EPPC-MIB

File: EPPC-MIB.mib (84212 bytes)

Imported modules

RFC-1215 SNMPv2-TC RFC-1212
RFC1155-SMI UPS-MIB

Imported symbols

TRAP-TYPE DisplayString OBJECT-TYPE
enterprises Counter IpAddress
Integer32 PositiveInteger NonNegativeInteger

Defined Types

UpsSystemInputEntry  
SEQUENCE    
  upsESystemInputPhase PositiveInteger
  upsESystemInputFrequency NonNegativeInteger
  upsESystemInputVoltage NonNegativeInteger
  upsESystemInputCurrent NonNegativeInteger
  upsESystemInputWatts NonNegativeInteger

UpsSystemOutputEntry  
SEQUENCE    
  upsESystemOutputPhase PositiveInteger
  upsESystemOutputFrequency NonNegativeInteger
  upsESystemOutputVoltage NonNegativeInteger
  upsESystemOutputCurrent NonNegativeInteger
  upsESystemOutputWatts NonNegativeInteger
  upsESystemOutputVA NonNegativeInteger
  upsESystemOutputLoad NonNegativeInteger

UpsSystemBypassEntry  
SEQUENCE    
  upsESystemBypassPhase PositiveInteger
  upsESystemBypassFrequency NonNegativeInteger
  upsESystemBypassVoltage NonNegativeInteger
  upsESystemBypassCurrent NonNegativeInteger
  upsESystemBypassWatts NonNegativeInteger

UpsChargerModulesEntry  
SEQUENCE    
  chargerModulesNum PositiveInteger
  chargerModulesAddress NonNegativeInteger
  positiveChargeVotlage NonNegativeInteger
  negativeChargeVoltage NonNegativeInteger
  positiveChargeCurrent NonNegativeInteger
  negativeChargeCurrent NonNegativeInteger
  chargerModulesTemperature INTEGER
  chargerModulesMode INTEGER

UpsModulesEntry  
SEQUENCE    
  upsEModulesNum PositiveInteger
  upsEModuleAddress INTEGER
  upsEModulePositiveBusVolt NonNegativeInteger
  upsEModuleNegativeBusVolt NonNegativeInteger
  upsEModuleTemperature INTEGER
  upsEModuleWorkingMode INTEGER
  upsEModuleOutputCurrentR NonNegativeInteger
  upsEModuleOutputWattR NonNegativeInteger
  upsEModuleOutputLoadR INTEGER
  upsEModuleWarningCode DisplayString
  upsEModuleFaultCode DisplayString
  upsEModuleTrapState DisplayString
  upsEModuleConfigOutputVA NonNegativeInteger
  upsEModuleOutputCurrentS NonNegativeInteger
  upsEModuleOutputCurrentT NonNegativeInteger
  upsEModuleOutputWattS NonNegativeInteger
  upsEModuleOutputWattT NonNegativeInteger
  upsEModuleOutputLoadS INTEGER
  upsEModuleOutputLoadT INTEGER
  upsEModuleOutputVAR NonNegativeInteger
  upsEModuleOutputVAS NonNegativeInteger
  upsEModuleOutputVAT NonNegativeInteger

UpsEEnvironmentContactEntry  
SEQUENCE    
  upsEEnvironmentContactIndex PositiveInteger
  upsEEnvironmentContactType INTEGER
  upsEEnvironmentContactState INTEGER
  upsEEnvironmentContactDescription DisplayString

UpsBatteryTestScheduleEntry  
SEQUENCE    
  upsEBatteryTestScheduleIndex PositiveInteger
  upsEBatteryTestScheduleDay INTEGER
  upsEBatteryTestScheduleTime DisplayString
  upsEBatteryTestScheduleType INTEGER
  upsEBatteryTestScheduleTestWithTime NonNegativeInteger
  upsEBatteryTestScheduleSpecialDay DisplayString

UpsShutdownEventsEntry  
SEQUENCE    
  upsEShutdownEvent INTEGER
  upsEShutdownEventAction INTEGER
  upsEShutdownwarningPeriodTime NonNegativeInteger
  upsEShutdownWarningPeriodInterval NonNegativeInteger

UpsControlWeeklyScheduleEntry  
SEQUENCE    
  upsEControlWeeklyScheduleIndex PositiveInteger
  upsEWeeklyScheduleShutdownDay INTEGER
  upsEWeeklyScheduleShutdownTime DisplayString
  upsEWeeklyScheduleRestartDay INTEGER
  upsEWeeklyScheduleRestartTime DisplayString

UpsControlSpecialDayScheduleEntry  
SEQUENCE    
  upsEControlSpecialDayScheduleIndex PositiveInteger
  upsESpecialDayScheduleShutdownDay DisplayString
  upsESpecialDayScheduleShutdownTime DisplayString
  upsESpecialDayScheduleRestartDay DisplayString
  upsESpecialDayScheduleRestartTime DisplayString

UpsTrapsReceiversEntry  
SEQUENCE    
  upsETrapsReceiversIndex PositiveInteger
  upsETrapsReceiverAddress DisplayString
  upsETrapReceiverCommunityString DisplayString
  upsETrapType INTEGER
  upsETrapsSeverityLevel INTEGER
  upsETrapReceiverDescription DisplayString

Defined Values

ppc 1.3.6.1.4.1.935
OBJECT IDENTIFIER    

device 1.3.6.1.4.1.935.10
OBJECT IDENTIFIER    

upsAgent 1.3.6.1.4.1.935.10.1
OBJECT IDENTIFIER    

upsE 1.3.6.1.4.1.935.10.1.1
OBJECT IDENTIFIER    

upsETraps 1.3.6.1.4.1.935.10.1.2
OBJECT IDENTIFIER    

upsEIdentity 1.3.6.1.4.1.935.10.1.1.1
OBJECT IDENTIFIER    

upsESystemSummary 1.3.6.1.4.1.935.10.1.1.2
OBJECT IDENTIFIER    

upsEBatterySystem 1.3.6.1.4.1.935.10.1.1.3
OBJECT IDENTIFIER    

upsEPowerConverterSystem 1.3.6.1.4.1.935.10.1.1.4
OBJECT IDENTIFIER    

upsELoadSegment 1.3.6.1.4.1.935.10.1.1.5
OBJECT IDENTIFIER    

upsEEnvironment 1.3.6.1.4.1.935.10.1.1.6
OBJECT IDENTIFIER    

upsEBatteryTest 1.3.6.1.4.1.935.10.1.1.7
OBJECT IDENTIFIER    

upsEControl 1.3.6.1.4.1.935.10.1.1.8
OBJECT IDENTIFIER    

upsETrapControl 1.3.6.1.4.1.935.10.1.1.9
OBJECT IDENTIFIER    

upsEIdentityManufacturer 1.3.6.1.4.1.935.10.1.1.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEIdentityModel 1.3.6.1.4.1.935.10.1.1.1.2
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsEIdentityUPSFirmwareVerison 1.3.6.1.4.1.935.10.1.1.1.3
The UPS firmware/software version(s).
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEIndentityUPSSerialNumber 1.3.6.1.4.1.935.10.1.1.1.4
optional. Most UPS don't supply the value of UPS serial No.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEIdentityDescription 1.3.6.1.4.1.935.10.1.1.1.5
A string to identify the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsEIdentityAgentSoftwareVerison 1.3.6.1.4.1.935.10.1.1.1.6
The Network Management Card software/firmware version. This variable may or may not have the same value as upsEIdentGroupUPSSoftwareVersion in some implementations.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEIdentityAttachedDevices 1.3.6.1.4.1.935.10.1.1.1.7
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsESystemStatus 1.3.6.1.4.1.935.10.1.1.2.1
The indication of UPS system status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER power-on(1), stand-by(2), by-pass(3), line(4), battery(5), battery-test(6), fault(7), converter(8), eco(9), shutdown(10), on-booster(11), on-reducer(12), other(13)  

upsESystemTemperature 1.3.6.1.4.1.935.10.1.1.2.2
The temperature of UPS presented in 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsESystemWarningCode 1.3.6.1.4.1.935.10.1.1.2.3
The warning code of UPS. Please refer the warning table of 'Q6' for details.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsESystemFaultCode 1.3.6.1.4.1.935.10.1.1.2.4
The fault code of UPS.Please refer the fault code of 'Q6' for details.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsESystemConfigInputVoltage 1.3.6.1.4.1.935.10.1.1.2.5
The magnitude of the nominal input voltage presented in 0.1 V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigInputFrequence 1.3.6.1.4.1.935.10.1.1.2.6
The nominal input frequency presented in 0.1 Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOutputVoltage 1.3.6.1.4.1.935.10.1.1.2.7
The magnitude of the nominal output voltage presented in 0.1V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOutputFrequency 1.3.6.1.4.1.935.10.1.1.2.8
The nominal output frequency presented in 0.1Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOutputVA 1.3.6.1.4.1.935.10.1.1.2.9
The magnitude of the nominal Volt-Amp rating presented in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOutputPower 1.3.6.1.4.1.935.10.1.1.2.10
The magnitude of the nominal true power rating presented in W .
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOutputLoadHighSetPoint 1.3.6.1.4.1.935.10.1.1.2.11
The maximum output load allowed before the load is too high for UPS operation
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigOverTemperatureSetPoint 1.3.6.1.4.1.935.10.1.1.2.12
The maximum temperature allowed before the UPS operation temperature is too high, presented in 0.1 degree.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemInputSourceNum 1.3.6.1.4.1.935.10.1.1.2.13
The present external source of input power.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsESystemInputLineBads 1.3.6.1.4.1.935.10.1.1.2.14
The number of times the Input was out of tolerance in voltage or frequency. Its value should be initialized 0 after agent restarting.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Counter  

upsESystemInputNumPhases 1.3.6.1.4.1.935.10.1.1.2.15
The number of input phase utilized is this device, serves as the table index. This value indicate the device initialized feature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemInputTable 1.3.6.1.4.1.935.10.1.1.2.16
A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsSystemInputEntry

upsESystemInputEntry 1.3.6.1.4.1.935.10.1.1.2.16.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsSystemInputEntry  

upsESystemInputPhase 1.3.6.1.4.1.935.10.1.1.2.16.1.1
The number of the phase. Serves as index for input table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemInputFrequency 1.3.6.1.4.1.935.10.1.1.2.16.1.2
The measured input frquency from the UPS meters in 0.1Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemInputVoltage 1.3.6.1.4.1.935.10.1.1.2.16.1.3
The measured input voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemInputCurrent 1.3.6.1.4.1.935.10.1.1.2.16.1.4
The measured input mandatory from the UPS meters in 0.1 amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemInputWatts 1.3.6.1.4.1.935.10.1.1.2.16.1.5
The measured input real power in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputNumPhase 1.3.6.1.4.1.935.10.1.1.2.17
The number of metered output phases, serves as the table index. This value indicate the device initialized feature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemOutputTable 1.3.6.1.4.1.935.10.1.1.2.18
A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsSystemOutputEntry

upsESystemOutputEntry 1.3.6.1.4.1.935.10.1.1.2.18.1
An entry containing information applicable to a particular line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsSystemOutputEntry  

upsESystemOutputPhase 1.3.6.1.4.1.935.10.1.1.2.18.1.1
The number of the phase. Serves as index for output table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemOutputFrequency 1.3.6.1.4.1.935.10.1.1.2.18.1.2
The measured output frequency from the UPS meters in 0.1Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputVoltage 1.3.6.1.4.1.935.10.1.1.2.18.1.3
The measured output voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputCurrent 1.3.6.1.4.1.935.10.1.1.2.18.1.4
The measured output mandatory from the UPS meters in 0.1 amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputWatts 1.3.6.1.4.1.935.10.1.1.2.18.1.5
The measured output real power in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputVA 1.3.6.1.4.1.935.10.1.1.2.18.1.6
The measured output real complex power in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemOutputLoad 1.3.6.1.4.1.935.10.1.1.2.18.1.7
The UPS output load in percent of rated capacity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemBypassNumPhase 1.3.6.1.4.1.935.10.1.1.2.19
The number of bypass phases, serves as the table index. This value indicate the device initialized feature
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemBypassTable 1.3.6.1.4.1.935.10.1.1.2.20
A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsSystemBypassEntry

upsESystemBypassEntry 1.3.6.1.4.1.935.10.1.1.2.20.1
An entry containing information applicable to a particular line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsSystemBypassEntry  

upsESystemBypassPhase 1.3.6.1.4.1.935.10.1.1.2.20.1.1
The number of the phase. Serves as index for bypass table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger 1..3  

upsESystemBypassFrequency 1.3.6.1.4.1.935.10.1.1.2.20.1.2
The measured bypass frequency from the UPS meters in 0.1 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemBypassVoltage 1.3.6.1.4.1.935.10.1.1.2.20.1.3
The measured bypass voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemBypassCurrent 1.3.6.1.4.1.935.10.1.1.2.20.1.4
The measured bypass mandatory from the UPS meters in 0.1 amps
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemBypassWatts 1.3.6.1.4.1.935.10.1.1.2.20.1.5
The measured input real power in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigBelowCapacityLimit 1.3.6.1.4.1.935.10.1.1.2.21
The UPS batteries capacity(%) limit for shutdown
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsESystemConfigBelowRemainTimeLimit 1.3.6.1.4.1.935.10.1.1.2.22
The UPS batteries backup time(minute) limit for shutdown
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryStatus 1.3.6.1.4.1.935.10.1.1.3.1
The status of UPS battery, a value of batteryLow indicates that the battery-low status bit has been set from device. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is mandatoryly absent and the UPS is unable to sustain the output)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6)  

upsESecondsOnBattery 1.3.6.1.4.1.935.10.1.1.3.2
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryEstimatedMinutesRemaining 1.3.6.1.4.1.935.10.1.1.3.3
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: mandatory Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsEBatteryEstimatedChargeRemaining 1.3.6.1.4.1.935.10.1.1.3.4
An estimate of the battery charge remaining expressed as a percent of full charge
Status: mandatory Access: read-only
OBJECT-TYPE    
  Integer32 0..100  

upsEPositiveBatteryVoltage 1.3.6.1.4.1.935.10.1.1.3.5
The magnitude of the present positive battery voltage in 0.1 Volt DC
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsENegativeBatteryVoltage 1.3.6.1.4.1.935.10.1.1.3.6
The magnitude of the present negative battery voltage in 0.1 Volt DC
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryCellNumber 1.3.6.1.4.1.935.10.1.1.3.7
This object indicate the cell number of each set.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryTemperature 1.3.6.1.4.1.935.10.1.1.3.8
The ambient temperature at or near the UPS Battery casing in 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEBatteryLastReplacedDate 1.3.6.1.4.1.935.10.1.1.3.9
The date when the Batteries in this UPS were last replaced. The format should be DD/MM/YYYY.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsEBatteryABMStatus 1.3.6.1.4.1.935.10.1.1.3.10
The status of ABM.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER charge(1), float(2), rest(3), discharge(4), disable(5)  

upsEChargerModulesNum 1.3.6.1.4.1.935.10.1.1.3.11
The number of charger modules inserted to UPS systems. served as the index of the upsEChargerModulesTable. The default value 0 indicate that the UPS system don't have separate charger module.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger 0..32  

upsEChargerModulesTable 1.3.6.1.4.1.935.10.1.1.3.12
A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsChargerModulesEntry

upsEChargerModulesEntry 1.3.6.1.4.1.935.10.1.1.3.12.1
An entry containing information applicable to a particular charger module.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsChargerModulesEntry  

chargerModulesNum 1.3.6.1.4.1.935.10.1.1.3.12.1.1
The number of charger modules. Serves as index for charger module table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger 1..32  

chargerModulesAddress 1.3.6.1.4.1.935.10.1.1.3.12.1.2
Charger Modules' address.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

positiveChargeVotlage 1.3.6.1.4.1.935.10.1.1.3.12.1.3
The measured positive charger voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

negativeChargeVoltage 1.3.6.1.4.1.935.10.1.1.3.12.1.4
The measured nepositive charger voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

positiveChargeCurrent 1.3.6.1.4.1.935.10.1.1.3.12.1.5
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

negativeChargeCurrent 1.3.6.1.4.1.935.10.1.1.3.12.1.6
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

chargerModulesTemperature 1.3.6.1.4.1.935.10.1.1.3.12.1.7
The measured charger temperature from the UPS meters in 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

chargerModulesMode 1.3.6.1.4.1.935.10.1.1.3.12.1.8
The working mode of charger modules.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER powerOn(1), standyby(2), fault(3), shutdown(4), running(5), suicide(6), unknown(7)  

upsEUPSModulesNum 1.3.6.1.4.1.935.10.1.1.4.1
The number of UPS modules inserted to UPS systems. served as the index of the upsEModulesTable. the default value 0 indicate that the UPS system do not have separate UPS module.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger 0..32  

upsEModulesTable 1.3.6.1.4.1.935.10.1.1.4.2
A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsModulesEntry

upsEModulesEntry 1.3.6.1.4.1.935.10.1.1.4.2.1
An entry containing information applicable to a particular upsE module.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsModulesEntry  

upsEModulesNum 1.3.6.1.4.1.935.10.1.1.4.2.1.1
The number of UPS modules. Serves as index for UPS module table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger 1..32  

upsEModuleAddress 1.3.6.1.4.1.935.10.1.1.4.2.1.2
the address of UPS modules.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEModulePositiveBusVolt 1.3.6.1.4.1.935.10.1.1.4.2.1.3
The measured positive upsE module voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleNegativeBusVolt 1.3.6.1.4.1.935.10.1.1.4.2.1.4
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleTemperature 1.3.6.1.4.1.935.10.1.1.4.2.1.5
The measured upsE module temperature from the UPS meters in 0.1 degree.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEModuleWorkingMode 1.3.6.1.4.1.935.10.1.1.4.2.1.6
The working mode of UPS modules.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER power-on(1), stand-by(2), by-pass(3), line(4), battery(5), battery-test(6), fault(7), converter(8), eco(9), shutdown(10), on-booster(11), on-reducer(12), other(13)  

upsEModuleOutputCurrentR 1.3.6.1.4.1.935.10.1.1.4.2.1.7
The measured upsE module output mandatory from the UPS meters in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputWattR 1.3.6.1.4.1.935.10.1.1.4.2.1.8
The measured upsE module output watts from the UPS meters in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputLoadR 1.3.6.1.4.1.935.10.1.1.4.2.1.9
The output load of UPS modules in %.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEModuleWarningCode 1.3.6.1.4.1.935.10.1.1.4.2.1.10
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsEModuleFaultCode 1.3.6.1.4.1.935.10.1.1.4.2.1.11
The fault code of ups modules.Please refer command 'QU,XX' for details.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsEModuleTrapState 1.3.6.1.4.1.935.10.1.1.4.2.1.12
the values indicate the unrestored traps. For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEModuleTrapState should change to empty.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..127)  

upsEModuleConfigOutputVA 1.3.6.1.4.1.935.10.1.1.4.2.1.13
The magnitude of the nominal Volt-Amp rating presented in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputCurrentS 1.3.6.1.4.1.935.10.1.1.4.2.1.14
The measured upsE module output mandatory from the UPS meters in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputCurrentT 1.3.6.1.4.1.935.10.1.1.4.2.1.15
The measured upsE module output mandatory from the UPS meters in 0.1 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputWattS 1.3.6.1.4.1.935.10.1.1.4.2.1.16
The measured upsE module output watts from the UPS meters in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputWattT 1.3.6.1.4.1.935.10.1.1.4.2.1.17
The measured upsE module output watts from the UPS meters in watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputLoadS 1.3.6.1.4.1.935.10.1.1.4.2.1.18
The output load of UPS modules in %.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEModuleOutputLoadT 1.3.6.1.4.1.935.10.1.1.4.2.1.19
The output load of UPS modules in %.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEModuleOutputVAR 1.3.6.1.4.1.935.10.1.1.4.2.1.20
The magnitude of the nominal Volt-Amp rating presented in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputVAS 1.3.6.1.4.1.935.10.1.1.4.2.1.21
The magnitude of the nominal Volt-Amp rating presented in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEModuleOutputVAT 1.3.6.1.4.1.935.10.1.1.4.2.1.22
The magnitude of the nominal Volt-Amp rating presented in VA.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsELoadSegment1OffDelay 1.3.6.1.4.1.935.10.1.1.5.1
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment1OnDelay 1.3.6.1.4.1.935.10.1.1.5.2
Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment1AutoOffTimer 1.3.6.1.4.1.935.10.1.1.5.3
The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment1AutoOnTimer 1.3.6.1.4.1.935.10.1.1.5.4
The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment1State 1.3.6.1.4.1.935.10.1.1.5.5
Load segment output state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2), off-pending(3), on-pending(4), not-support(5)  

upsELoadSegment2OffDelay 1.3.6.1.4.1.935.10.1.1.5.6
Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment2OnDelay 1.3.6.1.4.1.935.10.1.1.5.7
Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment2AutoOffTimer 1.3.6.1.4.1.935.10.1.1.5.8
The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment2AutoOnTimer 1.3.6.1.4.1.935.10.1.1.5.9
The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsELoadSegment2State 1.3.6.1.4.1.935.10.1.1.5.10
Load segment output state.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(1), on(2), off-pending(3), on-pending(4), not-support(5)  

upsEEnvironmentTemperature 1.3.6.1.4.1.935.10.1.1.6.1
OBJECT IDENTIFIER    

upsEEnvironmentCurrentTemperature 1.3.6.1.4.1.935.10.1.1.6.1.1
The measurement of temperature sensor, in 0.1 degree
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentTemperatureHighSetPoint 1.3.6.1.4.1.935.10.1.1.6.1.2
The set point for high temperature warning, in 0.1 degrees. This value must be greater than upsEEnvironmentTemperatureLowSetPoint, and the least significant digit must be zero.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentTemperatureHighStatus 1.3.6.1.4.1.935.10.1.1.6.1.3
To enable/disable high set point check with sensor temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsEEnvironmentTemperatureLowSetPoint 1.3.6.1.4.1.935.10.1.1.6.1.4
The set point for low temperature warning, in 0.1 degrees. This value must be less than upsEEnvironmentTemperatureHighSetPoint, and the least significant digit must be zero.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentTemperatureLowStatus 1.3.6.1.4.1.935.10.1.1.6.1.5
To enable/disable low set point check with sensor temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsEEnvironmentTemperatureOffset 1.3.6.1.4.1.935.10.1.1.6.1.6
The offset to calibrate temperature of EMD, in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentHumidity 1.3.6.1.4.1.935.10.1.1.6.2
OBJECT IDENTIFIER    

upsEEnvironmentCurrentHumidity 1.3.6.1.4.1.935.10.1.1.6.2.1
The measurement of sensor humidity present in %.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentHumidityHighSetPoint 1.3.6.1.4.1.935.10.1.1.6.2.2
The set point for high humidity warning, in %. This value must be greater than upsEEnvironmentHumidityLowSetPoint.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentHumidityHighStatus 1.3.6.1.4.1.935.10.1.1.6.2.3
To enable/disable high set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsEEnvironmentHumidityLowSetPoint 1.3.6.1.4.1.935.10.1.1.6.2.4
The set point for low humidity warning, in %. This value must be less than upsEEnvironmentHumidityHighSetPoint.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentHumidityLowStatus 1.3.6.1.4.1.935.10.1.1.6.2.5
To enable/disable high set point check with emd humidity.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enable(1), disable(2)  

upsEEnvironmentHumidityOffset 1.3.6.1.4.1.935.10.1.1.6.2.6
The offset to calibrate humidity of EMD, in %.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

upsEEnvironmentContactsNum 1.3.6.1.4.1.935.10.1.1.6.3
The number of environment contacts, serves as the table index.
Status: mandatory Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsEEnvironmentContactTable 1.3.6.1.4.1.935.10.1.1.6.4
A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsEEnvironmentContactEntry

upsEEnvironmentContactEntry 1.3.6.1.4.1.935.10.1.1.6.4.1
An entry containing information applicable to a particular contact
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsEEnvironmentContactEntry  

upsEEnvironmentContactIndex 1.3.6.1.4.1.935.10.1.1.6.4.1.1
The number of environment contacts. Serves as index for environment contact table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsEEnvironmentContactType 1.3.6.1.4.1.935.10.1.1.6.4.1.2
operation type
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normallyOpen(1), normallyClosed(2), notUsed(3)  

upsEEnvironmentContactState 1.3.6.1.4.1.935.10.1.1.6.4.1.3
The mandatory status.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(1), closed(2), openWithNotice(3), closedWithNotice(4)  

upsEEnvironmentContactDescription 1.3.6.1.4.1.935.10.1.1.6.4.1.4
Description of environment contact.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsEBatteryTestStart 1.3.6.1.4.1.935.10.1.1.7.1
This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), batteryTest10Sec(2), batteryTestUntilLow(3), batteryTestWithTime(4), cancelBatteryTest(5), clearBatteryInfo(6)  

upsEBatteryTestSettingTime 1.3.6.1.4.1.935.10.1.1.7.2
The object specify the test time for battery test in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryTestResult 1.3.6.1.4.1.935.10.1.1.7.3
This object indicate the test result of battery.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER idle(1), processing(2), noFailure(3), failureOrWarning(4), notPossible(5), testCancel(6)  

upsEBatteryTestStartTime 1.3.6.1.4.1.935.10.1.1.7.4
The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsETestBatteryTestResult is noTestsInitiated(6), upsETestStartTime has the value 01/01/1970 00:00:00.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(19..19)  

upsEBatteryTestElapsedTime 1.3.6.1.4.1.935.10.1.1.7.5
The amount of time in format hh:mm:ss, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is idle(1), upsTestElapsedTime has the value 00:00:00.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(11..11)  

upsEBatteryTestScheduleTable 1.3.6.1.4.1.935.10.1.1.7.6
This table describes the schedule for automatically battery test.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBatteryTestScheduleEntry

upsEBatteryTestScheduleEntry 1.3.6.1.4.1.935.10.1.1.7.6.1
An entry containing information applicable to schedule test.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsBatteryTestScheduleEntry  

upsEBatteryTestScheduleIndex 1.3.6.1.4.1.935.10.1.1.7.6.1.1
The index of battery test scheduled.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsEBatteryTestScheduleDay 1.3.6.1.4.1.935.10.1.1.7.6.1.2
The weekday or specaial day on which the UPS should start battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER monday(1), tuesday(2), wednsday(3), thusday(4), friday(5), saturday(6), sunday(7), specialday(8), none(9)  

upsEBatteryTestScheduleTime 1.3.6.1.4.1.935.10.1.1.7.6.1.3
The time that the battery test will be initiated in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5)  

upsEBatteryTestScheduleType 1.3.6.1.4.1.935.10.1.1.7.6.1.5
The type of battery test.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), batteryTest10sec(2), batteryTestUntilLow(3), batteryTestWithTime(4)  

upsEBatteryTestScheduleTestWithTime 1.3.6.1.4.1.935.10.1.1.7.6.1.6
The battery time of setting time test in seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEBatteryTestScheduleSpecialDay 1.3.6.1.4.1.935.10.1.1.7.6.1.7
The special day that the battery test will be initiated in dd/mm/yyyy format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10)  

upsEControlOutputOffDelay 1.3.6.1.4.1.935.10.1.1.8.1
Setting this value to other than zero will cause the UPS output to turn off after the number of seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEControlOutputOnDelay 1.3.6.1.4.1.935.10.1.1.8.2
Setting this value to other than zero will cause the UPS output to turn on after the number of seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEControlOutputOnOffControl 1.3.6.1.4.1.935.10.1.1.8.3
upsEOutputOff ( 1 ) indicates the shutdown sequence, upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence, upsESleep( 3 ) indicates shutdown UPS first, then switch on.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER upsEOutputOff(1), upsEOutputOffCancel(2), upsESleep(3), none(4)  

upsEShutdownEventsTable 1.3.6.1.4.1.935.10.1.1.8.4
This table describes the parametes for shutdown process when shutdown event occurs
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsShutdownEventsEntry

upsEShutdownEventsEntry 1.3.6.1.4.1.935.10.1.1.8.4.1
An entry containing information applicable to a particular shutdown event line
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsShutdownEventsEntry  

upsEShutdownEvent 1.3.6.1.4.1.935.10.1.1.8.4.1.1
The shutdown event identification
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  INTEGER acFail(1), batteryLow(2), upsEOverLoad(3), upsEOverTemperature(4), upsEWeeklySchedule(5), upsESpecialSchedule(6), environmentTemperatureOverThreshold(7), environmentHumidityOverThreshold(8), environmentContact1Alarm(9), environmentContact2Alarm(10), belowCapacityLimit(11), belowRemainTimeLimit(12)  

upsEShutdownEventAction 1.3.6.1.4.1.935.10.1.1.8.4.1.2
Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disable(1), warning(2), shutdownClient(3), shutdownUPS(4)  

upsEShutdownwarningPeriodTime 1.3.6.1.4.1.935.10.1.1.8.4.1.3
The Delay in seconds after the occurance of the curresponding shutdown event, and warning message should be popped in this period.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEShutdownWarningPeriodInterval 1.3.6.1.4.1.935.10.1.1.8.4.1.4
The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
Status: mandatory Access: read-write
OBJECT-TYPE    
  NonNegativeInteger  

upsEControlWeeklyScheduleTable 1.3.6.1.4.1.935.10.1.1.8.5
The table to schedule shutting down the ups by weekly
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlWeeklyScheduleEntry

upsEControlWeeklyScheduleEntry 1.3.6.1.4.1.935.10.1.1.8.5.1
An entry containing information applicable to a particular line
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlWeeklyScheduleEntry  

upsEControlWeeklyScheduleIndex 1.3.6.1.4.1.935.10.1.1.8.5.1.1
the index of schedule events.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsEWeeklyScheduleShutdownDay 1.3.6.1.4.1.935.10.1.1.8.5.1.2
the weekday on which upsE shoud shutdown
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6), sunday(7), none(8)  

upsEWeeklyScheduleShutdownTime 1.3.6.1.4.1.935.10.1.1.8.5.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5)  

upsEWeeklyScheduleRestartDay 1.3.6.1.4.1.935.10.1.1.8.5.1.4
the weekday on which the UPS should restart.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6), sunday(7), none(8)  

upsEWeeklyScheduleRestartTime 1.3.6.1.4.1.935.10.1.1.8.5.1.5
The time the UPS will restart in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsEControlSpecialDayScheduleTable 1.3.6.1.4.1.935.10.1.1.8.6
The table to schedule shutting down the ups.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsControlSpecialDayScheduleEntry

upsEControlSpecialDayScheduleEntry 1.3.6.1.4.1.935.10.1.1.8.6.1
An entry containing information applicable to a particular line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsControlSpecialDayScheduleEntry  

upsEControlSpecialDayScheduleIndex 1.3.6.1.4.1.935.10.1.1.8.6.1.1
The index of special day schedule.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsESpecialDayScheduleShutdownDay 1.3.6.1.4.1.935.10.1.1.8.6.1.2
The special day on which UPS should shutdown with the format of DD/MM/YYYY.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsESpecialDayScheduleShutdownTime 1.3.6.1.4.1.935.10.1.1.8.6.1.3
The time that the process of shutting down the UPS will be initiated in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsESpecialDayScheduleRestartDay 1.3.6.1.4.1.935.10.1.1.8.6.1.4
The special day on which the UPS should restart with the format of DD/MM/YYYY.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

upsESpecialDayScheduleRestartTime 1.3.6.1.4.1.935.10.1.1.8.6.1.5
The time the UPS will restart in hh:mm format.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(5..5)  

upsESystemMasterOffDelay 1.3.6.1.4.1.935.10.1.1.8.7
The UPS output will shutdown after the indicated number of seconds, -1 indicate no action.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsESystemMasterOnDelay 1.3.6.1.4.1.935.10.1.1.8.8
The UPS output will start on after the indicated number of seconds, -1 indicate no action.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

upsETrapsReceiversTable 1.3.6.1.4.1.935.10.1.1.9.1
This table list the managers'IP to send traps to.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsTrapsReceiversEntry

upsETrapsReceiversEntry 1.3.6.1.4.1.935.10.1.1.9.1.1
An entry containing information applicable to a particular input line.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  UpsTrapsReceiversEntry  

upsETrapsReceiversIndex 1.3.6.1.4.1.935.10.1.1.9.1.1.1
The index to a trap receiver entry
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  PositiveInteger  

upsETrapsReceiverAddress 1.3.6.1.4.1.935.10.1.1.9.1.1.2
The IP address of the manager to send a trap to.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..45)  

upsETrapReceiverCommunityString 1.3.6.1.4.1.935.10.1.1.9.1.1.3
The community name to use in the trap when sent to the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

upsETrapType 1.3.6.1.4.1.935.10.1.1.9.1.1.4
The type of trap to be received by the manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER none(1), rfc1628Trap(2), eppcTrap(3)  

upsETrapsSeverityLevel 1.3.6.1.4.1.935.10.1.1.9.1.1.5
The severity level of traps to be received by this manager.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER informational(1), warning(2), severe(3)  

upsETrapReceiverDescription 1.3.6.1.4.1.935.10.1.1.9.1.1.6
Description of trap receivers
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

upsETrapState 1.3.6.1.4.1.935.10.1.1.9.2
the values indicate the unrestored traps. For example, after AC fail, the agent send the trap 1(AC Fail) and trap 7(battery on) to NMS. so the value of upsETrapState should be '1,7'. And then the AC restore, the value of upsETrapState should change to empty.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..127)  

upsEPowerFail 1
WARNING: Utility power not available.
TRAP-TYPE    

upsEPowerRestored 2
INFORMATION: Utility power has restored.
TRAP-TYPE    

upsELowBattery 3
SEVERE: The UPS batteries are low and will soon be exhausted.
TRAP-TYPE    

upsEReturnFromLowBattery 4
INFORMATION: The UPS has return from a low battery condition.
TRAP-TYPE    

upsEFailed 5
SEVERE: The UPS is not working fine.
TRAP-TYPE    

upsEOk 6
INFORMATION: The UPS is working fine.
TRAP-TYPE    

upsEOnBattery 7
WARNING: The UPS has switched to battery backup power.
TRAP-TYPE    

upsENotOnBattery 8
INFORMATION: The UPS is not on battery power.
TRAP-TYPE    

upsETestInProgress 9
INFORMATION: The testing is going on ups.
TRAP-TYPE    

upsETestOver 10
INFORMATION: The testing of UPS is completed.
TRAP-TYPE    

upsEBypassOn 11
INFORMATION: The UPS has enabled bypass.
TRAP-TYPE    

upsEOnline 12
INFORMATION: The UPS is not on Bypass and return to normal status.
TRAP-TYPE    

upsECommunicationLost 13
SEVERE: Communication to the UPS has been lost.
TRAP-TYPE    

upsECommunicationEstablished 14
INFORMATION: Communication with the UPS has been established.
TRAP-TYPE    

upsEGoingShutdown 15
WARNING: The UPS is going to shutdown output.
TRAP-TYPE    

upsEShutdownCancelled 16
INFORMATION: The UPS is not going to shutdown output.
TRAP-TYPE    

upsEOutlet1GoingShutdown 17
WARNING: The UPS is going to shutdown outlet1.
TRAP-TYPE    

upsEOutlet1ShutdownCancelled 18
INFORMATION: The UPS is not going to shutdown outlet1.
TRAP-TYPE    

upsEOutlet2GoingShutdown 19
WARNING: The UPS is going to shutdown outlet2.
TRAP-TYPE    

upsEOutlet2ShutdownCancelled 20
INFORMATION: The UPS is not going to shutdown outlet2.
TRAP-TYPE    

upsESleeping 21
INFORMATION: UPS has entered sleep mode and power to load has been cut off.
TRAP-TYPE    

upsEWokeUp 22
INFORMATION: The UPS woke up from sleep mode and power to load has been restored.
TRAP-TYPE    

upsEOverTemperature 23
WARNING: The UPS temperature is over the setting limit.
TRAP-TYPE    

upsENotOverTemperature 24
INFORMATION: The UPS temperature is not over the setting limit.
TRAP-TYPE    

upsEOverLoad 25
WARNING: The UPS load is over the setting limit.
TRAP-TYPE    

upsENotOverLoad 26
INFORMATION: The UPS load is not over the setting limit.
TRAP-TYPE    

upsEModuleInserted 27
WARNING: UPS module or charger module plug-in.
TRAP-TYPE    

upsEModuleRemoved 28
WARNING: UPS module or charger module unplugs.
TRAP-TYPE    

sensorTemperatureTooHigh 29
WARNING: Sensor Temperature over high Set point.
TRAP-TYPE    

sensorTemperatureNotHigh 30
INFORMATION: Sensor Temperature not over high Set point.
TRAP-TYPE    

sensorTemperatureTooLow 31
WARNING: Sensor Temperature under low Set point.
TRAP-TYPE    

sensorTemperatureNotLow 32
INFORMATION: Sensor Temperature not under low Set point.
TRAP-TYPE    

sensorHumidityTooHigh 33
WARNING: Sensor Humidity over high Set point.
TRAP-TYPE    

sensorHumidityNotHigh 34
INFORMATION: Sensor Humidity not over high Set point.
TRAP-TYPE    

sensorHumidityTooLow 35
WARNING: Sensor Humidity under low Set point.
TRAP-TYPE    

sensorHumidityNotLow 36
INFORMATION: Sensor Humidity not under low Set point.
TRAP-TYPE    

contactAlarm1Active 37
WARNING: Contact Alarm-1 activated.
TRAP-TYPE    

concactAlarm1Normal 38
INFORMATION: Contact Alarm-1 not active.
TRAP-TYPE    

contactAlarm2Active 39
WARNING: Contact Alarm-2 activated.
TRAP-TYPE    

contactAlarm2Normal 40
INFORMATION: Contact Alarm-2 not active.
TRAP-TYPE    

upsEInternalwarning 41
WARNING: Internal warning.
TRAP-TYPE    

upsEReturnFromInternalwarning 42
INFORMATION: Return from Internal warning.
TRAP-TYPE    

upsEEPOActive 43
WARNING: EPO Active.
TRAP-TYPE    

upsEReturnFromEPOActive 44
INFORMATION: Return from EPO Active.
TRAP-TYPE    

upsEModuleUnlock 45
WARNING: Module Unlock.
TRAP-TYPE    

upsEReturnFromModuleUnlock 46
INFORMATION: Return from Module Unlock.
TRAP-TYPE    

upsEMain1Neutralloss 47
WARNING: Main 1 Neutral loss.
TRAP-TYPE    

upsEReturnFromMain1Neutralloss 48
INFORMATION: Return from Main 1 Neutral loss.
TRAP-TYPE    

upsEMain1phaseerror 49
WARNING: Main 1 phase error.
TRAP-TYPE    

upsEReturnFromMain1phaseerror 50
INFORMATION: Return from Main 1 phase error.
TRAP-TYPE    

upsESitefault 51
WARNING: Site fault.
TRAP-TYPE    

upsEReturnFromSitefault 52
INFORMATION: Return from Site fault.
TRAP-TYPE    

upsEBypassAbnormal 53
WARNING: Bypass Abnormal.
TRAP-TYPE    

upsEReturnFromBypassAbnormal 54
INFORMATION: Return from Bypass Abnormal.
TRAP-TYPE    

upsEBypassPhaseError 55
WARNING: Bypass Phase Error.
TRAP-TYPE    

upsEReturnFromBypassPhaseError 56
INFORMATION: Return from Bypass Phase Error.
TRAP-TYPE    

upsEBatteryOpen 57
WARNING: Battery Open.
TRAP-TYPE    

upsEReturnFromBatteryOpen 58
INFORMATION: Return from Battery Open.
TRAP-TYPE    

upsEBatteryOverCharge 59
WARNING: Battery Over Charge.
TRAP-TYPE    

upsEReturnFromBatteryOverCharge 60
INFORMATION: Return from Battery Over Charge.
TRAP-TYPE    

upsEBatteryReverse 61
WARNING: Battery Reverse.
TRAP-TYPE    

upsEReturnFromBatteryReverse 62
INFORMATION: Return from Battery Reverse.
TRAP-TYPE    

upsEOverloadforewarning 63
WARNING: Overload forewarning.
TRAP-TYPE    

upsEReturnFromOverloadforewarning 64
INFORMATION: Return from Overload forewarning.
TRAP-TYPE    

upsEOverloadWarning 65
WARNING: Overload Warning.
TRAP-TYPE    

upsEReturnFromOverloadWarning 66
INFORMATION: Return from Overload Warning.
TRAP-TYPE    

upsEFanLock 67
WARNING: Fan Lock.
TRAP-TYPE    

upsEReturnFromFanLock 68
INFORMATION: Return from Fan Lock.
TRAP-TYPE    

upsEMaintaincoverisopen 69
WARNING: Maintain cover is open.
TRAP-TYPE    

upsEReturnFromMaintaincoverisopen 70
INFORMATION: Return from Maintain cover is open.
TRAP-TYPE    

upsEChargerfault 71
WARNING: Charger fault.
TRAP-TYPE    

upsEReturnFromChargerfault 72
INFORMATION: Return from Charger fault.
TRAP-TYPE    

upsEModulelocationerror 73
WARNING: Module location error.
TRAP-TYPE    

upsEReturnFromModulelocationerror 74
INFORMATION: Return from Module location error.
TRAP-TYPE    

upsETurnonabnormal 75
WARNING: Turn on abnormal.
TRAP-TYPE    

upsEReturnFromTurnonabnormal 76
INFORMATION: Return from Turn on abnormal.
TRAP-TYPE    

upsERedundancyloss 77
WARNING: Redundancy loss.
TRAP-TYPE    

upsEReturnFromRedundancyloss 78
INFORMATION: Return from Redundancy loss.
TRAP-TYPE    

upsEHotSwapActived 79
WARNING: Hot Swap Active.
TRAP-TYPE    

upsEReturnFromHotSwapActived 80
INFORMATION: Return from Hot Swap Active.
TRAP-TYPE    

upsEBatteryInform 81
WARNING: Battery Inform.
TRAP-TYPE    

upsEReturnFromBatteryInform 82
INFORMATION: Return from Battery Inform.
TRAP-TYPE    

upsEInspectionInform 83
WARNING: Inspection Inform.
TRAP-TYPE    

upsEReturnFromInspectionInform 84
INFORMATION: Return from Inspection Inform.
TRAP-TYPE    

upsEGuaranteeInform 85
WARNING: Guarantee Inform.
TRAP-TYPE    

upsEReturnFromGuaranteeInform 86
INFORMATION: Return from Guarantee Inform.
TRAP-TYPE    

upsETemperatureLow 87
WARNING: Temperature Low.
TRAP-TYPE    

upsEReturnFromTemperatureLow 88
INFORMATION: Return from Temperature Low.
TRAP-TYPE    

upsETemperatureHigh 89
WARNING: Temperature High.
TRAP-TYPE    

upsEReturnFromTemperatureHigh 90
INFORMATION: Return from Temperature High.
TRAP-TYPE    

upsEBatteryOverTemperature 91
WARNING: Battery Over Temperature.
TRAP-TYPE    

upsEReturnFromBatteryOverTemperature 92
INFORMATION: Return from Battery Over Temperature.
TRAP-TYPE    

upsEFanMaintainInform 93
WARNING: Fan Maintain Inform.
TRAP-TYPE    

upsEReturnFromFanMaintainInform 94
INFORMATION: Return from Fan Maintain Inform.
TRAP-TYPE    

upsEBusCapacitanceMaintainInform 95
WARNING: Bus Capacitance Maintain Inform.
TRAP-TYPE    

upsEReturnFromBusCapacitanceMaintainInform 96
INFORMATION: Return from Bus Capacitance Maintain Inform.
TRAP-TYPE    

upsESystemOverCapacity 97
WARNING: System Over Capacity.
TRAP-TYPE    

upsEReturnFromSystemOverCapacity 98
INFORMATION: Return from System Over Capacity.
TRAP-TYPE    

upsEBelowCapacityLimit 123
SEVERE: The UPS batteries capacity is lower than setting limit.
TRAP-TYPE    

upsENotBelowCapacityLimit 124
INFORMATION: The UPS batteries capacity is not lower than setting limit.
TRAP-TYPE    

upsEBelowRemainTimeLimit 125
SEVERE: The UPS batteries backup time is below the setting limit.
TRAP-TYPE    

upsENotBelowRemainTimeLimit 126
INFORMATION: The UPS batteries backup time is not below the setting limit.
TRAP-TYPE    

upsELoadSegment1Off 127
WARNING: Load segment 1 is off.
TRAP-TYPE    

upsELoadSegment1On 128
INFORMATION: Load segment 1 is on.
TRAP-TYPE    

upsELoadSegment2Off 129
WARNING: Load segment 2 is off.
TRAP-TYPE    

upsELoadSegment2On 130
INFORMATION: Load segment 2 is on.
TRAP-TYPE