NETWORK-TECHNOLOGIES-GLOBAL-REG

File: NETWORK-TECHNOLOGIES-GLOBAL-REG.mib (29503 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC

Imported symbols

MODULE-IDENTITY OBJECT-TYPE OBJECT-IDENTITY
enterprises Integer32 DisplayString
TEXTUAL-CONVENTION

Defined Types

DecimalPointValue  
Display integer values using a decimal point before last digit
TEXTUAL-CONVENTION    
  Integer32  

Defined Values

nti 1.3.6.1.4.1.3699
OBJECT IDENTIFIER    

products 1.3.6.1.4.1.3699.1
OBJECT IDENTIFIER    

experimental 1.3.6.1.4.1.3699.2
OBJECT IDENTIFIER    

hardware 1.3.6.1.4.1.3699.1.1
OBJECT IDENTIFIER    

software 1.3.6.1.4.1.3699.1.2
OBJECT IDENTIFIER    

enviromux-MINI 1.3.6.1.4.1.3699.1.1.3
OBJECT IDENTIFIER    

otherProduct 1.3.6.1.4.1.3699.1.1.200
OBJECT IDENTIFIER    

monitoring 1.3.6.1.4.1.3699.1.1.3.1
OBJECT IDENTIFIER    

administration 1.3.6.1.4.1.3699.1.1.3.2
OBJECT IDENTIFIER    

envTraps 1.3.6.1.4.1.3699.1.1.3.100
OBJECT IDENTIFIER    

temperatureSensor1 1.3.6.1.4.1.3699.1.1.3.1.1
OBJECT IDENTIFIER    

temperatureSensor2 1.3.6.1.4.1.3699.1.1.3.1.2
OBJECT IDENTIFIER    

humiditySensor1 1.3.6.1.4.1.3699.1.1.3.1.3
OBJECT IDENTIFIER    

humiditySensor2 1.3.6.1.4.1.3699.1.1.3.1.4
OBJECT IDENTIFIER    

dryContact1 1.3.6.1.4.1.3699.1.1.3.1.5
OBJECT IDENTIFIER    

dryContact2 1.3.6.1.4.1.3699.1.1.3.1.6
OBJECT IDENTIFIER    

dryContact3 1.3.6.1.4.1.3699.1.1.3.1.7
OBJECT IDENTIFIER    

dryContact4 1.3.6.1.4.1.3699.1.1.3.1.8
OBJECT IDENTIFIER    

waterSensor 1.3.6.1.4.1.3699.1.1.3.1.9
OBJECT IDENTIFIER    

hostSystem 1.3.6.1.4.1.3699.1.1.3.2.1
OBJECT IDENTIFIER    

temperatureSensor1Adm 1.3.6.1.4.1.3699.1.1.3.2.2
OBJECT IDENTIFIER    

temperatureSensor2Adm 1.3.6.1.4.1.3699.1.1.3.2.3
OBJECT IDENTIFIER    

humiditySensor1Adm 1.3.6.1.4.1.3699.1.1.3.2.4
OBJECT IDENTIFIER    

humiditySensor2Adm 1.3.6.1.4.1.3699.1.1.3.2.5
OBJECT IDENTIFIER    

dryContact1Adm 1.3.6.1.4.1.3699.1.1.3.2.6
OBJECT IDENTIFIER    

dryContact2Adm 1.3.6.1.4.1.3699.1.1.3.2.7
OBJECT IDENTIFIER    

dryContact3Adm 1.3.6.1.4.1.3699.1.1.3.2.8
OBJECT IDENTIFIER    

dryContact4Adm 1.3.6.1.4.1.3699.1.1.3.2.9
OBJECT IDENTIFIER    

waterSensorAdm 1.3.6.1.4.1.3699.1.1.3.2.10
OBJECT IDENTIFIER    

version 1.3.6.1.4.1.3699.1.1.3.3
Code version
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

temperatureSensor1CurrentValue 1.3.6.1.4.1.3699.1.1.3.1.1.1
Current value of the temperature sensor connected to port 1 in tenths of degrees . This port is the right RJ-45 sensor port. The value is expressed in the units indicated in temperatureSensor1Unit. This object is only applicable if a temperature sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DecimalPointValue  

temperatureSensor1Alert 1.3.6.1.4.1.3699.1.1.3.1.1.2
Current alert status of the temperature sensor connected to port 1. This port is the right RJ-45 sensor port. A value of 0 indicates that the sensor has not crossed either of its specified thresholds, while a value of 1 indicates that it has. This object is only applicable if a temperature sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

temperatureSensor1Name 1.3.6.1.4.1.3699.1.1.3.2.2.1
Current name assigned to the temperature sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor1Unit 1.3.6.1.4.1.3699.1.1.3.2.2.2
Temperature units for the value of the temperature sensor connected to port 1. This port is the right RJ-45 sensor port. The unit may either be Fahrenheit or Celsius, and corresponds directly with the unit chosen on the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 1 or 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor1LowThreshold 1.3.6.1.4.1.3699.1.1.3.2.2.3
Low threshold assigned to the temperature sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the low threshold value entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor1HighThreshold 1.3.6.1.4.1.3699.1.1.3.2.2.4
High threshold assigned to the temperature sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the high threshold value entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor2CurrentValue 1.3.6.1.4.1.3699.1.1.3.1.2.1
Current value of the temperature sensor connected to port 2 in tenths of degrees . This port is the left RJ-45 sensor port. The value is expressed in the units indicated in temperatureSensor2Unit. This object is only applicable if a temperature sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DecimalPointValue  

temperatureSensor2Alert 1.3.6.1.4.1.3699.1.1.3.1.2.2
Current alert status of the temperature sensor connected to port 2. This port is the left RJ-45 sensor port. A value of 0 indicates that the sensor has not crossed either of its specified thresholds, while a value of 1 indicates that it has. This object is only applicable if a temperature sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

temperatureSensor2Name 1.3.6.1.4.1.3699.1.1.3.2.3.1
Current name assigned to the temperature sensor connected to port 2. This port is the left RJ-45 sensor port. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor2Unit 1.3.6.1.4.1.3699.1.1.3.2.3.2
Temperature units for the value of the temperature sensor connected to port 2. This port is the left RJ-45 sensor port. The unit may either be Fahrenheit or Celsius, and corresponds directly with the unit chosen on the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 1 or 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor2LowThreshold 1.3.6.1.4.1.3699.1.1.3.2.3.3
Low threshold assigned to the temperature sensor connected to port 2. This port is the left RJ-45 sensor port. This value corresponds directly with the low threshold value entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

temperatureSensor2HighThreshold 1.3.6.1.4.1.3699.1.1.3.2.3.4
High threshold assigned to the temperature sensor connected to port 2. This port is the left RJ-45 sensor port. This value corresponds directly with the high threshold value entered in the configuration page for this sensor. This object is only applicable if a temperature sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor1CurrentValue 1.3.6.1.4.1.3699.1.1.3.1.3.1
Current integer value in tenths of percents of the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DecimalPointValue  

humiditySensor1Alert 1.3.6.1.4.1.3699.1.1.3.1.3.2
Current alert status of the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. A value of 0 indicates that the sensor has not crossed either of its specified thresholds, while a value of 1 indicates that it has. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

humiditySensor1Name 1.3.6.1.4.1.3699.1.1.3.2.4.1
Current name assigned to the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor1LowThreshold 1.3.6.1.4.1.3699.1.1.3.2.4.2
Low threshold assigned to the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the low threshold value entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor1HighThreshold 1.3.6.1.4.1.3699.1.1.3.2.4.3
High threshold assigned to the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the high threshold value entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor2CurrentValue 1.3.6.1.4.1.3699.1.1.3.1.4.1
Current integer value in tenths of percents of the humidity sensor connected to port 2. This port is the left RJ-45 sensor port. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a humidity sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DecimalPointValue  

humiditySensor2Alert 1.3.6.1.4.1.3699.1.1.3.1.4.2
Current alert status of the humidity sensor connected to port 2. This port is the left RJ-45 sensor port. A value of 0 indicates that the sensor has not crossed either of its specified thresholds, while a value of 1 indicates that it has. his object is only applicable if a humidity sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

humiditySensor2Name 1.3.6.1.4.1.3699.1.1.3.2.5.1
Current name assigned to the humidity sensor connected to port 2. This port is the left RJ-45 sensor port. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor2LowThreshold 1.3.6.1.4.1.3699.1.1.3.2.5.2
Low threshold assigned to the humidity sensor connected to port 2. This port is the left RJ-45 sensor port. This value corresponds directly with the low threshold value entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

humiditySensor2HighThreshold 1.3.6.1.4.1.3699.1.1.3.2.5.3
High threshold assigned to the humidity sensor connected to port 1. This port is the right RJ-45 sensor port. This value corresponds directly with the high threshold value entered in the configuration page for this sensor. This object is only applicable if a humidity sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

dryContact1Status 1.3.6.1.4.1.3699.1.1.3.1.5.1
Current integer value of the dry contact sensor connected to port 1. A value of 0 represents OPEN, and a value of 1 represents CLOSED. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a dry contact sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(0), closed(1)  

dryContact1Alert 1.3.6.1.4.1.3699.1.1.3.1.5.2
Current alert status of the dry contact sensor connected to port 1. A value of 0 indicates that the sensor has not been set to its alert condition, while a value of 1 indicates that it has. This object is only applicable if a dry contact sensor is connected to port 1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dryContact1Name 1.3.6.1.4.1.3699.1.1.3.2.6.1
Current name assigned to the dry contact sensor connected to port 1. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

dryContact1AlertStatus 1.3.6.1.4.1.3699.1.1.3.2.6.2
Status which generates an alert condition for the dry contact sensor connected to port 1. A value of 0 represents OPEN, and a value of 1 represents CLOSED. This value corresponds directly with the Alert When value entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 1.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alert-when-open(0), alert-when-closed(1)  

dryContact2Status 1.3.6.1.4.1.3699.1.1.3.1.6.1
Current integer value of the dry contact sensor connected to port 2. A value of 0 represents OPEN, and a value of 1 represents CLOSED. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a dry contact sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(0), closed(1)  

dryContact2Alert 1.3.6.1.4.1.3699.1.1.3.1.6.2
Current alert status of the dry contact sensor connected to port 2. value of 0 indicates that the sensor has not been set to its alert condition, while a value of 1 indicates that it has. This object is only applicable if a dry contact sensor is connected to port 2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dryContact2Name 1.3.6.1.4.1.3699.1.1.3.2.7.1
Current name assigned to the dry contact sensor connected to port 2. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

dryContact2AlertStatus 1.3.6.1.4.1.3699.1.1.3.2.7.2
Status which generates an alert condition for the dry contact sensor connected to port 2. A value of 0 represents OPEN, and a value of 1 represents CLOSED. This value corresponds directly with the Alert When value entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 2.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alert-when-open(0), alert-when-closed(1)  

dryContact3Status 1.3.6.1.4.1.3699.1.1.3.1.7.1
Current integer value of the dry contact sensor connected to port 3. A value of 0 represents OPEN, and a value of 1 represents CLOSED. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a dry contact sensor is connected to port 3.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(0), closed(1)  

dryContact3Alert 1.3.6.1.4.1.3699.1.1.3.1.7.2
Current alert status of the dry contact sensor connected to port 3. A value of 0 indicates that the sensor has not been set to its alert condition, while a value of 1 indicates that it has. This object is only applicable if a dry contact sensor is connected to port 3.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dryContact3Name 1.3.6.1.4.1.3699.1.1.3.2.8.1
Current name assigned to the dry contact sensor connected to port 3. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 3.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

dryContact3AlertStatus 1.3.6.1.4.1.3699.1.1.3.2.8.2
Status which generates an alert condition for the dry contact sensor connected to port 3. A value of 0 represents OPEN, and a value of 1 represents CLOSED. This value corresponds directly with the Alert When value entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 3.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alert-when-open(0), alert-when-closed(1)  

dryContact4Status 1.3.6.1.4.1.3699.1.1.3.1.8.1
Current integer value of the dry contact sensor connected to port 4. A value of 0 represents OPEN, and a value of 1 represents CLOSED. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a dry contact sensor is connected to port 4.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(0), closed(1)  

dryContact4Alert 1.3.6.1.4.1.3699.1.1.3.1.8.2
Current alert status of the dry contact sensor connected to port 4. A value of 0 indicates that the sensor has not been set to its alert condition, while a value of 1 indicates that it has. This object is only applicable if a dry contact sensor is connected to port 4.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dryContact4Name 1.3.6.1.4.1.3699.1.1.3.2.9.1
Current name assigned to the dry contact sensor connected to port 4. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 4.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

dryContact4AlertStatus 1.3.6.1.4.1.3699.1.1.3.2.9.2
Status which generates an alert condition for the dry contact sensor connected to port 4. A value of 0 represents OPEN, and a value of 1 represents CLOSED. This value corresponds directly with the Alert When value entered in the configuration page for this sensor. This object is only applicable if a dry contact sensor is connected to port 4.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alert-when-open(0), alert-when-closed(1)  

waterStatus 1.3.6.1.4.1.3699.1.1.3.1.9.1
Current integer value of the water sensor. A value of 0 represents OPEN, and a value of 1 represents CLOSED. The value corresponds directly with the value displayed on the summary page and the status page for this sensor. This object is only applicable if a water sensor is connected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER open(0), closed(1)  

waterAlert 1.3.6.1.4.1.3699.1.1.3.1.9.2
Current alert status of the water sensor. A value of 0 indicates that the sensor has not been set to its alert condition, while a value of 1 indicates that it has. This object is only applicable if a water sensor is connected.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

waterName 1.3.6.1.4.1.3699.1.1.3.2.10.1
Current name assigned to the water sensor. This value corresponds directly with the name entered in the configuration page for this sensor. This object is only applicable if a water sensor is connected.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

waterAlertStatus 1.3.6.1.4.1.3699.1.1.3.2.10.2
Status which generates an alert condition for the water sensor. A value of 0 represents OPEN, and a value of 1 represents CLOSED. This value corresponds directly with the Alert When value entered in the configuration page for this sensor. This object is only applicable if a water sensor is connected.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER alert-when-open(0), alert-when-closed(1)  

sysName 1.3.6.1.4.1.3699.1.1.3.2.1.1
System node name. This value corresponds directly with the Node Name field on the General configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysLocation 1.3.6.1.4.1.3699.1.1.3.2.1.2
System node location. his value corresponds directly with the Node Location field on the General configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysIP 1.3.6.1.4.1.3699.1.1.3.2.1.3
System IP address. This value corresponds directly with the IP address assigned to the enviromux-MINI on the Network configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysMask 1.3.6.1.4.1.3699.1.1.3.2.1.4
System Subnet Mask. This value corresponds directly with the Subnet Mask assigned to the enviromux-MINI on the Network configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysGateway 1.3.6.1.4.1.3699.1.1.3.2.1.5
System Default Gateway. This value corresponds directly with the Default Gateway assigned to the enviromux-MINI on the Network configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

sysDNS 1.3.6.1.4.1.3699.1.1.3.2.1.6
System DNS server. This value corresponds directly with the DNS server assigned to the enviromux-MINI on the Network configuration page under the ADMINISTRATION menu.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

temperatureSensor1Trap 1.3.6.1.4.1.3699.1.1.3.100.1
Trap for alert from temperature sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

temperatureSensor2Trap 1.3.6.1.4.1.3699.1.1.3.100.2
Trap for alert from temperature sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

humiditySensor1Trap 1.3.6.1.4.1.3699.1.1.3.100.3
Trap for alert from humidity sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

humiditySensor2Trap 1.3.6.1.4.1.3699.1.1.3.100.4
Trap for alert from humidity sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

dryContactSensor1Trap 1.3.6.1.4.1.3699.1.1.3.100.5
Trap for alert from dry contact sensor connected to port 1. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

dryContactSensor2Trap 1.3.6.1.4.1.3699.1.1.3.100.6
Trap for alert from dry contact sensor connected to port 2. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

dryContactSensor3Trap 1.3.6.1.4.1.3699.1.1.3.100.7
Trap for alert from dry contact sensor connected to port 3. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

dryContactSensor4Trap 1.3.6.1.4.1.3699.1.1.3.100.8
Trap for alert from dry contact sensor connected to port 4. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

waterSensor1Trap 1.3.6.1.4.1.3699.1.1.3.100.9
Trap for alert from water sensor. Received if this sensor is configured to send SNMP traps using the Configuration page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

logTrap 1.3.6.1.4.1.3699.1.1.3.100.100
Trap generated when a log entry is created. Received if log entries are configured to be sent as SNMP traps using the Log Methods page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE    

overflowTrap 1.3.6.1.4.1.3699.1.1.3.100.101
Trap generated when has reached 90% capacity. Received if log overflow alerts are enabled and are configured to be sent as SNMP traps using the Log Overflow page, and SNMP is enabled on the Network configuration page under the ADMINISTRATION menu.
Status: current Access: read-only
NOTIFICATION-TYPE