RMS-COMPACT-SNMPv1-MAIN-MIB

File: RMS-COMPACT-SNMPv1-MAIN-MIB.mib (67060 bytes)

Imported modules

RFC-1215 RFC1213-MIB RFC-1212
RFC1155-SMI

Imported symbols

TRAP-TYPE sysDescr sysName
DisplayString OBJECT-TYPE enterprises

Defined Values

sinetica 1.3.6.1.4.1.3711
OBJECT IDENTIFIER    

rms-compact 1.3.6.1.4.1.3711.15
OBJECT IDENTIFIER    

rms-compact1 1.3.6.1.4.1.3711.15.1
OBJECT IDENTIFIER    

rms-cObjects 1.3.6.1.4.1.3711.15.1.1
OBJECT IDENTIFIER    

rms-cEnviroment 1.3.6.1.4.1.3711.15.1.1.1
OBJECT IDENTIFIER    

rms-cContact 1.3.6.1.4.1.3711.15.1.1.2
OBJECT IDENTIFIER    

rms-cOutput 1.3.6.1.4.1.3711.15.1.1.3
OBJECT IDENTIFIER    

rms-cTemp1 1.3.6.1.4.1.3711.15.1.1.1.1
OBJECT IDENTIFIER    

rms-cHumid1 1.3.6.1.4.1.3711.15.1.1.1.2
OBJECT IDENTIFIER    

rms-cTemp2 1.3.6.1.4.1.3711.15.1.1.1.3
OBJECT IDENTIFIER    

rms-cHumid2 1.3.6.1.4.1.3711.15.1.1.1.4
OBJECT IDENTIFIER    

rms-cTemp1EnableMonitoring 1.3.6.1.4.1.3711.15.1.1.1.1.1
Setting to one enables monitoring of Temperature
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cTemp1Name 1.3.6.1.4.1.3711.15.1.1.1.1.2
The name of the temperature reading
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cTemp1CalibrationOffset 1.3.6.1.4.1.3711.15.1.1.1.1.3
Calibration offset in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

rms-cTemp1Current 1.3.6.1.4.1.3711.15.1.1.1.1.4
The current temperature reading in 0.1%
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp1Thresholds 1.3.6.1.4.1.3711.15.1.1.1.1.5
OBJECT IDENTIFIER    

rms-cTemp1OFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.1.1.6
OBJECT IDENTIFIER    

rms-cTemp1OFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.1.7
OBJECT IDENTIFIER    

rms-cTemp1ONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.1.1.8
OBJECT IDENTIFIER    

rms-cTemp1ONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.1.9
OBJECT IDENTIFIER    

rms-cTemp1LowerControlLevel 1.3.6.1.4.1.3711.15.1.1.1.1.5.1
The Lower Limit temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp1LowerWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.1.5.2
The Lower Control temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp1UpperWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.1.5.3
The Upper Control temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp1UpperControlLevel 1.3.6.1.4.1.3711.15.1.1.1.1.5.4
The Upper Limit temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp1OFFtoONtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.1.6.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1OFFtoONontrapLWL 1.3.6.1.4.1.3711.15.1.1.1.1.6.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1OFFtoONtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.1.6.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1OFFtoONtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.1.6.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1OFFtoONrepLCL 1.3.6.1.4.1.3711.15.1.1.1.1.7.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1OFFtoONrepLWL 1.3.6.1.4.1.3711.15.1.1.1.1.7.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1OFFtoONrepUWL 1.3.6.1.4.1.3711.15.1.1.1.1.7.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1OFFtoONrepUCL 1.3.6.1.4.1.3711.15.1.1.1.1.7.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1ONtoOFFtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.1.8.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1ONtoOFFtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.1.8.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1ONtoOFFtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.1.8.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1ONtoOFFtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.1.8.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp1ONtoOFFrepLCL 1.3.6.1.4.1.3711.15.1.1.1.1.9.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1ONtoOFFrepLWL 1.3.6.1.4.1.3711.15.1.1.1.1.9.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1ONtoOFFrepUWL 1.3.6.1.4.1.3711.15.1.1.1.1.9.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1ONtoOFFrepUCL 1.3.6.1.4.1.3711.15.1.1.1.1.9.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp1LowControlLimitAlarm 101
Temperature is below the low control limit.
TRAP-TYPE    

rms-cTemp1LowWarningLimitAlarm 102
Temperature is below the low warning limit.
TRAP-TYPE    

rms-cTemp1HighWarningLimitAlarm 103
Temperature is over the high warning limit.
TRAP-TYPE    

rms-cTemp1HighControlLimitAlarm 104
Temperature is over the high control limit.
TRAP-TYPE    

rms-cTemp1LowControlLimitNormal 105
Temperature is inside the low control limit.
TRAP-TYPE    

rms-cTemp1LowWarningLimitNormal 106
Temperature is inside the low warning limit.
TRAP-TYPE    

rms-cTemp1HighWarningLimitNormal 107
Temperature is inside the high warning limit.
TRAP-TYPE    

rms-cTemp1HighControlLimitNormal 108
Temperature is inside the high control limit.
TRAP-TYPE    

rms-cHumid1EnableMonitoring 1.3.6.1.4.1.3711.15.1.1.1.2.1
Setting to one enables monitoring of Humidity
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cHumid1Name 1.3.6.1.4.1.3711.15.1.1.1.2.2
The name of the humidity reading
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cHumid1CalibrationOffset 1.3.6.1.4.1.3711.15.1.1.1.2.3
Calibration offset in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

rms-cHumid1Current 1.3.6.1.4.1.3711.15.1.1.1.2.4
The current humidity reading in 0.1%
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid1Thresholds 1.3.6.1.4.1.3711.15.1.1.1.2.5
OBJECT IDENTIFIER    

rms-cHumid1OFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.1.2.6
OBJECT IDENTIFIER    

rms-cHumid1OFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.2.7
OBJECT IDENTIFIER    

rms-cHumid1ONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.1.2.8
OBJECT IDENTIFIER    

rms-cHumid1ONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.2.9
OBJECT IDENTIFIER    

rms-cHumid1LowerControlLevel 1.3.6.1.4.1.3711.15.1.1.1.2.5.1
The Lower Limit Humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid1LowerWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.2.5.2
The Lower Control humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid1UpperWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.2.5.3
The Upper Control humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid1UpperControlLevel 1.3.6.1.4.1.3711.15.1.1.1.2.5.4
The Upper Limit humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid1OFFtoONtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.2.6.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1OFFtoONtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.2.6.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1OFFtoONtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.2.6.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1OFFtoONtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.2.6.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1OFFtoONrepLCL 1.3.6.1.4.1.3711.15.1.1.1.2.7.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1OFFtoONrepLWL 1.3.6.1.4.1.3711.15.1.1.1.2.7.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1OFFtoONrepUWL 1.3.6.1.4.1.3711.15.1.1.1.2.7.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1OFFtoONrepUCL 1.3.6.1.4.1.3711.15.1.1.1.2.7.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1ONtoOFFtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.2.8.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1ONtoOFFtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.2.8.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1ONtoOFFtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.2.8.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1ONtoOFFtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.2.8.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid1ONtoOFFrepLCL 1.3.6.1.4.1.3711.15.1.1.1.2.9.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1ONtoOFFrepLWL 1.3.6.1.4.1.3711.15.1.1.1.2.9.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1ONtoOFFrepUWL 1.3.6.1.4.1.3711.15.1.1.1.2.9.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid1ONtoOFFrepUCL 1.3.6.1.4.1.3711.15.1.1.1.2.9.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2EnableMonitoring 1.3.6.1.4.1.3711.15.1.1.1.3.1
Setting to one enables monitoring of Temperature
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cTemp2Name 1.3.6.1.4.1.3711.15.1.1.1.3.2
The name of the temperature reading
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cTemp2CalibrationOffset 1.3.6.1.4.1.3711.15.1.1.1.3.3
Calibration offset in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

rms-cTemp2Current 1.3.6.1.4.1.3711.15.1.1.1.3.4
The current temperature reading in 0.1%
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp2Thresholds 1.3.6.1.4.1.3711.15.1.1.1.3.5
OBJECT IDENTIFIER    

rms-cTemp2OFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.1.3.6
OBJECT IDENTIFIER    

rms-cTemp2OFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.3.7
OBJECT IDENTIFIER    

rms-cTemp2ONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.1.3.8
OBJECT IDENTIFIER    

rms-cTemp2ONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.3.9
OBJECT IDENTIFIER    

rms-cTemp2LowerControlLevel 1.3.6.1.4.1.3711.15.1.1.1.3.5.1
The Lower Limit temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp2LowerWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.3.5.2
The Lower Control temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp2UpperWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.3.5.3
The Upper Control temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp2UpperControlLevel 1.3.6.1.4.1.3711.15.1.1.1.3.5.4
The Upper Limit temperature threshold in 0.1 degrees
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cTemp2OFFtoONtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.3.6.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2OFFtoONontrapLWL 1.3.6.1.4.1.3711.15.1.1.1.3.6.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2OFFtoONtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.3.6.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2OFFtoONtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.3.6.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2OFFtoONrepLCL 1.3.6.1.4.1.3711.15.1.1.1.3.7.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2OFFtoONrepLWL 1.3.6.1.4.1.3711.15.1.1.1.3.7.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2OFFtoONrepUWL 1.3.6.1.4.1.3711.15.1.1.1.3.7.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2OFFtoONrepUCL 1.3.6.1.4.1.3711.15.1.1.1.3.7.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2ONtoOFFtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.3.8.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2ONtoOFFtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.3.8.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2ONtoOFFtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.3.8.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2ONtoOFFtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.3.8.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cTemp2ONtoOFFrepLCL 1.3.6.1.4.1.3711.15.1.1.1.3.9.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2ONtoOFFrepLWL 1.3.6.1.4.1.3711.15.1.1.1.3.9.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2ONtoOFFrepUWL 1.3.6.1.4.1.3711.15.1.1.1.3.9.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cTemp2ONtoOFFrepUCL 1.3.6.1.4.1.3711.15.1.1.1.3.9.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2EnableMonitoring 1.3.6.1.4.1.3711.15.1.1.1.4.1
Setting to one enables monitoring of Humidity
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cHumid2Name 1.3.6.1.4.1.3711.15.1.1.1.4.2
The name of the humidity reading
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cHumid2CalibrationOffset 1.3.6.1.4.1.3711.15.1.1.1.4.3
Calibration offset in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -100..100  

rms-cHumid2Current 1.3.6.1.4.1.3711.15.1.1.1.4.4
The current humidity reading in 0.1%
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid2Thresholds 1.3.6.1.4.1.3711.15.1.1.1.4.5
OBJECT IDENTIFIER    

rms-cHumid2OFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.1.4.6
OBJECT IDENTIFIER    

rms-cHumid2OFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.4.7
OBJECT IDENTIFIER    

rms-cHumid2ONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.1.4.8
OBJECT IDENTIFIER    

rms-cHumid2ONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.1.4.9
OBJECT IDENTIFIER    

rms-cHumid2LowerControlLevel 1.3.6.1.4.1.3711.15.1.1.1.4.5.1
The Lower Limit Humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid2LowerWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.4.5.2
The Lower Control humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid2UpperWarningLevel 1.3.6.1.4.1.3711.15.1.1.1.4.5.3
The Upper Control humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid2UpperControlLevel 1.3.6.1.4.1.3711.15.1.1.1.4.5.4
The Upper Limit humidity threshold in 0.1 percent
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -200..1000  

rms-cHumid2OFFtoONtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.4.6.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2OFFtoONtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.4.6.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2OFFtoONtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.4.6.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2OFFtoONtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.4.6.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2OFFtoONrepLCL 1.3.6.1.4.1.3711.15.1.1.1.4.7.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2OFFtoONrepLWL 1.3.6.1.4.1.3711.15.1.1.1.4.7.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2OFFtoONrepUWL 1.3.6.1.4.1.3711.15.1.1.1.4.7.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2OFFtoONrepUCL 1.3.6.1.4.1.3711.15.1.1.1.4.7.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2ONtoOFFtrapLCL 1.3.6.1.4.1.3711.15.1.1.1.4.8.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2ONtoOFFtrapLWL 1.3.6.1.4.1.3711.15.1.1.1.4.8.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2ONtoOFFtrapUWL 1.3.6.1.4.1.3711.15.1.1.1.4.8.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2ONtoOFFtrapUCL 1.3.6.1.4.1.3711.15.1.1.1.4.8.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cHumid2ONtoOFFrepLCL 1.3.6.1.4.1.3711.15.1.1.1.4.9.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2ONtoOFFrepLWL 1.3.6.1.4.1.3711.15.1.1.1.4.9.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2ONtoOFFrepUWL 1.3.6.1.4.1.3711.15.1.1.1.4.9.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cHumid2ONtoOFFrepUCL 1.3.6.1.4.1.3711.15.1.1.1.4.9.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContactNames 1.3.6.1.4.1.3711.15.1.1.2.1
OBJECT IDENTIFIER    

rms-cContactType 1.3.6.1.4.1.3711.15.1.1.2.2
OBJECT IDENTIFIER    

rms-cContactReset 1.3.6.1.4.1.3711.15.1.1.2.3
OBJECT IDENTIFIER    

rms-cContactNormalStates 1.3.6.1.4.1.3711.15.1.1.2.4
OBJECT IDENTIFIER    

rms-cContactCurrentStates 1.3.6.1.4.1.3711.15.1.1.2.5
OBJECT IDENTIFIER    

rms-cContactOFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.2.6
OBJECT IDENTIFIER    

rms-cContactOFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.2.7
OBJECT IDENTIFIER    

rms-cContactONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.2.8
OBJECT IDENTIFIER    

rms-cContactONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.2.9
OBJECT IDENTIFIER    

rms-cContact1Name 1.3.6.1.4.1.3711.15.1.1.2.1.1
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact2Name 1.3.6.1.4.1.3711.15.1.1.2.1.2
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact3Name 1.3.6.1.4.1.3711.15.1.1.2.1.3
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact4Name 1.3.6.1.4.1.3711.15.1.1.2.1.4
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact5Name 1.3.6.1.4.1.3711.15.1.1.2.1.5
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact6Name 1.3.6.1.4.1.3711.15.1.1.2.1.6
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact7Name 1.3.6.1.4.1.3711.15.1.1.2.1.7
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact8Name 1.3.6.1.4.1.3711.15.1.1.2.1.8
The name of the contact
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cContact1Type 1.3.6.1.4.1.3711.15.1.1.2.2.1
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact2Type 1.3.6.1.4.1.3711.15.1.1.2.2.2
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact3Type 1.3.6.1.4.1.3711.15.1.1.2.2.3
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact4Type 1.3.6.1.4.1.3711.15.1.1.2.2.4
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact5Type 1.3.6.1.4.1.3711.15.1.1.2.2.5
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact6Type 1.3.6.1.4.1.3711.15.1.1.2.2.6
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact7Type 1.3.6.1.4.1.3711.15.1.1.2.2.7
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact8Type 1.3.6.1.4.1.3711.15.1.1.2.2.8
Level or posedge or negedge input detection
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER level(0), positive-edge(1), negative-edge(2)  

rms-cContact1Reset 1.3.6.1.4.1.3711.15.1.1.2.3.1
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact2Reset 1.3.6.1.4.1.3711.15.1.1.2.3.2
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact3Reset 1.3.6.1.4.1.3711.15.1.1.2.3.3
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact4Reset 1.3.6.1.4.1.3711.15.1.1.2.3.4
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact5Reset 1.3.6.1.4.1.3711.15.1.1.2.3.5
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact6Reset 1.3.6.1.4.1.3711.15.1.1.2.3.6
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact7Reset 1.3.6.1.4.1.3711.15.1.1.2.3.7
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact8Reset 1.3.6.1.4.1.3711.15.1.1.2.3.8
Resets edge triggered input
Status: mandatory Access: write-only
OBJECT-TYPE    
  INTEGER reset(1)  

rms-cContact1NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.1
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact2NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.2
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact3NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.3
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact4NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.4
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact5NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.5
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact6NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.6
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact7NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.7
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact8NormalState 1.3.6.1.4.1.3711.15.1.1.2.4.8
Set to 0 for normally open condition, 1 for normally closed
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact1CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.1
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact2CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.2
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact3CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.3
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact4CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.4
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact5CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.5
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact6CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.6
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact7CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.7
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact8CurrentState 1.3.6.1.4.1.3711.15.1.1.2.5.8
The current state of the contact
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cContact1OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact2OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact3OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact4OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact5OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.5
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact6OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.6
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact7OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.7
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact8OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.2.6.8
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact1OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact2OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact3OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact4OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact5OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.5
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact6OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.6
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact7OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.7
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact8OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.2.7.8
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact1ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact2ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact3ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact4ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact5ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.5
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact6ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.6
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact7ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.7
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact8ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.2.8.8
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cContact1ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact2ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact3ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact4ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact5ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.5
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact6ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.6
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact7ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.7
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cContact8ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.2.9.8
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutputEnables 1.3.6.1.4.1.3711.15.1.1.3.1
OBJECT IDENTIFIER    

rms-cOutputNames 1.3.6.1.4.1.3711.15.1.1.3.2
OBJECT IDENTIFIER    

rms-cOutputStates 1.3.6.1.4.1.3711.15.1.1.3.3
OBJECT IDENTIFIER    

rms-cOutputBooleanStates 1.3.6.1.4.1.3711.15.1.1.3.4
OBJECT IDENTIFIER    

rms-cOutputOnDelay 1.3.6.1.4.1.3711.15.1.1.3.5
OBJECT IDENTIFIER    

rms-cOutputOffDelay 1.3.6.1.4.1.3711.15.1.1.3.6
OBJECT IDENTIFIER    

rms-cOutputStrings 1.3.6.1.4.1.3711.15.1.1.3.7
OBJECT IDENTIFIER    

rms-cOutputBooleanSelector 1.3.6.1.4.1.3711.15.1.1.3.8
OBJECT IDENTIFIER    

rms-cOutputOFFtoONtraps 1.3.6.1.4.1.3711.15.1.1.3.9
OBJECT IDENTIFIER    

rms-cOutputOFFtoONrepeatTimers 1.3.6.1.4.1.3711.15.1.1.3.10
OBJECT IDENTIFIER    

rms-cOutputONtoOFFtraps 1.3.6.1.4.1.3711.15.1.1.3.11
OBJECT IDENTIFIER    

rms-cOutputONtoOFFrepeatTimers 1.3.6.1.4.1.3711.15.1.1.3.12
OBJECT IDENTIFIER    

rms-cOutput1Enable 1.3.6.1.4.1.3711.15.1.1.3.1.1
Set to one enables the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput2Enable 1.3.6.1.4.1.3711.15.1.1.3.1.2
Set to one enables the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput3Enable 1.3.6.1.4.1.3711.15.1.1.3.1.3
Set to one enables the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput1Name 1.3.6.1.4.1.3711.15.1.1.3.2.1
The name of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cOutput2Name 1.3.6.1.4.1.3711.15.1.1.3.2.2
The name of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cOutput3Name 1.3.6.1.4.1.3711.15.1.1.3.2.3
The name of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cOutput4Name 1.3.6.1.4.1.3711.15.1.1.3.2.4
The name of the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..47)  

rms-cOutput1State 1.3.6.1.4.1.3711.15.1.1.3.3.1
Default State for the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput2State 1.3.6.1.4.1.3711.15.1.1.3.3.2
Default State for the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput3State 1.3.6.1.4.1.3711.15.1.1.3.3.3
Default State for the output
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput1BooleanState 1.3.6.1.4.1.3711.15.1.1.3.4.1
Set as a result of the AND/OR comparison
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput2BooleanState 1.3.6.1.4.1.3711.15.1.1.3.4.2
Set as a result of the AND/OR comparison
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput3BooleanState 1.3.6.1.4.1.3711.15.1.1.3.4.3
Set as a result of the AND/OR comparison
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput4BooleanState 1.3.6.1.4.1.3711.15.1.1.3.4.4
Set as a result of the AND/OR comparison
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

rms-cOutput1OnDelay 1.3.6.1.4.1.3711.15.1.1.3.5.1
Delay in seconds for the activation of the output in response to a change into the on state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput2OnDelay 1.3.6.1.4.1.3711.15.1.1.3.5.2
Delay in seconds for the activation of the output in response to a change into the on state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput3OnDelay 1.3.6.1.4.1.3711.15.1.1.3.5.3
Delay in seconds for the activation of the output in response to a change into the on state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput4OnDelay 1.3.6.1.4.1.3711.15.1.1.3.5.4
Delay in seconds for the activation of the output in response to a change into the on state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput1OffDelay 1.3.6.1.4.1.3711.15.1.1.3.6.1
Delay in seconds for the activation of the output in response to a change into the OFF state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput2OffDelay 1.3.6.1.4.1.3711.15.1.1.3.6.2
Delay in seconds for the activation of the output in response to a change into the OFF state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput3OffDelay 1.3.6.1.4.1.3711.15.1.1.3.6.3
Delay in seconds for the activation of the output in response to a change into the OFF state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput4OffDelay 1.3.6.1.4.1.3711.15.1.1.3.6.4
Delay in seconds for the activation of the output in response to a change into the OFF state
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..32000  

rms-cOutput1BooleanInput 1.3.6.1.4.1.3711.15.1.1.3.7.1
Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

rms-cOutput2BooleanInput 1.3.6.1.4.1.3711.15.1.1.3.7.2
Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

rms-cOutput3BooleanInput 1.3.6.1.4.1.3711.15.1.1.3.7.3
Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

rms-cOutput4BooleanInput 1.3.6.1.4.1.3711.15.1.1.3.7.4
Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

rms-cOutput1BooleanSelector 1.3.6.1.4.1.3711.15.1.1.3.8.1
Set 0 to select OR, and 1 to select AND
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER or(0), and(1)  

rms-cOutput2BooleanSelector 1.3.6.1.4.1.3711.15.1.1.3.8.2
Set 0 to select OR, and 1 to select AND
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER or(0), and(1)  

rms-cOutput3BooleanSelector 1.3.6.1.4.1.3711.15.1.1.3.8.3
Set 0 to select OR, and 1 to select AND
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER or(0), and(1)  

rms-cOutput4BooleanSelector 1.3.6.1.4.1.3711.15.1.1.3.8.4
Set 0 to select OR, and 1 to select AND
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER or(0), and(1)  

rms-cOutput1OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.3.9.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput2OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.3.9.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput3OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.3.9.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput4OFFtoONtrap 1.3.6.1.4.1.3711.15.1.1.3.9.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput1OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.3.10.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput2OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.3.10.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput3OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.3.10.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput4OFFtoONrep 1.3.6.1.4.1.3711.15.1.1.3.10.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput1ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.3.11.1
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput2ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.3.11.2
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput3ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.3.11.3
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput4ONtoOFFtrap 1.3.6.1.4.1.3711.15.1.1.3.11.4
Set to 0 for trap disabled, 1 for enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

rms-cOutput1ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.3.12.1
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput2ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.3.12.2
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput3ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.3.12.3
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000  

rms-cOutput4ONtoOFFrep 1.3.6.1.4.1.3711.15.1.1.3.12.4
Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 30..32000