NextUPSSystems

File: NextUPSSystems.mib (152055 bytes)

Imported modules

RFC1155-SMI SNMPv2-SMI SNMPv2-TC
RFC-1215 UPS-MIB

Imported symbols

enterprises MODULE-IDENTITY OBJECT-TYPE
OBJECT-IDENTITY DisplayString TRAP-TYPE
PositiveInteger NonNegativeInteger

Defined Types

UpsInEntry  
SEQUENCE    
  upsInLineIndex PositiveInteger
  upsInFrequency NonNegativeInteger
  upsInVoltage NonNegativeInteger
  upsInCurrent NonNegativeInteger
  upsInApparentPower NonNegativeInteger
  upsInTruePower NonNegativeInteger
  upsInPowerFactor NonNegativeInteger
  upsInLineVoltage NonNegativeInteger

UpsOutEntry  
SEQUENCE    
  upsOutLineIndex PositiveInteger
  upsOutVoltage NonNegativeInteger
  upsOutCurrent NonNegativeInteger
  upsOutApparentPower NonNegativeInteger
  upsOutTruePower NonNegativeInteger
  upsOutPowerFactor NonNegativeInteger
  upsOutPercentLoad INTEGER
  upsOutLineVoltage NonNegativeInteger

UpsByEntry  
SEQUENCE    
  upsByLineIndex PositiveInteger
  upsByVoltage NonNegativeInteger
  upsByCurrent NonNegativeInteger
  upsByPower NonNegativeInteger
  upsByLineVoltage INTEGER

SolarGridEntry  
SEQUENCE    
  solarGridLineIndex PositiveInteger
  solarGridVoltage INTEGER
  solarGridCurrent INTEGER
  solarGridPower INTEGER

SolarACOutEntry  
SEQUENCE    
  solarACOutLineIndex PositiveInteger
  solarACOutVoltage INTEGER
  solarACOutTruePower NonNegativeInteger
  solarACOutCurrent INTEGER
  solarACOutPercentLoad NonNegativeInteger

SolarPVEntry  
SEQUENCE    
  solarPVLineIndex PositiveInteger
  solarPVVoltage INTEGER
  solarPVPower NonNegativeInteger

SolarFaultEntry  
SEQUENCE    
  solarFaultLineIndex PositiveInteger
  solarFaultInverterVolt INTEGER
  solarFaultInverterCurr INTEGER
  solarFaultGridVoltage INTEGER
  solarFaultGridCurrent INTEGER
  solarFaultACOutputVolt INTEGER
  solarFaultACOutputCurr INTEGER

Defined Values

nextUPSSystems 1.3.6.1.4.1.21111
The MIB module to describe UPS, Inverter, Salor Power
MODULE-IDENTITY    

products 1.3.6.1.4.1.21111.1
OBJECT IDENTIFIER    

ups 1.3.6.1.4.1.21111.1.1
OBJECT IDENTIFIER    

inverter 1.3.6.1.4.1.21111.1.2
OBJECT IDENTIFIER    

charger 1.3.6.1.4.1.21111.1.3
OBJECT IDENTIFIER    

ats 1.3.6.1.4.1.21111.1.4
OBJECT IDENTIFIER    

upsIdent 1.3.6.1.4.1.21111.1.1.1
OBJECT IDENTIFIER    

upsRating 1.3.6.1.4.1.21111.1.1.2
OBJECT IDENTIFIER    

upsBattery 1.3.6.1.4.1.21111.1.1.3
OBJECT IDENTIFIER    

upsInput 1.3.6.1.4.1.21111.1.1.4
OBJECT IDENTIFIER    

upsOutput 1.3.6.1.4.1.21111.1.1.5
OBJECT IDENTIFIER    

upsBypass 1.3.6.1.4.1.21111.1.1.6
OBJECT IDENTIFIER    

upsTest 1.3.6.1.4.1.21111.1.1.7
OBJECT IDENTIFIER    

upsControl 1.3.6.1.4.1.21111.1.1.8
OBJECT IDENTIFIER    

agentConfig 1.3.6.1.4.1.21111.1.1.9
OBJECT IDENTIFIER    

commConfig 1.3.6.1.4.1.21111.1.1.10
OBJECT IDENTIFIER    

upsConfig 1.3.6.1.4.1.21111.1.1.11
OBJECT IDENTIFIER    

upsTraps 1.3.6.1.4.1.21111.1.1.12
OBJECT IDENTIFIER    

extend 1.3.6.1.4.1.21111.1.1.13
OBJECT IDENTIFIER    

solarIdent 1.3.6.1.4.1.21111.1.2.1
OBJECT IDENTIFIER    

solarRating 1.3.6.1.4.1.21111.1.2.2
OBJECT IDENTIFIER    

solarBattery 1.3.6.1.4.1.21111.1.2.3
OBJECT IDENTIFIER    

solarGrid 1.3.6.1.4.1.21111.1.2.4
OBJECT IDENTIFIER    

solarACOutput 1.3.6.1.4.1.21111.1.2.5
OBJECT IDENTIFIER    

solarPV 1.3.6.1.4.1.21111.1.2.6
OBJECT IDENTIFIER    

solarEnergy 1.3.6.1.4.1.21111.1.2.7
OBJECT IDENTIFIER    

solarTest 1.3.6.1.4.1.21111.1.2.8
OBJECT IDENTIFIER    

solarDefValue 1.3.6.1.4.1.21111.1.2.9
OBJECT IDENTIFIER    

solarFaultInfo 1.3.6.1.4.1.21111.1.2.10
OBJECT IDENTIFIER    

solarControl 1.3.6.1.4.1.21111.1.2.11
OBJECT IDENTIFIER    

solarAgentConfig 1.3.6.1.4.1.21111.1.2.12
OBJECT IDENTIFIER    

solarCommConfig 1.3.6.1.4.1.21111.1.2.13
OBJECT IDENTIFIER    

solarConfig 1.3.6.1.4.1.21111.1.2.14
OBJECT IDENTIFIER    

solarTraps 1.3.6.1.4.1.21111.1.2.15
OBJECT IDENTIFIER    

solarExtend 1.3.6.1.4.1.21111.1.2.16
OBJECT IDENTIFIER    

atsIdent 1.3.6.1.4.1.21111.1.4.1
OBJECT IDENTIFIER    

atsRating 1.3.6.1.4.1.21111.1.4.2
OBJECT IDENTIFIER    

atsInformation 1.3.6.1.4.1.21111.1.4.3
OBJECT IDENTIFIER    

atsControl 1.3.6.1.4.1.21111.1.4.4
OBJECT IDENTIFIER    

atsAgentConfig 1.3.6.1.4.1.21111.1.4.5
OBJECT IDENTIFIER    

atsCommConfig 1.3.6.1.4.1.21111.1.4.6
OBJECT IDENTIFIER    

atsConfig 1.3.6.1.4.1.21111.1.4.7
OBJECT IDENTIFIER    

atsTraps 1.3.6.1.4.1.21111.1.4.8
OBJECT IDENTIFIER    

atsExtend 1.3.6.1.4.1.21111.1.4.9
OBJECT IDENTIFIER    

upsIdManufacturer 1.3.6.1.4.1.21111.1.1.1.1
The name of the UPS manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdProtocol 1.3.6.1.4.1.21111.1.1.1.2
The UPS Protocol id.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80)  

upsIdModelName 1.3.6.1.4.1.21111.1.1.1.3
The UPS Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

upsIdSerialNumber 1.3.6.1.4.1.21111.1.1.1.4
The UPS serial no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdName 1.3.6.1.4.1.21111.1.1.1.5
A string identifying the UPS. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdFWVersion 1.3.6.1.4.1.21111.1.1.1.6
Main CPU firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

upsIdUPSType 1.3.6.1.4.1.21111.1.1.1.7
UPS type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER standy(0), line-interactive(1), on-line(2)  

upsRatinVoltage 1.3.6.1.4.1.21111.1.1.2.1
The rating input voltage of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatoutVoltage 1.3.6.1.4.1.21111.1.1.2.2
The rating output voltage of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatoutFrequency 1.3.6.1.4.1.21111.1.1.2.3
The rating output frequency of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatoutCurrent 1.3.6.1.4.1.21111.1.1.2.4
The rating output current of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatoutApparentPower 1.3.6.1.4.1.21111.1.1.2.5
The rating output apparent power of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatoutTruePower 1.3.6.1.4.1.21111.1.1.2.6
The rating output true power of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsRatBatVoltage 1.3.6.1.4.1.21111.1.1.2.7
The rating battery voltage of UPS
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatStatus 1.3.6.1.4.1.21111.1.1.3.1
The indication of the status in the UPS system's batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8)  

upsBatSecondsOnBattery 1.3.6.1.4.1.21111.1.1.3.2
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatEstMinutesRemaining 1.3.6.1.4.1.21111.1.1.3.3
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatEstChargeRemaining 1.3.6.1.4.1.21111.1.1.3.4
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

upsBatPBatVoltage 1.3.6.1.4.1.21111.1.1.3.5
The magnitude of the present Positive battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatNBatVoltage 1.3.6.1.4.1.21111.1.1.3.6
The magnitude of the present negative battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsBatPBatCurrent 1.3.6.1.4.1.21111.1.1.3.7
The positive battery present current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatNBatCurrent 1.3.6.1.4.1.21111.1.1.3.8
The present negative battery current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatPBatChargCurrent 1.3.6.1.4.1.21111.1.1.3.9
The Positive battery charging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatNBatchargCurrent 1.3.6.1.4.1.21111.1.1.3.10
The present negative battery charging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatPBatDischargCurrent 1.3.6.1.4.1.21111.1.1.3.11
The present positive battery discharging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatNBatDischargCurrent 1.3.6.1.4.1.21111.1.1.3.12
The present negative battery discharging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatTemperature 1.3.6.1.4.1.21111.1.1.3.13
The ambient temperature at or near the UPS Battery casing.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsBatNumberInSeries 1.3.6.1.4.1.21111.1.1.3.14
The number of battery in series.
Status: current Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsBatNumberInParallel 1.3.6.1.4.1.21111.1.1.3.15
The number of battery in Parallel.
Status: current Access: read-only
OBJECT-TYPE    
  PositiveInteger  

upsBatPBatDischargCurrent2 1.3.6.1.4.1.21111.1.1.3.16
The present positive battery pipe2 discharging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInLineBads 1.3.6.1.4.1.21111.1.1.4.1
A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInTtlApparentPower 1.3.6.1.4.1.21111.1.1.4.2
Total input apparent power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInTtlTruePower 1.3.6.1.4.1.21111.1.1.4.3
Total input active(true) power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInNumLines 1.3.6.1.4.1.21111.1.1.4.4
The number of input lines utilized in this device. This variable indicates the number of rows in the input table.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInTable 1.3.6.1.4.1.21111.1.1.4.5
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInEntry

upsInTtlVoltage 1.3.6.1.4.1.21111.1.1.4.6
The input utility line tatol voltage .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInTtlCurrent 1.3.6.1.4.1.21111.1.1.4.7
The input utility line tatol current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInEntry 1.3.6.1.4.1.21111.1.1.4.5.1
An entry containing information applicable to a particular input line.
Status: current Access: not-accessible
OBJECT-TYPE    
  UpsInEntry  

upsInLineIndex 1.3.6.1.4.1.21111.1.1.4.5.1.1
The number of output lines
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

upsInFrequency 1.3.6.1.4.1.21111.1.1.4.5.1.2
The present input frequency.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInVoltage 1.3.6.1.4.1.21111.1.1.4.5.1.3
The input utility line voltage .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInCurrent 1.3.6.1.4.1.21111.1.1.4.5.1.4
The magnitude of the present input current
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsInApparentPower 1.3.6.1.4.1.21111.1.1.4.5.1.5
The magnitude of the present input Apparent power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInTruePower 1.3.6.1.4.1.21111.1.1.4.5.1.6
The magnitude of the present input true power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInPowerFactor 1.3.6.1.4.1.21111.1.1.4.5.1.7
Input true power/apparent power factor
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsInLineVoltage 1.3.6.1.4.1.21111.1.1.4.5.1.8
The input utility line voltage . if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase; if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase; if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutSource 1.3.6.1.4.1.21111.1.1.5.1
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), he-eco-mode(10), converter-mode(11)  

upsOutFrequency 1.3.6.1.4.1.21111.1.1.5.2
The current output frequency of the UPS system
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutTtlApparentPower 1.3.6.1.4.1.21111.1.1.5.3
Total output apparent power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutTtlTruePower 1.3.6.1.4.1.21111.1.1.5.4
Total output active(true) power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutTtlPercentLoad 1.3.6.1.4.1.21111.1.1.5.5
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

upsOutNumLines 1.3.6.1.4.1.21111.1.1.5.6
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutTable 1.3.6.1.4.1.21111.1.1.5.7
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutEntry

upsOutTtlVoltage 1.3.6.1.4.1.21111.1.1.5.8
Total output voltage .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutTtlCurrent 1.3.6.1.4.1.21111.1.1.5.9
Total output current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutStatus 1.3.6.1.4.1.21111.1.1.5.10
For HVDC device. char status[4]; status[0]status[1]:00, no output1; 01, line output1; 02, bat output1 status[2]status[3]:00, no output2; 01, line output2; 02, bat output2
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(4..4)  

upsOutSource2 1.3.6.1.4.1.21111.1.1.5.11
For HVDC(protocol:P12) machine. The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), he-eco-mode(10), converter-mode(11)  

upsOutEntry 1.3.6.1.4.1.21111.1.1.5.7.1
An entry containing information applicable to a particular output line.
Status: current Access: not-accessible
OBJECT-TYPE    
  UpsOutEntry  

upsOutLineIndex 1.3.6.1.4.1.21111.1.1.5.7.1.1
The output line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

upsOutVoltage 1.3.6.1.4.1.21111.1.1.5.7.1.2
The output voltage of the UPS system.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutCurrent 1.3.6.1.4.1.21111.1.1.5.7.1.3
The output current of the UPS system
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutApparentPower 1.3.6.1.4.1.21111.1.1.5.7.1.4
The present output apparent power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutTruePower 1.3.6.1.4.1.21111.1.1.5.7.1.5
The present output true power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutPowerFactor 1.3.6.1.4.1.21111.1.1.5.7.1.6
Output true power/apparent power factor
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsOutPercentLoad 1.3.6.1.4.1.21111.1.1.5.7.1.7
The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

upsOutLineVoltage 1.3.6.1.4.1.21111.1.1.5.7.1.8
The output line voltage of the UPS system. if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase; if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase; if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsOutFrequency 1.3.6.1.4.1.21111.1.1.5.7.1.9
The present output frequency.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsByFrequency 1.3.6.1.4.1.21111.1.1.6.1
The present bypass frequency.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsByNumLines 1.3.6.1.4.1.21111.1.1.6.2
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsByTable 1.3.6.1.4.1.21111.1.1.6.3
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    UpsByEntry

upsByEntry 1.3.6.1.4.1.21111.1.1.6.3.1
An entry containing information applicable to a particular bypass input.
Status: current Access: not-accessible
OBJECT-TYPE    
  UpsByEntry  

upsByLineIndex 1.3.6.1.4.1.21111.1.1.6.3.1.1
The bypass line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

upsByVoltage 1.3.6.1.4.1.21111.1.1.6.3.1.2
The present bypass voltage.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsByCurrent 1.3.6.1.4.1.21111.1.1.6.3.1.3
The present bypass current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsByPower 1.3.6.1.4.1.21111.1.1.6.3.1.4
The present true power conveyed by the bypass.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

upsByLineVoltage 1.3.6.1.4.1.21111.1.1.6.3.1.5
The present bypass line voltage. if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase; if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase; if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsTstBatteryTest 1.3.6.1.4.1.21111.1.1.7.1
This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(1), battTest10sec(2), battTestUntilLow(3), battTestWithTime(4), battTestCancelTest(5), battTestClearInfo(6)  

upsTstBatteryTestResult 1.3.6.1.4.1.21111.1.1.7.2
The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6)  

upsTstBatteryTestStartTime 1.3.6.1.4.1.21111.1.1.7.3
The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(19..19)  

upsTstBatterySettingTime 1.3.6.1.4.1.21111.1.1.7.4
The object specify the test time for battery test
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 12..5940  

upsCtlShutdownDelay 1.3.6.1.4.1.21111.1.1.8.1
The delay in seconds the UPS remains on after being told to turn off. if value=-2 cancel shutdown, if value=-1 donothing, value=0 shutdown ups immediately
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -2..2147483648  

upsCtlSleepTime 1.3.6.1.4.1.21111.1.1.8.2
The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -1..2147483648  

upsCtlStartupAfterDelay 1.3.6.1.4.1.21111.1.1.8.3
Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. -1 mean not startup. must set upsCtlStartupAfterDelay before upsCtlShutdownDelay
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 60..2147483648  

upsCtlbuzzer 1.3.6.1.4.1.21111.1.1.8.4
Setting this object to 'on' or 'off' to enable or disable buzzer
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

upsCtlRemoteControlUPS 1.3.6.1.4.1.21111.1.1.8.5
Setting this object to turn 'on' or 'off' UPS
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

upsCtloutletPoweron 1.3.6.1.4.1.21111.1.1.8.6
Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process
Status: current Access: write-only
OBJECT-TYPE    
  INTEGER 1..2  

upsCtloutletPoweroff 1.3.6.1.4.1.21111.1.1.8.7
Setting this object to 1 means 1st outlet, 2 means 2nd outlet , immediately process
Status: current Access: write-only
OBJECT-TYPE    
  INTEGER 1..2  

upsCtlOutlet1Powerofftime 1.3.6.1.4.1.21111.1.1.8.8
setting this object to -1 means this control not effect, 0 means immediately process, >0 means wait times .use in battery mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -1..999  

upsCtlOutlet2Powerofftime 1.3.6.1.4.1.21111.1.1.8.9
setting this object to -1 means this control not effect, 0 means immediately process , >0 means wait times .use in battery mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER -1..999  

upsCtlResetConfigure 1.3.6.1.4.1.21111.1.1.8.10
reset all configure para to default.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(0), reset(1)  

agentConfigDatetime 1.3.6.1.4.1.21111.1.1.9.1
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(19..19)  

commBaudRate 1.3.6.1.4.1.21111.1.1.10.1
The UPS communicate baudrate
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER b1200(1), b2400(2), b4800(3), b9600(4), b19200(5)  

commDatabits 1.3.6.1.4.1.21111.1.1.10.2
The UPS communicate data bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 8..9  

commStopbits 1.3.6.1.4.1.21111.1.1.10.3
The UPS communicate stop bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

commParity 1.3.6.1.4.1.21111.1.1.10.4
The UPS communicate Parity
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(0), odd(1), even(2)  

commTimeout 1.3.6.1.4.1.21111.1.1.10.5
The UPS communicate timeout
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 100..1000  

upsCfgAlarmbypass 1.3.6.1.4.1.21111.1.1.11.1
Setting this object enable /disable alarm bypass mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgAlarmbattery 1.3.6.1.4.1.21111.1.1.11.2
Setting this object enable/disable alarm battery mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgAutoReboot 1.3.6.1.4.1.21111.1.1.11.3
Setting this object enable/disable auto reboot
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBypasswhenupsoff 1.3.6.1.4.1.21111.1.1.11.4
Setting this object start/stop bypass when ups off
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBatterDDP 1.3.6.1.4.1.21111.1.1.11.5
Setting this object to enable/disable battery deep-discharge protection
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgConvertermode 1.3.6.1.4.1.21111.1.1.11.6
Setting this object to enable/disable converter mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgECOmode 1.3.6.1.4.1.21111.1.1.11.7
Setting this object to enable/disable ECO mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgAdvanceECOmode 1.3.6.1.4.1.21111.1.1.11.8
Setting this object to enable/disable advance ECO mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgGreenPowerFunction 1.3.6.1.4.1.21111.1.1.11.9
Setting this object to enable/disable green power function
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBatteryOSC 1.3.6.1.4.1.21111.1.1.11.10
Setting this object to enable/disable battery open status check
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgAllowShort3times 1.3.6.1.4.1.21111.1.1.11.11
Setting this object to enable/disable short 3 times
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgColdstart 1.3.6.1.4.1.21111.1.1.11.12
Setting this object to cold start ups
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBypassNotAllowed 1.3.6.1.4.1.21111.1.1.11.13
Setting this object to enable/disable bypass mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBatterylowprotect 1.3.6.1.4.1.21111.1.1.11.14
Setting this object to enable/disable battery low protect
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgP1progoutletcontrol 1.3.6.1.4.1.21111.1.1.11.15
Setting this object to enable/disable p1 programmable outlet control (battery mode)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgP2progoutletcontrol 1.3.6.1.4.1.21111.1.1.11.16
Setting this object to enable/disable p2 programmable outlet control (battery mode)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgInverterShortClear 1.3.6.1.4.1.21111.1.1.11.17
Setting this object to enable/disable Inverter short clear function
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgSitefaildetection 1.3.6.1.4.1.21111.1.1.11.18
Setting this object to enable/disable site fail detection
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgBatNumInParallel 1.3.6.1.4.1.21111.1.1.11.19
Battery numbers in parallel (battery numbers setting)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..99  

upsCfgBatNumInSeries 1.3.6.1.4.1.21111.1.1.11.20
Battery numbers in series (battery numbers setting)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..20  

upsCfgBypassmaxvoltage 1.3.6.1.4.1.21111.1.1.11.21
Bypass mode max voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1760..2760  

upsCfgBypassminvoltage 1.3.6.1.4.1.21111.1.1.11.22
Bypass mode min voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1760..2640  

upsCfgBypassmaxfrequency 1.3.6.1.4.1.21111.1.1.11.23
Bypass mode max frequency
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 510..700  

upsCfgBypassminfrequency 1.3.6.1.4.1.21111.1.1.11.24
Bypass mode min frequency
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..590  

upsCfgECOmaxvoltage 1.3.6.1.4.1.21111.1.1.11.25
ECO mode max voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 10..3000  

upsCfgECOminvoltage 1.3.6.1.4.1.21111.1.1.11.26
ECO mode min voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 10..3000  

upsCfgFreeRunMaxFrequency 1.3.6.1.4.1.21111.1.1.11.27
Free run mode max frequency
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

upsCfgFreeRunMinFrequency 1.3.6.1.4.1.21111.1.1.11.28
Free run mode min frequency
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

upsCfgEPOStatus 1.3.6.1.4.1.21111.1.1.11.29
Get EPO status,configured by mamual
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

upsCfgQSK1Status 1.3.6.1.4.1.21111.1.1.11.30
Get QSK 1 status
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

upsCfgQSK2Status 1.3.6.1.4.1.21111.1.1.11.31
Get QSK 2 status
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

upsCfgQSKT1Delaytime 1.3.6.1.4.1.21111.1.1.11.32
Get QSKT 1 time delay
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 000..999  

upsCfgQSKT2Delaytime 1.3.6.1.4.1.21111.1.1.11.33
Get QSKT 2 time delay
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 000..999  

upsCfgConstantPhaseAngle 1.3.6.1.4.1.21111.1.1.11.34
setting this object to Enable/disable Constant Phase Angle function
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

upsCfgInPhaseAngle 1.3.6.1.4.1.21111.1.1.11.35
Get input phase angle
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER b000(0), b120(120), b180(180), b240(240)  

upsCfgOutPhaseAngle 1.3.6.1.4.1.21111.1.1.11.36
Set output phase angle
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER b000(0), b120(120), b180(180), b240(240)  

upsCfgLimiRunOnBatMode 1.3.6.1.4.1.21111.1.1.11.37
Enable/disable limited runtime on battery mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

upsCfgChargingCurrent 1.3.6.1.4.1.21111.1.1.11.38
Set charging current to battery .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

upsCfgBatSeftCheckVolt 1.3.6.1.4.1.21111.1.1.11.39
BatTest until battery voltage lower than
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 2400..2800  

upsCfgOverChargVolt 1.3.6.1.4.1.21111.1.1.11.40
set over charging voltage to per battery
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 130..143  

upsCfgBattUnderVolt 1.3.6.1.4.1.21111.1.1.11.41
set battery under voltage of setting value.value is a number ranging from 200V to 240V
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 2000..2400  

upsCfgBattLowVolt 1.3.6.1.4.1.21111.1.1.11.42
set battery low voltage of setting value.it is 10 to 40V high than battery under voltage. it is 10 to 40V high than battery under voltage.default 20. it means that the battery low point is battery under add 20. for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

upsCfgIn1VoltHLoss 1.3.6.1.4.1.21111.1.1.11.43
set input1 voltage high loss point.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

upsCfgIn1VoltLLoss 1.3.6.1.4.1.21111.1.1.11.44
set input1 voltage low loss point.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

upsCfgIn2VoltHLoss 1.3.6.1.4.1.21111.1.1.11.45
set input2 voltage high loss point.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

upsCfgIn2VoltLLoss 1.3.6.1.4.1.21111.1.1.11.46
set input2 voltage low loss point.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

upsCfgBatteryTurnOn 1.3.6.1.4.1.21111.1.1.11.47
Enable/disable battery turn on.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

trapleafnodev103 1.3.6.1.4.1.21111.1.1.12.998
The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node char trap[16]; trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap
Status: current Access: not-accessible
OBJECT-TYPE    
  DisplayString Size(16..16)  

trapleafnodev1v2 1.3.6.1.4.1.21111.1.1.12.999
The share trap-node for send all traps
Status: current Access: not-accessible
OBJECT-TYPE    
  INTEGER 0..255  

cmpACFailure 1
AC failure
TRAP-TYPE    

cmpFanFailure 2
Fan failure
TRAP-TYPE    

cmpUPSFailure 3
UPS failure
TRAP-TYPE    

cmpChargerFailure 4
Charger failure
TRAP-TYPE    

cmpOverloadFailure 5
Overload failure
TRAP-TYPE    

cmpOvertempFailure 6
Over temperature fault.
TRAP-TYPE    

cmpInvertershortcircuited 7
Inverter short-circuited
TRAP-TYPE    

cmpbatteryfusebeingoc 8
Battery fuse being open-dcircuited failure
TRAP-TYPE    

cmpLowbattery 9
The UPS has returned from a low battery condition.
TRAP-TYPE    

cmpSysgotoshutdown 10
System is going to shutdown
TRAP-TYPE    

cmpSitefault 11
Site fault
TRAP-TYPE    

cmpPhasesequenceincorrect 12
Phase sequence incorrect
TRAP-TYPE    

cmpPhasesequenceincorrectbypass 13
Phase sequence incorrect in bypass
TRAP-TYPE    

cmpFanalarm 14
Fan alarm.
TRAP-TYPE    

cmpEPOenabled 15
EPO enabled
TRAP-TYPE    

cmpUnabletotrunonUPS 16
Unalbe to turn on UPS
TRAP-TYPE    

cmpOvertemperaturealarm 17
Over temperature alarm
TRAP-TYPE    

cmpInputfrequnstablebypass 18
Input frequency unstable in bypass
TRAP-TYPE    

cmpChargeralarm 19
Charger alarm
TRAP-TYPE    

cmpL1inputfusenotwork 20
L1 input fuse not working
TRAP-TYPE    

cmpNeutralnotConnected 21
Neutral not connected
TRAP-TYPE    

cmpL2inputfusenotwork 22
L2 input fuse not working
TRAP-TYPE    

cmpL3inputfusenotwork 23
L3 input fuse not working
TRAP-TYPE    

cmpPositivePFCabnormalL1 24
Positive PFC abnormal in L1
TRAP-TYPE    

cmpNegativePFCabnormalL1 25
Negative PFC abnormal in L1
TRAP-TYPE    

cmpPositivePFCabnormalL2 26
Positive PFC abnormal in L2
TRAP-TYPE    

cmpNegativePFCabnormalL2 27
Negative PFC abnormal in L2
TRAP-TYPE    

cmpPositivePFCabnormalL3 28
Positive PFC abnormal in L3
TRAP-TYPE    

cmpNegativePFCabnormalL3 29
Negative PFC abnormal in L3
TRAP-TYPE    

cmpBusvoltagenotwds 30
Bus voltage not within default setting
TRAP-TYPE    

cmpBusvoltageovermaxvalue 31
Bus voltage over maxinum value
TRAP-TYPE    

cmpBusvoltagebelowminvalue 32
Bus voltage below mininum value
TRAP-TYPE    

cmpBusvoltagediffoutofrange 33
Bus voltage differences out fo acceptable range
TRAP-TYPE    

cmpBusvoltageofsloperatetoofast 34
Bus voltage of slope rate drops too fast
TRAP-TYPE    

cmpOvercurrentinPFCII 35
WARNING:Over current in PFC input inductor.
TRAP-TYPE    

cmpInvertervoloutofrange 36
Inverter voltage not within default setting.
TRAP-TYPE    

cmpInvertervolovermaxvalue 37
Inverter voltage over maximum value.
TRAP-TYPE    

cmpInvertervolbelowminvalue 38
Inverter voltage below minimum value.
TRAP-TYPE    

cmpBatteryoppositelyconnected 39
Battery oppositely connected.
TRAP-TYPE    

cmpL2phaseshortcicuited 40
L2Phase inverter short-cicuited.
TRAP-TYPE    

cmpL3phaseshortcicuited 41
L3Phase inverter short-cicuited.
TRAP-TYPE    

cmpL1L2invertershortcicuited 42
L1L2Inverter short-cicuited.
TRAP-TYPE    

cmpL2L3invertershortcicuited 43
L2L3Inverter short-cicuited.
TRAP-TYPE    

cmpL3L1invertershortcicuited 44
L3L1Inverter short-cicuited.
TRAP-TYPE    

cmpL1negativepoweroutofrange 45
L1 inverter negative powere out of acceptable range.
TRAP-TYPE    

cmpL2negativepoweroutofrange 46
L2 inverter negative powere out of acceptable range.
TRAP-TYPE    

cmpL3negativepoweroutofrange 47
L3 inverter negative powere out of acceptable range.
TRAP-TYPE    

cmpBatterySCRshortcircuited 48
Battery SCR short-circuited.
TRAP-TYPE    

cmpLineSCRshortcircuited 49
Line SCR short-circuited.
TRAP-TYPE    

cmpInverterrelayopenfault 50
Inverter relay open fault.
TRAP-TYPE    

cmpInverterrelayshortcircuited 51
Inverter relay short-circuited.
TRAP-TYPE    

cmpInoutwiresoppositelyconnected 52
Input and output wires oppositely connected.
TRAP-TYPE    

cmpabnormalcanbuscommunication 53
Abnormal in CAN-bus communication.
TRAP-TYPE    

cmpcommfailurebcupsboard 54
Communication failure between cpus in control board.Or DSP and MCU communication error
TRAP-TYPE    

cmpabnormalsyncsignalcircuit 55
Abnomal in synchronous signal circuit.
TRAP-TYPE    

cmpabnormalsyncpulsesignalcircuit 56
Abnomal in synchronous pulse signal circuit.
TRAP-TYPE    

cmpcurrent3punbalancedetected 57
Warning for a three-phase input current unbalance detected.
TRAP-TYPE    

cmpbatteryselftestfailure 58
Battery self-test failure.
TRAP-TYPE    

cmpintercurrentunbalance 59
Inverter inter-current unbalance.
TRAP-TYPE    

cmpbatterydisconnected 60
Battery disconnected.
TRAP-TYPE    

cmpabnormalhostsignalcircuit 61
Abnormal in host signal circuit.
TRAP-TYPE    

cmpbatteryovercharged 62
Bettery overcharged.
TRAP-TYPE    

cmpbatteryvoltoohigh 63
Bettery voltage is too high.
TRAP-TYPE    

cmpbatteryvoltoolow 64
Bettery voltage is too low.
TRAP-TYPE    

cmpfemaleconnectornotconnwell 65
Female connector of parallel cable not connected well.
TRAP-TYPE    

cmpmaleconnectornotconnwell 66
Male connector of parallel cable not connected well.
TRAP-TYPE    

cmplockingbypassA3COW30M 67
Locking inbypass mode after 3 consecutive overloads within 30 minutes
TRAP-TYPE    

cmpparallelcabledisconnected 68
Parallel cable disconnected
TRAP-TYPE    

cmpsyncpulsecircuitfault 69
Synchronous pulse signal circuit fault
TRAP-TYPE    

cmpsyncsignalcircuitfalt 70
Synchronous signal circuit fault
TRAP-TYPE    

cmphostsignalcircuitfault 71
Host signal circuit fault
TRAP-TYPE    

cmpcanbuscommunicationfault 72
Can-bus communication fault
TRAP-TYPE    

cmplowlosspointforvolinACmode 73
Low loss point for voltage in ac mode not consistent in parallel systems
TRAP-TYPE    

cmphighlosspointforvolinACmode 74
High loss point for voltage in ac mode not consistent in parallel systems
TRAP-TYPE    

cmplowlosspointforfreqinACmode 75
Low loss point for frequency in ac mode not consistent in parallel systems
TRAP-TYPE    

cmphighlosspointforfreqinACmode 76
High loss point for frequency in ac mode not consistent in parallel systems
TRAP-TYPE    

cmplowlosspointforvolinbypassmode 77
Low loss point for voltage in bypass mode not consistent in parallel systems
TRAP-TYPE    

cmphighlosspointforvolinbypassmode 78
High loss point for voltage in bypass mode not consistent in parallel systems
TRAP-TYPE    

cmplowlosspointforfreqinbypassmode 79
Low loss point for frequency in bypass mode not consistent in parallel systems
TRAP-TYPE    

cmphighlosspointforfreqinbypassmode 80
High loss point for frequency in bypass mode not consistent in parallel systems
TRAP-TYPE    

cmploadunbalanced 81
Load unbalanced
TRAP-TYPE    

cmpoverloadalarm 82
Overload alarm
TRAP-TYPE    

cmpparallelnotconnectedwell 83
Parallel cable not connected well
TRAP-TYPE    

cmpcommunicationlost 84
Communication lost
TRAP-TYPE    

cmpbatteryconnnotsonsistent 85
Battery connection not consistent in parallel systems
TRAP-TYPE    

cmpconverternotconsisstent 86
Converter setting not consistent in parallel systems
TRAP-TYPE    

cmpbypassnotallownotconsistent 87
Bypass not allowed setting not consistent in parallel systems
TRAP-TYPE    

cmpACconnnotconsistent 88
AC connection not consistent in parallel systems
TRAP-TYPE    

cmpinput3pcurrentunbalance 89
Warning for three-phase ac input current unbalance
TRAP-TYPE    

cmpbypassconnnotconsistent 90
Bypass connection not consistent in parallel systems
TRAP-TYPE    

cmpbatteryprotectionnotconsistent 91
Battery protection setting not consistent in parallel systems
TRAP-TYPE    

cmpbatterydetectionnotconsistent 92
Battery detection setting not consistent in parallel systems
TRAP-TYPE    

cmpupsmodeltypesnotconsistent 93
UPS model types not consistent in parallel systems
TRAP-TYPE    

cmpbypassnotconsistent 94
Bypass setting not consistent in parallel systems
TRAP-TYPE    

cmpcapacitynotconsistent 95
Capacity of upss not consistent in parallel systems
TRAP-TYPE    

cmpautorestartnotconsistent 96
Auto restart setting not consistent in parallel systems
TRAP-TYPE    

cmpBatteryReplace 97
Battery need to be replace
TRAP-TYPE    

cmpACNormal 100
AC normal
TRAP-TYPE    

cmpOutputBadAlarm 103
Output bad alarm
TRAP-TYPE    

cmpBypassBadAlarm 104
Bypass bad alarm
TRAP-TYPE    

cmpOutputOffAlarm 105
Output off alarm
TRAP-TYPE    

cmpUPSShutAlarm 106
UPS shutdown alarm
TRAP-TYPE    

cmpSystemOffAlarm 107
System off alarm
TRAP-TYPE    

cmpFuseFailureAlarm 108
Fuse failure alarm
TRAP-TYPE    

cmpGenFailureAlarm 109
General failure alarm
TRAP-TYPE    

cmpAwaitPowerAlarm 110
Awaiting power alarm
TRAP-TYPE    

cmpShutPendingAlarm 111
Shutdown pending alarm
TRAP-TYPE    

cmpBatDepleted 112
Battery depleted
TRAP-TYPE    

cmpUnknowStatus 113
Battery unknow status
TRAP-TYPE    

cmpOutputOn 114
Output on
TRAP-TYPE    

cmpTurntobypass 115
Ups turn to bypass mode
TRAP-TYPE    

cmpTurntobattery 116
Ups turn to battery mode
TRAP-TYPE    

cmpOutBooster 117
Turn to booster
TRAP-TYPE    

cmpOutReducer 118
Turn to reducer
TRAP-TYPE    

cmpOutBattest 119
Turn to battery test mode
TRAP-TYPE    

cmpOtherSource 120
Other source
TRAP-TYPE    

cmpBatfailure 121
Battery failure
TRAP-TYPE    

cmpBatTestDonePassed 122
Battery test passed
TRAP-TYPE    

cmpBatTestDoneWarning 123
Battery test done warning
TRAP-TYPE    

cmpBatTestDoneAborted 124
Battery test done Aborted
TRAP-TYPE    

cmpBatteryNormal 125
Battery normal
TRAP-TYPE    

cmpBatteryDischarging 126
Battery Discharging
TRAP-TYPE    

cmpP1cutoffprealarm 127
P1 cut off pre-alarm
TRAP-TYPE    

cmpInputPhaseError 128
Warning for input phase error for LV 6-10K UPS
TRAP-TYPE    

cmpMaintainSwitchOpenalarm 129
Warning for maintain switch open
TRAP-TYPE    

cmpEMDChAbnormal1 130
EMD Channels 1 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal2 131
EMD Channels 2 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal3 132
EMD Channels 3 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal4 133
EMD Channels 4 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal5 134
EMD Channels 5 Abnormal: smoke alarm
TRAP-TYPE    

cmpEMDChAbnormal6 135
EMD Channels 6 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal7 136
EMD Channels 7 Abnormal
TRAP-TYPE    

cmpEMDChAbnormal8 137
EMD Channels 8 Abnormal
TRAP-TYPE    

extendWorkTemperature 1.3.6.1.4.1.21111.1.1.13.1
The temperature of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER -2200..2200  

extendWorkhumidity 1.3.6.1.4.1.21111.1.1.13.2
The humidity of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

extendSmokeScope 1.3.6.1.4.1.21111.1.1.13.3
The smokeScope of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..1000000  

extendEMDAlarm1 1.3.6.1.4.1.21111.1.1.13.4
Environment detector alarm 1
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

extendEMDAlarm2 1.3.6.1.4.1.21111.1.1.13.5
Environment detector alarm 2
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

extendEMDAlarm3 1.3.6.1.4.1.21111.1.1.13.6
Environment detector alarm 3
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

extendEMDAlarm4 1.3.6.1.4.1.21111.1.1.13.7
Environment detector alarm 4
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

solarIdManufacturer 1.3.6.1.4.1.21111.1.2.1.1
The name of the solar manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

solarIdProtocol 1.3.6.1.4.1.21111.1.2.1.2
The solar Protocol id.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80), p15(15)  

solarIdModelName 1.3.6.1.4.1.21111.1.2.1.3
The solar Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

solarIdSerialNumber 1.3.6.1.4.1.21111.1.2.1.4
The solar serial no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

solarIdFWVersion 1.3.6.1.4.1.21111.1.2.1.5
Main CPU firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

solarIdFW2Version 1.3.6.1.4.1.21111.1.2.1.6
Main CPU 2 firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

solarIdSolarType 1.3.6.1.4.1.21111.1.2.1.7
solar type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER grid-tie(0), off-grid(1), hybrid(10)  

solarIdTopology 1.3.6.1.4.1.21111.1.2.1.8
solar Topology.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER transformerless(0), transformer(1)  

solarIdCriterion 1.3.6.1.4.1.21111.1.2.1.9
solar device criterion.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

solarRatOutPower 1.3.6.1.4.1.21111.1.2.2.1
The rating Output Power of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatApparentPower 1.3.6.1.4.1.21111.1.2.2.2
The rating output apparent power of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatGridVoltage 1.3.6.1.4.1.21111.1.2.2.3
The rating output voltage of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatGridFrequency 1.3.6.1.4.1.21111.1.2.2.4
The rating grid frequency of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatGridCurrent 1.3.6.1.4.1.21111.1.2.2.5
The rating grid current of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatPerMPPTCurrent 1.3.6.1.4.1.21111.1.2.2.6
Per MPPT rating current
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatPVInputVoltage 1.3.6.1.4.1.21111.1.2.2.7
Nominal device Voltage,pv input Voltage
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatACOutVoltage 1.3.6.1.4.1.21111.1.2.2.8
The rating AC output voltage of solar inverter
Status: current Access: read-write
OBJECT-TYPE    
  NonNegativeInteger a(208), b(220), c(230), d(240)  

solarRatACOutCurrent 1.3.6.1.4.1.21111.1.2.2.9
The rating AC output current of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarRatBatVoltage 1.3.6.1.4.1.21111.1.2.2.10
The rating battery voltage of solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarBatStatus 1.3.6.1.4.1.21111.1.2.3.1
The indication of the status in the solar system's batteries.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8)  

solarBatSecondsOnBattery 1.3.6.1.4.1.21111.1.2.3.2
If the unit is on battery power, the elapsed time since the solar last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatEstMinutesRemaining 1.3.6.1.4.1.21111.1.2.3.3
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatEstChargeRemaining 1.3.6.1.4.1.21111.1.2.3.4
An estimate of the battery charge remaining expressed as a percent of full charge.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

solarBatPBatVoltage 1.3.6.1.4.1.21111.1.2.3.5
The magnitude of the present Positive battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarBatNBatVoltage 1.3.6.1.4.1.21111.1.2.3.6
The magnitude of the present negative battery voltage.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarBatPBatCurrent 1.3.6.1.4.1.21111.1.2.3.7
The positive battery present current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatNBatCurrent 1.3.6.1.4.1.21111.1.2.3.8
The present negative battery current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatPBatChargCurrent 1.3.6.1.4.1.21111.1.2.3.9
The Positive battery charging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatNBatchargCurrent 1.3.6.1.4.1.21111.1.2.3.10
The present negative battery charging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatPBatDischargCurrent 1.3.6.1.4.1.21111.1.2.3.11
The present positive battery discharging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatNBatDischargCurrent 1.3.6.1.4.1.21111.1.2.3.12
The present negative battery discharging current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatTemperature 1.3.6.1.4.1.21111.1.2.3.13
The ambient temperature at or near the solar Battery casing.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarBatNumberInSeries 1.3.6.1.4.1.21111.1.2.3.14
The number of battery in series.
Status: current Access: read-only
OBJECT-TYPE    
  PositiveInteger  

solarBatNumberInParallel 1.3.6.1.4.1.21111.1.2.3.15
The number of battery in Parallel.
Status: current Access: read-only
OBJECT-TYPE    
  PositiveInteger  

solarBatChargingCurrent 1.3.6.1.4.1.21111.1.2.3.16
Charging Current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridSource 1.3.6.1.4.1.21111.1.2.4.1
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), poweron(6), shutdown(7), batterytest(8), fault(9), grid-mode(10), charge-mode(11)  

solarGridTtlApparentPower 1.3.6.1.4.1.21111.1.2.4.2
Total grid output apparent power .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridTtlTruePower 1.3.6.1.4.1.21111.1.2.4.3
Total grid output active(true) power .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridFrequency 1.3.6.1.4.1.21111.1.2.4.4
Total grid frequency.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarGridNumLine 1.3.6.1.4.1.21111.1.2.4.5
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridTemperature 1.3.6.1.4.1.21111.1.2.4.6
Max Temperature of the detecting pointers.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridStatus 1.3.6.1.4.1.21111.1.2.4.7
Device status. b31-b16:NG b15: NG b14: NG b13: NG b12: NG b11: Load status 0: Load off 1:Load on b10: Battery status b9: Battery status b10b9: 00: Do nothing 01: Charging 10: Discharging b8: Inv direction 0: DC-AC 1: AC-DC b7: Line direction b6: Line direction a7a6: 00 means unsteady 01 means Line input 10 means Line output b5-b0:NG
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridTable 1.3.6.1.4.1.21111.1.2.4.8
A list of solar grid table entries. The number of entries is given by the value of solarGridputNumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarGridEntry

solarGridEntry 1.3.6.1.4.1.21111.1.2.4.8.1
An entry containing information applicable to a particular grid line.
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarGridEntry  

solarGridLineIndex 1.3.6.1.4.1.21111.1.2.4.8.1.1
The grid line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

solarGridVoltage 1.3.6.1.4.1.21111.1.2.4.8.1.2
The Grid voltage of the solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridCurrent 1.3.6.1.4.1.21111.1.2.4.8.1.3
The Grid current of the solar inverter
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarGridPower 1.3.6.1.4.1.21111.1.2.4.8.1.4
The present Grid output true power.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarACOutNumLines 1.3.6.1.4.1.21111.1.2.5.1
AC output lines number.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarACOutFrequency 1.3.6.1.4.1.21111.1.2.5.2
AC output frequency .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarACOutTtlPower 1.3.6.1.4.1.21111.1.2.5.3
Total AC output total active(true) power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarACOutTtlPercentLoad 1.3.6.1.4.1.21111.1.2.5.4
Total AC output total percent load.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

solarACOutTable 1.3.6.1.4.1.21111.1.2.5.5
A list of AC output table entries. The number of entries is given by the value of solarACOut NumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarACOutEntry

solarACOutEntry 1.3.6.1.4.1.21111.1.2.5.5.1
An entry containing information applicable to a particular input line.
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarACOutEntry  

solarACOutLineIndex 1.3.6.1.4.1.21111.1.2.5.5.1.1
The number of PV line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

solarACOutVoltage 1.3.6.1.4.1.21111.1.2.5.5.1.2
The AC output voltage .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarACOutTruePower 1.3.6.1.4.1.21111.1.2.5.5.1.3
The magnitude of the present AC output true power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarACOutCurrent 1.3.6.1.4.1.21111.1.2.5.5.1.4
The magnitude of the present AC output current.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarACOutPercentLoad 1.3.6.1.4.1.21111.1.2.5.5.1.5
The magnitude of the present AC output percent load
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

solarPVNumLines 1.3.6.1.4.1.21111.1.2.6.1
PV input lines number.
Status: current Access: read-write
OBJECT-TYPE    
  NonNegativeInteger 0..99  

solarPVTtlPower 1.3.6.1.4.1.21111.1.2.6.2
Total PV input active(true) power .
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarPVTable 1.3.6.1.4.1.21111.1.2.6.3
A list of solar PV input table entries. The number of entries is given by the value of solarPV NumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarPVEntry

solarPVEntry 1.3.6.1.4.1.21111.1.2.6.3.1
An entry containing information applicable to a particular input line.
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarPVEntry  

solarPVLineIndex 1.3.6.1.4.1.21111.1.2.6.3.1.1
The number of PV line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

solarPVVoltage 1.3.6.1.4.1.21111.1.2.6.3.1.2
The PV input voltage .
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarPVPower 1.3.6.1.4.1.21111.1.2.6.3.1.3
The magnitude of the present input true power.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarEnergyFirstTimeEnergy 1.3.6.1.4.1.21111.1.2.7.1
the time when the user fist storage capacity
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10..10)  

solarEnergyHourT 1.3.6.1.4.1.21111.1.2.7.2
write the hour when we will inquiry energy in the hour
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(10..10)  

solarEnergyHourE 1.3.6.1.4.1.21111.1.2.7.3
0xfeffffff:doing inquiry 0xffffffff:error
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(9..9)  

solarEnergyDayT 1.3.6.1.4.1.21111.1.2.7.4
the time when we will inquiry energy in the day
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(8..8)  

solarEnergyDayE 1.3.6.1.4.1.21111.1.2.7.5
0xfeffffff:doing inquiry 0xffffffff:error
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(9..9)  

solarEnergyMonT 1.3.6.1.4.1.21111.1.2.7.6
the time
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(6..6)  

solarEnergyMonE 1.3.6.1.4.1.21111.1.2.7.7
0xfeffffff:doing inquiry 0xffffffff:error
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(9..9)  

solarEnergyYearT 1.3.6.1.4.1.21111.1.2.7.8
The time
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(4..4)  

solarEnergyYearE 1.3.6.1.4.1.21111.1.2.7.9
0xfeffffff:doing inquiry 0xffffffff:error
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(9..9)  

solarEnergyHourID 1.3.6.1.4.1.21111.1.2.7.10
ID.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarEnergyDayID 1.3.6.1.4.1.21111.1.2.7.11
ID.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarEnergyMonID 1.3.6.1.4.1.21111.1.2.7.12
ID.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarEnergyYearID 1.3.6.1.4.1.21111.1.2.7.13
ID.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarTestStartSelfTest 1.3.6.1.4.1.21111.1.2.8.1
Setting this object to 'start' to start test
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER null(0), start(1)  

solarTestSelfTestResult 1.3.6.1.4.1.21111.1.2.8.2
an Integer ranging from 0 to 9. 0 means self test being processed, 1 means self test succeed, 2 means self test fail.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER processeing(0), succeed(1), fail(2)  

solarTestGridOutHVol 1.3.6.1.4.1.21111.1.2.8.3
Self test grid output high voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarTestGridOutLVol 1.3.6.1.4.1.21111.1.2.8.4
Self test grid output low voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarTestGridOutHFreq 1.3.6.1.4.1.21111.1.2.8.5
Self test grid output high frequency
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarTestGridOutLFreq 1.3.6.1.4.1.21111.1.2.8.6
Self test grid output low frequency
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarTestChOutHVol 1.3.6.1.4.1.21111.1.2.8.7
The check time of self test grid output high voltage
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarTestChOutLVol 1.3.6.1.4.1.21111.1.2.8.8
The check time of self test grid output low voltage
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarTestChOutHFreq 1.3.6.1.4.1.21111.1.2.8.9
The check time of self test grid output high frequency
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarTestChOutLFreq 1.3.6.1.4.1.21111.1.2.8.10
The check time of self test grid output low frequency
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarDefGridOutVolHLoss 1.3.6.1.4.1.21111.1.2.9.1
The default setting value of grid output voltage high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridOutVolLLoss 1.3.6.1.4.1.21111.1.2.9.2
The default setting value of grid output voltage lowloss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridOutFreqHLoss 1.3.6.1.4.1.21111.1.2.9.3
The default setting value Grid output frequency high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridOutFreqLLoss 1.3.6.1.4.1.21111.1.2.9.4
The default setting value Grid output frequency low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridInVolHLoss 1.3.6.1.4.1.21111.1.2.9.5
The default setting value Grid input voltage high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridInVolLLoss 1.3.6.1.4.1.21111.1.2.9.6
The default setting value Grid input voltage low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridInFreqHLoss 1.3.6.1.4.1.21111.1.2.9.7
The default setting value Grid input frequency high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefGridInFreqLLoss 1.3.6.1.4.1.21111.1.2.9.8
The default setting value Grid input frequency low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefUpLimitPVVol 1.3.6.1.4.1.21111.1.2.9.9
The default setting value The upper limit of PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefLowLimitPVVol 1.3.6.1.4.1.21111.1.2.9.10
The default setting value The lowest limit of PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefPVHVolMPPT 1.3.6.1.4.1.21111.1.2.9.11
The default setting value The PV input high voltage for MPPT
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefPVLVolMPPT 1.3.6.1.4.1.21111.1.2.9.12
The default setting value The PV input low voltage for MPPT
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxOutPower 1.3.6.1.4.1.21111.1.2.9.13
The default setting value Max output power
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefAverageVolHLoss 1.3.6.1.4.1.21111.1.2.9.14
The default setting value Long time grid average voltage high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefLCDSleepTime 1.3.6.1.4.1.21111.1.2.9.15
The default setting value LCD sleep time
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefBatteryNum 1.3.6.1.4.1.21111.1.2.9.16
The default setting value Battery piece number
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarDefBattTtlCapacit 1.3.6.1.4.1.21111.1.2.9.17
The default setting value Battery total capacity
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarDefChargerCurrent 1.3.6.1.4.1.21111.1.2.9.18
The default setting value Charger current
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarDefMaxChargeVol 1.3.6.1.4.1.21111.1.2.9.19
The default setting the max charging voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxChargeCurr 1.3.6.1.4.1.21111.1.2.9.20
The default setting the max charging current
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefWaiteTimeFeed 1.3.6.1.4.1.21111.1.2.9.21
The default setting waiting time for feeding
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMaxGridOutVolHLoss 1.3.6.1.4.1.21111.1.2.9.22
The max grid output voltage high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMinGridOutVolHLoss 1.3.6.1.4.1.21111.1.2.9.23
The min grid output voltage high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxGridOutVolLLoss 1.3.6.1.4.1.21111.1.2.9.24
The max grid output voltage low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMinGridOutVolLLoss 1.3.6.1.4.1.21111.1.2.9.25
The min grid output voltage low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxGridOutFreqHLoss 1.3.6.1.4.1.21111.1.2.9.26
The max grid output frequency high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMinGridOutFreqHLoss 1.3.6.1.4.1.21111.1.2.9.27
The min grid output frequency high loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxGridOutFreqLLoss 1.3.6.1.4.1.21111.1.2.9.28
The max grid output frequency low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMinGridOutFreqLLoss 1.3.6.1.4.1.21111.1.2.9.29
The min grid output frequency low loss point
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarDefMaxWaiteTimeFeed 1.3.6.1.4.1.21111.1.2.9.30
The max waiting time for feeding
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMinWaiteTimeFeed 1.3.6.1.4.1.21111.1.2.9.31
The min waiting time for feeding
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMaxMaxFChargVolt 1.3.6.1.4.1.21111.1.2.9.32
The max voltage for max floating charging voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMinMaxFChargVolt 1.3.6.1.4.1.21111.1.2.9.33
The min voltage for max floating charging voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMaxMaxRChargCurr 1.3.6.1.4.1.21111.1.2.9.34
The upper limit of max charging current(real charging)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMinMaxRChargCurr 1.3.6.1.4.1.21111.1.2.9.35
The lower limit of max charging current(real charging)
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMaxMaxPVInputVolt 1.3.6.1.4.1.21111.1.2.9.36
The upper limit of max PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMinMaxPVInputVolt 1.3.6.1.4.1.21111.1.2.9.37
The lower limit of max PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMaxMinPVInputVolt 1.3.6.1.4.1.21111.1.2.9.38
The upper limit of min PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMinMinPVInputVolt 1.3.6.1.4.1.21111.1.2.9.39
The lowest limit of min PV input voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMaxHighMPPTVolt 1.3.6.1.4.1.21111.1.2.9.40
The max MPPT high voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMinHighMPPTVolt 1.3.6.1.4.1.21111.1.2.9.41
The min MPPT high voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMaxLowMPPTVolt 1.3.6.1.4.1.21111.1.2.9.42
The max MPPT low voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMinLowMPPTVolt 1.3.6.1.4.1.21111.1.2.9.43
The min MPPT low voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..9990  

solarDefMaxOutputPower 1.3.6.1.4.1.21111.1.2.9.44
The max output power
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999990  

solarDefMinOutputPower 1.3.6.1.4.1.21111.1.2.9.45
The min output power
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999990  

solarDefMaxRChargVolt 1.3.6.1.4.1.21111.1.2.9.46
The min charging voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarDefMinRChargVolt 1.3.6.1.4.1.21111.1.2.9.47
The max charging voltage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..999  

solarFaultCurrentID 1.3.6.1.4.1.21111.1.2.10.1
current fault ID.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..8  

solarFaultQueryFaultID 1.3.6.1.4.1.21111.1.2.10.2
query fault ID.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..8  

solarFaultQueryResult 1.3.6.1.4.1.21111.1.2.10.3
Query fault info result.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER doneSucess(1), doneError(2), inProgress(3)  

solarFaultFaultKind 1.3.6.1.4.1.21111.1.2.10.4
Device Fault kind.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2..2)  

solarFaultFaultTime 1.3.6.1.4.1.21111.1.2.10.5
Device Fault time.format is YYYYMMDDHHMMSS
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(14..14)  

solarFaultPVStatus 1.3.6.1.4.1.21111.1.2.10.6
PV running status before fault. b31-b16:reserved b15 : PV1 boost on b14 : PV2 boost on b13 : PV3 boost on b12 : Inverter on b11 : 1: PV1 MPPT by boost; 0: PV1 MPPT by inverter b10 : 1: PV2 MPPT by boost; 0: PV2 MPPT by inverter b9 : 1: PV3 MPPT by boost; 0: PV3 MPPT by inverter b8 : O/P relay on b7 : Inverter relay on b6 : Safe relay on b5 : Main relay on b4 : AC relay on b3 : Reserved b2 : Reserved b1 : Reserved b0 : DC TO DC on
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultTemperature 1.3.6.1.4.1.21111.1.2.10.7
Max Temperature of the detecting pointers before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultBattVolt 1.3.6.1.4.1.21111.1.2.10.8
Battery voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultPV1Voltage 1.3.6.1.4.1.21111.1.2.10.9
PV1 input voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultPV1Current 1.3.6.1.4.1.21111.1.2.10.10
PV1 current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultPV2Voltage 1.3.6.1.4.1.21111.1.2.10.11
PV2 input voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultPV2Current 1.3.6.1.4.1.21111.1.2.10.12
PV2 current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultPV3Voltage 1.3.6.1.4.1.21111.1.2.10.13
PV3 input voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultPV3Current 1.3.6.1.4.1.21111.1.2.10.14
PV3 current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultNumLines 1.3.6.1.4.1.21111.1.2.10.15
AC output,Grid and Inverter lines number.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultGridFrequency 1.3.6.1.4.1.21111.1.2.10.16
Grid frequency before fault.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultACOutFrequency 1.3.6.1.4.1.21111.1.2.10.17
AC output Frequency before fault.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultLoadPercent 1.3.6.1.4.1.21111.1.2.10.18
Output load percentage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

solarFaultTable 1.3.6.1.4.1.21111.1.2.10.19
A list of fault table entries. The number of entries is given by the value of solarFault NumLines.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SolarFaultEntry

solarFaultEntry 1.3.6.1.4.1.21111.1.2.10.19.1
An entry containing information applicable to a particular input line.
Status: current Access: not-accessible
OBJECT-TYPE    
  SolarFaultEntry  

solarFaultLineIndex 1.3.6.1.4.1.21111.1.2.10.19.1.1
The number of inverter,grid and ACOutput line identifier.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..10  

solarFaultInverterVolt 1.3.6.1.4.1.21111.1.2.10.19.1.2
Inverter voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultInverterCurr 1.3.6.1.4.1.21111.1.2.10.19.1.3
Inverter current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultGridVoltage 1.3.6.1.4.1.21111.1.2.10.19.1.4
Grid voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultGridCurrent 1.3.6.1.4.1.21111.1.2.10.19.1.5
Grid current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultACOutputVolt 1.3.6.1.4.1.21111.1.2.10.19.1.6
AC output voltage before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarFaultACOutputCurr 1.3.6.1.4.1.21111.1.2.10.19.1.7
AC output current before fault.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

solarCtlFeedGrid 1.3.6.1.4.1.21111.1.2.11.1
Setting this object to turn feeding grid enable(1) or disable(2)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(1), off(2)  

solarAgentDatetime 1.3.6.1.4.1.21111.1.2.12.1
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(19..19)  

solarCommBaudRate 1.3.6.1.4.1.21111.1.2.13.1
The solar inverter communicate baudrate
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER b1200(1), b2400(2), b4800(3), b9600(4), b19200(5)  

solarCommDatabits 1.3.6.1.4.1.21111.1.2.13.2
The solar inverter communicate data bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 8..9  

solarCommStopbits 1.3.6.1.4.1.21111.1.2.13.3
The solar inverter communicate stop bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

solarCommParity 1.3.6.1.4.1.21111.1.2.13.4
The solar inverter communicate Parity
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(0), odd(1), even(2)  

solarCommTimeout 1.3.6.1.4.1.21111.1.2.13.5
The solar inverter communicate timeout
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 100..1000  

solarCfgGridOutVolHLoss 1.3.6.1.4.1.21111.1.2.14.1
grid output voltage high loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 2400..2760  

solarCfgGridOutVolLLoss 1.3.6.1.4.1.21111.1.2.14.2
grid output voltage low loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1780..2200  

solarCfgGridOutFreqHLoss 1.3.6.1.4.1.21111.1.2.14.3
grid output frequency high loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

solarCfgGridOutFreqLLoss 1.3.6.1.4.1.21111.1.2.14.4
grid output frequency low loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

solarCfgCurrentMaxOutPower 1.3.6.1.4.1.21111.1.2.14.5
the max output power. ener solar:0-030000
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..999990  

solarCfgPVHVolMPPT 1.3.6.1.4.1.21111.1.2.14.6
the PV input high voltage for MPPT
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 4000..4500  

solarCfgPVLVolMPPT 1.3.6.1.4.1.21111.1.2.14.7
Set the PV input low voltage for MPPT
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1100..2000  

solarCfgUpLimitPVVol 1.3.6.1.4.1.21111.1.2.14.8
Set the upper limit of PV input voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 4500..5100  

solarCfgLowLimitPVVol 1.3.6.1.4.1.21111.1.2.14.9
Set the lowest limit of PV input voltage
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 900..2000  

solarCfgLCDSleepTime 1.3.6.1.4.1.21111.1.2.14.10
Setting LCD sleep time,0 means always light, the unit is 30s.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER always(0), s30s(1), s60s(2), s300s(10), s600s(20)  

solarCfgGridInVolHLoss 1.3.6.1.4.1.21111.1.2.14.11
Set grid input voltage high loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1760..2760  

solarCfgGridInVolLLoss 1.3.6.1.4.1.21111.1.2.14.12
Set grid input voltage low loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1760..2640  

solarCfgGridInFreqHLoss 1.3.6.1.4.1.21111.1.2.14.13
grid input frequency high loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

solarCfgGridInFreqLLoss 1.3.6.1.4.1.21111.1.2.14.14
grid input frequency low loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER  

solarCfgAverageVolHLoss 1.3.6.1.4.1.21111.1.2.14.15
the grid long time average voltage high loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 2530..2640  

solarCfgAverageVolLLoss 1.3.6.1.4.1.21111.1.2.14.16
the grid long time average voltage low loss point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1840..1950  

solarCfgSetDefaultValue 1.3.6.1.4.1.21111.1.2.14.17
Setting control parsameter to default valuse
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1)  

solarCfgWaiteTimeFeed 1.3.6.1.4.1.21111.1.2.14.18
Setting waiting time for feeding
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..999  

solarCfgSilenceBuzzer 1.3.6.1.4.1.21111.1.2.14.19
Setting this object to Enable/disable silence buzzer or open buzzer
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBuzzerInStandby 1.3.6.1.4.1.21111.1.2.14.20
Setting this object to Enable/disable buzzer audible in standby mode
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgAutoRestart 1.3.6.1.4.1.21111.1.2.14.21
Enable/disable auto-Restart. (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBatMAudibleWarn 1.3.6.1.4.1.21111.1.2.14.22
Enable/disable battery mode audible warning (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBatOpenCheck 1.3.6.1.4.1.21111.1.2.14.23
Enable/disable battery open status check (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgSiteFaultDetect 1.3.6.1.4.1.21111.1.2.14.24
Enable/disable Site fault detect (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgHotStandbyMS 1.3.6.1.4.1.21111.1.2.14.25
Hot standby master/slave PEM means master, PDM means slave (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBatDpDischgProt 1.3.6.1.4.1.21111.1.2.14.26
Enable/disable battery deep discharge protect (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBatLowDischgProt 1.3.6.1.4.1.21111.1.2.14.27
Enable/disable battery low protect (if disable, the battery will discharge to 6V) (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgCodeStart 1.3.6.1.4.1.21111.1.2.14.28
Enable/disable code start (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBypassForbid 1.3.6.1.4.1.21111.1.2.14.29
Enable/disable bypass forbidding (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgBypassWhenOff 1.3.6.1.4.1.21111.1.2.14.30
Enable/disable bypass when device turn off. (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgShortRestart3 1.3.6.1.4.1.21111.1.2.14.31
Enable/disable short restart 3 times (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgShortClear 1.3.6.1.4.1.21111.1.2.14.32
Enable/disable inverter short clear function (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solarCfgMaxChargeVol 1.3.6.1.4.1.21111.1.2.14.33
Max floating charging voltage (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 480..580  

solarCfgMaxChargeCurr 1.3.6.1.4.1.21111.1.2.14.34
Max floating charging current (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 5..250  

solarCfgChargingEnable 1.3.6.1.4.1.21111.1.2.14.35
Enable/disable charging on grid mode (for hybrid)
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disable(0), enable(1), notsupport(2)  

solartrapfaultnodev1v2 1.3.6.1.4.1.21111.1.2.15.998
The share trap-node for send fault traps
Status: current Access: not-accessible
OBJECT-TYPE    
  INTEGER 0..255  

solartrapleafnodev1v2 1.3.6.1.4.1.21111.1.2.15.999
The share trap-node for send all warn traps
Status: current Access: not-accessible
OBJECT-TYPE    
  DisplayString Size(16..16)  

cmpPVFailure 1
PV fail
TRAP-TYPE    

cmpAutoAdjustFailure 2
Auto adjust processing
TRAP-TYPE    

cmpExFlashFailure 3
External flash fail
TRAP-TYPE    

cmpPVLossFailure 4
PV loss
TRAP-TYPE    

cmpPVLowFailure 5
PV low
TRAP-TYPE    

cmpLandingFailure 6
Islanding detect
TRAP-TYPE    

cmpInitialFailure 7
Initial fail
TRAP-TYPE    

cmpGridVolHLossFailure 8
Grid voltage high loss
TRAP-TYPE    

cmpGridVolLLossFailure 9
Grid voltage low loss
TRAP-TYPE    

cmpGridFreqHLossFailure 10
Grid frequency high loss
TRAP-TYPE    

cmpGridFreqLLossFailure 11
Grid frequency low loss
TRAP-TYPE    

cmpFeedVolOverFailure 12
Feeding average voltage over
TRAP-TYPE    

cmpGetEnergyFGridWarn 13
get energy from the grid
TRAP-TYPE    

cmpEPOActiveWarn 14
EPO active
TRAP-TYPE    

cmpBusOverVolFail 15
Bus over voltage
TRAP-TYPE    

cmpBusUnderVolFail 16
Bus under voltage
TRAP-TYPE    

cmpBusSoftStartTimeOut 17
Bus soft start time out
TRAP-TYPE    

cmpInverterStartTimeOut 18
Inverter soft start time out
TRAP-TYPE    

cmpInverterShort 19
Inverter short
TRAP-TYPE    

cmpPVOverTemperature 20
Over temperature
TRAP-TYPE    

cmpPVRelayFault 21
Relay fault
TRAP-TYPE    

cmpDCCurrentFail 22
DC current fail
TRAP-TYPE    

cmpPVHighVolFail 23
PV high voltage
TRAP-TYPE    

cmpPVPowerDown 24
Power down
TRAP-TYPE    

cmpPVInputShortFail 25
PV input short
TRAP-TYPE    

cmpPVGFCIOverFail 26
GFCI over
TRAP-TYPE    

cmpPVIsolationLow 27
PV isolation low
TRAP-TYPE    

cmpInverterDCCurrOver 28
Inverter DC current over
TRAP-TYPE    

cmpMCUDSPLineFail 29
Line value consistent fail between MCU & DSP
TRAP-TYPE    

cmpPVGFCISensorFail 30
GFCI sensor fail
TRAP-TYPE    

cmpMCUDSPConnectFail 31
Connect fail between MCU & DSP
TRAP-TYPE    

cmpMCUDSPCommuicateFail 32
Communication fail between MCU & DSP
TRAP-TYPE    

cmpPVGroundLossFail 33
Ground loss
TRAP-TYPE    

cmpPVPowerOnMode 34
Power On Mode
TRAP-TYPE    

cmpPVStandbyMode 35
Standby Mode
TRAP-TYPE    

cmpPVBypassMode 36
Bypass Mode
TRAP-TYPE    

cmpPVLineMode 37
Line Mode
TRAP-TYPE    

cmpPVBatteryMode 38
Battery Mode
TRAP-TYPE    

cmpPVBatteryTestMode 39
Battery Test Mode
TRAP-TYPE    

cmpPVFaultMode 40
Fault Mode
TRAP-TYPE    

cmpPVShutdownMode 41
Shutdown Mode
TRAP-TYPE    

cmpPVGridMode 42
Grid mode
TRAP-TYPE    

cmpPVOtherMode 43
other solar inverter mode
TRAP-TYPE    

cmpPVChargeMode 44
Charge mode
TRAP-TYPE    

cmpPVBatteryUnder 45
Battery under
TRAP-TYPE    

cmpPVBatteryLow 46
Battery low
TRAP-TYPE    

cmpPVBatteryOpen 47
Battery open
TRAP-TYPE    

cmpPVBatDischatgeLow 48
Battery discharge low
TRAP-TYPE    

cmpPVOverLow 49
Over low
TRAP-TYPE    

cmpPVChAbnormal1 130
EMD Channels 1 Abnormal
TRAP-TYPE    

cmpPVChAbnormal2 131
EMD Channels 2 Abnormal
TRAP-TYPE    

cmpPVChAbnormal3 132
EMD Channels 3 Abnormal
TRAP-TYPE    

cmpPVChAbnormal4 133
EMD Channels 4 Abnormal
TRAP-TYPE    

cmpPVChAbnormal5 134
EMD Channels 5 Abnormal: smoke alarm
TRAP-TYPE    

cmpPVChAbnormal6 135
EMD Channels 6 Abnormal
TRAP-TYPE    

cmpPVChAbnormal7 136
EMD Channels 7 Abnormal
TRAP-TYPE    

cmpPVChAbnormal8 137
EMD Channels 8 Abnormal
TRAP-TYPE    

solarExWorkTemperature 1.3.6.1.4.1.21111.1.2.16.1
The temperature of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER -2200..2200  

solarExWorkhumidity 1.3.6.1.4.1.21111.1.2.16.2
The humidity of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

solarExSmokeScope 1.3.6.1.4.1.21111.1.2.16.3
The smokeScope of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..1000000  

solarExEMDAlarm1 1.3.6.1.4.1.21111.1.2.16.4
Environment detector alarm 1
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

solarExEMDAlarm2 1.3.6.1.4.1.21111.1.2.16.5
Environment detector alarm 2
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

solarExEMDAlarm3 1.3.6.1.4.1.21111.1.2.16.6
Environment detector alarm 3
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

solarExEMDAlarm4 1.3.6.1.4.1.21111.1.2.16.7
Environment detector alarm 4
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

atsIdManufacturer 1.3.6.1.4.1.21111.1.4.1.1
The name of the solar manufacturer.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

atsIdProtocol 1.3.6.1.4.1.21111.1.4.1.2
The solar Protocol id.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80), p15(15), p97(97)  

atsIdModelName 1.3.6.1.4.1.21111.1.4.1.3
The ats Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..15)  

atsIdSerialNumber 1.3.6.1.4.1.21111.1.4.1.4
The ats serial no.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

atsIdName 1.3.6.1.4.1.21111.1.4.1.5
A string identifying the ats. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

atsIdFWVersion 1.3.6.1.4.1.21111.1.4.1.6
Main CPU firmware version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

atsIdatsType 1.3.6.1.4.1.21111.1.4.1.7
ats type.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER null(0)  

atsRatOutVoltage 1.3.6.1.4.1.21111.1.4.2.1
The rating output voltage of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsRatOutCurrent 1.3.6.1.4.1.21111.1.4.2.2
The rating output current of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsRatOutFrequency 1.3.6.1.4.1.21111.1.4.2.3
The rating output frequency of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsInfoSource1InVol 1.3.6.1.4.1.21111.1.4.3.1
The source 1 input voltage of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsInfoSource1Freq 1.3.6.1.4.1.21111.1.4.3.2
The source 1 frequency of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsInfoSource2InVol 1.3.6.1.4.1.21111.1.4.3.3
The source 2 input voltage of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsInfoSource2Freq 1.3.6.1.4.1.21111.1.4.3.4
The source 2 frequency of ats
Status: current Access: read-only
OBJECT-TYPE    
  NonNegativeInteger  

atsInfoOutputLoad 1.3.6.1.4.1.21111.1.4.3.5
Load percentage
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

atsInfoOutputCurrent 1.3.6.1.4.1.21111.1.4.3.6
The output current of the ats system
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInfoSynchronAngle 1.3.6.1.4.1.21111.1.4.3.7
The Synchron Angle of the ats system
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

atsInfoTemperature 1.3.6.1.4.1.21111.1.4.3.8
The Internal temperature of the ats system
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER  

atsAgentDatetime 1.3.6.1.4.1.21111.1.4.5.1
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(19..19)  

atsCommBaudRate 1.3.6.1.4.1.21111.1.4.6.1
The ats communicate baudrate
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER b1200(1), b2400(2), b4800(3), b9600(4), b19200(5)  

atsCommDatabits 1.3.6.1.4.1.21111.1.4.6.2
The ats communicate data bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 8..9  

atsCommStopbits 1.3.6.1.4.1.21111.1.4.6.3
The ats communicate stop bits
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1..2  

atsCommParity 1.3.6.1.4.1.21111.1.4.6.4
The ats communicate Parity
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(0), odd(1), even(2)  

atsCommTimeout 1.3.6.1.4.1.21111.1.4.6.5
The ats communicate timeout
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 100..1000  

atsCfgSource1VolHLoss 1.3.6.1.4.1.21111.1.4.7.1
Set source1 voltage high loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource1VolHBack 1.3.6.1.4.1.21111.1.4.7.2
Set source1 voltage high back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource1VolLLoss 1.3.6.1.4.1.21111.1.4.7.3
Set source1 voltage low loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource1VolLBack 1.3.6.1.4.1.21111.1.4.7.4
Set source1 voltage low back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource1FreqHLoss 1.3.6.1.4.1.21111.1.4.7.5
Set source1 frequency high loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource1FreqHBack 1.3.6.1.4.1.21111.1.4.7.6
Set source1 frequency high back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource1FreqLLoss 1.3.6.1.4.1.21111.1.4.7.7
Set source1 frequency low loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource1FreqLBack 1.3.6.1.4.1.21111.1.4.7.8
Set source1 frequency low back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource2VolHLoss 1.3.6.1.4.1.21111.1.4.7.9
Set source2 voltage high loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource2VolHBack 1.3.6.1.4.1.21111.1.4.7.10
Set source2 voltage high back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource2VolLLoss 1.3.6.1.4.1.21111.1.4.7.11
Set source2 voltage low loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource2VolLBack 1.3.6.1.4.1.21111.1.4.7.12
Set source2 voltage low back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 1000..3000  

atsCfgSource2FreqHLoss 1.3.6.1.4.1.21111.1.4.7.13
Set source2 frequency high loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource2FreqHBack 1.3.6.1.4.1.21111.1.4.7.14
Set source2 frequency high back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource2FreqLLoss 1.3.6.1.4.1.21111.1.4.7.15
Set source2 frequency low loss
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgSource2FreqLBack 1.3.6.1.4.1.21111.1.4.7.16
Set source2 frequency low back
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 400..700  

atsCfgOverLoadAlarmPoint 1.3.6.1.4.1.21111.1.4.7.17
Set over load alarm point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..150  

atsCfgOverLoadFaultPoint 1.3.6.1.4.1.21111.1.4.7.18
Set over load fault point
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..250  

atsCfgAcceptablePhases 1.3.6.1.4.1.21111.1.4.7.19
Set acceptable phases
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..180  

atsCfgBreakingTime 1.3.6.1.4.1.21111.1.4.7.20
Set breaking time
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..9999  

atsCfgBlankingTime 1.3.6.1.4.1.21111.1.4.7.21
Set blanking time
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1000  

atstrapleafnodev1v2 1.3.6.1.4.1.21111.1.4.8.999
The share trap-node for send all traps
Status: current Access: not-accessible
OBJECT-TYPE    
  INTEGER 0..255  

cmpatsSourceS1VolBad 1
Source S1 Voltage rms bad
TRAP-TYPE    

cmpatsSourceS1FreqBad 2
Source S1 frequency bad
TRAP-TYPE    

cmpatsSourceS1WaveBad 3
Source S1 wave bad
TRAP-TYPE    

cmpatsSourceS2VolBad 4
Source S2 Voltage rms bad
TRAP-TYPE    

cmpatsSourceS2FreqBad 5
Source S2 frequency bad
TRAP-TYPE    

cmpatsSourceS2WaveBad 6
Source S2 wave bad
TRAP-TYPE    

cmpatsOnSourceS2 7
On Source S2
TRAP-TYPE    

cmpatsOnSourceS1 8
On Source S1
TRAP-TYPE    

cmpatsSourceS2Preferred 9
Source S2 Preferred Source
TRAP-TYPE    

cmpatsSynchronBad 10
Synchron bad
TRAP-TYPE    

cmpatsAuxPower1Fail 11
Aux. Power1 failure
TRAP-TYPE    

cmpatsAuxPower2Fail 12
Aux. Power2 failure
TRAP-TYPE    

cmpatsShortFault 13
Short fault
TRAP-TYPE    

cmpatsOverloadFault 14
Overload fault
TRAP-TYPE    

cmpatsOverloadAlarm 15
Overload Alarm
TRAP-TYPE    

cmpatsOnFaultMode 16
On fault mode
TRAP-TYPE    

cmpatsChAbnormal1 130
EMD Channels 1 Abnormal
TRAP-TYPE    

cmpatsChAbnormal2 131
EMD Channels 2 Abnormal
TRAP-TYPE    

cmpatsChAbnormal3 132
EMD Channels 3 Abnormal
TRAP-TYPE    

cmpatsChAbnormal4 133
EMD Channels 4 Abnormal
TRAP-TYPE    

cmpatsChAbnormal5 134
EMD Channels 5 Abnormal: smoke alarm
TRAP-TYPE    

cmpatsChAbnormal6 135
EMD Channels 6 Abnormal
TRAP-TYPE    

cmpatsChAbnormal7 136
EMD Channels 7 Abnormal
TRAP-TYPE    

cmpatsChAbnormal8 137
EMD Channels 8 Abnormal
TRAP-TYPE    

atsExWorkTemperature 1.3.6.1.4.1.21111.1.4.9.1
The temperature of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER -2200..2200  

atsExWorkhumidity 1.3.6.1.4.1.21111.1.4.9.2
The humidity of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

atsExSmokeScope 1.3.6.1.4.1.21111.1.4.9.3
The smokeScope of work environment
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER 0..1000000  

atsExEMDAlarm1 1.3.6.1.4.1.21111.1.4.9.4
Environment detector alarm 1
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

atsExEMDAlarm2 1.3.6.1.4.1.21111.1.4.9.5
Environment detector alarm 2
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

atsExEMDAlarm3 1.3.6.1.4.1.21111.1.4.9.6
Environment detector alarm 3
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)  

atsExEMDAlarm4 1.3.6.1.4.1.21111.1.4.9.7
Environment detector alarm 4
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER on(1), off(0)