ROOMALERT11E-MIB

File: ROOMALERT11E-MIB.mib (21955 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC-1215

Imported symbols

enterprises IpAddress Counter
TimeTicks OBJECT-TYPE TRAP-TYPE

Defined Values

avtech 1.3.6.1.4.1.20916
OBJECT IDENTIFIER    

products 1.3.6.1.4.1.20916.1
OBJECT IDENTIFIER    

roomalert11E 1.3.6.1.4.1.20916.1.3
OBJECT IDENTIFIER    

sensors 1.3.6.1.4.1.20916.1.3.1
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.20916.1.3.2
OBJECT IDENTIFIER    

thresholds 1.3.6.1.4.1.20916.1.3.3
OBJECT IDENTIFIER    

channel1 1.3.6.1.4.1.20916.1.3.1.1
OBJECT IDENTIFIER    

channel2 1.3.6.1.4.1.20916.1.3.1.2
OBJECT IDENTIFIER    

channel3 1.3.6.1.4.1.20916.1.3.1.3
OBJECT IDENTIFIER    

channel4 1.3.6.1.4.1.20916.1.3.1.4
OBJECT IDENTIFIER    

channels 1.3.6.1.4.1.20916.1.3.3.1
OBJECT IDENTIFIER    

channels1 1.3.6.1.4.1.20916.1.3.3.1.1
OBJECT IDENTIFIER    

channels2 1.3.6.1.4.1.20916.1.3.3.1.2
OBJECT IDENTIFIER    

channels3 1.3.6.1.4.1.20916.1.3.3.1.3
OBJECT IDENTIFIER    

channels4 1.3.6.1.4.1.20916.1.3.3.1.4
OBJECT IDENTIFIER    

sensor1-1 1.3.6.1.4.1.20916.1.3.1.1.1
The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-2 1.3.6.1.4.1.20916.1.3.1.1.2
The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-3 1.3.6.1.4.1.20916.1.3.1.1.3
The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-4 1.3.6.1.4.1.20916.1.3.1.1.4
The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-5 1.3.6.1.4.1.20916.1.3.1.1.5
The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-6 1.3.6.1.4.1.20916.1.3.1.1.6
The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-7 1.3.6.1.4.1.20916.1.3.1.1.7
The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

sensor1-8 1.3.6.1.4.1.20916.1.3.1.1.8
The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

switch-label-1 1.3.6.1.4.1.20916.1.3.1.1.9
The label for switch sensor 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-2 1.3.6.1.4.1.20916.1.3.1.1.10
The label for switch sensor 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-3 1.3.6.1.4.1.20916.1.3.1.1.11
The label for switch sensor 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-4 1.3.6.1.4.1.20916.1.3.1.1.12
The label for switch sensor 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-5 1.3.6.1.4.1.20916.1.3.1.1.13
The label for switch sensor 5
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-6 1.3.6.1.4.1.20916.1.3.1.1.14
The label for switch sensor 6
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-7 1.3.6.1.4.1.20916.1.3.1.1.15
The label for switch sensor 7
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

switch-label-8 1.3.6.1.4.1.20916.1.3.1.1.16
The label for switch sensor 8
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

sensor2-1 1.3.6.1.4.1.20916.1.3.1.2.1
The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor2-2 1.3.6.1.4.1.20916.1.3.1.2.2
The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor2-3 1.3.6.1.4.1.20916.1.3.1.2.3
The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor2-4 1.3.6.1.4.1.20916.1.3.1.2.4
The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor2-5 1.3.6.1.4.1.20916.1.3.1.2.5
The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor2-6-label 1.3.6.1.4.1.20916.1.3.1.2.6
The label of this sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

sensor3-1 1.3.6.1.4.1.20916.1.3.1.3.1
The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor3-2 1.3.6.1.4.1.20916.1.3.1.3.2
The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor3-3 1.3.6.1.4.1.20916.1.3.1.3.3
The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor3-4 1.3.6.1.4.1.20916.1.3.1.3.4
The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor3-5 1.3.6.1.4.1.20916.1.3.1.3.5
The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor3-6-label 1.3.6.1.4.1.20916.1.3.1.3.6
The label of this sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

sensor4-1 1.3.6.1.4.1.20916.1.3.1.4.1
The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor4-2 1.3.6.1.4.1.20916.1.3.1.4.2
The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor4-3 1.3.6.1.4.1.20916.1.3.1.4.3
The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor4-4 1.3.6.1.4.1.20916.1.3.1.4.4
The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor4-5 1.3.6.1.4.1.20916.1.3.1.4.5
The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

sensor4-6-label 1.3.6.1.4.1.20916.1.3.1.4.6
The label of this sensor
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alarm1 1.3.6.1.4.1.20916.1.3.2.1
Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..255  

alarm2 1.3.6.1.4.1.20916.1.3.2.2
Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..255  

alarm3 1.3.6.1.4.1.20916.1.3.2.3
Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..255  

alarm4 1.3.6.1.4.1.20916.1.3.2.4
Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..255  

alarmMessage1 1.3.6.1.4.1.20916.1.3.2.5
Alarm Message from sensor channel 1 (Internal)
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alarmMessage2 1.3.6.1.4.1.20916.1.3.2.6
Alarm Message from sensor channel 2 (External)
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alarmMessage3 1.3.6.1.4.1.20916.1.3.2.7
Alarm Message from sensor channel 3 (External)
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

alarmMessage4 1.3.6.1.4.1.20916.1.3.2.8
Alarm Message from sensor channel 4 (External)
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

threshold1-1 1.3.6.1.4.1.20916.1.3.3.1.1.1
Threshold 1 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-2 1.3.6.1.4.1.20916.1.3.3.1.1.2
Threshold 2 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-3 1.3.6.1.4.1.20916.1.3.3.1.1.3
Threshold 3 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-4 1.3.6.1.4.1.20916.1.3.3.1.1.4
Threshold 4 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-5 1.3.6.1.4.1.20916.1.3.3.1.1.5
Threshold 5 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-6 1.3.6.1.4.1.20916.1.3.3.1.1.6
Threshold 6 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-7 1.3.6.1.4.1.20916.1.3.3.1.1.7
Threshold 7 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold1-8 1.3.6.1.4.1.20916.1.3.3.1.1.8
Threshold 8 defined for Channel 1
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold2-1 1.3.6.1.4.1.20916.1.3.3.1.2.1
Threshold 1 defined for Channel 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold2-2 1.3.6.1.4.1.20916.1.3.3.1.2.2
Threshold 2 defined for Channel 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold2-3 1.3.6.1.4.1.20916.1.3.3.1.2.3
Threshold 3 defined for Channel 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold2-4 1.3.6.1.4.1.20916.1.3.3.1.2.4
Threshold 4 defined for Channel 2
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold3-1 1.3.6.1.4.1.20916.1.3.3.1.3.1
Threshold 1 defined for Channel 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold3-2 1.3.6.1.4.1.20916.1.3.3.1.3.2
Threshold 2 defined for Channel 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold3-3 1.3.6.1.4.1.20916.1.3.3.1.3.3
Threshold 3 defined for Channel 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold3-4 1.3.6.1.4.1.20916.1.3.3.1.3.4
Threshold 4 defined for Channel 3
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold4-1 1.3.6.1.4.1.20916.1.3.3.1.4.1
Threshold 1 defined for Channel 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold4-2 1.3.6.1.4.1.20916.1.3.3.1.4.2
Threshold 2 defined for Channel 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold4-3 1.3.6.1.4.1.20916.1.3.3.1.4.3
Threshold 3 defined for Channel 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

threshold4-4 1.3.6.1.4.1.20916.1.3.3.1.4.4
Threshold 4 defined for Channel 4
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

tempAlarm1-11e 1
A tempAlarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE    

room-alert-11E-SNMP-trap 2
A Room Alert 11E SNMP Trap indicates that an alarm condition has occurred on the sensor inidcated by the alarmMessage variable.
TRAP-TYPE    

tempAlarm2-11e 3
A tempAlarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE    

tempClear2-11e 4
A tempClear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

tempAlarm3-11e 5
A tempAlarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE    

tempClear3-11e 6
A tempClear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityAlarm1-11e 7
A humidityAlarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE    

humidityClear1-11e 8
A humidityClear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityAlarm2-11e 9
A humidityAlarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE    

humidityClear2-11e 10
A humidityClear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

humidityAlarm3-11e 11
A humidityAlarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE    

humidityClear3-11e 12
A humidityClear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE    

switchAlarm1-11e 13
A switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
TRAP-TYPE    

switchClear1-11e 14
A switchClear1 trap signifies that the switch sensor 1 has returned to a normal state.
TRAP-TYPE    

switchAlarm2-11e 15
A switchAlarm2 trap signifies that switch sensor 2 is in an alarm state.
TRAP-TYPE    

switchClear2-11e 16
A switchClear2 trap signifies that the switch sensor 2 has returned to a normal state.
TRAP-TYPE    

switchAlarm3-11e 17
A switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
TRAP-TYPE    

switchClear3-11e 18
A switchClear3 trap signifies that the switch sensor 3 has returned to a normal state.
TRAP-TYPE    

switchAlarm4-11e 19
A switchAlarm4 trap signifies that switch sensor 4 is in an alarm state.
TRAP-TYPE    

switchClear4-11e 20
A switchClear4 trap signifies that the switch sensor 4 has returned to a normal state.
TRAP-TYPE    

switchAlarm5-11e 21
A switchAlarm5 trap signifies that switch sensor 5 is in an alarm state.
TRAP-TYPE    

switchClear5-11e 22
A switchClear5 trap signifies that the switch sensor 5 has returned to a normal state.
TRAP-TYPE    

switchAlarm6-11e 23
A switchAlarm6 trap signifies that switch sensor 6 is in an alarm state.
TRAP-TYPE    

switchClear6-11e 24
A switchClear6 trap signifies that the switch sensor 6 has returned to a normal state.
TRAP-TYPE    

switchAlarm7-11e 25
A switchAlarm7 trap signifies that switch sensor 7 is in an alarm state.
TRAP-TYPE    

switchClear7-11e 26
A switchClear7 trap signifies that the switch sensor 7 has returned to a normal state.
TRAP-TYPE    

switchAlarm8-11e 27
A switchAlarm8 trap signifies that switch sensor 8 is in an alarm state.
TRAP-TYPE    

switchClear8-11e 28
A switchClear8 trap signifies that the switch sensor 8 has returned to a normal state.
TRAP-TYPE