LIEBERT-GP-SYSTEM-MIB

File: LIEBERT-GP-SYSTEM-MIB.mib (18872 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC LIEBERT-GP-REGISTRATION-MIB
RFC1213-MIB LIEBERT-GP-AGENT-MIB

Imported symbols

OBJECT-TYPE MODULE-IDENTITY OBJECT-IDENTITY
NOTIFICATION-TYPE Integer32 Unsigned32
DisplayString lgpSystem liebertSystemModuleReg
sysUpTime lgpAgentConnectedDeviceCount lgpAgentDeviceIndex

Defined Types

LgpSysDeviceComponentEntry  
SEQUENCE    
  lgpSysDeviceComponentIndex Unsigned32
  lgpSysDeviceComponentDescr OBJECT IDENTIFIER
  lgpSysDeviceComponentSerialNum DisplayString Size(255)
  lgpSysDeviceComponentModelNum DisplayString Size(255)

Defined Values

liebertSystemModule 1.3.6.1.4.1.476.1.42.1.8.1
The MIB module used to specify Liebert Controller OIDs Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY    

lgpSysStatistics 1.3.6.1.4.1.476.1.42.3.7.1
This sub-tree is used to register Liebert System Statistics object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysStatus 1.3.6.1.4.1.476.1.42.3.7.2
This sub-tree is used to register Liebert System Status object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysSettings 1.3.6.1.4.1.476.1.42.3.7.3
This sub-tree is used to register Liebert System Settings object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysControl 1.3.6.1.4.1.476.1.42.3.7.4
This sub-tree is used to register Liebert System Control object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysTime 1.3.6.1.4.1.476.1.42.3.7.5
This sub-tree is used to register Liebert System Time object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysMaintenance 1.3.6.1.4.1.476.1.42.3.7.6
This sub-tree is used to register Liebert System Maintenance object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysEventDescription 1.3.6.1.4.1.476.1.42.3.7.7
An ASCII textual description for the event. This object is primarily used in the varbind of some notifications to provide a simple human-readable description.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(255)  

lgpSysEventNotifications 1.3.6.1.4.1.476.1.42.3.7.8
This sub-tree is used to register Liebert System Notification object identifiers.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysDeviceComponentGroup 1.3.6.1.4.1.476.1.42.3.7.9
This sub-tree registers well known device components.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysDeviceComponentTable 1.3.6.1.4.1.476.1.42.3.7.9.1
A list of components of devices identified by their serial number and or model number. This table contains zero, one, or many rows. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    LgpSysDeviceComponentEntry

lgpSysDeviceComponentEntry 1.3.6.1.4.1.476.1.42.3.7.9.1.1
This entry defines the contents of the columns for the table 'lgpSysDeviceComponentTable'.
Status: current Access: not-accessible
OBJECT-TYPE    
  LgpSysDeviceComponentEntry  

lgpSysDeviceComponentIndex 1.3.6.1.4.1.476.1.42.3.7.9.1.1.1
This is the index indicating the row in the table 'lgpSysDeviceComponentTable' for a component entry.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32  

lgpSysDeviceComponentDescr 1.3.6.1.4.1.476.1.42.3.7.9.1.1.2
An OID representing a component of the device indicated by the index lgpAgentDeviceIndex.
Status: current Access: read-only
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpSysDeviceComponentSerialNum 1.3.6.1.4.1.476.1.42.3.7.9.1.1.3
This is the serial number of the component described by the OID 'lgpSysDeviceComponentDescr'. This data is intended for display / human consumption. Do not use this field for determining programmatic behavior.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(255)  

lgpSysDeviceComponentModelNum 1.3.6.1.4.1.476.1.42.3.7.9.1.1.4
This is the model identifier of the component described by the OID 'lgpSysDeviceComponentDescr'. This data is intended for display / human consumption. Do not use this field for determining programmatic behavior.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(255)  

lgpSysDeviceComponentWellknown 1.3.6.1.4.1.476.1.42.3.7.9.5
This sub-tree registers well known Liebert System Components.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysDeviceBatCabinet 1.3.6.1.4.1.476.1.42.3.7.9.5.5
This sub-tree is used to register a battery cabinet component. To determine the cabinet being described in a multi-cabinet system, this point implements an additional two indexes. The first index describes the module the cabinet is located in. The second index describes the cabinet number. In an SMS (Single-Module System) the first index is always 1. Example: lgpSysDeviceComponentCabinet.2.4 'lgpSysDeviceCabinet' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4 in second module
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysDeviceParallelCabinet 1.3.6.1.4.1.476.1.42.3.7.9.5.6
This sub-tree is used to register a parallel cabinet.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysDeviceMaintBypass 1.3.6.1.4.1.476.1.42.3.7.9.5.7
This sub-tree is used to register the maintenance bypass.
Status: current Access: read-only
OBJECT-IDENTITY    

lgpSysNotification 1.3.6.1.4.1.476.1.42.3.7.8.1
This notification is a generic notification intended for direct user visibility. The user event description identifies the system condition that has occurred. This text will be prefixed with either 'Active:', 'Cleared:', or 'Message:' depending on the state of the event. Note: That a prefix of 'Message:' identifies a stateless event and as such there will be no corresponding 'Cleared:' trap sent.
Status: current Access: read-only
NOTIFICATION-TYPE    

lgpSysNormal 1.3.6.1.4.1.476.1.42.3.7.8.2
The system has returned to a normal operating state. This implies prior to the generation of this event the system was operating in a state where one or more alarm or warning conditions were present. All of those alarms or conditions have now cleared. NOTE: This notification may be generated after a short delay during a cold boot of the system -- if no alarms or conditions are present in the monitored device(s) at that time.
Status: current Access: read-only
NOTIFICATION-TYPE    

lgpSysStatisticsRunHrs 1.3.6.1.4.1.476.1.42.3.7.1.1
Accumulated run hours of the system.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpSysSelfTestResult 1.3.6.1.4.1.476.1.42.3.7.2.1
The outcome of the previous self-test.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), inhibited(6)  

lgpSysState 1.3.6.1.4.1.476.1.42.3.7.2.2
The operating status for the system. The intent of this data is to provide a high level status of the system. The possible states are: normalOperation(1) The system is operating normally with no active warnings or alarms. startUp(2) The system is in a startup state (initializing). Monitoring operations and information may not be fully supported at this time. This state will clear automatically when the system is fully initialized and ready to accept monitoring commands. normalWithWarning(3) The system is operating normally with one or more active warnings. Appropriate personnel should investigate the warning(s) as soon as possible and take appropriate action. normalWithAlarm(4) The system is operating normally with one or more active alarms. Appropriate personnel should investigate the alarm(s) as soon as possible and take appropriate action. abnormalOperation(5) They system is operating abnormally. There is a failure within the system that is unexpected under normal operating conditions. Appropriate personnel should investigate the cause as soon as possible. The normal functioning of the system is likely inhibited.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER normalOperation(1), startUp(2), normalWithWarning(3), normalWithAlarm(4), abnormalOperation(5)  

lgpSysAudibleAlarm 1.3.6.1.4.1.476.1.42.3.7.3.1
The state of the audible alarm of the device.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpSysSelfTest 1.3.6.1.4.1.476.1.42.3.7.4.1
Self-Test Command. This command will initiate a system self-test of the system. If already initiated, this command will abort the self-test. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

lgpSysControlOperationOnOff 1.3.6.1.4.1.476.1.42.3.7.4.2
This object allows control of the system functionality. This will not affect the communications or control of the system, so that once turned off, the system operation can be restored by setting this value to 'on'.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpSysTimeEpoch 1.3.6.1.4.1.476.1.42.3.7.5.1
The present time of the system. This time is represented as the number of seconds since the epoch of 1970-01-01 00:00:00 GMT.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

lgpSysMaintenanceCapacity 1.3.6.1.4.1.476.1.42.3.7.6.1
The relative percentage of time that has elapsed since the last scheduled maintenance was performed. When this value reaches 100%, the device is due for another scheduled maintenance procedure.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpSysMaintenanceYear 1.3.6.1.4.1.476.1.42.3.7.6.2
The year in which the next scheduled service is due
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

lgpSysMaintenanceMonth 1.3.6.1.4.1.476.1.42.3.7.6.3
The month in which the next scheduled service is due
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32