HAWK-I2-MIB

File: HAWK-I2-MIB.mib (70116 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC INET-ADDRESS-MIB

Imported symbols

MODULE-IDENTITY OBJECT-TYPE NOTIFICATION-TYPE
enterprises Unsigned32 TEXTUAL-CONVENTION
RowStatus TruthValue MacAddress
InetAddress InetAddressType

Defined Types

DisplayString  
OCTET STRING    

ContactState  
Represents the state of a set of contacts.
TEXTUAL-CONVENTION    
  INTEGER open(1), closed(2)  

InputContactState  
Represents the state of a set of input contacts.
TEXTUAL-CONVENTION    
  INTEGER open(1), closed(2), armed(3), triggered(4)  

RelayState  
Represents the energised state of a relay.
TEXTUAL-CONVENTION    
  INTEGER on(1), off(2)  

OutputControlState  
Represents the control setiing for an output.
TEXTUAL-CONVENTION    
  INTEGER activate(1), deactivate(2), logic(3)  

EnableState  
Represents the state of an enabling flag.
TEXTUAL-CONVENTION    
  INTEGER enabled(1), disabled(2)  

InputDataType  
Represents the type of data read at an input.
TEXTUAL-CONVENTION    
  INTEGER autodetect(1), temperature(2), humidity(3), analogue(4), contact(5), inactive(255)  

IpTHAEntry  
SEQUENCE    
  ipTHAChan INTEGER
  ipTHARS RowStatus
  ipTHAName DisplayString
  ipTHALocn DisplayString
  ipTHAAutoDetect TruthValue
  ipTHAType InputDataType
  ipTHAValue INTEGER
  ipTHAScaling INTEGER
  ipTHAOffset INTEGER
  ipTHAHysteresis INTEGER

IpTHAThreshEntry  
SEQUENCE    
  ipTHAThreshChan INTEGER
  ipTHAThreshRS RowStatus
  ipTHAUCL INTEGER
  ipTHAUWL INTEGER
  ipTHALWL INTEGER
  ipTHALCL INTEGER

IpTHATrapEnEntry  
SEQUENCE    
  ipTHATrapEnChan INTEGER
  ipTHATrapEnRS RowStatus
  ipTHAUCLTrapEn TruthValue
  ipTHAUWLTrapEn TruthValue
  ipTHALWLTrapEn TruthValue
  ipTHALCLTrapEn TruthValue

IpTHATrapPerEntry  
SEQUENCE    
  ipTHATrapPerChan INTEGER
  ipTHATrapPerRS RowStatus
  ipTHATrapUCLPer INTEGER
  ipTHATrapUWLPer INTEGER
  ipTHATrapLWLPer INTEGER
  ipTHATrapLCLPer INTEGER

IpContEntry  
SEQUENCE    
  ipContChan INTEGER
  ipContRS RowStatus
  ipContName DisplayString
  ipContLocn DisplayString
  ipContAutoDetect TruthValue
  ipContNormState ContactState
  ipContCurrState InputContactState
  ipContTrigMode INTEGER
  ipContReset Unsigned32
  ipContTrapEn INTEGER
  ipContTrapPeriod INTEGER

OpEntry  
SEQUENCE    
  opChan INTEGER
  opRS RowStatus
  opName DisplayString
  opLocn DisplayString
  opNormState RelayState
  opCurrState RelayState
  opOnDelTime Unsigned32
  opOffDelTime Unsigned32
  opBooleanEqn DisplayString
  opTrapEn INTEGER
  opTrapPeriod INTEGER
  opControlState OutputControlState

KpCtlEntry  
SEQUENCE    
  kpNumber INTEGER
  kpRS RowStatus
  kpManufacturer DisplayString
  kpName DisplayString
  kpDoorLatchTimeOut Unsigned32
  kpRtnToStndbyTimeOut INTEGER
  kpEntryCodeValid TruthValue
  kpDoorOpenTimeOut INTEGER
  kpRemoteDoorOpen TruthValue
  kpInUseTrapEn INTEGER

AcuCtlEntry  
SEQUENCE    
  acuNumber INTEGER
  acuCtlRS RowStatus
  acuManufacturer DisplayString
  acuName DisplayString
  acuDoorLatchTimeOut Unsigned32
  acuRtnToStndbyTimeOut INTEGER
  acuEntryCodeValid TruthValue
  acuDoorOpenTimeOut INTEGER
  acuRemoteDoorOpen TruthValue
  acuInUseTrapEn INTEGER

AccUserEntry  
SEQUENCE    
  accUserNumber INTEGER
  accUserRS RowStatus
  accUserName DisplayString
  accUserCode OCTET STRING
  accUserPrivileges DisplayString
  accUserExpires DisplayString

PduEntry  
SEQUENCE    
  pduNumber INTEGER
  pduRS RowStatus
  pduName DisplayString
  pduOutEn TruthValue
  pduMonEn TruthValue
  pduCommsFail INTEGER

PduOutCmnEntry  
SEQUENCE    
  pduOutCmnPduNumber INTEGER
  pduOutCmnRS RowStatus
  pduNumOfOutlets INTEGER
  pduOutCycle INTEGER
  pduOutCyclePwd DisplayString
  pduOutCycleAbortTask Unsigned32
  pduOutCycleAbortTime Unsigned32

PduOutEntry  
SEQUENCE    
  pduOutPduNumber INTEGER
  pduOutNumber INTEGER
  pduOutRS RowStatus
  pduOutName DisplayString
  pduOutOn INTEGER
  pduOutPwd DisplayString
  pduOutCycleDelay Unsigned32
  pduOutRebootPeriod Unsigned32

PduMonEntry  
SEQUENCE    
  pduMonPduNumber INTEGER
  pduMonRS RowStatus
  pduRMSVoltsValue INTEGER
  pduRMSAmpsValue INTEGER
  pduTotalEnergyValue INTEGER
  pduMeanKVAValue INTEGER
  pduMeanKWattsValue INTEGER
  pduPwrFactorValue INTEGER

PduTrapThreshEntry  
SEQUENCE    
  pduTrapThreshPduNumber INTEGER
  pduTrapThreshRS RowStatus
  pduRMSVoltsUCL INTEGER
  pduRMSVoltsUWL INTEGER
  pduRMSVoltsLWL INTEGER
  pduRMSVoltsLCL INTEGER
  pduRMSAmpsUCL INTEGER
  pduRMSAmpsUWL INTEGER
  pduRMSAmpsLWL INTEGER
  pduRMSAmpsLCL INTEGER
  pduEnergyUCL INTEGER
  pduEnergyUWL INTEGER
  pduMeanKVAUCL INTEGER
  pduMeanKVAUWL INTEGER
  pduMeanKVALWL INTEGER
  pduMeanKVALCL INTEGER
  pduMeanKWattsUCL INTEGER
  pduMeanKWattsUWL INTEGER
  pduMeanKWattsLWL INTEGER
  pduMeanKWattsLCL INTEGER
  pduPwrFactorUCL INTEGER
  pduPwrFactorUWL INTEGER
  pduPwrFactorLWL INTEGER
  pduPwrFactorLCL INTEGER

PduTrapEnEntry  
SEQUENCE    
  pduTrapEnPduNumber INTEGER
  pduTrapEnRS RowStatus
  pduRMSVoltsUCLTrapEn TruthValue
  pduRMSVoltsUWLTrapEn TruthValue
  pduRMSVoltsLWLTrapEn TruthValue
  pduRMSVoltsLCLTrapEn TruthValue
  pduRMSAmpsUCLTrapEn TruthValue
  pduRMSAmpsUWLTrapEn TruthValue
  pduRMSAmpsLWLTrapEn TruthValue
  pduRMSAmpsLCLTrapEn TruthValue
  pduEnergyUCLTrapEn TruthValue
  pduEnergyUWLTrapEn TruthValue
  pduMeanKVAUCLTrapEn TruthValue
  pduMeanKVAUWLTrapEn TruthValue
  pduMeanKVALWLTrapEn TruthValue
  pduMeanKVALCLTrapEn TruthValue
  pduMeanKWattsUCLTrapEn TruthValue
  pduMeanKWattsUWLTrapEn TruthValue
  pduMeanKWattsLWLTrapEn TruthValue
  pduMeanKWattsLCLTrapEn TruthValue
  pduPwrFactorUCLTrapEn TruthValue
  pduPwrFactorUWLTrapEn TruthValue
  pduPwrFactorLWLTrapEn TruthValue
  pduPwrFactorLCLTrapEn TruthValue

PduTrapPerEntry  
SEQUENCE    
  pduTrapPduNumber INTEGER
  pduTrapPerRS RowStatus
  pduRMSVoltsUCLTrapPer INTEGER
  pduRMSVoltsUWLTrapPer INTEGER
  pduRMSVoltsLWLTrapPer INTEGER
  pduRMSVoltsLCLTrapPer INTEGER
  pduRMSAmpsUCLTrapPer INTEGER
  pduRMSAmpsUWLTrapPer INTEGER
  pduRMSAmpsLWLTrapPer INTEGER
  pduRMSAmpsLCLTrapPer INTEGER
  pduEnergyUCLTrapPer INTEGER
  pduEnergyUWLTrapPer INTEGER
  pduMeanKVAUCLTrapPer INTEGER
  pduMeanKVAUWLTrapPer INTEGER
  pduMeanKVALWLTrapPer INTEGER
  pduMeanKVALCLTrapPer INTEGER
  pduMeanKWattsUCLTrapPer INTEGER
  pduMeanKWattsUWLTrapPer INTEGER
  pduMeanKWattsLWLTrapPer INTEGER
  pduMeanKWattsLCLTrapPer INTEGER
  pduPwrFactorUCLTrapPer INTEGER
  pduPwrFactorUWLTrapPer INTEGER
  pduPwrFactorLWLTrapPer INTEGER
  pduPwrFactorLCLTrapPer INTEGER

Defined Values

hawki2MIB 1.3.6.1.4.1.3711.24
The MIB module for the Sinetica Hawk-i2.
MODULE-IDENTITY    

sinetica 1.3.6.1.4.1.3711
OBJECT IDENTIFIER    

v1 1.3.6.1.4.1.3711.24.1
OBJECT IDENTIFIER    

objects 1.3.6.1.4.1.3711.24.1.1
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.3711.24.0
OBJECT IDENTIFIER    

inputs 1.3.6.1.4.1.3711.24.1.1.1
OBJECT IDENTIFIER    

outputs 1.3.6.1.4.1.3711.24.1.1.2
OBJECT IDENTIFIER    

keypads 1.3.6.1.4.1.3711.24.1.1.4
OBJECT IDENTIFIER    

acus 1.3.6.1.4.1.3711.24.1.1.5
OBJECT IDENTIFIER    

access 1.3.6.1.4.1.3711.24.1.1.6
OBJECT IDENTIFIER    

pdus 1.3.6.1.4.1.3711.24.1.1.7
OBJECT IDENTIFIER    

inventory 1.3.6.1.4.1.3711.24.1.1.99
OBJECT IDENTIFIER    

trapInfo 1.3.6.1.4.1.3711.24.1.1.100
OBJECT IDENTIFIER    

ipCommon 1.3.6.1.4.1.3711.24.1.1.1.1
OBJECT IDENTIFIER    

ipTHA 1.3.6.1.4.1.3711.24.1.1.1.2
OBJECT IDENTIFIER    

ipContact 1.3.6.1.4.1.3711.24.1.1.1.3
OBJECT IDENTIFIER    

ipEnable 1.3.6.1.4.1.3711.24.1.1.1.1.1
OBJECT IDENTIFIER    

ipSelect 1.3.6.1.4.1.3711.24.1.1.1.1.1.1
Selects the channel to be enabled or disabled by ipInsert. A value of 0 selects no channel.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..24  

ipInsert 1.3.6.1.4.1.3711.24.1.1.1.1.1.2
Inserts or removes the channel selected by ipSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  InputDataType  

ipTempScaleFlag 1.3.6.1.4.1.3711.24.1.1.1.2.1
Temperature scale (Celsius/Fahrenheit) for temperature monitoring.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2), kelvin(3)  

ipTHATable 1.3.6.1.4.1.3711.24.1.1.1.2.2
A table giving data for all enabled inputs with analogue-type monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IpTHAEntry

ipTHAEntry 1.3.6.1.4.1.3711.24.1.1.1.2.2.1
A conceptual row containing information about one analogue-type input.
Status: current Access: not-accessible
OBJECT-TYPE    
  IpTHAEntry  

ipTHAChan 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1
The input number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

ipTHARS 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2
The analogue-type input table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

ipTHAName 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3
The name of this input
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

ipTHALocn 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4
A system-defined name for the physical location of this input, e.g. MCU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..4)  

ipTHAAutoDetect 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5
Indicates that the type of data this input is monitoring is selected automatically.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipTHAType 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6
Indicates the type of data this input is monitoring.
Status: current Access: read-write
OBJECT-TYPE    
  InputDataType  

ipTHAValue 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7
The current reading in the relevant measurement units.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER -200..1000  

ipTHAScaling 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8
Scaling factor for ipTHAValue when ipTHAType=analogue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

ipTHAOffset 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9
Calibration offset in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

ipTHAHysteresis 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10
Hysteresis on threshold levels in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

ipTHATrapsCfg 1.3.6.1.4.1.3711.24.1.1.1.2.3
OBJECT IDENTIFIER    

ipTHAThreshTable 1.3.6.1.4.1.3711.24.1.1.1.2.3.1
A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IpTHAThreshEntry

ipTHAThreshEntry 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1
A conceptual row containing threshold information for one analogue-type input.
Status: current Access: not-accessible
OBJECT-TYPE    
  IpTHAThreshEntry  

ipTHAThreshChan 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1
The input number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

ipTHAThreshRS 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2
The analogue-type input table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

ipTHAUCL 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3
The Upper Critical Limit for this input in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

ipTHAUWL 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4
The Upper Warning Limit for this input in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

ipTHALWL 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5
The Lower Warning Limit for this input in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

ipTHALCL 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6
The Lower Critical Limit for this input in the same units as for ipTHAValue.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

ipTHATrapEnTable 1.3.6.1.4.1.3711.24.1.1.1.2.3.2
The table that controls trap enabling for all enabled inputs with analogue-type monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IpTHATrapEnEntry

ipTHATrapEnEntry 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1
A conceptual row containing trap enabling information for one analogue-type input.
Status: current Access: not-accessible
OBJECT-TYPE    
  IpTHATrapEnEntry  

ipTHATrapEnChan 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1
The input number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

ipTHATrapEnRS 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2
The analogue-type input table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

ipTHAUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3
Enables and disables input UCL alarm traps.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipTHAUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4
Enables and disables input UWL alarm traps.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipTHALWLTrapEn 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5
Enables and disables input LWL alarm traps.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipTHALCLTrapEn 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6
Enables and disables input LCL alarm traps.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipTHATrapPerTable 1.3.6.1.4.1.3711.24.1.1.1.2.3.3
The table that controls trap repetition for all enabled inputs with analogue-type monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IpTHATrapPerEntry

ipTHATrapPerEntry 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1
A conceptual row containing trap repetition information for one analogue-type input.
Status: current Access: not-accessible
OBJECT-TYPE    
  IpTHATrapPerEntry  

ipTHATrapPerChan 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1
The input number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

ipTHATrapPerRS 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2
The table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

ipTHATrapUCLPer 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

ipTHATrapUWLPer 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

ipTHATrapLWLPer 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

ipTHATrapLCLPer 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

ipContTable 1.3.6.1.4.1.3711.24.1.1.1.3.1
A table listing the parameters and data for all enabled inputs with contact-type monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    IpContEntry

ipContEntry 1.3.6.1.4.1.3711.24.1.1.1.3.1.1
A conceptual row containing information about one contact input.
Status: current Access: not-accessible
OBJECT-TYPE    
  IpContEntry  

ipContChan 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1
The input number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

ipContRS 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2
The contact input table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

ipContName 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3
The name of this input
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

ipContLocn 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4
A system-defined name for the physical location of this input, e.g. MCU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..4)  

ipContAutoDetect 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5
Indicates that the type of data this input is monitoring is selected automatically.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

ipContNormState 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6
The normal state for this contact.
Status: current Access: read-write
OBJECT-TYPE    
  ContactState  

ipContCurrState 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7
The current state of this contact.
Status: current Access: read-only
OBJECT-TYPE    
  InputContactState  

ipContTrigMode 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8
The contact trigger mode, level, +ve edge, -ve edge.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER positiveEdge(1), negativeEdge(2), level(3)  

ipContReset 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9
Resets the contact after triggering in edge mode.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

ipContTrapEn 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10
Configure contact input traps.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), warning(2), information(3), disabled(255)  

ipContTrapPeriod 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

opEnable 1.3.6.1.4.1.3711.24.1.1.2.1
OBJECT IDENTIFIER    

opSelect 1.3.6.1.4.1.3711.24.1.1.2.1.1
Selects the channel to be enabled or disabled by opEnable. A value of 0 selects no channel.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..24  

opInsert 1.3.6.1.4.1.3711.24.1.1.2.1.2
Enables or disables the channel selected by opSelect - causes an entry for that channel to be created or deleted in the relevant tables. - Read behaviour is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  EnableState  

opTable 1.3.6.1.4.1.3711.24.1.1.2.2
A table listing the parameters and data for all outputs that are enabled and available (i.e. its extension unit is connected).
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OpEntry

opEntry 1.3.6.1.4.1.3711.24.1.1.2.2.1
A conceptual row containing information about one output.
Status: current Access: not-accessible
OBJECT-TYPE    
  OpEntry  

opChan 1.3.6.1.4.1.3711.24.1.1.2.2.1.1
The output number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..18  

opRS 1.3.6.1.4.1.3711.24.1.1.2.2.1.2
The contact input table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

opName 1.3.6.1.4.1.3711.24.1.1.2.2.1.3
A user-defined name for this output.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

opLocn 1.3.6.1.4.1.3711.24.1.1.2.2.1.4
A system-defined name for the physical location of this output, e.g. MCU.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..4)  

opNormState 1.3.6.1.4.1.3711.24.1.1.2.2.1.5
Sets or reads the required normal state of this output.
Status: current Access: read-write
OBJECT-TYPE    
  RelayState  

opCurrState 1.3.6.1.4.1.3711.24.1.1.2.2.1.6
Reads the current state of this output.
Status: current Access: read-only
OBJECT-TYPE    
  RelayState  

opOnDelTime 1.3.6.1.4.1.3711.24.1.1.2.2.1.7
Sets the 'on' delay time for this output.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

opOffDelTime 1.3.6.1.4.1.3711.24.1.1.2.2.1.8
Sets the 'off' delay time for this output.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

opBooleanEqn 1.3.6.1.4.1.3711.24.1.1.2.2.1.9
Boolean equation string
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

opTrapEn 1.3.6.1.4.1.3711.24.1.1.2.2.1.10
Configure output traps.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), warning(2), information(3), disabled(255)  

opTrapPeriod 1.3.6.1.4.1.3711.24.1.1.2.2.1.11
Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

opControlState 1.3.6.1.4.1.3711.24.1.1.2.2.1.12
Reads the current control state of an output.
Status: current Access: read-write
OBJECT-TYPE    
  OutputControlState  

kpEnable 1.3.6.1.4.1.3711.24.1.1.4.1
OBJECT IDENTIFIER    

kpSelect 1.3.6.1.4.1.3711.24.1.1.4.1.1
Selects the keypad to be enabled or disabled by kpEnable. A value of 0 selects no keypad.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..24  

kpInsert 1.3.6.1.4.1.3711.24.1.1.4.1.2
Enables or disables the keypad selected by kpSelect - causes an entry for that keypad to be created or deleted in the relevant tables. - Read behaviour is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  EnableState  

kpCtlTable 1.3.6.1.4.1.3711.24.1.1.4.2
A table listing the parameters and data for the keypads.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    KpCtlEntry

kpCtlEntry 1.3.6.1.4.1.3711.24.1.1.4.2.1
A conceptual row containing information about one keypad.
Status: current Access: not-accessible
OBJECT-TYPE    
  KpCtlEntry  

kpNumber 1.3.6.1.4.1.3711.24.1.1.4.2.1.1
The keypad number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..2  

kpRS 1.3.6.1.4.1.3711.24.1.1.4.2.1.2
The keypad table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

kpManufacturer 1.3.6.1.4.1.3711.24.1.1.4.2.1.3
The name of the manufacturer of the keypad.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

kpName 1.3.6.1.4.1.3711.24.1.1.4.2.1.4
A name identifying the keypad.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

kpDoorLatchTimeOut 1.3.6.1.4.1.3711.24.1.1.4.2.1.5
Time-out value in seconds for which the door latch is held open.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

kpRtnToStndbyTimeOut 1.3.6.1.4.1.3711.24.1.1.4.2.1.6
Time-out value in seconds for Return to Standby Mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..99  

kpEntryCodeValid 1.3.6.1.4.1.3711.24.1.1.4.2.1.7
Set if previous keypad entry was valid.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

kpDoorOpenTimeOut 1.3.6.1.4.1.3711.24.1.1.4.2.1.8
Time-out value in seconds for Door Open.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..99  

kpRemoteDoorOpen 1.3.6.1.4.1.3711.24.1.1.4.2.1.9
Set to open the door.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

kpInUseTrapEn 1.3.6.1.4.1.3711.24.1.1.4.2.1.10
'keypad in use' trap enable
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), warning(2), information(3), disabled(255)  

acuEnable 1.3.6.1.4.1.3711.24.1.1.5.1
OBJECT IDENTIFIER    

acuSelect 1.3.6.1.4.1.3711.24.1.1.5.1.1
Selects the ACU to be enabled or disabled by acuEnable. A value of 0 selects no ACU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..24  

acuInsert 1.3.6.1.4.1.3711.24.1.1.5.1.2
Enables or disables the ACU selected by acuSelect - causes an entry for that ACU to be created or deleted in the relevant tables. - Read behaviour is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  EnableState  

acuCtlTable 1.3.6.1.4.1.3711.24.1.1.5.2
A table listing the parameters and data for the ACUs.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AcuCtlEntry

acuCtlEntry 1.3.6.1.4.1.3711.24.1.1.5.2.1
A conceptual row containing information about one ACU.
Status: current Access: not-accessible
OBJECT-TYPE    
  AcuCtlEntry  

acuNumber 1.3.6.1.4.1.3711.24.1.1.5.2.1.1
The ACU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..6  

acuCtlRS 1.3.6.1.4.1.3711.24.1.1.5.2.1.2
The ACU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

acuManufacturer 1.3.6.1.4.1.3711.24.1.1.5.2.1.3
The name of the manufacturer of the ACU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

acuName 1.3.6.1.4.1.3711.24.1.1.5.2.1.4
A name identifying the ACU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

acuDoorLatchTimeOut 1.3.6.1.4.1.3711.24.1.1.5.2.1.5
Time-out value in seconds for which the door latch is held open.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

acuRtnToStndbyTimeOut 1.3.6.1.4.1.3711.24.1.1.5.2.1.6
Time-out value in seconds for Return to Standby Mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..99  

acuEntryCodeValid 1.3.6.1.4.1.3711.24.1.1.5.2.1.7
Set if previous ACU entry was valid.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

acuDoorOpenTimeOut 1.3.6.1.4.1.3711.24.1.1.5.2.1.8
Time-out value in seconds for Door Open.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..99  

acuRemoteDoorOpen 1.3.6.1.4.1.3711.24.1.1.5.2.1.9
Set to open the door.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

acuInUseTrapEn 1.3.6.1.4.1.3711.24.1.1.5.2.1.10
'ACU in use' trap enable
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER critical(1), warning(2), information(3), disabled(255)  

accUserCtl 1.3.6.1.4.1.3711.24.1.1.6.1
OBJECT IDENTIFIER    

accUserInstance 1.3.6.1.4.1.3711.24.1.1.6.1.1
A value of 0 causes an access user to be created in the relevant tables. A non-zero value causes the nominated access user table entries to be deleted.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

accUserTable 1.3.6.1.4.1.3711.24.1.1.6.1.2
A table controlling the access users.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AccUserEntry

accUserEntry 1.3.6.1.4.1.3711.24.1.1.6.1.2.1
A conceptual row containing information about one ACU user.
Status: current Access: not-accessible
OBJECT-TYPE    
  AccUserEntry  

accUserNumber 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1
The the access user-table entry number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..20  

accUserRS 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2
The access user table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

accUserName 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3
A name identifying the access user.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

accUserCode 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4
The user's access code.
Status: current Access: read-write
OBJECT-TYPE    
  OCTET STRING Size(0..15)  

accUserPrivileges 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5
The ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..11)  

accUserExpires 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6
A text string which specifies when the access code in the row expires. The format is defined by the application.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString  

accUserSetup 1.3.6.1.4.1.3711.24.1.1.6.1.3
A free form octet string for programming accUserTable. The format is defined by the application.
Status: current Access: read-write
OBJECT-TYPE    
  OCTET STRING  

pduCommon 1.3.6.1.4.1.3711.24.1.1.7.1
OBJECT IDENTIFIER    

pduOutlets 1.3.6.1.4.1.3711.24.1.1.7.2
OBJECT IDENTIFIER    

pduMonitor 1.3.6.1.4.1.3711.24.1.1.7.3
OBJECT IDENTIFIER    

pdusEnable 1.3.6.1.4.1.3711.24.1.1.7.1.1
OBJECT IDENTIFIER    

pduSelect 1.3.6.1.4.1.3711.24.1.1.7.1.1.1
Selects the PDU to be enabled or disabled by pduEnable. A value of 0 selects no PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..6  

pduInsert 1.3.6.1.4.1.3711.24.1.1.7.1.1.2
Enables or disables the PDU selected by pduSelect - causes an entry for that PDU to be created or deleted in the relevant tables. - Read behaviour is undefined.
Status: current Access: read-write
OBJECT-TYPE    
  EnableState  

pduTable 1.3.6.1.4.1.3711.24.1.1.7.1.2
A table containing information about each enabled PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduEntry

pduEntry 1.3.6.1.4.1.3711.24.1.1.7.1.2.1
A conceptual row containing information about one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduEntry  

pduNumber 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduRS 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduName 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3
A string identifying the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

pduOutEn 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4
Enables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMonEn 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5
Enables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduCommsFail 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6
Indicates comms. status for the PDU.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER commsGood(1), commsFailed(2), commsBadData(3)  

pduOutAll 1.3.6.1.4.1.3711.24.1.1.7.2.1
OBJECT IDENTIFIER    

pduOutCycleAll 1.3.6.1.4.1.3711.24.1.1.7.2.1.1
Sets the required state of all power outlets on all connected PDUs.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER up(1), down(2)  

pduOutCycleAllPwd 1.3.6.1.4.1.3711.24.1.1.7.2.1.2
Controls access to setting the required state of all power outlets on all connected PDUs.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..7)  

pduOutCycleAllAbort 1.3.6.1.4.1.3711.24.1.1.7.2.1.3
Abort command for pduOutCycleAll.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutGlobalCycleDelay 1.3.6.1.4.1.3711.24.1.1.7.2.1.4
Sets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutGlobalRebootTime 1.3.6.1.4.1.3711.24.1.1.7.2.1.5
Sets the off to on delay period for a pdu outlet reboot.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutGlobalCycleAbortTime 1.3.6.1.4.1.3711.24.1.1.7.2.1.6
Time delay to abort power outlet setting task.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutCmnTable 1.3.6.1.4.1.3711.24.1.1.7.2.2
A table containing information about the power outlets of all PDUs enabled for outlet control.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutCmnEntry

pduOutCmnEntry 1.3.6.1.4.1.3711.24.1.1.7.2.2.1
A conceptual row containing information about the power outlets of one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutCmnEntry  

pduOutCmnPduNumber 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduOutCmnRS 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduNumOfOutlets 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3
The number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..32  

pduOutCycle 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4
Sets the required state of all power outlets on the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER up(1), down(2)  

pduOutCyclePwd 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5
Password controling access to setting the required state of all power outlets on the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..7)  

pduOutCycleAbortTask 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6
Abort power outlet setting task.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutCycleAbortTime 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7
Time delay to abort power outlet setting task.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

pduOutTable 1.3.6.1.4.1.3711.24.1.1.7.2.3
A table listing the states and descriptions for each outlet on the PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutEntry

pduOutEntry 1.3.6.1.4.1.3711.24.1.1.7.2.3.1
A row containing information about one PDU outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduOutEntry  

pduOutPduNumber 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1
The PDU number on which the outlet resides.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduOutNumber 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2
The outlet number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..32  

pduOutRS 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduOutName 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4
A name identifying the outlet.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

pduOutOn 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5
The current state for this outlet.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2), reboot(3)  

pduOutPwd 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6
The password for this outlet.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..7)  

pduOutCycleDelay 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7
The on/off delay for this outlet in seconds.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduOutRebootPeriod 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8
The pduOutOn reboot off period for this outlet in seconds.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduMonTable 1.3.6.1.4.1.3711.24.1.1.7.3.1
A table containing monitor information for all PDUs enabled for monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduMonEntry

pduMonEntry 1.3.6.1.4.1.3711.24.1.1.7.3.1.1
A conceptual row containing monitor information for one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduMonEntry  

pduMonPduNumber 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduMonRS 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduRMSVoltsValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3
RMS Volts value in volts
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSAmpsValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4
RMS current value in 0.1 Amps
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..500  

pduTotalEnergyValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5
Total energy value in 0.1 kWh
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9999999  

pduMeanKVAValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6
Kilo Volt-Amperes value in 0.1 kVA
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKWattsValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7
Kilo Watts value in 0.1 kW
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100000  

pduPwrFactorValue 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8
Power factor value in 0.01
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

pduTrapThreshTable 1.3.6.1.4.1.3711.24.1.1.7.3.2
A table containing information about the trap threshold values for all PDUs enabled for monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduTrapThreshEntry

pduTrapThreshEntry 1.3.6.1.4.1.3711.24.1.1.7.3.2.1
A conceptual row containing information about the trap threshold values for one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduTrapThreshEntry  

pduTrapThreshPduNumber 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduTrapThreshRS 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduRMSVoltsUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3
rms UCL value in volts
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSVoltsUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4
rms UWL value in volts
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSVoltsLWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5
rms LWL value in volts
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSVoltsLCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6
rms LCL value in volts
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSAmpsUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7
rms UCL value in 0.1 amps
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSAmpsUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8
rms UWL value in 0.1 amps
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSAmpsLWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9
rms LWL value in 0.1 amps
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduRMSAmpsLCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10
rms LCL value in 0.1 amps
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..500  

pduEnergyUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11
Total energy UCL value in 0.1 kWh
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..9999999  

pduEnergyUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12
Total energy UWL value in 0.1 kWh
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..9999999  

pduMeanKVAUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13
Mean kVA UCL value in 0.1 kVA
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKVAUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14
Mean kVA UWL value in 0.1 kVA
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKVALWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15
Mean kVA LWL value in 0.1 kVA
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKVALCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16
Mean kVA LCL value in 0.1 kVA
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKWattsUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17
Mean power UCL value in 0.1 kW
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKWattsUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18
Mean power UWL value in 0.1 kW
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKWattsLWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19
Mean power LWL value in 0.1 kW
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduMeanKWattsLCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20
Mean power LCL value in 0.1 kW
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100000  

pduPwrFactorUCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21
Power factor UCL value in 0.01
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

pduPwrFactorUWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22
Power factor UWL value in 0.01
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

pduPwrFactorLWL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.23
Power factor LWL value in 0.01
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

pduPwrFactorLCL 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.24
Power factor LCL value in 0.01
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

pduTrapEnTable 1.3.6.1.4.1.3711.24.1.1.7.3.3
The table which controls threshold value trap enabling for all PDUs enabled for monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduTrapEnEntry

pduTrapEnEntry 1.3.6.1.4.1.3711.24.1.1.7.3.3.1
A conceptual row containing information about one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduTrapEnEntry  

pduTrapEnPduNumber 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduTrapEnRS 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduRMSVoltsUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3
Enables Volts UCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSVoltsUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4
Enables UWL Volts trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSVoltsLWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5
Enables LWL Volts trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSVoltsLCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6
Enables LCL Volts trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSAmpsUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7
Enables UCL current trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSAmpsUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8
Enables UWL current trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSAmpsLWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9
Enables LWL current trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduRMSAmpsLCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10
Enables LCL current trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduEnergyUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11
Enables UCL total energy trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduEnergyUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12
Enables UWL total energy trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKVAUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13
Enables mean kVA UCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKVAUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14
Enables mean kVA UWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKVALWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15
Enables mean kVA LWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKVALCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16
Enables mean kVA LCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKWattsUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17
Enables mean power UCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKWattsUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18
Enables mean power UWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKWattsLWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19
Enables mean power LWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduMeanKWattsLCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20
Enables mean power LCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduPwrFactorUCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21
Enables power factor UCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduPwrFactorUWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22
Enables power factor UWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduPwrFactorLWLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.23
Enables power factor LWL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduPwrFactorLCLTrapEn 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.24
Enables power factor LCL trap.
Status: current Access: read-write
OBJECT-TYPE    
  TruthValue  

pduTrapPerTable 1.3.6.1.4.1.3711.24.1.1.7.3.4
The table which controls threshold value trap repetition for all PDUs enabled for monitoring.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    PduTrapPerEntry

pduTrapPerEntry 1.3.6.1.4.1.3711.24.1.1.7.3.4.1
A conceptual row containing information about one PDU.
Status: current Access: not-accessible
OBJECT-TYPE    
  PduTrapPerEntry  

pduTrapPduNumber 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1
The PDU number.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 1..8  

pduTrapPerRS 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2
The PDU table row status.
Status: current Access: read-only
OBJECT-TYPE    
  RowStatus  

pduRMSVoltsUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3
Sets UCL Volts trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSVoltsUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4
Sets UWL Volts trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSVoltsLWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5
Sets LWL Volts trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSVoltsLCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6
Sets LCL Volts trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSAmpsUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7
Sets UCL current trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSAmpsUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8
Sets UWL current trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSAmpsLWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9
Sets LWL current trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduRMSAmpsLCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10
Sets LCL current trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduEnergyUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11
Sets UCL total energy trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduEnergyUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12
Sets UWL total energy trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKVAUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13
Sets mean kVA UCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKVAUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14
Sets mean kVA UWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKVALWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15
Sets mean kVA LWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKVALCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16
Sets mean kVA LCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKWattsUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17
Sets mean power UCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKWattsUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18
Sets mean power UWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKWattsLWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19
Sets mean power LWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduMeanKWattsLCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20
Sets mean power LCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduPwrFactorUCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21
Sets power factor UCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduPwrFactorUWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22
Sets power factor UWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduPwrFactorLWLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.23
Sets power factor LWL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

pduPwrFactorLCLTrapPer 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.24
Sets power factor LCL trap repeat rate in seconds
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

invProdSignature 1.3.6.1.4.1.3711.24.1.1.99.1
Product data signature.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..7)  

invProdFormatVer 1.3.6.1.4.1.3711.24.1.1.99.2
Product data format version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..7)  

invManufCode 1.3.6.1.4.1.3711.24.1.1.99.3
Manufacturer code.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

invOrderNum 1.3.6.1.4.1.3711.24.1.1.99.4
Order number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..7)  

invBatchNum 1.3.6.1.4.1.3711.24.1.1.99.5
Batch number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..7)  

invProdTestTime 1.3.6.1.4.1.3711.24.1.1.99.6
Data and time of production test.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

invUnitName 1.3.6.1.4.1.3711.24.1.1.99.7
Unit name.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

invUnitPartNum 1.3.6.1.4.1.3711.24.1.1.99.8
Unit part number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

invHwRevision 1.3.6.1.4.1.3711.24.1.1.99.9
Hardware revision number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

invFwRevision 1.3.6.1.4.1.3711.24.1.1.99.10
Firmware revision number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

invSerialNum 1.3.6.1.4.1.3711.24.1.1.99.11
Serial number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

invDefaultIPAddrType 1.3.6.1.4.1.3711.24.1.1.99.12
The type of the IP addresses.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddressType  

invDefaultIPAddr 1.3.6.1.4.1.3711.24.1.1.99.13
Default unit IP address.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

invDefaultSubNetMask 1.3.6.1.4.1.3711.24.1.1.99.14
Default unit sub-network mask.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

invDefaultGWAddr 1.3.6.1.4.1.3711.24.1.1.99.15
Default unit default gateway address.
Status: current Access: read-only
OBJECT-TYPE    
  InetAddress  

invMacAddr 1.3.6.1.4.1.3711.24.1.1.99.16
Unit medium access control (MAC) address.
Status: current Access: read-only
OBJECT-TYPE    
  MacAddress  

invOk 1.3.6.1.4.1.3711.24.1.1.99.20
Confirms that the inventory record isn't corrupted.
Status: current Access: read-only
OBJECT-TYPE    
  TruthValue  

invInputCount 1.3.6.1.4.1.3711.24.1.1.99.50
The maximum number of inputs that can be connected to the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

invOutputCount 1.3.6.1.4.1.3711.24.1.1.99.51
The maximum number of outputs that can be connected to the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..24  

invKeypadCount 1.3.6.1.4.1.3711.24.1.1.99.52
The maximum number of keypads that can be connected to the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..2  

invAcuCount 1.3.6.1.4.1.3711.24.1.1.99.53
The maximum number of ACU's that can be connected to the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..6  

invAccessUserCount 1.3.6.1.4.1.3711.24.1.1.99.54
The maximum number of user entries on the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..20  

invPduCount 1.3.6.1.4.1.3711.24.1.1.99.55
The maximum number of PDU's that can be connected to the unit
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..6  

trapCode 1.3.6.1.4.1.3711.24.1.1.100.1
A decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this number is BBEEffCCT where BB is the number of the relevant MIB branch. EE indicates what type of event caused the notification. This value is dependent upon branch number and implementation. CC is the channel number which was the source of the notification. T discriminates the type of data, e.g. temperature. This value is dependent upon branch number and implementation. ff future use. Fields are packed with leading zeros and are set to zero if not relevant to a particular notification.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

trapDescription 1.3.6.1.4.1.3711.24.1.1.100.2
A string to be carried on notifications of types 1 to 4 identifying the event which caused it. The format of this string is as follows. Field 1 - type of notification, e.g. warning, critical, etc. Field 2 - data source, e.g. inputs. Generally this relates to a particular MIB branch. Field 3 - channel number, e.g. input 1. Field 4 - event, i.e. what caused the trap. Field 5 - value at which the event occured, e.g. 900, indicating 90% humidity. Field 6 - type of data, e.g. relative humidity Fields are omitted if not relevant to a particular notification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

alarmCritical 1.3.6.1.4.1.3711.24.0.1
Critical alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmWarning 1.3.6.1.4.1.3711.24.0.2
Warning alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmInformation 1.3.6.1.4.1.3711.24.0.3
Information alarm.
Status: current Access: read-only
NOTIFICATION-TYPE    

alarmCleared 1.3.6.1.4.1.3711.24.0.4
Alarm cleared.
Status: current Access: read-only
NOTIFICATION-TYPE