ROOMALERT4E-MIB

File: ROOMALERT4E-MIB.mib (7288 bytes)

Imported modules

RFC1155-SMI RFC-1212 RFC-1215

Imported symbols

enterprises IpAddress Counter
TimeTicks OBJECT-TYPE TRAP-TYPE

Defined Values

avtech 1.3.6.1.4.1.20916
OBJECT IDENTIFIER    

products 1.3.6.1.4.1.20916.1
OBJECT IDENTIFIER    

roomALERT4E 1.3.6.1.4.1.20916.1.6
OBJECT IDENTIFIER    

sensors 1.3.6.1.4.1.20916.1.6.1
OBJECT IDENTIFIER    

signaltower 1.3.6.1.4.1.20916.1.6.2
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.20916.1.6.3
OBJECT IDENTIFIER    

internal 1.3.6.1.4.1.20916.1.6.1.1
OBJECT IDENTIFIER    

temperature 1.3.6.1.4.1.20916.1.6.1.1.1
OBJECT IDENTIFIER    

humidity 1.3.6.1.4.1.20916.1.6.1.1.2
OBJECT IDENTIFIER    

heat-index 1.3.6.1.4.1.20916.1.6.1.1.3
OBJECT IDENTIFIER    

digital 1.3.6.1.4.1.20916.1.6.1.2
OBJECT IDENTIFIER    

digital-sen1 1.3.6.1.4.1.20916.1.6.1.2.1
OBJECT IDENTIFIER    

digital-sen2 1.3.6.1.4.1.20916.1.6.1.2.2
OBJECT IDENTIFIER    

switch 1.3.6.1.4.1.20916.1.6.1.3
OBJECT IDENTIFIER    

internal-tempf 1.3.6.1.4.1.20916.1.6.1.1.1.1
The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-tempc 1.3.6.1.4.1.20916.1.6.1.1.1.2
The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-humidity 1.3.6.1.4.1.20916.1.6.1.1.2.1
The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

internal-heat-index 1.3.6.1.4.1.20916.1.6.1.1.3.1
The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-1 1.3.6.1.4.1.20916.1.6.1.2.1.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-2 1.3.6.1.4.1.20916.1.6.1.2.1.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-3 1.3.6.1.4.1.20916.1.6.1.2.1.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen1-4 1.3.6.1.4.1.20916.1.6.1.2.1.4
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-1 1.3.6.1.4.1.20916.1.6.1.2.2.1
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-2 1.3.6.1.4.1.20916.1.6.1.2.2.2
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-3 1.3.6.1.4.1.20916.1.6.1.2.2.3
If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

digital-sen2-4 1.3.6.1.4.1.20916.1.6.1.2.2.4
If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

switch-sen1 1.3.6.1.4.1.20916.1.6.1.3.1
The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1  

red-led 1.3.6.1.4.1.20916.1.6.2.1
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

amber-led 1.3.6.1.4.1.20916.1.6.2.2
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

green-led 1.3.6.1.4.1.20916.1.6.2.3
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

blue-led 1.3.6.1.4.1.20916.1.6.2.4
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

white-led 1.3.6.1.4.1.20916.1.6.2.5
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

alarm1 1.3.6.1.4.1.20916.1.6.2.6
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

alarm2 1.3.6.1.4.1.20916.1.6.2.7
The status of this Signal Tower element (0 = OFF, 1 = ON).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER 0..1  

alarmmessage 1.3.6.1.4.1.20916.1.6.3.1
Last Alarm Message
Status: mandatory Access: read-only
OBJECT-TYPE    
  OCTET STRING  

room-alert-4e-snmp-trap 2
A room-alert-4e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable.
TRAP-TYPE