NextUPSSystems
File:
NextUPSSystems.mib (152055 bytes)
Imported modules
Imported symbols
Defined Types
UpsOutEntry |
|
SEQUENCE |
|
|
|
|
upsOutLineIndex |
PositiveInteger |
|
|
upsOutVoltage |
NonNegativeInteger |
|
|
upsOutCurrent |
NonNegativeInteger |
|
|
upsOutApparentPower |
NonNegativeInteger |
|
|
upsOutTruePower |
NonNegativeInteger |
|
|
upsOutPowerFactor |
NonNegativeInteger |
|
|
upsOutPercentLoad |
INTEGER |
|
|
upsOutLineVoltage |
NonNegativeInteger |
|
UpsByEntry |
|
SEQUENCE |
|
|
|
|
upsByLineIndex |
PositiveInteger |
|
|
upsByVoltage |
NonNegativeInteger |
|
|
upsByCurrent |
NonNegativeInteger |
|
|
upsByPower |
NonNegativeInteger |
|
|
upsByLineVoltage |
INTEGER |
|
SolarGridEntry |
|
SEQUENCE |
|
|
|
|
solarGridLineIndex |
PositiveInteger |
|
|
solarGridVoltage |
INTEGER |
|
|
solarGridCurrent |
INTEGER |
|
|
solarGridPower |
INTEGER |
|
SolarACOutEntry |
|
SEQUENCE |
|
|
|
|
solarACOutLineIndex |
PositiveInteger |
|
|
solarACOutVoltage |
INTEGER |
|
|
solarACOutTruePower |
NonNegativeInteger |
|
|
solarACOutCurrent |
INTEGER |
|
|
solarACOutPercentLoad |
NonNegativeInteger |
|
SolarPVEntry |
|
SEQUENCE |
|
|
|
|
solarPVLineIndex |
PositiveInteger |
|
|
solarPVVoltage |
INTEGER |
|
|
solarPVPower |
NonNegativeInteger |
|
SolarFaultEntry |
|
SEQUENCE |
|
|
|
|
solarFaultLineIndex |
PositiveInteger |
|
|
solarFaultInverterVolt |
INTEGER |
|
|
solarFaultInverterCurr |
INTEGER |
|
|
solarFaultGridVoltage |
INTEGER |
|
|
solarFaultGridCurrent |
INTEGER |
|
|
solarFaultACOutputVolt |
INTEGER |
|
|
solarFaultACOutputCurr |
INTEGER |
|
Defined Values
nextUPSSystems |
1.3.6.1.4.1.21111 |
The MIB module to describe UPS, Inverter, Salor Power |
MODULE-IDENTITY |
|
|
|
products |
1.3.6.1.4.1.21111.1 |
OBJECT IDENTIFIER |
|
|
|
ups |
1.3.6.1.4.1.21111.1.1 |
OBJECT IDENTIFIER |
|
|
|
inverter |
1.3.6.1.4.1.21111.1.2 |
OBJECT IDENTIFIER |
|
|
|
charger |
1.3.6.1.4.1.21111.1.3 |
OBJECT IDENTIFIER |
|
|
|
ats |
1.3.6.1.4.1.21111.1.4 |
OBJECT IDENTIFIER |
|
|
|
upsIdent |
1.3.6.1.4.1.21111.1.1.1 |
OBJECT IDENTIFIER |
|
|
|
upsRating |
1.3.6.1.4.1.21111.1.1.2 |
OBJECT IDENTIFIER |
|
|
|
upsBattery |
1.3.6.1.4.1.21111.1.1.3 |
OBJECT IDENTIFIER |
|
|
|
upsOutput |
1.3.6.1.4.1.21111.1.1.5 |
OBJECT IDENTIFIER |
|
|
|
upsBypass |
1.3.6.1.4.1.21111.1.1.6 |
OBJECT IDENTIFIER |
|
|
|
upsTest |
1.3.6.1.4.1.21111.1.1.7 |
OBJECT IDENTIFIER |
|
|
|
upsControl |
1.3.6.1.4.1.21111.1.1.8 |
OBJECT IDENTIFIER |
|
|
|
commConfig |
1.3.6.1.4.1.21111.1.1.10 |
OBJECT IDENTIFIER |
|
|
|
upsConfig |
1.3.6.1.4.1.21111.1.1.11 |
OBJECT IDENTIFIER |
|
|
|
upsTraps |
1.3.6.1.4.1.21111.1.1.12 |
OBJECT IDENTIFIER |
|
|
|
extend |
1.3.6.1.4.1.21111.1.1.13 |
OBJECT IDENTIFIER |
|
|
|
solarIdent |
1.3.6.1.4.1.21111.1.2.1 |
OBJECT IDENTIFIER |
|
|
|
solarGrid |
1.3.6.1.4.1.21111.1.2.4 |
OBJECT IDENTIFIER |
|
|
|
solarPV |
1.3.6.1.4.1.21111.1.2.6 |
OBJECT IDENTIFIER |
|
|
|
solarTest |
1.3.6.1.4.1.21111.1.2.8 |
OBJECT IDENTIFIER |
|
|
|
solarTraps |
1.3.6.1.4.1.21111.1.2.15 |
OBJECT IDENTIFIER |
|
|
|
atsIdent |
1.3.6.1.4.1.21111.1.4.1 |
OBJECT IDENTIFIER |
|
|
|
atsRating |
1.3.6.1.4.1.21111.1.4.2 |
OBJECT IDENTIFIER |
|
|
|
atsControl |
1.3.6.1.4.1.21111.1.4.4 |
OBJECT IDENTIFIER |
|
|
|
atsConfig |
1.3.6.1.4.1.21111.1.4.7 |
OBJECT IDENTIFIER |
|
|
|
atsTraps |
1.3.6.1.4.1.21111.1.4.8 |
OBJECT IDENTIFIER |
|
|
|
atsExtend |
1.3.6.1.4.1.21111.1.4.9 |
OBJECT IDENTIFIER |
|
|
|
upsIdManufacturer |
1.3.6.1.4.1.21111.1.1.1.1 |
The name of the UPS manufacturer. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsIdProtocol |
1.3.6.1.4.1.21111.1.1.1.2 |
The UPS Protocol id. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80) |
|
upsIdModelName |
1.3.6.1.4.1.21111.1.1.1.3 |
The UPS Model designation. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsIdName |
1.3.6.1.4.1.21111.1.1.1.5 |
A string identifying the UPS. This object should be
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsIdFWVersion |
1.3.6.1.4.1.21111.1.1.1.6 |
Main CPU firmware version. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsIdUPSType |
1.3.6.1.4.1.21111.1.1.1.7 |
UPS type. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
standy(0), line-interactive(1), on-line(2) |
|
upsBatStatus |
1.3.6.1.4.1.21111.1.1.3.1 |
The indication of the status in the UPS system's batteries. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8) |
|
upsBatSecondsOnBattery |
1.3.6.1.4.1.21111.1.1.3.2 |
If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. -1 shall be returned
if the unit is not on battery power. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatEstMinutesRemaining |
1.3.6.1.4.1.21111.1.1.3.3 |
An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatEstChargeRemaining |
1.3.6.1.4.1.21111.1.1.3.4 |
An estimate of the battery charge remaining expressed
as a percent of full charge. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
upsBatPBatCurrent |
1.3.6.1.4.1.21111.1.1.3.7 |
The positive battery present current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatNBatCurrent |
1.3.6.1.4.1.21111.1.1.3.8 |
The present negative battery current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatPBatChargCurrent |
1.3.6.1.4.1.21111.1.1.3.9 |
The Positive battery charging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatNBatchargCurrent |
1.3.6.1.4.1.21111.1.1.3.10 |
The present negative battery charging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatPBatDischargCurrent |
1.3.6.1.4.1.21111.1.1.3.11 |
The present positive battery discharging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatNBatDischargCurrent |
1.3.6.1.4.1.21111.1.1.3.12 |
The present negative battery discharging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatTemperature |
1.3.6.1.4.1.21111.1.1.3.13 |
The ambient temperature at or near the UPS Battery
casing. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatPBatDischargCurrent2 |
1.3.6.1.4.1.21111.1.1.3.16 |
The present positive battery pipe2 discharging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInLineBads |
1.3.6.1.4.1.21111.1.1.4.1 |
A count of the number of times the input entered an
out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each
time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsInNumLines |
1.3.6.1.4.1.21111.1.1.4.4 |
The number of input lines utilized in this device.
This variable indicates the number of rows in the
input table. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsInTable |
1.3.6.1.4.1.21111.1.1.4.5 |
A list of input table entries. The number of entries
is given by the value of upsInputNumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsInEntry |
|
upsInTtlVoltage |
1.3.6.1.4.1.21111.1.1.4.6 |
The input utility line tatol voltage . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInTtlCurrent |
1.3.6.1.4.1.21111.1.1.4.7 |
The input utility line tatol current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInEntry |
1.3.6.1.4.1.21111.1.1.4.5.1 |
An entry containing information applicable to a
particular input line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsInEntry |
|
|
upsInLineIndex |
1.3.6.1.4.1.21111.1.1.4.5.1.1 |
The number of output lines |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
upsInVoltage |
1.3.6.1.4.1.21111.1.1.4.5.1.3 |
The input utility line voltage . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInCurrent |
1.3.6.1.4.1.21111.1.1.4.5.1.4 |
The magnitude of the present input current |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInLineVoltage |
1.3.6.1.4.1.21111.1.1.4.5.1.8 |
The input utility line voltage .
if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase;
if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase;
if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutSource |
1.3.6.1.4.1.21111.1.1.5.1 |
The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.==UPS standby mode |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), he-eco-mode(10), converter-mode(11) |
|
upsOutFrequency |
1.3.6.1.4.1.21111.1.1.5.2 |
The current output frequency of the UPS system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutTtlPercentLoad |
1.3.6.1.4.1.21111.1.1.5.5 |
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
upsOutNumLines |
1.3.6.1.4.1.21111.1.1.5.6 |
The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutTable |
1.3.6.1.4.1.21111.1.1.5.7 |
A list of output table entries. The number of
entries is given by the value of upsOutputNumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsOutEntry |
|
upsOutTtlVoltage |
1.3.6.1.4.1.21111.1.1.5.8 |
Total output voltage . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutTtlCurrent |
1.3.6.1.4.1.21111.1.1.5.9 |
Total output current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutStatus |
1.3.6.1.4.1.21111.1.1.5.10 |
For HVDC device.
char status[4];
status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
status[2]status[3]:00, no output2; 01, line output2; 02, bat output2
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(4..4) |
|
upsOutSource2 |
1.3.6.1.4.1.21111.1.1.5.11 |
For HVDC(protocol:P12) machine. The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.==UPS standby mode |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), he-eco-mode(10), converter-mode(11) |
|
upsOutEntry |
1.3.6.1.4.1.21111.1.1.5.7.1 |
An entry containing information applicable to a
particular output line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsOutEntry |
|
|
upsOutLineIndex |
1.3.6.1.4.1.21111.1.1.5.7.1.1 |
The output line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
upsOutVoltage |
1.3.6.1.4.1.21111.1.1.5.7.1.2 |
The output voltage of the UPS system. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutCurrent |
1.3.6.1.4.1.21111.1.1.5.7.1.3 |
The output current of the UPS system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutPercentLoad |
1.3.6.1.4.1.21111.1.1.5.7.1.7 |
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
upsOutLineVoltage |
1.3.6.1.4.1.21111.1.1.5.7.1.8 |
The output line voltage of the UPS system.
if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase;
if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase;
if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsByFrequency |
1.3.6.1.4.1.21111.1.1.6.1 |
The present bypass frequency. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsByNumLines |
1.3.6.1.4.1.21111.1.1.6.2 |
The number of bypass lines utilized in this device.
This entry indicates the number of rows in the bypass
table. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsByTable |
1.3.6.1.4.1.21111.1.1.6.3 |
A list of bypass table entries. The number of
entries is given by the value of upsBypassNumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsByEntry |
|
upsByEntry |
1.3.6.1.4.1.21111.1.1.6.3.1 |
An entry containing information applicable to a
particular bypass input. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsByEntry |
|
|
upsByLineIndex |
1.3.6.1.4.1.21111.1.1.6.3.1.1 |
The bypass line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65535 |
|
upsByVoltage |
1.3.6.1.4.1.21111.1.1.6.3.1.2 |
The present bypass voltage. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsByCurrent |
1.3.6.1.4.1.21111.1.1.6.3.1.3 |
The present bypass current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsByPower |
1.3.6.1.4.1.21111.1.1.6.3.1.4 |
The present true power conveyed by the bypass. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsByLineVoltage |
1.3.6.1.4.1.21111.1.1.6.3.1.5 |
The present bypass line voltage.
if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase;
if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase;
if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsTstBatteryTest |
1.3.6.1.4.1.21111.1.1.7.1 |
This object specify the battery test type and initiate
battery test. If battTestWithTime selected, the test
time is refer to upsTestBatteryTestTime. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(1), battTest10sec(2), battTestUntilLow(3), battTestWithTime(4), battTestCancelTest(5), battTestClearInfo(6) |
|
upsTstBatteryTestResult |
1.3.6.1.4.1.21111.1.1.7.2 |
The results of the current or last UPS diagnostics
test performed. The values for donePassed(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6) |
|
upsTstBatteryTestStartTime |
1.3.6.1.4.1.21111.1.1.7.3 |
The value of the time the test in progress was initiated,
or, if no test is in progress, the time the previous test
was initiated. If the value of upsTestBatteryTestResult
is noTestsInitiated(6), upsTestStartTime has the value
01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(19..19) |
|
upsTstBatterySettingTime |
1.3.6.1.4.1.21111.1.1.7.4 |
The object specify the test time for battery test |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
12..5940 |
|
upsCtlShutdownDelay |
1.3.6.1.4.1.21111.1.1.8.1 |
The delay in seconds the UPS remains on after being told
to turn off. if value=-2 cancel shutdown, if value=-1 donothing,
value=0 shutdown ups immediately |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-2..2147483648 |
|
upsCtlSleepTime |
1.3.6.1.4.1.21111.1.1.8.2 |
The time in minutes for the UPS to go to sleep when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable
value, the highest acceptable value is used. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1..2147483648 |
|
upsCtlStartupAfterDelay |
1.3.6.1.4.1.21111.1.1.8.3 |
Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. -1 mean not startup.
must set upsCtlStartupAfterDelay before upsCtlShutdownDelay |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
60..2147483648 |
|
upsCtlbuzzer |
1.3.6.1.4.1.21111.1.1.8.4 |
Setting this object to 'on' or 'off' to enable or disable buzzer |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(2) |
|
upsCtlRemoteControlUPS |
1.3.6.1.4.1.21111.1.1.8.5 |
Setting this object to turn 'on' or 'off' UPS |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(2) |
|
upsCtloutletPoweron |
1.3.6.1.4.1.21111.1.1.8.6 |
Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process |
Status: current |
Access: write-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
upsCtloutletPoweroff |
1.3.6.1.4.1.21111.1.1.8.7 |
Setting this object to 1 means 1st outlet,
2 means 2nd outlet , immediately process |
Status: current |
Access: write-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
upsCtlOutlet1Powerofftime |
1.3.6.1.4.1.21111.1.1.8.8 |
setting this object to -1 means this control not effect,
0 means immediately process,
>0 means wait times .use in battery mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1..999 |
|
upsCtlOutlet2Powerofftime |
1.3.6.1.4.1.21111.1.1.8.9 |
setting this object to -1 means this control not effect,
0 means immediately process ,
>0 means wait times .use in battery mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-1..999 |
|
agentConfigDatetime |
1.3.6.1.4.1.21111.1.1.9.1 |
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(19..19) |
|
commBaudRate |
1.3.6.1.4.1.21111.1.1.10.1 |
The UPS communicate baudrate |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
b1200(1), b2400(2), b4800(3), b9600(4), b19200(5) |
|
commDatabits |
1.3.6.1.4.1.21111.1.1.10.2 |
The UPS communicate data bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
8..9 |
|
commStopbits |
1.3.6.1.4.1.21111.1.1.10.3 |
The UPS communicate stop bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
commParity |
1.3.6.1.4.1.21111.1.1.10.4 |
The UPS communicate Parity |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(0), odd(1), even(2) |
|
commTimeout |
1.3.6.1.4.1.21111.1.1.10.5 |
The UPS communicate timeout |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
100..1000 |
|
upsCfgAlarmbypass |
1.3.6.1.4.1.21111.1.1.11.1 |
Setting this object enable /disable alarm bypass mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgAlarmbattery |
1.3.6.1.4.1.21111.1.1.11.2 |
Setting this object enable/disable alarm battery mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgAutoReboot |
1.3.6.1.4.1.21111.1.1.11.3 |
Setting this object enable/disable auto reboot |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBypasswhenupsoff |
1.3.6.1.4.1.21111.1.1.11.4 |
Setting this object start/stop bypass when ups off |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBatterDDP |
1.3.6.1.4.1.21111.1.1.11.5 |
Setting this object to enable/disable battery deep-discharge protection |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgConvertermode |
1.3.6.1.4.1.21111.1.1.11.6 |
Setting this object to enable/disable converter mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgECOmode |
1.3.6.1.4.1.21111.1.1.11.7 |
Setting this object to enable/disable ECO mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgAdvanceECOmode |
1.3.6.1.4.1.21111.1.1.11.8 |
Setting this object to enable/disable advance ECO mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgGreenPowerFunction |
1.3.6.1.4.1.21111.1.1.11.9 |
Setting this object to enable/disable green power function |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBatteryOSC |
1.3.6.1.4.1.21111.1.1.11.10 |
Setting this object to enable/disable battery open status check |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgAllowShort3times |
1.3.6.1.4.1.21111.1.1.11.11 |
Setting this object to enable/disable short 3 times |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgColdstart |
1.3.6.1.4.1.21111.1.1.11.12 |
Setting this object to cold start ups |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBypassNotAllowed |
1.3.6.1.4.1.21111.1.1.11.13 |
Setting this object to enable/disable bypass mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBatterylowprotect |
1.3.6.1.4.1.21111.1.1.11.14 |
Setting this object to enable/disable battery low protect |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgP1progoutletcontrol |
1.3.6.1.4.1.21111.1.1.11.15 |
Setting this object to enable/disable p1 programmable outlet control (battery mode) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgP2progoutletcontrol |
1.3.6.1.4.1.21111.1.1.11.16 |
Setting this object to enable/disable p2 programmable outlet control (battery mode) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgInverterShortClear |
1.3.6.1.4.1.21111.1.1.11.17 |
Setting this object to enable/disable Inverter short clear function |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgSitefaildetection |
1.3.6.1.4.1.21111.1.1.11.18 |
Setting this object to enable/disable site fail detection |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgBatNumInParallel |
1.3.6.1.4.1.21111.1.1.11.19 |
Battery numbers in parallel (battery numbers setting) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..99 |
|
upsCfgBatNumInSeries |
1.3.6.1.4.1.21111.1.1.11.20 |
Battery numbers in series (battery numbers setting) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..20 |
|
upsCfgBypassmaxvoltage |
1.3.6.1.4.1.21111.1.1.11.21 |
Bypass mode max voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1760..2760 |
|
upsCfgBypassminvoltage |
1.3.6.1.4.1.21111.1.1.11.22 |
Bypass mode min voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1760..2640 |
|
upsCfgBypassmaxfrequency |
1.3.6.1.4.1.21111.1.1.11.23 |
Bypass mode max frequency |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
510..700 |
|
upsCfgBypassminfrequency |
1.3.6.1.4.1.21111.1.1.11.24 |
Bypass mode min frequency |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..590 |
|
upsCfgECOmaxvoltage |
1.3.6.1.4.1.21111.1.1.11.25 |
ECO mode max voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
10..3000 |
|
upsCfgECOminvoltage |
1.3.6.1.4.1.21111.1.1.11.26 |
ECO mode min voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
10..3000 |
|
upsCfgFreeRunMaxFrequency |
1.3.6.1.4.1.21111.1.1.11.27 |
Free run mode max frequency |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
upsCfgFreeRunMinFrequency |
1.3.6.1.4.1.21111.1.1.11.28 |
Free run mode min frequency |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
upsCfgEPOStatus |
1.3.6.1.4.1.21111.1.1.11.29 |
Get EPO status,configured by mamual |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
upsCfgQSK1Status |
1.3.6.1.4.1.21111.1.1.11.30 |
Get QSK 1 status |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
upsCfgQSK2Status |
1.3.6.1.4.1.21111.1.1.11.31 |
Get QSK 2 status |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
upsCfgQSKT1Delaytime |
1.3.6.1.4.1.21111.1.1.11.32 |
Get QSKT 1 time delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
000..999 |
|
upsCfgQSKT2Delaytime |
1.3.6.1.4.1.21111.1.1.11.33 |
Get QSKT 2 time delay |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
000..999 |
|
upsCfgConstantPhaseAngle |
1.3.6.1.4.1.21111.1.1.11.34 |
setting this object to Enable/disable Constant Phase Angle function |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
upsCfgInPhaseAngle |
1.3.6.1.4.1.21111.1.1.11.35 |
Get input phase angle |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
b000(0), b120(120), b180(180), b240(240) |
|
upsCfgOutPhaseAngle |
1.3.6.1.4.1.21111.1.1.11.36 |
Set output phase angle |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
b000(0), b120(120), b180(180), b240(240) |
|
upsCfgLimiRunOnBatMode |
1.3.6.1.4.1.21111.1.1.11.37 |
Enable/disable limited runtime on battery mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
upsCfgChargingCurrent |
1.3.6.1.4.1.21111.1.1.11.38 |
Set charging current to battery . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgBatSeftCheckVolt |
1.3.6.1.4.1.21111.1.1.11.39 |
BatTest until battery voltage lower than |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
2400..2800 |
|
upsCfgOverChargVolt |
1.3.6.1.4.1.21111.1.1.11.40 |
set over charging voltage to per battery |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
130..143 |
|
upsCfgBattUnderVolt |
1.3.6.1.4.1.21111.1.1.11.41 |
set battery under voltage of setting value.value is a number ranging from 200V to 240V |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
2000..2400 |
|
upsCfgBattLowVolt |
1.3.6.1.4.1.21111.1.1.11.42 |
set battery low voltage of setting value.it is 10 to 40V high than battery under voltage.
it is 10 to 40V high than battery under voltage.default 20.
it means that the battery low point is battery under add 20.
for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
|
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgIn1VoltHLoss |
1.3.6.1.4.1.21111.1.1.11.43 |
set input1 voltage high loss point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgIn1VoltLLoss |
1.3.6.1.4.1.21111.1.1.11.44 |
set input1 voltage low loss point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgIn2VoltHLoss |
1.3.6.1.4.1.21111.1.1.11.45 |
set input2 voltage high loss point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgIn2VoltLLoss |
1.3.6.1.4.1.21111.1.1.11.46 |
set input2 voltage low loss point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsCfgBatteryTurnOn |
1.3.6.1.4.1.21111.1.1.11.47 |
Enable/disable battery turn on. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
trapleafnodev103 |
1.3.6.1.4.1.21111.1.1.12.998 |
The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node
char trap[16];
trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(16..16) |
|
trapleafnodev1v2 |
1.3.6.1.4.1.21111.1.1.12.999 |
The share trap-node for send all traps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..255 |
|
cmpLowbattery |
9 |
The UPS has returned from a low battery
condition. |
TRAP-TYPE |
|
|
|
cmpcommfailurebcupsboard |
54 |
Communication failure between cpus in control board.Or DSP and MCU communication error |
TRAP-TYPE |
|
|
|
cmpMaintainSwitchOpenalarm |
129 |
Warning for maintain switch open |
TRAP-TYPE |
|
|
|
extendWorkTemperature |
1.3.6.1.4.1.21111.1.1.13.1 |
The temperature of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-2200..2200 |
|
extendWorkhumidity |
1.3.6.1.4.1.21111.1.1.13.2 |
The humidity of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
extendSmokeScope |
1.3.6.1.4.1.21111.1.1.13.3 |
The smokeScope of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..1000000 |
|
extendEMDAlarm1 |
1.3.6.1.4.1.21111.1.1.13.4 |
Environment detector alarm 1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
extendEMDAlarm2 |
1.3.6.1.4.1.21111.1.1.13.5 |
Environment detector alarm 2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
extendEMDAlarm3 |
1.3.6.1.4.1.21111.1.1.13.6 |
Environment detector alarm 3 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
extendEMDAlarm4 |
1.3.6.1.4.1.21111.1.1.13.7 |
Environment detector alarm 4 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
solarIdProtocol |
1.3.6.1.4.1.21111.1.2.1.2 |
The solar Protocol id. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80), p15(15) |
|
solarIdModelName |
1.3.6.1.4.1.21111.1.2.1.3 |
The solar Model designation. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
solarIdSolarType |
1.3.6.1.4.1.21111.1.2.1.7 |
solar type. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
grid-tie(0), off-grid(1), hybrid(10) |
|
solarIdTopology |
1.3.6.1.4.1.21111.1.2.1.8 |
solar Topology. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
transformerless(0), transformer(1) |
|
solarIdCriterion |
1.3.6.1.4.1.21111.1.2.1.9 |
solar device criterion. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarRatACOutVoltage |
1.3.6.1.4.1.21111.1.2.2.8 |
The rating AC output voltage of solar inverter |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
a(208), b(220), c(230), d(240) |
|
solarBatStatus |
1.3.6.1.4.1.21111.1.2.3.1 |
The indication of the status in the solar system's batteries. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8) |
|
solarBatSecondsOnBattery |
1.3.6.1.4.1.21111.1.2.3.2 |
If the unit is on battery power, the elapsed time
since the solar last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. -1 shall be returned
if the unit is not on battery power. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatEstMinutesRemaining |
1.3.6.1.4.1.21111.1.2.3.3 |
An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatEstChargeRemaining |
1.3.6.1.4.1.21111.1.2.3.4 |
An estimate of the battery charge remaining expressed
as a percent of full charge. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
solarBatPBatCurrent |
1.3.6.1.4.1.21111.1.2.3.7 |
The positive battery present current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatNBatCurrent |
1.3.6.1.4.1.21111.1.2.3.8 |
The present negative battery current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatPBatChargCurrent |
1.3.6.1.4.1.21111.1.2.3.9 |
The Positive battery charging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatNBatchargCurrent |
1.3.6.1.4.1.21111.1.2.3.10 |
The present negative battery charging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatPBatDischargCurrent |
1.3.6.1.4.1.21111.1.2.3.11 |
The present positive battery discharging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatNBatDischargCurrent |
1.3.6.1.4.1.21111.1.2.3.12 |
The present negative battery discharging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatTemperature |
1.3.6.1.4.1.21111.1.2.3.13 |
The ambient temperature at or near the solar Battery
casing. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarBatChargingCurrent |
1.3.6.1.4.1.21111.1.2.3.16 |
Charging Current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridSource |
1.3.6.1.4.1.21111.1.2.4.1 |
The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.==UPS standby mode |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), none(2), normal(3), bypass(4), battery(5), poweron(6), shutdown(7), batterytest(8), fault(9), grid-mode(10), charge-mode(11) |
|
solarGridTtlApparentPower |
1.3.6.1.4.1.21111.1.2.4.2 |
Total grid output apparent power . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridTtlTruePower |
1.3.6.1.4.1.21111.1.2.4.3 |
Total grid output active(true) power . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridNumLine |
1.3.6.1.4.1.21111.1.2.4.5 |
The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridTemperature |
1.3.6.1.4.1.21111.1.2.4.6 |
Max Temperature of the detecting pointers. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridStatus |
1.3.6.1.4.1.21111.1.2.4.7 |
Device status.
b31-b16:NG
b15: NG
b14: NG
b13: NG
b12: NG
b11: Load status 0: Load off 1:Load on
b10: Battery status
b9: Battery status b10b9: 00: Do nothing
01: Charging
10: Discharging
b8: Inv direction 0: DC-AC 1: AC-DC
b7: Line direction
b6: Line direction a7a6: 00 means unsteady
01 means Line input
10 means Line output
b5-b0:NG
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridTable |
1.3.6.1.4.1.21111.1.2.4.8 |
A list of solar grid table entries. The number of
entries is given by the value of solarGridputNumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
SolarGridEntry |
|
solarGridEntry |
1.3.6.1.4.1.21111.1.2.4.8.1 |
An entry containing information applicable to a
particular grid line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SolarGridEntry |
|
|
solarGridLineIndex |
1.3.6.1.4.1.21111.1.2.4.8.1.1 |
The grid line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
solarGridVoltage |
1.3.6.1.4.1.21111.1.2.4.8.1.2 |
The Grid voltage of the solar inverter |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridCurrent |
1.3.6.1.4.1.21111.1.2.4.8.1.3 |
The Grid current of the solar inverter |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarGridPower |
1.3.6.1.4.1.21111.1.2.4.8.1.4 |
The present Grid output true power. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarACOutTtlPercentLoad |
1.3.6.1.4.1.21111.1.2.5.4 |
Total AC output total percent load. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
solarACOutTable |
1.3.6.1.4.1.21111.1.2.5.5 |
A list of AC output table entries. The number of entries
is given by the value of solarACOut NumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
SolarACOutEntry |
|
solarACOutEntry |
1.3.6.1.4.1.21111.1.2.5.5.1 |
An entry containing information applicable to a
particular input line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SolarACOutEntry |
|
|
solarACOutLineIndex |
1.3.6.1.4.1.21111.1.2.5.5.1.1 |
The number of PV line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
solarACOutVoltage |
1.3.6.1.4.1.21111.1.2.5.5.1.2 |
The AC output voltage . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarACOutCurrent |
1.3.6.1.4.1.21111.1.2.5.5.1.4 |
The magnitude of the present AC output current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarACOutPercentLoad |
1.3.6.1.4.1.21111.1.2.5.5.1.5 |
The magnitude of the present AC output percent load |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
solarPVTable |
1.3.6.1.4.1.21111.1.2.6.3 |
A list of solar PV input table entries. The number of entries
is given by the value of solarPV NumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
SolarPVEntry |
|
solarPVEntry |
1.3.6.1.4.1.21111.1.2.6.3.1 |
An entry containing information applicable to a
particular input line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SolarPVEntry |
|
|
solarPVLineIndex |
1.3.6.1.4.1.21111.1.2.6.3.1.1 |
The number of PV line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
solarPVVoltage |
1.3.6.1.4.1.21111.1.2.6.3.1.2 |
The PV input voltage . |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarPVPower |
1.3.6.1.4.1.21111.1.2.6.3.1.3 |
The magnitude of the present input true power. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
solarEnergyHourT |
1.3.6.1.4.1.21111.1.2.7.2 |
write the hour when we will inquiry energy in the hour |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(10..10) |
|
solarEnergyHourE |
1.3.6.1.4.1.21111.1.2.7.3 |
0xfeffffff:doing inquiry
0xffffffff:error |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(9..9) |
|
solarEnergyDayT |
1.3.6.1.4.1.21111.1.2.7.4 |
the time when we will inquiry energy in the day |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(8..8) |
|
solarEnergyDayE |
1.3.6.1.4.1.21111.1.2.7.5 |
0xfeffffff:doing inquiry
0xffffffff:error |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(9..9) |
|
solarEnergyMonE |
1.3.6.1.4.1.21111.1.2.7.7 |
0xfeffffff:doing inquiry
0xffffffff:error |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(9..9) |
|
solarEnergyYearE |
1.3.6.1.4.1.21111.1.2.7.9 |
0xfeffffff:doing inquiry
0xffffffff:error |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(9..9) |
|
solarEnergyHourID |
1.3.6.1.4.1.21111.1.2.7.10 |
ID. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarEnergyDayID |
1.3.6.1.4.1.21111.1.2.7.11 |
ID. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarEnergyMonID |
1.3.6.1.4.1.21111.1.2.7.12 |
ID. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarEnergyYearID |
1.3.6.1.4.1.21111.1.2.7.13 |
ID. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarTestStartSelfTest |
1.3.6.1.4.1.21111.1.2.8.1 |
Setting this object to 'start' to start test |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
null(0), start(1) |
|
solarTestSelfTestResult |
1.3.6.1.4.1.21111.1.2.8.2 |
an Integer ranging from 0 to 9.
0 means self test being processed,
1 means self test succeed,
2 means self test fail. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
processeing(0), succeed(1), fail(2) |
|
solarTestGridOutHVol |
1.3.6.1.4.1.21111.1.2.8.3 |
Self test grid output high voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarTestGridOutLVol |
1.3.6.1.4.1.21111.1.2.8.4 |
Self test grid output low voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarTestGridOutHFreq |
1.3.6.1.4.1.21111.1.2.8.5 |
Self test grid output high frequency |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarTestGridOutLFreq |
1.3.6.1.4.1.21111.1.2.8.6 |
Self test grid output low frequency |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridOutVolHLoss |
1.3.6.1.4.1.21111.1.2.9.1 |
The default setting value of grid output voltage high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridOutVolLLoss |
1.3.6.1.4.1.21111.1.2.9.2 |
The default setting value of grid output voltage lowloss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridOutFreqHLoss |
1.3.6.1.4.1.21111.1.2.9.3 |
The default setting value Grid output frequency high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridOutFreqLLoss |
1.3.6.1.4.1.21111.1.2.9.4 |
The default setting value Grid output frequency low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridInVolHLoss |
1.3.6.1.4.1.21111.1.2.9.5 |
The default setting value Grid input voltage high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridInVolLLoss |
1.3.6.1.4.1.21111.1.2.9.6 |
The default setting value Grid input voltage low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridInFreqHLoss |
1.3.6.1.4.1.21111.1.2.9.7 |
The default setting value Grid input frequency high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefGridInFreqLLoss |
1.3.6.1.4.1.21111.1.2.9.8 |
The default setting value Grid input frequency low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefUpLimitPVVol |
1.3.6.1.4.1.21111.1.2.9.9 |
The default setting value The upper limit of PV input voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefLowLimitPVVol |
1.3.6.1.4.1.21111.1.2.9.10 |
The default setting value The lowest limit of PV input voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefPVHVolMPPT |
1.3.6.1.4.1.21111.1.2.9.11 |
The default setting value The PV input high voltage for MPPT |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefPVLVolMPPT |
1.3.6.1.4.1.21111.1.2.9.12 |
The default setting value The PV input low voltage for MPPT |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxOutPower |
1.3.6.1.4.1.21111.1.2.9.13 |
The default setting value Max output power |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefAverageVolHLoss |
1.3.6.1.4.1.21111.1.2.9.14 |
The default setting value Long time grid average voltage high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefLCDSleepTime |
1.3.6.1.4.1.21111.1.2.9.15 |
The default setting value LCD sleep time |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxChargeVol |
1.3.6.1.4.1.21111.1.2.9.19 |
The default setting the max charging voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxChargeCurr |
1.3.6.1.4.1.21111.1.2.9.20 |
The default setting the max charging current |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefWaiteTimeFeed |
1.3.6.1.4.1.21111.1.2.9.21 |
The default setting waiting time for feeding |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMaxGridOutVolHLoss |
1.3.6.1.4.1.21111.1.2.9.22 |
The max grid output voltage high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMinGridOutVolHLoss |
1.3.6.1.4.1.21111.1.2.9.23 |
The min grid output voltage high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxGridOutVolLLoss |
1.3.6.1.4.1.21111.1.2.9.24 |
The max grid output voltage low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMinGridOutVolLLoss |
1.3.6.1.4.1.21111.1.2.9.25 |
The min grid output voltage low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxGridOutFreqHLoss |
1.3.6.1.4.1.21111.1.2.9.26 |
The max grid output frequency high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMinGridOutFreqHLoss |
1.3.6.1.4.1.21111.1.2.9.27 |
The min grid output frequency high loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxGridOutFreqLLoss |
1.3.6.1.4.1.21111.1.2.9.28 |
The max grid output frequency low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMinGridOutFreqLLoss |
1.3.6.1.4.1.21111.1.2.9.29 |
The min grid output frequency low loss point |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarDefMaxWaiteTimeFeed |
1.3.6.1.4.1.21111.1.2.9.30 |
The max waiting time for feeding |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMinWaiteTimeFeed |
1.3.6.1.4.1.21111.1.2.9.31 |
The min waiting time for feeding |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMaxMaxFChargVolt |
1.3.6.1.4.1.21111.1.2.9.32 |
The max voltage for max floating charging voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMinMaxFChargVolt |
1.3.6.1.4.1.21111.1.2.9.33 |
The min voltage for max floating charging voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMaxMaxRChargCurr |
1.3.6.1.4.1.21111.1.2.9.34 |
The upper limit of max charging current(real charging) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMinMaxRChargCurr |
1.3.6.1.4.1.21111.1.2.9.35 |
The lower limit of max charging current(real charging) |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMaxHighMPPTVolt |
1.3.6.1.4.1.21111.1.2.9.40 |
The max MPPT high voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..9990 |
|
solarDefMinHighMPPTVolt |
1.3.6.1.4.1.21111.1.2.9.41 |
The min MPPT high voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..9990 |
|
solarDefMaxLowMPPTVolt |
1.3.6.1.4.1.21111.1.2.9.42 |
The max MPPT low voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..9990 |
|
solarDefMinLowMPPTVolt |
1.3.6.1.4.1.21111.1.2.9.43 |
The min MPPT low voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..9990 |
|
solarDefMaxOutputPower |
1.3.6.1.4.1.21111.1.2.9.44 |
The max output power |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999990 |
|
solarDefMinOutputPower |
1.3.6.1.4.1.21111.1.2.9.45 |
The min output power |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999990 |
|
solarDefMaxRChargVolt |
1.3.6.1.4.1.21111.1.2.9.46 |
The min charging voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarDefMinRChargVolt |
1.3.6.1.4.1.21111.1.2.9.47 |
The max charging voltage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarFaultCurrentID |
1.3.6.1.4.1.21111.1.2.10.1 |
current fault ID. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..8 |
|
solarFaultQueryFaultID |
1.3.6.1.4.1.21111.1.2.10.2 |
query fault ID. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..8 |
|
solarFaultQueryResult |
1.3.6.1.4.1.21111.1.2.10.3 |
Query fault info result. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
doneSucess(1), doneError(2), inProgress(3) |
|
solarFaultFaultTime |
1.3.6.1.4.1.21111.1.2.10.5 |
Device Fault time.format is YYYYMMDDHHMMSS |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(14..14) |
|
solarFaultPVStatus |
1.3.6.1.4.1.21111.1.2.10.6 |
PV running status before fault.
b31-b16:reserved
b15 : PV1 boost on
b14 : PV2 boost on
b13 : PV3 boost on
b12 : Inverter on
b11 : 1: PV1 MPPT by boost; 0: PV1 MPPT by inverter
b10 : 1: PV2 MPPT by boost; 0: PV2 MPPT by inverter
b9 : 1: PV3 MPPT by boost; 0: PV3 MPPT by inverter
b8 : O/P relay on
b7 : Inverter relay on
b6 : Safe relay on
b5 : Main relay on
b4 : AC relay on
b3 : Reserved
b2 : Reserved
b1 : Reserved
b0 : DC TO DC on |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
solarFaultTemperature |
1.3.6.1.4.1.21111.1.2.10.7 |
Max Temperature of the detecting pointers before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV1Voltage |
1.3.6.1.4.1.21111.1.2.10.9 |
PV1 input voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV1Current |
1.3.6.1.4.1.21111.1.2.10.10 |
PV1 current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV2Voltage |
1.3.6.1.4.1.21111.1.2.10.11 |
PV2 input voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV2Current |
1.3.6.1.4.1.21111.1.2.10.12 |
PV2 current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV3Voltage |
1.3.6.1.4.1.21111.1.2.10.13 |
PV3 input voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultPV3Current |
1.3.6.1.4.1.21111.1.2.10.14 |
PV3 current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultTable |
1.3.6.1.4.1.21111.1.2.10.19 |
A list of fault table entries. The number of entries
is given by the value of solarFault NumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
SolarFaultEntry |
|
solarFaultEntry |
1.3.6.1.4.1.21111.1.2.10.19.1 |
An entry containing information applicable to a
particular input line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SolarFaultEntry |
|
|
solarFaultLineIndex |
1.3.6.1.4.1.21111.1.2.10.19.1.1 |
The number of inverter,grid and ACOutput line identifier. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..10 |
|
solarFaultInverterVolt |
1.3.6.1.4.1.21111.1.2.10.19.1.2 |
Inverter voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultInverterCurr |
1.3.6.1.4.1.21111.1.2.10.19.1.3 |
Inverter current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultGridVoltage |
1.3.6.1.4.1.21111.1.2.10.19.1.4 |
Grid voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultGridCurrent |
1.3.6.1.4.1.21111.1.2.10.19.1.5 |
Grid current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultACOutputVolt |
1.3.6.1.4.1.21111.1.2.10.19.1.6 |
AC output voltage before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarFaultACOutputCurr |
1.3.6.1.4.1.21111.1.2.10.19.1.7 |
AC output current before fault. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarCtlFeedGrid |
1.3.6.1.4.1.21111.1.2.11.1 |
Setting this object to turn feeding grid enable(1) or disable(2) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(2) |
|
solarAgentDatetime |
1.3.6.1.4.1.21111.1.2.12.1 |
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(19..19) |
|
solarCommBaudRate |
1.3.6.1.4.1.21111.1.2.13.1 |
The solar inverter communicate baudrate |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
b1200(1), b2400(2), b4800(3), b9600(4), b19200(5) |
|
solarCommDatabits |
1.3.6.1.4.1.21111.1.2.13.2 |
The solar inverter communicate data bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
8..9 |
|
solarCommStopbits |
1.3.6.1.4.1.21111.1.2.13.3 |
The solar inverter communicate stop bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
solarCommParity |
1.3.6.1.4.1.21111.1.2.13.4 |
The solar inverter communicate Parity |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(0), odd(1), even(2) |
|
solarCommTimeout |
1.3.6.1.4.1.21111.1.2.13.5 |
The solar inverter communicate timeout |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
100..1000 |
|
solarCfgGridOutVolHLoss |
1.3.6.1.4.1.21111.1.2.14.1 |
grid output voltage high loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
2400..2760 |
|
solarCfgGridOutVolLLoss |
1.3.6.1.4.1.21111.1.2.14.2 |
grid output voltage low loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1780..2200 |
|
solarCfgGridOutFreqHLoss |
1.3.6.1.4.1.21111.1.2.14.3 |
grid output frequency high loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarCfgGridOutFreqLLoss |
1.3.6.1.4.1.21111.1.2.14.4 |
grid output frequency low loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarCfgCurrentMaxOutPower |
1.3.6.1.4.1.21111.1.2.14.5 |
the max output power.
ener solar:0-030000 |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999990 |
|
solarCfgPVHVolMPPT |
1.3.6.1.4.1.21111.1.2.14.6 |
the PV input high voltage for MPPT |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
4000..4500 |
|
solarCfgPVLVolMPPT |
1.3.6.1.4.1.21111.1.2.14.7 |
Set the PV input low voltage for MPPT |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1100..2000 |
|
solarCfgUpLimitPVVol |
1.3.6.1.4.1.21111.1.2.14.8 |
Set the upper limit of PV input voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
4500..5100 |
|
solarCfgLowLimitPVVol |
1.3.6.1.4.1.21111.1.2.14.9 |
Set the lowest limit of PV input voltage |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
900..2000 |
|
solarCfgLCDSleepTime |
1.3.6.1.4.1.21111.1.2.14.10 |
Setting LCD sleep time,0 means always light, the unit is 30s. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
always(0), s30s(1), s60s(2), s300s(10), s600s(20) |
|
solarCfgGridInVolHLoss |
1.3.6.1.4.1.21111.1.2.14.11 |
Set grid input voltage high loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1760..2760 |
|
solarCfgGridInVolLLoss |
1.3.6.1.4.1.21111.1.2.14.12 |
Set grid input voltage low loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1760..2640 |
|
solarCfgGridInFreqHLoss |
1.3.6.1.4.1.21111.1.2.14.13 |
grid input frequency high loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarCfgGridInFreqLLoss |
1.3.6.1.4.1.21111.1.2.14.14 |
grid input frequency low loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
solarCfgAverageVolHLoss |
1.3.6.1.4.1.21111.1.2.14.15 |
the grid long time average voltage high loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
2530..2640 |
|
solarCfgAverageVolLLoss |
1.3.6.1.4.1.21111.1.2.14.16 |
the grid long time average voltage low loss point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1840..1950 |
|
solarCfgSetDefaultValue |
1.3.6.1.4.1.21111.1.2.14.17 |
Setting control parsameter to default valuse |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1) |
|
solarCfgWaiteTimeFeed |
1.3.6.1.4.1.21111.1.2.14.18 |
Setting waiting time for feeding |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..999 |
|
solarCfgSilenceBuzzer |
1.3.6.1.4.1.21111.1.2.14.19 |
Setting this object to Enable/disable silence buzzer or open buzzer |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBuzzerInStandby |
1.3.6.1.4.1.21111.1.2.14.20 |
Setting this object to Enable/disable buzzer audible in standby mode |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgAutoRestart |
1.3.6.1.4.1.21111.1.2.14.21 |
Enable/disable auto-Restart. (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBatMAudibleWarn |
1.3.6.1.4.1.21111.1.2.14.22 |
Enable/disable battery mode audible warning (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBatOpenCheck |
1.3.6.1.4.1.21111.1.2.14.23 |
Enable/disable battery open status check (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgSiteFaultDetect |
1.3.6.1.4.1.21111.1.2.14.24 |
Enable/disable Site fault detect (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgHotStandbyMS |
1.3.6.1.4.1.21111.1.2.14.25 |
Hot standby master/slave PEM means master, PDM means slave (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBatDpDischgProt |
1.3.6.1.4.1.21111.1.2.14.26 |
Enable/disable battery deep discharge protect (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBatLowDischgProt |
1.3.6.1.4.1.21111.1.2.14.27 |
Enable/disable battery low protect (if disable, the battery will discharge to 6V) (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgCodeStart |
1.3.6.1.4.1.21111.1.2.14.28 |
Enable/disable code start (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBypassForbid |
1.3.6.1.4.1.21111.1.2.14.29 |
Enable/disable bypass forbidding (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgBypassWhenOff |
1.3.6.1.4.1.21111.1.2.14.30 |
Enable/disable bypass when device turn off. (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgShortRestart3 |
1.3.6.1.4.1.21111.1.2.14.31 |
Enable/disable short restart 3 times (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgShortClear |
1.3.6.1.4.1.21111.1.2.14.32 |
Enable/disable inverter short clear function (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solarCfgMaxChargeVol |
1.3.6.1.4.1.21111.1.2.14.33 |
Max floating charging voltage (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
480..580 |
|
solarCfgMaxChargeCurr |
1.3.6.1.4.1.21111.1.2.14.34 |
Max floating charging current (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
5..250 |
|
solarCfgChargingEnable |
1.3.6.1.4.1.21111.1.2.14.35 |
Enable/disable charging on grid mode (for hybrid) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disable(0), enable(1), notsupport(2) |
|
solartrapfaultnodev1v2 |
1.3.6.1.4.1.21111.1.2.15.998 |
The share trap-node for send fault traps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..255 |
|
solartrapleafnodev1v2 |
1.3.6.1.4.1.21111.1.2.15.999 |
The share trap-node for send all warn traps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(16..16) |
|
solarExWorkTemperature |
1.3.6.1.4.1.21111.1.2.16.1 |
The temperature of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-2200..2200 |
|
solarExWorkhumidity |
1.3.6.1.4.1.21111.1.2.16.2 |
The humidity of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
solarExSmokeScope |
1.3.6.1.4.1.21111.1.2.16.3 |
The smokeScope of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..1000000 |
|
solarExEMDAlarm1 |
1.3.6.1.4.1.21111.1.2.16.4 |
Environment detector alarm 1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
solarExEMDAlarm2 |
1.3.6.1.4.1.21111.1.2.16.5 |
Environment detector alarm 2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
solarExEMDAlarm3 |
1.3.6.1.4.1.21111.1.2.16.6 |
Environment detector alarm 3 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
solarExEMDAlarm4 |
1.3.6.1.4.1.21111.1.2.16.7 |
Environment detector alarm 4 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
atsIdManufacturer |
1.3.6.1.4.1.21111.1.4.1.1 |
The name of the solar manufacturer. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
atsIdProtocol |
1.3.6.1.4.1.21111.1.4.1.2 |
The solar Protocol id. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80), p15(15), p97(97) |
|
atsIdModelName |
1.3.6.1.4.1.21111.1.4.1.3 |
The ats Model designation. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
atsIdName |
1.3.6.1.4.1.21111.1.4.1.5 |
A string identifying the ats. This object should be
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
atsIdFWVersion |
1.3.6.1.4.1.21111.1.4.1.6 |
Main CPU firmware version. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
atsIdatsType |
1.3.6.1.4.1.21111.1.4.1.7 |
ats type. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
null(0) |
|
atsInfoOutputLoad |
1.3.6.1.4.1.21111.1.4.3.5 |
Load percentage |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
atsInfoOutputCurrent |
1.3.6.1.4.1.21111.1.4.3.6 |
The output current of the ats system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
atsInfoSynchronAngle |
1.3.6.1.4.1.21111.1.4.3.7 |
The Synchron Angle of the ats system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
atsInfoTemperature |
1.3.6.1.4.1.21111.1.4.3.8 |
The Internal temperature of the ats system |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
atsAgentDatetime |
1.3.6.1.4.1.21111.1.4.5.1 |
The datetime in agent, format is (MM/DD/YYYY hh:mm:ss) |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(19..19) |
|
atsCommBaudRate |
1.3.6.1.4.1.21111.1.4.6.1 |
The ats communicate baudrate |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
b1200(1), b2400(2), b4800(3), b9600(4), b19200(5) |
|
atsCommDatabits |
1.3.6.1.4.1.21111.1.4.6.2 |
The ats communicate data bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
8..9 |
|
atsCommStopbits |
1.3.6.1.4.1.21111.1.4.6.3 |
The ats communicate stop bits |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1..2 |
|
atsCommParity |
1.3.6.1.4.1.21111.1.4.6.4 |
The ats communicate Parity |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
none(0), odd(1), even(2) |
|
atsCommTimeout |
1.3.6.1.4.1.21111.1.4.6.5 |
The ats communicate timeout |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
100..1000 |
|
atsCfgSource1VolHLoss |
1.3.6.1.4.1.21111.1.4.7.1 |
Set source1 voltage high loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource1VolHBack |
1.3.6.1.4.1.21111.1.4.7.2 |
Set source1 voltage high back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource1VolLLoss |
1.3.6.1.4.1.21111.1.4.7.3 |
Set source1 voltage low loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource1VolLBack |
1.3.6.1.4.1.21111.1.4.7.4 |
Set source1 voltage low back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource1FreqHLoss |
1.3.6.1.4.1.21111.1.4.7.5 |
Set source1 frequency high loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource1FreqHBack |
1.3.6.1.4.1.21111.1.4.7.6 |
Set source1 frequency high back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource1FreqLLoss |
1.3.6.1.4.1.21111.1.4.7.7 |
Set source1 frequency low loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource1FreqLBack |
1.3.6.1.4.1.21111.1.4.7.8 |
Set source1 frequency low back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource2VolHLoss |
1.3.6.1.4.1.21111.1.4.7.9 |
Set source2 voltage high loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource2VolHBack |
1.3.6.1.4.1.21111.1.4.7.10 |
Set source2 voltage high back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource2VolLLoss |
1.3.6.1.4.1.21111.1.4.7.11 |
Set source2 voltage low loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource2VolLBack |
1.3.6.1.4.1.21111.1.4.7.12 |
Set source2 voltage low back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
1000..3000 |
|
atsCfgSource2FreqHLoss |
1.3.6.1.4.1.21111.1.4.7.13 |
Set source2 frequency high loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource2FreqHBack |
1.3.6.1.4.1.21111.1.4.7.14 |
Set source2 frequency high back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource2FreqLLoss |
1.3.6.1.4.1.21111.1.4.7.15 |
Set source2 frequency low loss |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgSource2FreqLBack |
1.3.6.1.4.1.21111.1.4.7.16 |
Set source2 frequency low back |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
400..700 |
|
atsCfgOverLoadAlarmPoint |
1.3.6.1.4.1.21111.1.4.7.17 |
Set over load alarm point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..150 |
|
atsCfgOverLoadFaultPoint |
1.3.6.1.4.1.21111.1.4.7.18 |
Set over load fault point |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..250 |
|
atsCfgAcceptablePhases |
1.3.6.1.4.1.21111.1.4.7.19 |
Set acceptable phases |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..180 |
|
atsCfgBreakingTime |
1.3.6.1.4.1.21111.1.4.7.20 |
Set breaking time |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..9999 |
|
atsCfgBlankingTime |
1.3.6.1.4.1.21111.1.4.7.21 |
Set blanking time |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..1000 |
|
atstrapleafnodev1v2 |
1.3.6.1.4.1.21111.1.4.8.999 |
The share trap-node for send all traps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..255 |
|
atsExWorkTemperature |
1.3.6.1.4.1.21111.1.4.9.1 |
The temperature of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-2200..2200 |
|
atsExWorkhumidity |
1.3.6.1.4.1.21111.1.4.9.2 |
The humidity of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
atsExSmokeScope |
1.3.6.1.4.1.21111.1.4.9.3 |
The smokeScope of work environment |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..1000000 |
|
atsExEMDAlarm1 |
1.3.6.1.4.1.21111.1.4.9.4 |
Environment detector alarm 1 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
atsExEMDAlarm2 |
1.3.6.1.4.1.21111.1.4.9.5 |
Environment detector alarm 2 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
atsExEMDAlarm3 |
1.3.6.1.4.1.21111.1.4.9.6 |
Environment detector alarm 3 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|
atsExEMDAlarm4 |
1.3.6.1.4.1.21111.1.4.9.7 |
Environment detector alarm 4 |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
on(1), off(0) |
|