LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
File:
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB.mib (160250 bytes)
Imported modules
Imported symbols
Defined Values
liebertGlobalProductsFlexibleConditionsModule |
1.3.6.1.4.1.476.1.42.1.11.1 |
The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2016 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification. |
MODULE-IDENTITY |
|
|
|
lgpCondId4132BypassOverloadPhaseA |
1.3.6.1.4.1.476.1.42.3.2.7.1.4132 |
An overload exists on output phase A while operating on the bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4133BypassOverloadPhaseB |
1.3.6.1.4.1.476.1.42.3.2.7.1.4133 |
An overload exists on output phase B while operating on the bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4134BypassOverloadPhaseC |
1.3.6.1.4.1.476.1.42.3.2.7.1.4134 |
An overload exists on output phase C while operating on the bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4135BypassNotAvailable |
1.3.6.1.4.1.476.1.42.3.2.7.1.4135 |
A problem associated with the bypass has been detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4138BypassAutoRetransferFailed |
1.3.6.1.4.1.476.1.42.3.2.7.1.4138 |
After performing a recoverable transfer to bypass, an attempt to
auto retransfer from bypass to inverter failed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4139BypassExcessAutoRetransfers |
1.3.6.1.4.1.476.1.42.3.2.7.1.4139 |
The number of auto retransfers, from bypass to inverter, has
exceeded the maximum for a specified time interval. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4140BypassRestartInhibitExternal |
1.3.6.1.4.1.476.1.42.3.2.7.1.4140 |
Restart of the bypass is inhibited by the state of an external
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4144BypassExcessivePulseParallel |
1.3.6.1.4.1.476.1.42.3.2.7.1.4144 |
The system has performed too many pulse parallel operations within
a specified time interval. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4162BatteryLow |
1.3.6.1.4.1.476.1.42.3.2.7.1.4162 |
The calculated battery time remaining has reached the low battery
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4163OutputOffEndofDischarge |
1.3.6.1.4.1.476.1.42.3.2.7.1.4163 |
Output turned off due to battery reaching end-of-discharge. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4167OutputOff |
1.3.6.1.4.1.476.1.42.3.2.7.1.4167 |
Output is off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4170BatteryEqualize |
1.3.6.1.4.1.476.1.42.3.2.7.1.4170 |
The rectifier output voltage is increased to equalize the battery
voltage level. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4173MainBatteryDisconnectOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.4173 |
Main battery disconnect is open. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4175BypassFrequencyError |
1.3.6.1.4.1.476.1.42.3.2.7.1.4175 |
The bypass frequency is outside the inverter synchronization
limits. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4200BatteryChargingInhibited |
1.3.6.1.4.1.476.1.42.3.2.7.1.4200 |
Battery charging is inhibited due to an external inhibit signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4213SystemShutdownEPO |
1.3.6.1.4.1.476.1.42.3.2.7.1.4213 |
System shutdown due to Emergency Power Off (EPO). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4214SystemShutdownREPO |
1.3.6.1.4.1.476.1.42.3.2.7.1.4214 |
System shutdown due to Remote Emergency Power Off (REPO). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4216BypassBackfeedDetected |
1.3.6.1.4.1.476.1.42.3.2.7.1.4216 |
The system detected a voltage on the bypass when none was expected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4217BypassManualXfrInhibited |
1.3.6.1.4.1.476.1.42.3.2.7.1.4217 |
Manual transfer from inverter to bypass is inhibited - bypass not
qualified. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4218BypassManualRexfrInhibited |
1.3.6.1.4.1.476.1.42.3.2.7.1.4218 |
Manual transfer from bypass to inverter is inhibited - inverter
output not qualified. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4219BatteryOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4219 |
A battery temperature sensor is reporting a value above a
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4222BatteryGroundFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.4222 |
Battery system ground fault amperage exceeds the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4229EmergencyPowerOffLatched |
1.3.6.1.4.1.476.1.42.3.2.7.1.4229 |
System output is off - 'Emergency Power Off (EPO) - latched'
requires manual reset. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4230SystemOutputLowPowerFactor |
1.3.6.1.4.1.476.1.42.3.2.7.1.4230 |
The system output power factor is low, resulting in reduced output
capacity. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4233InverterFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4233 |
Inverter failure - inverter output is off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4237InverterInhibitExternal |
1.3.6.1.4.1.476.1.42.3.2.7.1.4237 |
Restart of the inverter is inhibited by an external signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4289InverterTransferInhibitExt |
1.3.6.1.4.1.476.1.42.3.2.7.1.4289 |
Transfer of critical bus source to inverter is inhibited by an
external signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4295RectifierFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4295 |
Rectifier failure - rectifier is off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4296RectifierOperationInhibitExt |
1.3.6.1.4.1.476.1.42.3.2.7.1.4296 |
The operation of the rectifier is inhibited by an external signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4297UPSOutputonInverter |
1.3.6.1.4.1.476.1.42.3.2.7.1.4297 |
The output power is supplied by the inverter. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4298UPSOutputonBypass |
1.3.6.1.4.1.476.1.42.3.2.7.1.4298 |
The output power is supplied by the bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4299OutputLoadonMaintBypass |
1.3.6.1.4.1.476.1.42.3.2.7.1.4299 |
The output power is supplied by the maintenance bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4300InternalCommunicationsFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4300 |
The control has detected a communication failure of a component on
the internal communication bus. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4311SystemFanFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4311 |
System fan failure - one or more fans have failed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4315OnGenerator |
1.3.6.1.4.1.476.1.42.3.2.7.1.4315 |
A generator is supplying the power to the system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4325BackfeedBreakerOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.4325 |
The backfeed breaker is in the open position. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4360ReceptacleOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4360 |
The system has detected a receptacle over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4361ReceptacleUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4361 |
The system has detected a receptacle under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4389SystemOutputFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.4389 |
A fault has been detected in the system output. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4390InverterOffExternal |
1.3.6.1.4.1.476.1.42.3.2.7.1.4390 |
Inverter is off (operation is inhibited) due to external signal
state. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4391InverterStaticSwitchSCRShort |
1.3.6.1.4.1.476.1.42.3.2.7.1.4391 |
The system has detected a short across one or more inverter static
switch Silicon Controlled Rectifiers (SCR). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4392TemperatureSensorError |
1.3.6.1.4.1.476.1.42.3.2.7.1.4392 |
One or more temperature sensors cannot provide a valid temperature
reading (i.e. sensor failure, wiring failure, sense circuit
failure, etc). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4406BranchOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4406 |
The system has detected a module over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4407BranchUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4407 |
The system has detected a module under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4416BranchOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4416 |
The system has detected a module over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4417BranchUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4417 |
The system has detected a module under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4421BranchFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4421 |
One or more conditions indicate a Branch Receptacle Module failure
, service is required. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4436PDUOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4436 |
The system has detected a module over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4437PDUUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4437 |
The system has detected a module under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4438SystemInternalTemperatureRise |
1.3.6.1.4.1.476.1.42.3.2.7.1.4438 |
Excessive temperature rise internal to the system (i.e. difference
between the output versus input temperature is too large). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4440FuseFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4440 |
A summary event indicating one or more fuse failures. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4448PDUOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4448 |
The system has detected a module over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4449PDUUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4449 |
The system has detected a module under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4468PDUOverCurrentL1 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4468 |
The system has detected a module over current condition on line 1. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4469PDUOverCurrentL2 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4469 |
The system has detected a module over current condition on line 2. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4470PDUOverCurrentL3 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4470 |
The system has detected a module over current condition on line 3. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4471PDUUnderCurrentL1 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4471 |
The system has detected a module under current condition on line 1. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4472PDUUnderCurrentL2 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4472 |
The system has detected a module under current condition on line 2. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4473PDUUnderCurrentL3 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4473 |
The system has detected a module under current condition on line 3. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4494BranchBreakerOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.4494 |
The Branch Receptacle Module's input breaker is open. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4500PDUOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4500 |
The system has detected a power module over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4501PDUUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4501 |
The system has detected a power module under current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4502PDUFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.4502 |
One or more conditions indicate a power module failure, service is
required. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4503PDUCommunicationFail |
1.3.6.1.4.1.476.1.42.3.2.7.1.4503 |
Internal communications failure with the Power Module. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4504BranchRemoved |
1.3.6.1.4.1.476.1.42.3.2.7.1.4504 |
Branch Receptacle Module Removed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4505BranchDiscovered |
1.3.6.1.4.1.476.1.42.3.2.7.1.4505 |
Branch Receptacle Module Discovered. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4506BranchOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4506 |
The system has detected a Branch Receptacle Module over current
condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4507BranchCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4507 |
The system has detected a Branch Receptacle Module under current
condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4509ReceptacleLoadAdded |
1.3.6.1.4.1.476.1.42.3.2.7.1.4509 |
The receptacle's load started to draw power. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4524ModuleAdded |
1.3.6.1.4.1.476.1.42.3.2.7.1.4524 |
Module Added. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4550FirmwareUpdateRequired |
1.3.6.1.4.1.476.1.42.3.2.7.1.4550 |
Module compatibility error requires a system firmware update to
resolve. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4551GenericTestEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4551 |
A generic test event designed to evaluate system handling of
events. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4580OverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4580 |
An over temperature condition was detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4581UnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4581 |
An under temperature condition was detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4588OverRelativeHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.4588 |
An over relative humidity condition was detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4615ExtDewPointOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4615 |
At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
[Ext Dew Point Over Temp Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4618ExternalAirSensorAIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.4618 |
The external air sensor A is disconnected or the signal is out of
range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4621ExternalAirSensorBIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.4621 |
The external air sensor B is disconnected or the signal is out of
range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4626SupplyChilledWaterOverTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.4626 |
[Supply Fluid Temperature] has exceeded [High Supply Fluid
Temperature Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4634SupplyRefrigerantOverTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.4634 |
Event that is activated when [Supply Refrigerant Temperature]
exceeds [Supply Refrig Over Temp Threshold]. The event is
deactivated when the temperature drops below the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4637SupplyRefrigerantUnderTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.4637 |
[Supply Refrigerant Temperature] has dropped below a specified
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4645SupplyFluidOverTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.4645 |
[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4648SupplyFluidUnderTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.4648 |
[Supply Fluid Temperature] has dropped below a specified threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4651SupplyFluidTempSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.4651 |
The supply fluid temperature sensor is disconnected or the signal
is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4656Pump1LossofFlow |
1.3.6.1.4.1.476.1.42.3.2.7.1.4656 |
Loss of flow is detected in pump 1. The loss of flow condition
occurs when no differential pressure is detected across the pump. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4659Pump2LossofFlow |
1.3.6.1.4.1.476.1.42.3.2.7.1.4659 |
Loss of flow is detected in pump 2. The loss of flow condition
occurs when no differential pressure is detected across the pump. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4662PumpShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4662 |
Pumps have short cycled. A short cycle is defined as turning on
and off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4681Compressor1AShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4681 |
Compressor 1A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4684Compressor1BShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4684 |
Compressor 1B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4687Compressor2AShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4687 |
Compressor 2A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4690Compressor2BShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4690 |
Compressor 2B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4703ChilledWaterControlValvePosition |
1.3.6.1.4.1.476.1.42.3.2.7.1.4703 |
Chilled water valve out of position. Chilled water control valve
position does not match expected value. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4714ShutdownLossOfPower |
1.3.6.1.4.1.476.1.42.3.2.7.1.4714 |
System lost power. This event becomes active when the unit is
powered on following an unexpected loss of power. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4723WaterUnderFloor |
1.3.6.1.4.1.476.1.42.3.2.7.1.4723 |
Water under the floor is detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4729FanIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.4729 |
One or more fans are not operating within their operational
parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4741BatterySelfTest |
1.3.6.1.4.1.476.1.42.3.2.7.1.4741 |
Battery self test is in progress. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4742BatteryLowShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.4742 |
Battery disconnect due to end-of-discharge. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4747EquipmentTemperatureSensorFail |
1.3.6.1.4.1.476.1.42.3.2.7.1.4747 |
One or more temperature sensors report a temperature outside of
the range of expected operation. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4753MainControllerFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.4753 |
A Main Controller fault has been detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4757LBSActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.4757 |
The Load Bus Sync option is active. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4758LBSInhibited |
1.3.6.1.4.1.476.1.42.3.2.7.1.4758 |
The system has detected that conditions to perform Load Bus Sync
are not satisfied. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4759LeadingPowerFactor |
1.3.6.1.4.1.476.1.42.3.2.7.1.4759 |
The leading output Power Factor has fallen below a specified value. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4760ControlsResetRequired |
1.3.6.1.4.1.476.1.42.3.2.7.1.4760 |
A controls reset is required due to one or more critical settings
changing. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4824SystemCommFail |
1.3.6.1.4.1.476.1.42.3.2.7.1.4824 |
Failure of a device on the multi-module system communication bus. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4825LossofRedundancy |
1.3.6.1.4.1.476.1.42.3.2.7.1.4825 |
The multi-module collection doesn't have enough modules to satisfy
the redundancy configuration. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4826BPSSStartupInhibit |
1.3.6.1.4.1.476.1.42.3.2.7.1.4826 |
The Bypass Static Switch startup is inhibited. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4827MMSTransferInhibit |
1.3.6.1.4.1.476.1.42.3.2.7.1.4827 |
The critical load can not be manually transferred from inverter to
bypass. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4828MMSRetransferInhibit |
1.3.6.1.4.1.476.1.42.3.2.7.1.4828 |
The critical load can not be manually retransferred from bypass to
inverter. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4830MMSLossofSyncPulse |
1.3.6.1.4.1.476.1.42.3.2.7.1.4830 |
Multi-module system loss of sync pulse. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4831MMSOverload |
1.3.6.1.4.1.476.1.42.3.2.7.1.4831 |
Multi-module system overload. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4834MMSOnBattery |
1.3.6.1.4.1.476.1.42.3.2.7.1.4834 |
The multi-module system is on battery. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4906LowAmbientTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4906 |
The system has detected a low ambient temperature condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4907HighAmbientTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4907 |
The system has detected a high ambient temperature condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4908LowOverallVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4908 |
The system has detected a low battery string overall voltage
condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4909HighOverallVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4909 |
The system has detected a high battery string overall voltage
condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4910HighBatteryStringCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.4910 |
The system has detected a high battery string current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4916DischargeLowOverallVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4916 |
The system has detected a low battery string overall voltage
condition during a discharge. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4917DischargeLowCellVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4917 |
The system has detected a low cell voltage condition during a
discharge. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4964LowCellVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4964 |
The system has detected a low cell voltage condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4965HighCellVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.4965 |
The system has detected a high cell voltage condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4966LowCellTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4966 |
The system has detected a low cell temperature condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4967HighCellTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.4967 |
The system has detected a high cell temperature condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4968LowInternalResistance |
1.3.6.1.4.1.476.1.42.3.2.7.1.4968 |
The system has detected a low internal resistance condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4969HighInternalResistance |
1.3.6.1.4.1.476.1.42.3.2.7.1.4969 |
The system has detected a high internal resistance condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4970HighIntercellResistance |
1.3.6.1.4.1.476.1.42.3.2.7.1.4970 |
The system has detected a high intercell resistance condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4978IntertierResistanceHigh |
1.3.6.1.4.1.476.1.42.3.2.7.1.4978 |
The system has detected a high intertier resistance condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4983SupplyRefrigOverTempBand1 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4983 |
[Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 1]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4986SupplyRefrigUnderTempBand1 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4986 |
[Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 1]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4990SupplyRefrigOverTempBand2 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4990 |
[Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 2]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4993SupplyRefrigUnderTempBand2 |
1.3.6.1.4.1.476.1.42.3.2.7.1.4993 |
[Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 2]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4996Inverter1ShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4996 |
Inverter for pump 1 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a number of times over a
set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId4999Inverter2ShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.4999 |
Inverter for pump 2 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a number of times over a
set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5015SupplyAirOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5015 |
[Supply Air Temperature] has exceeded [High Supply Air Temperature
Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5019SupplyAirUnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5019 |
[Supply Air Temperature] has dropped below [Low Supply Air
Temperature Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5023ReturnAirOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5023 |
[Return Air Temperature] has exceeded [High Return Air Temperature
Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5026SupplyAirSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5026 |
The air sensor at the outlet of the unit is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5034HighReturnHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.5034 |
[Return Humidity] has exceeded [High Return Humidity Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5036LowReturnHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.5036 |
[Return Humidity] has dropped below [Low Return Humidity
Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5037HumidifierHoursExceeded |
1.3.6.1.4.1.476.1.42.3.2.7.1.5037 |
Operating hours for the humidifier have exceeded the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5039HumidifierUnderCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5039 |
The electrical current to the humidifier has dropped below its
lower threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5040HumidifierOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5040 |
The electrical current to the humidifier has exceeded its upper
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5041HumidifierLowWater |
1.3.6.1.4.1.476.1.42.3.2.7.1.5041 |
The water level in the humidifier has dropped below its threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5042HumidifierCylinderWorn |
1.3.6.1.4.1.476.1.42.3.2.7.1.5042 |
Humidifier cylinder is not operating properly and needs to be
replaced. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5043HumidifierIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5043 |
Humidifier issue detected, causing it to be locked out. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5044ExtHumidifierLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5044 |
The humidifier is shut down and disabled by an external input
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5046ReturnHumidityOutOfProportionalBand |
1.3.6.1.4.1.476.1.42.3.2.7.1.5046 |
[Return Humidity] has exceeded the upper limit of
[Dehumidification Proportional Band], or has dropped below the
lower limit of [Humidification Proportional Band] ], for an
extended period of time. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5053LossofAirFlow |
1.3.6.1.4.1.476.1.42.3.2.7.1.5053 |
No air flow through the unit due to failure of all fans. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5054FanHoursExceeded |
1.3.6.1.4.1.476.1.42.3.2.7.1.5054 |
Operating hours for the unit blower fan have exceeded the
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5055TopFanIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5055 |
The top fan is not operating within its normal parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5056BottomFanIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5056 |
The bottom fan is not operating within its normal parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5060RemoteSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5060 |
Remote sensor is disconnected or the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5067ExtCompressorLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5067 |
The compressor is shut down and disabled by an external input
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5068ReheaterOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5068 |
The temperature of the reheater has exceeded its threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5070ExtReheatLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5070 |
The reheater is shut down and disabled by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5071Condenser1Issue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5071 |
Condenser 1 is not operating within its normal parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5072CondenserVFDIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5072 |
The condenser fan Variable Frequency Drive is offline. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5073CondenserTVSSIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5073 |
The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5104ExtOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5104 |
A temperature has exceeded its threshold, as indicated by an
external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5105ExtLossofFlow |
1.3.6.1.4.1.476.1.42.3.2.7.1.5105 |
Loss of flow is detected, as indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5106ExtCondenserPumpHighWater |
1.3.6.1.4.1.476.1.42.3.2.7.1.5106 |
High water is detected in the condensate pump by the auxiliary
float, as indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5107ExtStandbyGlycolPumpOn |
1.3.6.1.4.1.476.1.42.3.2.7.1.5107 |
The standby glycol pump is on, as indicated by an external input
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5108ExternalFireDetected |
1.3.6.1.4.1.476.1.42.3.2.7.1.5108 |
Fire detected, as indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5109UnitOn |
1.3.6.1.4.1.476.1.42.3.2.7.1.5109 |
Unit was turned on. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5110UnitOff |
1.3.6.1.4.1.476.1.42.3.2.7.1.5110 |
Unit was turned off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5111UnitStandby |
1.3.6.1.4.1.476.1.42.3.2.7.1.5111 |
Unit was placed in standby mode. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5112UnitPartialShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5112 |
An event has occurred requiring some system components to be
shutdown and disabled. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5113UnitShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5113 |
An event has occurred requiring the unit to be shutdown and
disabled to prevent damage to the system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5115BMSCommunicationsTimeout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5115 |
Building Management System (or external monitoring system) has not
communicated with the system within the expected timeframe. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5116MaintenanceDue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5116 |
The calculated maintenance date has been reached. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5117MaintenanceCompleted |
1.3.6.1.4.1.476.1.42.3.2.7.1.5117 |
Maintenance has been completed on the unit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5118CloggedAirFilter |
1.3.6.1.4.1.476.1.42.3.2.7.1.5118 |
Air filter is dirty and needs to be (cleaned or) replaced. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5119RAMBatteryIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5119 |
RAM or RAM backup battery is not operating correctly. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5121HighPowerShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5121 |
Supply to high power components has been shutdown. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5144OutputOfUf |
1.3.6.1.4.1.476.1.42.3.2.7.1.5144 |
The output frequency has exceeded a specified range for a
specified period of time. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5145MMSModuleAlarmActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.5145 |
Active alarm or fault of any module in a multi-module system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5146CompressorPumpDownIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5146 |
Unable to pump down suction-side pressure during compressor
shutdown. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5147ReturnAirSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5147 |
The air sensor at the inlet of the unit is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5149BatteryNotQualified |
1.3.6.1.4.1.476.1.42.3.2.7.1.5149 |
The UPS battery voltage is not qualified. This event will be
detected even in the absence of battery disconnect or when it is
open. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5150BatteryTerminalsReversed |
1.3.6.1.4.1.476.1.42.3.2.7.1.5150 |
The measured battery voltage is a negative value due to reverse
battery terminal connections. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5151BatteryConverterFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5151 |
Battery converter failure. This is a summary event caused by one
or more power sub-modules in a UPS module. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5152InverterSCROpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.5152 |
The system has detected an open across one or more inverter static
switch Silicon Controlled Rectifiers. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5153LoadSharingFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5153 |
Difference between any phase inverter current of unit and the
relevant average output current of parallel system is more than a
specific percent of nominal current. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5154DCBusAbnormal |
1.3.6.1.4.1.476.1.42.3.2.7.1.5154 |
The system has detected an abnormal DC Bus Voltage. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5158PowerSubModuleFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5158 |
One or more failures detected in power module, inverter or
rectifier. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5178OutputOvervoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5178 |
One or more of the output phase voltages has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5179OutputUndervoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5179 |
One or more of the output phase voltages has dropped below the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5180OutputOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5180 |
One or more of the phase currents has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5181NeutralOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5181 |
The system's neutral current has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5182GroundOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5182 |
System ground current has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5183OutputVoltageTHD |
1.3.6.1.4.1.476.1.42.3.2.7.1.5183 |
The Total Harmonic Distortion of the voltage on one or more of the
output phases has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5184OutputFrequencyError |
1.3.6.1.4.1.476.1.42.3.2.7.1.5184 |
The output frequency is outside a specified range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5212PanelSummaryStatus |
1.3.6.1.4.1.476.1.42.3.2.7.1.5212 |
The status for the panel. Detects and annunciates upon occurrence
of any branch or panelboard main breaker active event. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5213PanelOvervoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5213 |
One or more of the phase voltages of this panel has exceeded the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5214PanelUndervoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5214 |
One or more of the phase voltages of this panel is less than the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5215PanelOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5215 |
One or more of the phase currents of this panel has exceeded the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5217PanelGroundOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5217 |
The Ground current of this panel has exceeded the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5226BranchOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5226 |
The current in one or more phases of this branch exceeds the limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5227BranchUndercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5227 |
The current in one or more phases of this branch is less than the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5245SubfeedPhaseOvercurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5245 |
One or more of the phase currents in this subfeed has exceeded the
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5249EventState |
1.3.6.1.4.1.476.1.42.3.2.7.1.5249 |
The present state of this digital event input. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5263CompressorNotStopping |
1.3.6.1.4.1.476.1.42.3.2.7.1.5263 |
Compressor commanded to stop, but continues to run. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5269CompressorHoursExceeded |
1.3.6.1.4.1.476.1.42.3.2.7.1.5269 |
[Compressor Hours] has exceeded [Compressor Hours Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5277CondenserFanIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5277 |
Condenser fan is not operating within its operational parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5280LowFluidPressure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5280 |
[Fluid Pressure] has dropped below a specified threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5293ReturnFluidOverTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.5293 |
[Return Fluid Temperature] has exceeded a specified threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5294ReturnFluidUnderTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.5294 |
[Return Fluid Temperature] has dropped below a specified threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5295ReturnFluidTempSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5295 |
The return fluid temperature sensor is disconnected or the signal
is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5296TeamworkReturnFluidTempSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5296 |
The return fluid temperature sensors for all Teamwork units are
disconnected or the signals are out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5297AllPumpsLossofFlow |
1.3.6.1.4.1.476.1.42.3.2.7.1.5297 |
System is shut down due to loss of flow in all available pumps. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5300PumpHoursExceeded |
1.3.6.1.4.1.476.1.42.3.2.7.1.5300 |
[Pump Hours] has exceeded [Pump Hours Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5310EvaporatorFluidFreezeAutoReset |
1.3.6.1.4.1.476.1.42.3.2.7.1.5310 |
Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down, but will restart when
the temperature rises above the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5311EvaporatorFluidFreezeManualResetRequired |
1.3.6.1.4.1.476.1.42.3.2.7.1.5311 |
Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down and requires a manual
reset. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5335ReturnAirUnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5335 |
[Return Air Temperature] has dropped below [Low Return Air
Temperature Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5349ExtAirSensorAHighHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.5349 |
[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
Humidity Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5351ExtAirSensorALowHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.5351 |
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
Low Humidity Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5352CompressorShortCycle |
1.3.6.1.4.1.476.1.42.3.2.7.1.5352 |
Compressor short cycle. A short cycle is defined as turning on and
off a number of times over a set time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5361ExtFreeCoolingLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5361 |
Free cooling is disabled by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5362FreeCoolingTempSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5362 |
The free cooling fluid temperature sensor is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5376MainFanOverload |
1.3.6.1.4.1.476.1.42.3.2.7.1.5376 |
Main fan is shut down due to thermal overload. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5377Condenser |
1.3.6.1.4.1.476.1.42.3.2.7.1.5377 |
Condenser is not operating within its operational parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5415ExtLossofAirBlower |
1.3.6.1.4.1.476.1.42.3.2.7.1.5415 |
Loss of air blower is detected, as indicated by an external input
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5416ExtStandbyUnitOn |
1.3.6.1.4.1.476.1.42.3.2.7.1.5416 |
Standby unit is on, as indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5418UnitCodeMissing |
1.3.6.1.4.1.476.1.42.3.2.7.1.5418 |
Unit code has not been entered and saved. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5419UnitCommunicationLost |
1.3.6.1.4.1.476.1.42.3.2.7.1.5419 |
Master has lost communication with one or more networked units. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5423TooManySensors |
1.3.6.1.4.1.476.1.42.3.2.7.1.5423 |
The number of sensors connected to the PDU exceeds the allowable
limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5436LowAmbientTemperatureProbeTwo |
1.3.6.1.4.1.476.1.42.3.2.7.1.5436 |
The system has detected a low ambient temperature condition on
temperature probe 2. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5439BatteryStringEqualize |
1.3.6.1.4.1.476.1.42.3.2.7.1.5439 |
The system has detected a battery string equalize condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5440BatteryStringOffline |
1.3.6.1.4.1.476.1.42.3.2.7.1.5440 |
The system has detected the battery string is offline. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5442DischargeLowCellVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5442 |
The system has detected a low cell voltage condition during a
discharge. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5447MMSPowerSharing |
1.3.6.1.4.1.476.1.42.3.2.7.1.5447 |
A module is not sharing power with the other modules in a multi
-module system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5456ECOModeActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.5456 |
Conditions for Activation or Automatic Reactivation have been
satisfied. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5458ExcessECOSuspends |
1.3.6.1.4.1.476.1.42.3.2.7.1.5458 |
Number of automatic suspensions has exceeded the ECO Mode -
Maximum Auto Suspensions setting. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5471DoorOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.5471 |
An open door was detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5495ExtFanIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5495 |
One or more fans are not operating within their operational
parameters. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5500ExtRemoteShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5500 |
Unit is shut down by a remote signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5505HotAisleTempOutofRange |
1.3.6.1.4.1.476.1.42.3.2.7.1.5505 |
The air temperature in the Hot aisle is either above [Hot Aisle
Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5508ColdAisleTempOutofRange |
1.3.6.1.4.1.476.1.42.3.2.7.1.5508 |
The air temperature in the cold aisle is either above [Cold Aisle
Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5512RemoteShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5512 |
Unit is shut down by a remote signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5524PDUNeutralOverCurrent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5524 |
The system has detected a neutral over current condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5545CondenserMaxFanSpeedOverride |
1.3.6.1.4.1.476.1.42.3.2.7.1.5545 |
Fan speed exceeding the maximum set point in order to alleviate a
high temperature or pressure condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5559EvaporatorReturnFluidOverTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.5559 |
[Evaporator Return Fluid Temperature] has exceeded a threshold.
The event is deactivated when the temperature drops below the
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5560EvaporatorReturnFluidUnderTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.5560 |
[Evaporator Return Fluid Temperature] has dropped below a
threshold. The event is deactivated when the temperature rises
above the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5561LBSActiveMaster |
1.3.6.1.4.1.476.1.42.3.2.7.1.5561 |
This UPS system has been selected as the functional Master Load
Bus Synchronization (LBS) system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5562LBSActiveSlave |
1.3.6.1.4.1.476.1.42.3.2.7.1.5562 |
This UPS system is synchronized to the output bus of the UPS
system that has been selected as the Master Load Bus
Synchronization (LBS) system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5563DCBusLowFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5563 |
The DC Bus voltage has reached a critical low level. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5567IPInhibit |
1.3.6.1.4.1.476.1.42.3.2.7.1.5567 |
The intelligent paralleling operation is inhibited. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5573AmbientAirSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5573 |
Ambient air sensor is disconnected or the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5577ExtDewPointUnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5577 |
At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
below [Ext Dew Point Under Temp Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5578DewPointOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5578 |
Dew point temperature reading has exceeded the upper threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5579DewPointUnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5579 |
Dew point temperature reading has dropped below the lower
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5588UnspecifiedGeneralEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5588 |
One or more unspecified events active. See local unit display for
further details. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5597RemoteSensorOverTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5597 |
[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5598RemoteSensorUnderTemperature |
1.3.6.1.4.1.476.1.42.3.2.7.1.5598 |
[Remote Sensor Temperature] has dropped below [Remote Sensor Under
Temp Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5600AirEconomizerEmergencyOverride |
1.3.6.1.4.1.476.1.42.3.2.7.1.5600 |
Indoor room temperature has exceeded its upper threshold and the
outdoor air damper has been opened for emergency cooling. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5609 |
The delta temperature between a cell temperature and the ambient
temperature has exceeded the thermal runaway cell to ambient
temperature threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5617TemperatureControlSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5617 |
The air sensor selected for cooling control is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5623EEVBatteryIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5623 |
Electronic expansion valve battery cannot be recharged and needs
to be replaced. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5624EEVPowerIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5624 |
Electronic expansion valve lost power and is running on battery
backup. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5625EEVUnspecifiedGeneralEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5625 |
One or more unspecified electronic expansion valve events active.
See local unit display for further details. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5629StaticPressureSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5629 |
The static pressure sensor is disconnected or the signal is out of
range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5636PumpUnspecifiedGeneralEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5636 |
One or more unspecified pump events active. See local unit display
for further details. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5768OutletAirOvertemperatureLimit |
1.3.6.1.4.1.476.1.42.3.2.7.1.5768 |
The difference between the outlet air temperature and inlet air
temperature exceeds a specified maximum temperature. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5769EMOShutdown |
1.3.6.1.4.1.476.1.42.3.2.7.1.5769 |
An Emergency Module Off command has been detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5770TopOutletFanFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5770 |
Top outlet fan fault - one or more top outlet fans have failed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5771MMSOverCapacity |
1.3.6.1.4.1.476.1.42.3.2.7.1.5771 |
The multi-module system load is larger than the apparent power
limit setting. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5776PDULowVoltageLN |
1.3.6.1.4.1.476.1.42.3.2.7.1.5776 |
The system has detected a module under voltage condition (LN). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5777PDULowVoltageLL |
1.3.6.1.4.1.476.1.42.3.2.7.1.5777 |
The system has detected a module under voltage condition (LL). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5778PDULowVoltageL1L2 |
1.3.6.1.4.1.476.1.42.3.2.7.1.5778 |
The system has detected a line-to-line under voltage condition (L1
-L2). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5779PDULowVoltageL2L3 |
1.3.6.1.4.1.476.1.42.3.2.7.1.5779 |
The system has detected a line-to-line under voltage condition (L2
-L3). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5780PDULowVoltageL3L1 |
1.3.6.1.4.1.476.1.42.3.2.7.1.5780 |
The system has detected a line-to-line under voltage condition (L3
-L1). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5781PDULowVoltageL1N |
1.3.6.1.4.1.476.1.42.3.2.7.1.5781 |
The system has detected a line to neutral under voltage condition
(L1-N). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5782PDULowVoltageL2N |
1.3.6.1.4.1.476.1.42.3.2.7.1.5782 |
The system has detected a line to neutral under voltage condition
(L2-N). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5783PDULowVoltageL3N |
1.3.6.1.4.1.476.1.42.3.2.7.1.5783 |
The system has detected a line to neutral under voltage condition
(L3-N). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5784BranchLowVoltageLN |
1.3.6.1.4.1.476.1.42.3.2.7.1.5784 |
The system has detected a module under voltage condition (LN). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5785BranchLowVoltageLL |
1.3.6.1.4.1.476.1.42.3.2.7.1.5785 |
The system has detected a module under voltage condition (LL). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5786BranchLowVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5786 |
The system has detected a module under voltage condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5788ContTieActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.5788 |
Continuous Power Tie Active. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5792UserkWhReset |
1.3.6.1.4.1.476.1.42.3.2.7.1.5792 |
The user kWh accumulator was reset to zero by the operator. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5796PeakkWReset |
1.3.6.1.4.1.476.1.42.3.2.7.1.5796 |
The Peak kW was reset. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5798BypassOverload |
1.3.6.1.4.1.476.1.42.3.2.7.1.5798 |
Bypass overloaded, reduce load immediately. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5801LowBatteryShutdownImminent |
1.3.6.1.4.1.476.1.42.3.2.7.1.5801 |
If active and guaranteed shutdown is enabled, a low battery
reserve condition exists that will shutdown the UPS. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5806OutputOverload |
1.3.6.1.4.1.476.1.42.3.2.7.1.5806 |
An overload exists on the output. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5807OutputOffPending |
1.3.6.1.4.1.476.1.42.3.2.7.1.5807 |
Output off pending - shutdown imminent. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5817LossofRedundancy |
1.3.6.1.4.1.476.1.42.3.2.7.1.5817 |
The system has an insufficient number of power modules to provide
redundancy. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5818PowerModuleFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5818 |
One or more conditions indicate a power module failure, service is
required. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5819PowerModuleWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.5819 |
One or more power modules is reporting a warning condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5851MaximumLoadAlarm |
1.3.6.1.4.1.476.1.42.3.2.7.1.5851 |
Maximum load alarm indicating load setting has been exceeded. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5856BatteryModuleFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5856 |
One or more battery modules are reporting a fault condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5857BatteryModuleWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.5857 |
One or more battery modules are reporting a warning condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5862CheckAirFilter |
1.3.6.1.4.1.476.1.42.3.2.7.1.5862 |
Please check air filter, it may need to be cleaned or replaced. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5865NoLoadWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.5865 |
Indicates the UPS has output voltage but the output current is
below a set threshold [No Load Warning Current Threshold] for a
set period of time [No Load Warning Delay]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5871BatteryOverTemperatureLimit |
1.3.6.1.4.1.476.1.42.3.2.7.1.5871 |
A battery temperature sensor is reporting a value above a
predetermined limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5873UnexpectedMainBatteryDisconnectClosure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5873 |
The main battery disconnect has closed unexpectedly. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5874BatteryOverVoltage |
1.3.6.1.4.1.476.1.42.3.2.7.1.5874 |
The system has detected that the battery voltage has exceeded a
predetermined limit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5875BatteryFuseFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5875 |
One or more battery fuse faults has occurred. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5878MainBatteryDisconnectForcedToUnlock |
1.3.6.1.4.1.476.1.42.3.2.7.1.5878 |
The main battery disconnect is forced to the unlocked state. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5879VdcBackfeed |
1.3.6.1.4.1.476.1.42.3.2.7.1.5879 |
The voltage between battery and DC bus measurements is out of
tolerance. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5883RegenerationOperationFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5883 |
Regeneration operation has been terminated due to bypass source
instability or unit misoperation. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5896GroundFaultDetected |
1.3.6.1.4.1.476.1.42.3.2.7.1.5896 |
The system has detected a ground fault on a Battery-String. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5902ReturnHumiditySensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5902 |
The humidity sensor at the inlet of the unit is disconnected or
the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5906AirflowSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5906 |
Airflow sensor is disconnected or the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5907ExtAirDamperPositionIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5907 |
Air damper position does not match expected value, as indicated by
an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5908ExtPowerSourceAFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5908 |
Unit main power source A failure, as indicated by an external
input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5909ExtPowerSourceBFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.5909 |
Unit main power source B failure, as indicated by an external
input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5911FluidTemperatureSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5911 |
The fluid temperature sensor is disconnected or the signal is out
of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5912FluidFlowSensorIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.5912 |
The fluid flow sensor is disconnected or the signal is out of
range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5924MixedModeLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.5924 |
Mixed mode has been entered too many times over a rolling time
period and has been temporarily disabled. Mixed mode is defined
as the use of a compressor on one refrigeration circuit and the
use of a refrigerant pump on the other circuit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5928UnbalancedLoadCondition |
1.3.6.1.4.1.476.1.42.3.2.7.1.5928 |
The system has detected a line-to-line unbalanced load condition. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5948BranchLowVoltageLL |
1.3.6.1.4.1.476.1.42.3.2.7.1.5948 |
The system has detected a module under voltage condition (LL). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5969GenericDICFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5969 |
The control board reports a fault - Service required. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5970GroundFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.5970 |
An AC phase to ground fault or three phase fault to ground exists
on the output of the UPS. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5976MaintenanceBypassBreakerClosed |
1.3.6.1.4.1.476.1.42.3.2.7.1.5976 |
The maintenance bypass breaker is closed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5982BypassBreakerSBBOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.5982 |
The bypass circuit breaker (SBB) indicates that it is in the open
position. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5984BypassUndervoltageWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.5984 |
The voltage on one or more bypass phases is less than a specified
percentage of the nominal voltage. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId5998BattOvtempWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.5998 |
A battery temperature sensor is reporting a value above the
setpoint. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6009InverterOutputBreakerOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.6009 |
The inverter output breaker indicates that it is in the open
position. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6011EquipmentOverTempWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.6011 |
Equipment over temperature warning is a summary event based on the
detection of at least one measured temperature exceeding a
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6046LoadonUPS |
1.3.6.1.4.1.476.1.42.3.2.7.1.6046 |
The output is being supplied power from the inverter. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6060TransfertoBypassSystemOverload |
1.3.6.1.4.1.476.1.42.3.2.7.1.6060 |
The UPS System has transferred to bypass because the active power
modules cannot support the critical load. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6062LossofSynchronization |
1.3.6.1.4.1.476.1.42.3.2.7.1.6062 |
The inverter and bypass are no longer synchronized. . |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6064LBSCableFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6064 |
Load Bus Sync communications is abnormal. A problem with the LBS
cable may exist. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6066ParallelCableFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6066 |
The UPS parallel system communications is abnormal. A problem with
the parallel cable may exist. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6067BatteryFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.6067 |
A short circuit exists in the battery system. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6068BatteryRoomAlarm |
1.3.6.1.4.1.476.1.42.3.2.7.1.6068 |
The ambient temperature of the battery room is abnormal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6080UPSCCommunicationFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6080 |
The UPSC has failed to communicate in a designated time period. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6105ExternalCondenserTVSSIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.6105 |
The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed, as indicated by an external input
signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6106ExternalCondenserVFDIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.6106 |
The condenser fan Variable Frequency Drive is offline, as
indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6107ExternalCondenserIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.6107 |
Condenser is not operating within its operational parameters, as
indicated by an external input signal. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6119Slotsnotavailable |
1.3.6.1.4.1.476.1.42.3.2.7.1.6119 |
The number of sensors exceeds the number of allocated slots and
cannot be displayed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6182ReplaceBattery |
1.3.6.1.4.1.476.1.42.3.2.7.1.6182 |
The battery is due for replacement. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6203SensorAdded |
1.3.6.1.4.1.476.1.42.3.2.7.1.6203 |
Sensor Added. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6216PrechargeCircuitFailed |
1.3.6.1.4.1.476.1.42.3.2.7.1.6216 |
DC Bus precharge/discharge didn't reach specified level within a
specified time. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6217MemoryCardRemoved |
1.3.6.1.4.1.476.1.42.3.2.7.1.6217 |
The memory card on the control board has been removed. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6218AutoCalibrationActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.6218 |
The system is automatically calibrating ADC channels. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6222BranchLoadLoss |
1.3.6.1.4.1.476.1.42.3.2.7.1.6222 |
Loss of load on branch detected. Branch circuit breaker might be
open. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6225RemoteSensorLowHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6225 |
Remote sensor humidity has dropped below a lower threshold. The
event is deactivated when the humidity rises above the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6226RemoteSensorHighHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6226 |
Remote sensor humidity has exceeded an upper threshold. The event
is deactivated when the humidity drops below the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6227RemoteSensorAverageLowHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6227 |
The average humidity of multiple remote sensors on the cooling
unit has dropped below a lower threshold. The event is
deactivated when the humidity rises above the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6228RemoteSensorAverageHighHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6228 |
The average humidity of multiple remote sensors on the cooling
unit has exceeded an upper threshold. The event is deactivated
when the humidity drops below the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6229RemoteSensorSystemAverageLowHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6229 |
The average humidity of multiple remote sensors on interconnected
cooling units in a single system has dropped below a lower
threshold. The event is deactivated when the humidity rises
above the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6230RemoteSensorSystemAverageHighHumidity |
1.3.6.1.4.1.476.1.42.3.2.7.1.6230 |
The average humidity of multiple remote sensors on interconnected
cooling units in a single system has exceeded an upper threshold.
The event is deactivated when the humidity drops below the
threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6231LowCompressorSuperheat |
1.3.6.1.4.1.476.1.42.3.2.7.1.6231 |
Compressor suction superheat has dropped below a lower threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6232SECUnspecifiedGeneralEvent |
1.3.6.1.4.1.476.1.42.3.2.7.1.6232 |
One or more unspecified events active for the Superheat and
Envelope Controller. See local unit display for further details. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6233SECCommunicationLost |
1.3.6.1.4.1.476.1.42.3.2.7.1.6233 |
Communication with the Superheat and Envelope Controller has been
lost. The event is deactivated when communication is re
-established. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6236PowerSourceAIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.6236 |
No power is detected at power source input 'A'. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6237PowerSourceBIssue |
1.3.6.1.4.1.476.1.42.3.2.7.1.6237 |
No power is detected at power source input 'B'. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6239FluidValveHoursExceeded |
1.3.6.1.4.1.476.1.42.3.2.7.1.6239 |
Operating hours for the fluid valve have exceeded the threshold. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6253BoosterFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6253 |
Booster failure - boost is off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6254ChargerFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6254 |
Charger Failure - Charger is off. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6274UnitTopReturnAirSensorFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6274 |
Return air sensor at the top of the unit is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6277UnitTopSupplyAirSensorFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6277 |
Supply air sensor at the top of the unit is disconnected or the
signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6293ChilledWaterControlActive |
1.3.6.1.4.1.476.1.42.3.2.7.1.6293 |
Chilled water inlet temperature control function is enabled due to
'bad' water. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6295ChilledWaterInletTemperatureSensorFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6295 |
Chilled water inlet temperature sensor is disconnected or the
signal is out of range. The sensor is mandatory for the chilled
water flow function. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6297Modbus010VModuleCommunicationFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6297 |
Modbus 0-10V module for managing the second Chilled Water circuit
valve is disconnected or the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6299RackDoorsOpen |
1.3.6.1.4.1.476.1.42.3.2.7.1.6299 |
Rack doors opened due to supply air temperature exceeding the
[Rack Door Open High Supply Air Temperature Threshold]. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6304HeatingLockout |
1.3.6.1.4.1.476.1.42.3.2.7.1.6304 |
Heating is shut down and disabled. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6305FreeCoolingStoppedHighRoomTemp |
1.3.6.1.4.1.476.1.42.3.2.7.1.6305 |
Free cooling is temporarily disabled due to room temperature
exceeding a preset delta above the the set point. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6309ColdAisleAirSensorFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6309 |
Cold aisle sensor measuring air temperature and humidity is
disconnected or the signal is out of range. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6333Bypassoutofsync |
1.3.6.1.4.1.476.1.42.3.2.7.1.6333 |
Bypass and Inverter inputs are not in sync. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6350GeneralFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.6350 |
A general fault in the UPS has been detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6351UPSAwaitingPower |
1.3.6.1.4.1.476.1.42.3.2.7.1.6351 |
The UPS output is off and the UPS is awaiting the return of input
power. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6353GeneralWarning |
1.3.6.1.4.1.476.1.42.3.2.7.1.6353 |
A warning in the UPS has been detected. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6354BatteryCharging |
1.3.6.1.4.1.476.1.42.3.2.7.1.6354 |
The UPS battery is charging (battery charge percentage lower than
98). |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6440PowerModuleFuseFailure |
1.3.6.1.4.1.476.1.42.3.2.7.1.6440 |
A summary event indicating one or more fuse failures in the power
module. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6450PDUPoweredOn |
1.3.6.1.4.1.476.1.42.3.2.7.1.6450 |
The PDU was powered on. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6454DCtoDCConverterFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.6454 |
A failure has occurred in the battery discharge circuit. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
lgpCondId6455LeakSensorCableFault |
1.3.6.1.4.1.476.1.42.3.2.7.1.6455 |
A fault is detected in the 'Leak Sensor' cable. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|