SOCOMECPDU-MIB

File: SOCOMECPDU-MIB.mib (21592 bytes)

Imported modules

RFC1155-SMI RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

enterprises IpAddress DisplayString
OBJECT-TYPE TRAP-TYPE

Defined Values

socomec 1.3.6.1.4.1.4555
OBJECT IDENTIFIER    

ups 1.3.6.1.4.1.4555.2
OBJECT IDENTIFIER    

pdu 1.3.6.1.4.1.4555.2.30
OBJECT IDENTIFIER    

dpduIdent 1.3.6.1.4.1.4555.2.30.1
OBJECT IDENTIFIER    

dpduOutput 1.3.6.1.4.1.4555.2.30.2
OBJECT IDENTIFIER    

dpduAlarm 1.3.6.1.4.1.4555.2.30.3
OBJECT IDENTIFIER    

dpduEnvironment 1.3.6.1.4.1.4555.2.30.4
OBJECT IDENTIFIER    

dpduTraps 1.3.6.1.4.1.4555.2.30.20
OBJECT IDENTIFIER    

dpduIdentManufacturer 1.3.6.1.4.1.4555.2.30.1.1
The EnviroStation Vendor.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

dpduIdentModel 1.3.6.1.4.1.4555.2.30.1.2
The PDU Model designation.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

dpduIdentSerialNumber 1.3.6.1.4.1.4555.2.30.1.3
The PDU serial number
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

dpduIdentPDUFirmwareVersion 1.3.6.1.4.1.4555.2.30.1.4
The PDU firmware version
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

dpduIdentAgentSoftwareVersion 1.3.6.1.4.1.4555.2.30.1.5
The PDU NMC software version
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..16)  

dpduIdentName 1.3.6.1.4.1.4555.2.30.1.6
A string identifying the PDU. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

dpduAttachedDevices 1.3.6.1.4.1.4555.2.30.1.7
A string identifying the devices attached to the output(s) of the PDU. This object should be set by the administrator.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

dpduOutputFrequency 1.3.6.1.4.1.4555.2.30.2.1
The present output frequency in 1/10 Hz.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputVoltage1 1.3.6.1.4.1.4555.2.30.2.2
The Output line 1 voltage of the PDU system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputCurrent1 1.3.6.1.4.1.4555.2.30.2.3
The Output line 1 current of the PDU system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputVoltage2 1.3.6.1.4.1.4555.2.30.2.4
The Output line 2 voltage of the PDU system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputCurrent2 1.3.6.1.4.1.4555.2.30.2.5
The Output line 2 current of the PDU system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputVoltage3 1.3.6.1.4.1.4555.2.30.2.6
The Output line 3 voltage of the PDU system in 1/10 V.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduOutputCurrent3 1.3.6.1.4.1.4555.2.30.2.7
The Output line 3 current of the PDU system in 1/10 A.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduAlarmDisconnect 1.3.6.1.4.1.4555.2.30.3.1
Does the PDU disconnect?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL1LoadMajor 1.3.6.1.4.1.4555.2.30.3.2
L1 load major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL1LoadMinor 1.3.6.1.4.1.4555.2.30.3.3
L1 load minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL1OutVoltMajor 1.3.6.1.4.1.4555.2.30.3.4
L1 output votage major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL1OutVoltMinor 1.3.6.1.4.1.4555.2.30.3.5
L1 output voltage minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL2LoadMajor 1.3.6.1.4.1.4555.2.30.3.6
L2 load major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL2LoadMinor 1.3.6.1.4.1.4555.2.30.3.7
L2 load minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL2OutVoltMajor 1.3.6.1.4.1.4555.2.30.3.8
L2 output votage major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL2OutVoltMinor 1.3.6.1.4.1.4555.2.30.3.9
L2 output voltage minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL3LoadMajor 1.3.6.1.4.1.4555.2.30.3.10
L3 load major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL3LoadMinor 1.3.6.1.4.1.4555.2.30.3.11
L3 load minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL3OutVoltMajor 1.3.6.1.4.1.4555.2.30.3.12
L3 output votage major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL3OutVoltMinor 1.3.6.1.4.1.4555.2.30.3.13
L3 output voltage minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL12LoadMajor 1.3.6.1.4.1.4555.2.30.3.14
L1, L2 load major alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmL12LoadMinor 1.3.6.1.4.1.4555.2.30.3.15
L1, L2 load minor alarm
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduEnvTemperature 1.3.6.1.4.1.4555.2.30.4.1
The ambient environmental temperature.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduEnvHumidity 1.3.6.1.4.1.4555.2.30.4.2
The environmental humidity.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

dpduEnvSetTemperatureWarnLimit 1.3.6.1.4.1.4555.2.30.4.3
Alarm dpduEnvOverWarnTemperature on when the environmental temperature over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dpduEnvSetTemperatureAlarmLimit 1.3.6.1.4.1.4555.2.30.4.4
Alarm dpduEnvOverAlarmTemperature on when the environmental temperature over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dpduEnvSetHumidityWarnLimit 1.3.6.1.4.1.4555.2.30.4.5
Alarm dpduEnvOverWarnHumidity on when the environmental humidity over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dpduEnvSetHumidityAlarmLimit 1.3.6.1.4.1.4555.2.30.4.6
Alarm dpduEnvOverAlarmHumidity on when the environmental humidity over the value.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

dpduEnvSetEnvRelay1 1.3.6.1.4.1.4555.2.30.4.7
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dpduEnvSetEnvRelay2 1.3.6.1.4.1.4555.2.30.4.8
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dpduEnvSetEnvRelay3 1.3.6.1.4.1.4555.2.30.4.9
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dpduEnvSetEnvRelay4 1.3.6.1.4.1.4555.2.30.4.10
Tok_String
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normalOpen(0), normalClose(1)  

dpduWarnOverEnvTemperature 1.3.6.1.4.1.4555.2.30.4.11
Does the environment over warning temperature?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmOverEnvTemperature 1.3.6.1.4.1.4555.2.30.4.12
Does the environment over alarm temperature?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduWarnmOverEnvHumidity 1.3.6.1.4.1.4555.2.30.4.13
Does the environment over warn humidity?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmOverEnvHumidity 1.3.6.1.4.1.4555.2.30.4.14
Does the environment over alarm humidity?
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmEnvRelay1 1.3.6.1.4.1.4555.2.30.4.15
The alarm status of relay1.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmEnvRelay2 1.3.6.1.4.1.4555.2.30.4.16
The alarm status of relay2.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmEnvRelay3 1.3.6.1.4.1.4555.2.30.4.17
The alarm status of relay3.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmEnvRelay4 1.3.6.1.4.1.4555.2.30.4.18
The alarm status of relay4.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER off(0), on(1)  

dpduAlarmEnvDisconnect 1.3.6.1.4.1.4555.2.30.4.19
To indicate the communication status of EnviroProbe.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER no(0), yes(1)  

dpduCommunicationLost 1
Communication with the PDU failed.
TRAP-TYPE    

dpduCommunicationEstablished 2
Communication with the PDU reestablished.
TRAP-TYPE    

dpduL1LoadMajorAlarm 3
L1 load major alarm.
TRAP-TYPE    

dpduL1LoadMajorAlarmRecover 4
Recover from L1 load major alarm.
TRAP-TYPE    

dpduL1LoadMinorAlarm 5
L1 load minor alarm.
TRAP-TYPE    

dpduL1LoadMinorAlarmRecover 6
Recover from L1 load minor alarm.
TRAP-TYPE    

dpduL1OutVoltMajorAlarm 7
L1 output voltage major alarm.
TRAP-TYPE    

dpduL1OutVoltMajorAlarmRecover 8
Recover from L1 output voltage major alarm.
TRAP-TYPE    

dpduL1OutVoltMinorAlarm 9
L1 output voltage minor alarm.
TRAP-TYPE    

dpduL1OutVoltMinorAlarmRecover 10
Recover from L1 output voltage minor alarm.
TRAP-TYPE    

dpduL2LoadMajorAlarm 11
L2 load major alarm.
TRAP-TYPE    

dpduL2LoadMajorAlarmRecover 12
Recover from L2 load major alarm.
TRAP-TYPE    

dpduL2LoadMinorAlarm 13
L2 load minor alarm.
TRAP-TYPE    

dpduL2LoadMinorAlarmRecover 14
Recover from L2 load minor alarm.
TRAP-TYPE    

dpduL2OutVoltMajorAlarm 15
L2 output voltage major alarm.
TRAP-TYPE    

dpduL2OutVoltMajorAlarmRecover 16
Recover from L2 output voltage major alarm.
TRAP-TYPE    

dpduL2OutVoltMinorAlarm 17
L2 output voltage minor alarm.
TRAP-TYPE    

dpduL2OutVoltMinorAlarmRecover 18
Recover from L2 output voltage minor alarm.
TRAP-TYPE    

dpduL3LoadMajorAlarm 19
L3 load major alarm.
TRAP-TYPE    

dpduL3LoadMajorAlarmRecover 20
Recover from L3 load major alarm.
TRAP-TYPE    

dpduL3LoadMinorAlarm 21
L3 load minor alarm.
TRAP-TYPE    

dpduL3LoadMinorAlarmRecover 22
Recover from L3 load minor alarm.
TRAP-TYPE    

dpduL3OutVoltMajorAlarm 23
L3 output voltage major alarm.
TRAP-TYPE    

dpduL3OutVoltMajorAlarmRecover 24
Recover from L3 output voltage major alarm.
TRAP-TYPE    

dpduL3OutVoltMinorAlarm 25
L3 output voltage minor alarm.
TRAP-TYPE    

dpduL3OutVoltMinorAlarmRecover 26
Recover from L3 output voltage minor alarm.
TRAP-TYPE    

dpduL12LoadMajorAlarm 27
L1 L2 load major alarm.
TRAP-TYPE    

dpduL12LoadMajorAlarmRecover 28
Recover from L1 L2 load major alarm.
TRAP-TYPE    

dpduL12LoadMinorAlarm 29
L1 L2 load minor alarm.
TRAP-TYPE    

dpduL12LoadMinorAlarmRecover 30
Recover from L1 L2 load minor alarm.
TRAP-TYPE    

dpduEnvCommunicationLost 31
Communication with the environmental sensor failed.
TRAP-TYPE    

dpduEnvCommunicationEstablished 32
Communication with the environmental sensor reestablished.
TRAP-TYPE    

dpduEnvOverWarnTemperature 33
The environment over warning temperature.
TRAP-TYPE    

dpduNoLongerEnvOverWarnTemperature 34
The environment recovered from over warning temperature.
TRAP-TYPE    

dpduEnvOverWarnHumidity 35
The environment over warning humidity.
TRAP-TYPE    

dpduNoLongerEnvOverWarnHumidity 36
The environment recovered from over warning humidity.
TRAP-TYPE    

dpduEnvOverAlarmTemperature 37
The environment over alarm temperature.
TRAP-TYPE    

dpduNoLongerEnvOverAlarmTemperature 38
The environment recovered from over alarm temperature.
TRAP-TYPE    

dpduEnvOverAlarmHumidity 39
The environment over alarm humidity.
TRAP-TYPE    

dpduNoLongerEnvOverAlarmHumidity 40
The environment recovered from over alarm humidity.
TRAP-TYPE    

dpduEnvRelay1Alarm 41
The environment relay1 is not in normal state.
TRAP-TYPE    

dpduEnvRelay1Normal 42
The environment relay1 is in normal state.
TRAP-TYPE    

dpduEnvRelay2Alarm 43
The environment relay2 is not in normal state.
TRAP-TYPE    

dpduEnvRelay2Normal 44
The environment relay2 is in normal state.
TRAP-TYPE    

dpduEnvRelay3Alarm 45
The environment relay3 is not in normal state.
TRAP-TYPE    

dpduEnvRelay3Normal 46
The environment relay3 is in normal state.
TRAP-TYPE    

dpduEnvRelay4Alarm 47
The environment relay4 is not in normal state.
TRAP-TYPE    

dpduEnvRelay4Normal 48
The environment relay4 is in normal state.
TRAP-TYPE