ICT-DISTRIBUTION-PANEL-MIB

File: ICT-DISTRIBUTION-PANEL-MIB.mib (7949 bytes)

Imported modules

RFC1155-SMI RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

enterprises IpAddress DisplayString
OBJECT-TYPE TRAP-TYPE

Defined Types

OutputEntry  
SEQUENCE    
  outputNumber INTEGER
  outputName DisplayString
  outputCurrent DisplayString
  outputFuseStatus INTEGER
  outputEnable INTEGER

AlarmEntry  
SEQUENCE    
  alarmNumber INTEGER
  alarmName DisplayString
  alarmStatus INTEGER

BusEntry  
SEQUENCE    
  busNumber INTEGER
  busName DisplayString
  busVoltage DisplayString
  busCurrent DisplayString

Defined Values

ictPower 1.3.6.1.4.1.39145
OBJECT IDENTIFIER    

distPanel 1.3.6.1.4.1.39145.10
OBJECT IDENTIFIER    

deviceModel 1.3.6.1.4.1.39145.10.1
Model Number
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

deviceName 1.3.6.1.4.1.39145.10.2
Site Name
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

deviceHardware 1.3.6.1.4.1.39145.10.3
Hardware Version
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..127  

deviceFirmware 1.3.6.1.4.1.39145.10.4
Firmware Version
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

deviceMacAddress 1.3.6.1.4.1.39145.10.5
MAC Address
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

systemVoltage 1.3.6.1.4.1.39145.10.6
System Voltage (Volts)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

systemCurrent 1.3.6.1.4.1.39145.10.7
System Current (Amps)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

outputTable 1.3.6.1.4.1.39145.10.8
Output Table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputEntry

outputEntry 1.3.6.1.4.1.39145.10.8.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  OutputEntry  

outputNumber 1.3.6.1.4.1.39145.10.8.1.1
Output Number
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..11  

outputName 1.3.6.1.4.1.39145.10.8.1.2
Output Label
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

outputCurrent 1.3.6.1.4.1.39145.10.8.1.3
Output Current (Amps)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

outputFuseStatus 1.3.6.1.4.1.39145.10.8.1.4
Output Fuse Status ('1' indicates Fuse is OK, and '2' indicates Fuse is OPEN)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), open(2)  

outputEnable 1.3.6.1.4.1.39145.10.8.1.5
Output Relay Enable ('1' indicates the Output is ENABLED, and '2' indicates the Output is DISABLED)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

alarmTable 1.3.6.1.4.1.39145.10.9
Alarm Input Table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    AlarmEntry

alarmEntry 1.3.6.1.4.1.39145.10.9.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  AlarmEntry  

alarmNumber 1.3.6.1.4.1.39145.10.9.1.1
Alarm Input Number
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..4  

alarmName 1.3.6.1.4.1.39145.10.9.1.2
Alarm Input Name
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

alarmStatus 1.3.6.1.4.1.39145.10.9.1.3
Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER inactive(1), ready(2), alarm(3)  

busTable 1.3.6.1.4.1.39145.10.10
Output Table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    OutputEntry

busEntry 1.3.6.1.4.1.39145.10.10.1
Tok_String
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  BusEntry  

busNumber 1.3.6.1.4.1.39145.10.10.1.1
Bus Number
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

busName 1.3.6.1.4.1.39145.10.10.1.2
Bus Name
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

busVoltage 1.3.6.1.4.1.39145.10.10.1.3
Bus Voltage (Volts)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

busCurrent 1.3.6.1.4.1.39145.10.10.1.4
Total Bus Current (Amps)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysUndervoltageAlarmTrap 101
Trap generated when a System/Bus Undervoltage Alarm is triggered
TRAP-TYPE    

sysOvervoltageAlarmTrap 102
Trap generated when a System/Bus Overvoltage Alarm is triggered
TRAP-TYPE    

sysOvercurrentAlarmTrap 103
Trap generated when a System/Bus Overcurrent Alarm is triggered
TRAP-TYPE    

fuseAlarmTrap 104
Trap generated when an Output Fuse Alarm is triggered
TRAP-TYPE    

undercurrentAlarmTrap 105
Trap generated when an Output Undercurrent Alarm is triggered
TRAP-TYPE    

overcurrentAlarmTrap 106
Trap generated when an Output Overcurrent Alarm is triggered
TRAP-TYPE    

loadshedTrap 107
Trap generated when Load-Shedding is activated on an Output
TRAP-TYPE    

alarmInputTrap 108
Trap generated when an Alarm Input is activated
TRAP-TYPE    

sysUndervoltageAlarmClear 111
Trap generated when a System/Bus Undervoltage Alarm is cleared
TRAP-TYPE    

sysOvervoltageAlarmClear 112
Trap generated when a System/Bus Overvoltage Alarm is cleared
TRAP-TYPE    

sysOvercurrentAlarmClear 113
Trap generated when a System/Bus Overcurrent Alarm is cleared
TRAP-TYPE    

fuseAlarmClear 114
Trap generated when an Output Fuse Alarm is cleared
TRAP-TYPE    

undercurrentAlarmClear 115
Trap generated when an Output Undercurrent Alarm is cleared
TRAP-TYPE    

overcurrentAlarmClear 116
Trap generated when an Output Overcurrent Alarm is cleared
TRAP-TYPE    

loadshedClear 117
Trap generated when an Output has recovered from a Load-Shedding condition
TRAP-TYPE    

alarmInputClear 118
Trap generated when an Alarm Input is cleared
TRAP-TYPE