3.4.1.5
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Input Phase being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espInputPhaseStatusVoltage 1.3.6.1.4.1.38446.2.3.4.1.6
Returns the voltage, in Volts(V), of the PDU Input Phase being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espInputPhaseStatusActivePower 1.3.6.1.4.1.38446.2.3.4.1.7
Returns power consumption, in Watts(W), consumed on the PDU Input Phase being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espInputPhaseStatusApparentPower 1.3.6.1.4.1.38446.2.3.4.1.8
Returns power consumption, in Volt-Amps(VA), of the PDU Input Phase being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espInputPhaseStatusPowerFactor 1.3.6.1.4.1.38446.2.3.4.1.9
Returns the ratio of active to apparent power of the PDU Input Phase being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espCircuitBreakerConfigTable 1.3.6.1.4.1.38446.2.4.2
A table of PDU Circuit Breaker configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspCircuitBreakerConfigEntry

espCircuitBreakerConfigEntry 1.3.6.1.4.1.38446.2.4.2.1
A circuit breaker configuration entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspCircuitBreakerConfigEntry  

espCircuitBreakerConfigIndex 1.3.6.1.4.1.38446.2.4.2.1.1
The index of the PDU Circuit Breaker configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espCircuitBreakerConfigCount 1.3.6.1.4.1.38446.2.4.2.1.2
The number of circuit breakers on the PDU
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espCircuitBreakerName 1.3.6.1.4.1.38446.2.4.2.1.3
The label of the circuit breaker
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espCircuitBreakerPropertiesTable 1.3.6.1.4.1.38446.2.4.3
A table of PDU circuit breaker properties
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspCircuitBreakerPropertiesEntry

espCircuitBreakerPropertiesEntry 1.3.6.1.4.1.38446.2.4.3.1
A circuit breaker properties entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspCircuitBreakerPropertiesEntry  

espCircuitBreakerPropertiesIndex 1.3.6.1.4.1.38446.2.4.3.1.1
The index of the PDU Circuit Breaker properties table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espCircuitBreakerPropertiesCount 1.3.6.1.4.1.38446.2.4.3.1.2
The number of Circuit Breakers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espCircuitBreakerPropertiesInputLayout 1.3.6.1.4.1.38446.2.4.3.1.3
This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6)  

espCircuitBreakerStatusTable 1.3.6.1.4.1.38446.2.4.4
A table of PDU circuit breaker status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspCircuitBreakerStatusEntry

espCircuitBreakerStatusEntry 1.3.6.1.4.1.38446.2.4.4.1
A circuit breaker status entry containing objects for a particular circuit breaker.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspCircuitBreakerStatusEntry  

espCircuitBreakerStatusIndex 1.3.6.1.4.1.38446.2.4.4.1.1
The index of the PDU Circuit Breaker status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espCircuitBreakerStatusCount 1.3.6.1.4.1.38446.2.4.4.1.2
The number of Circuit Breakers
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..255  

espCircuitBreakerLabel 1.3.6.1.4.1.38446.2.4.4.1.3
The label on the PDU identifying the circuit breaker
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espCircuitBreakerStatusLoadState 1.3.6.1.4.1.38446.2.4.4.1.4
Indicates the present load status of the PDU Circuit Breaker being queried
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER upperCritical(1), upperWarning(2), lowerWarning(3), lowerCritical(4), normal(5), off(6)  

espCircuitBreakerStatusCurrent 1.3.6.1.4.1.38446.2.4.4.1.5
Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espExternalSensorNamePlateTable 1.3.6.1.4.1.38446.2.6.2
A table of PDU ExternalSensorNamePlate data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspExternalSensorNamePlateEntry

espExternalSensorNamePlateEntry 1.3.6.1.4.1.38446.2.6.2.1
External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of espExternalSensorNamePlateTableSize.
Status: current Access: not-accessible
OBJECT-TYPE    
  EspExternalSensorNamePlateEntry  

espExternalSensorNamePlateIndex 1.3.6.1.4.1.38446.2.6.2.1.1
The index of the PDU External Sensor status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

espExternalSensorNamePlateName 1.3.6.1.4.1.38446.2.6.2.1.2
A user-defined string identifying the external sensor
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espExternalSensorNamePlateSerialNumber 1.3.6.1.4.1.38446.2.6.2.1.5
The serial number of the external sensor being queried
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espExternalSensorNamePlateType 1.3.6.1.4.1.38446.2.6.2.1.6
The type of external sensor.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER temperature(1), humidity(2), doorSwitch(3), dryContact(4), spotFluid(5), ropeFluid(6), smoke(7), beacon(8)  

espExternalSensorNamePlateUnits 1.3.6.1.4.1.38446.2.6.2.1.7
The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER logic(0), degreeC(1), degreeF(2), percent(3)  

espExternalSensorConfigTable 1.3.6.1.4.1.38446.2.6.3
A table of PDU External Sensor configuration data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspExternalSensorConfigEntry

espExternalSensorConfigEntry 1.3.6.1.4.1.38446.2.6.3.1
Configuration data from the PDU External Sensor being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  EspExternalSensorConfigEntry  

espExternalSensorConfigIndex 1.3.6.1.4.1.38446.2.6.3.1.1
The index of the PDU External Sensor configuration table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

espExternalSensorConfigAlarmState 1.3.6.1.4.1.38446.2.6.3.1.9
User defined alarm state of external sensor
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(0)  

espExternalSensorStatusTable 1.3.6.1.4.1.38446.2.6.4
A table of PDU External Sensor status data
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    EspExternalSensorStatusEntry

espExternalSensorStatusEntry 1.3.6.1.4.1.38446.2.6.4.1
Status data from the PDU External Sensor being queried
Status: current Access: not-accessible
OBJECT-TYPE    
  EspExternalSensorStatusEntry  

espExternalSensorStatusIndex 1.3.6.1.4.1.38446.2.6.4.1.1
The index of the PDU External Sensor status table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..255  

espExternalSensorStatusName 1.3.6.1.4.1.38446.2.6.4.1.2
The user-defined name for the External Sensor
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espExternalSensorStatusAisle 1.3.6.1.4.1.38446.2.6.4.1.3
Indicates whether the external sensor is in a hot or cold aisle
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER hotAisle(1), coldAisle(2)  

espExternalSensorStatusCommStatus 1.3.6.1.4.1.38446.2.6.4.1.4
The communications status of the sensor
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notInstalled(1), commsOk(2), commsLost(3)  

espExternalSensorStatusState 1.3.6.1.4.1.38446.2.6.4.1.5
This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notPresent(0), alarmed(1), normal(2), belowLowerCritical(3), belowLowerWarning(4), aboveUpperWarning(5), aboveUpperCritical(6)  

espExternalSensorStatusValue 1.3.6.1.4.1.38446.2.6.4.1.6
Sensor reading in espExternalSensorConfigUnits value.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espExternalSensorStatusHighPrecisionValue 1.3.6.1.4.1.38446.2.6.4.1.8
Temperature sensor reading in tenths of espExternalSensorConfigUnits value. This OID is applied to temperature sensor only
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

espTrapsInfoIndex 1.3.6.1.4.1.38446.2.9.1
The index of the traps table entry
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..256  

espUserName 1.3.6.1.4.1.38446.2.9.2
The user currently logged in.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espFirmwareVersion 1.3.6.1.4.1.38446.2.9.4
The version of Firmware.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString  

espIndex 1.3.6.1.4.1.38446.2.9.5
A unique value for PDU. Its value ranges between 1 and the value of PDU count
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

espExternalSensorIndex 1.3.6.1.4.1.38446.2.9.6
A unique value for each sensor. Its value ranges between 1 and the value of external sensor count.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

espErrorDescription 1.3.6.1.4.1.38446.2.9.7
Description of the Error
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  DisplayString  

espNetworkCardStart 1.3.6.1.4.1.38446.2.9.8
The network card has started
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espNetworkCardReset 1.3.6.1.4.1.38446.2.9.9
The network card was reset via the web or command line interface.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espFirmwareUpdateCompleted 1.3.6.1.4.1.38446.2.9.10
The firmware update has completed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espUserPasswordChange 1.3.6.1.4.1.38446.2.9.11
A user password was changed.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espLogFileCleared 1.3.6.1.4.1.38446.2.9.12
The log file has been cleared.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espConfigurationFileExported 1.3.6.1.4.1.38446.2.9.13
PDU configuration file was exported
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espUnitActivePowerStateChange 1.3.6.1.4.1.38446.2.9.14
PDU unit active power state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espInputphaseVoltageStateChange 1.3.6.1.4.1.38446.2.9.15
PDU input phase voltage state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espInputphaseCurrentStateChange 1.3.6.1.4.1.38446.2.9.16
PDU input phase Current state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espCircuitBreakerCurrentStateChange 1.3.6.1.4.1.38446.2.9.17
PDU Circuit Breaker Current state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espExternalSensorStateChange 1.3.6.1.4.1.38446.2.9.18
PDU External Sensor state changes.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espConfigurationFileImported 1.3.6.1.4.1.38446.2.9.19
PDU configuration file was imported
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

espNetworkUp 1.3.6.1.4.1.38446.2.9.20
PDU Network is up
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE