DeviceStatus |
|
Status returned by devices. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
normal(0), disabled(1), purged(2), reading(5), settle(6), notFound(7), lost(8), readError(9), noComm(10), pwrError(11), breakerTripped(12), fuseBlown(13), lowAlarm(14), lowWarning(15), highWarning(16), highAlarm(17), alarm(18), underLimit(19), overLimit(20), nvmFail(21), profileError(22), conflict(23) |
|
St4UnitConfigEntry |
|
SEQUENCE |
|
|
|
|
st4UnitIndex |
Integer32 |
|
|
st4UnitID |
DisplayString |
|
|
st4UnitName |
DisplayString |
|
|
st4UnitProductSN |
DisplayString |
|
|
st4UnitModel |
DisplayString |
|
|
st4UnitAssetTag |
DisplayString |
|
|
st4UnitType |
INTEGER |
|
|
st4UnitCapabilities |
BITS |
|
|
st4UnitProductMfrDate |
DisplayString |
|
|
st4UnitDisplayOrientation |
INTEGER |
|
|
st4UnitOutletSequenceOrder |
INTEGER |
|
|
st4UnitInputCordCount |
Integer32 |
|
|
st4UnitTempSensorCount |
Integer32 |
|
|
st4UnitHumidSensorCount |
Integer32 |
|
|
st4UnitWaterSensorCount |
Integer32 |
|
|
st4UnitCcSensorCount |
Integer32 |
|
|
st4UnitAdcSensorCount |
Integer32 |
|
St4LineEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4LineNotifications |
EventNotificationMethods |
|
|
st4LineCurrentLowAlarm |
Integer32 |
|
|
st4LineCurrentLowWarning |
Integer32 |
|
|
st4LineCurrentHighWarning |
Integer32 |
|
|
st4LineCurrentHighAlarm |
Integer32 |
|
St4PhaseMonitorEntry |
|
SEQUENCE |
|
|
|
|
st4PhaseState |
DeviceState |
|
|
st4PhaseStatus |
DeviceStatus |
|
|
st4PhaseVoltage |
Integer32 |
|
|
st4PhaseVoltageStatus |
DeviceStatus |
|
|
st4PhaseVoltageDeviation |
Integer32 |
|
|
st4PhaseCurrent |
Integer32 |
|
|
st4PhaseCurrentCrestFactor |
Integer32 |
|
|
st4PhaseActivePower |
Integer32 |
|
|
st4PhaseApparentPower |
Integer32 |
|
|
st4PhasePowerFactor |
Integer32 |
|
|
st4PhasePowerFactorStatus |
DeviceStatus |
|
|
st4PhaseReactance |
Integer32 |
|
|
st4PhaseEnergy |
Integer32 |
|
St4PhaseEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4PhaseNotifications |
EventNotificationMethods |
|
|
st4PhaseVoltageLowAlarm |
Integer32 |
|
|
st4PhaseVoltageLowWarning |
Integer32 |
|
|
st4PhaseVoltageHighWarning |
Integer32 |
|
|
st4PhaseVoltageHighAlarm |
Integer32 |
|
|
st4PhasePowerFactorLowAlarm |
Integer32 |
|
|
st4PhasePowerFactorLowWarning |
Integer32 |
|
St4BranchEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4BranchNotifications |
EventNotificationMethods |
|
|
st4BranchCurrentLowAlarm |
Integer32 |
|
|
st4BranchCurrentLowWarning |
Integer32 |
|
|
st4BranchCurrentHighWarning |
Integer32 |
|
|
st4BranchCurrentHighAlarm |
Integer32 |
|
St4OutletMonitorEntry |
|
SEQUENCE |
|
|
|
|
st4OutletState |
DeviceState |
|
|
st4OutletStatus |
DeviceStatus |
|
|
st4OutletCurrent |
Integer32 |
|
|
st4OutletCurrentStatus |
DeviceStatus |
|
|
st4OutletCurrentUtilized |
Integer32 |
|
|
st4OutletVoltage |
Integer32 |
|
|
st4OutletActivePower |
Integer32 |
|
|
st4OutletActivePowerStatus |
DeviceStatus |
|
|
st4OutletApparentPower |
Integer32 |
|
|
st4OutletPowerFactor |
Integer32 |
|
|
st4OutletPowerFactorStatus |
DeviceStatus |
|
|
st4OutletCurrentCrestFactor |
Integer32 |
|
|
st4OutletReactance |
INTEGER |
|
|
st4OutletEnergy |
Integer32 |
|
St4OutletEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4OutletNotifications |
EventNotificationMethods |
|
|
st4OutletCurrentLowAlarm |
Integer32 |
|
|
st4OutletCurrentLowWarning |
Integer32 |
|
|
st4OutletCurrentHighWarning |
Integer32 |
|
|
st4OutletCurrentHighAlarm |
Integer32 |
|
|
st4OutletActivePowerLowAlarm |
Integer32 |
|
|
st4OutletActivePowerLowWarning |
Integer32 |
|
|
st4OutletActivePowerHighWarning |
Integer32 |
|
|
st4OutletActivePowerHighAlarm |
Integer32 |
|
|
st4OutletPowerFactorLowAlarm |
Integer32 |
|
|
st4OutletPowerFactorLowWarning |
Integer32 |
|
St4TempSensorMonitorEntry |
|
SEQUENCE |
|
|
|
|
st4TempSensorValue |
Integer32 |
|
|
st4TempSensorStatus |
DeviceStatus |
|
St4TempSensorEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4TempSensorNotifications |
EventNotificationMethods |
|
|
st4TempSensorLowAlarm |
Integer32 |
|
|
st4TempSensorLowWarning |
Integer32 |
|
|
st4TempSensorHighWarning |
Integer32 |
|
|
st4TempSensorHighAlarm |
Integer32 |
|
St4HumidSensorConfigEntry |
|
SEQUENCE |
|
|
|
|
st4HumidSensorIndex |
Integer32 |
|
|
st4HumidSensorID |
DisplayString |
|
|
st4HumidSensorName |
DisplayString |
|
St4HumidSensorMonitorEntry |
|
SEQUENCE |
|
|
|
|
st4HumidSensorValue |
Integer32 |
|
|
st4HumidSensorStatus |
DeviceStatus |
|
St4HumidSensorEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4HumidSensorNotifications |
EventNotificationMethods |
|
|
st4HumidSensorLowAlarm |
Integer32 |
|
|
st4HumidSensorLowWarning |
Integer32 |
|
|
st4HumidSensorHighWarning |
Integer32 |
|
|
st4HumidSensorHighAlarm |
Integer32 |
|
St4WaterSensorConfigEntry |
|
SEQUENCE |
|
|
|
|
st4WaterSensorIndex |
Integer32 |
|
|
st4WaterSensorID |
DisplayString |
|
|
st4WaterSensorName |
DisplayString |
|
St4AdcSensorEventConfigEntry |
|
SEQUENCE |
|
|
|
|
st4AdcSensorNotifications |
EventNotificationMethods |
|
|
st4AdcSensorLowAlarm |
Integer32 |
|
|
st4AdcSensorLowWarning |
Integer32 |
|
|
st4AdcSensorHighWarning |
Integer32 |
|
|
st4AdcSensorHighAlarm |
Integer32 |
|
sentry4 |
1.3.6.1.4.1.1718.4 |
This is the MIB module for the fourth generation of the
Sentry product family. This includes the PRO1 and PRO2
series of Smart and Switched Cabinet Distribution Unit (CDU)
and Power Distribution Unit (PDU) products. |
MODULE-IDENTITY |
|
|
|
st4UnitConfigEntry |
1.3.6.1.4.1.1718.4.1.2.2.1 |
Configuration objects for a particular unit. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4UnitConfigEntry |
|
|
st4UnitMonitorEntry |
1.3.6.1.4.1.1718.4.1.2.3.1 |
Objects to monitor for a particular unit. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4UnitMonitorEntry |
|
|
st4UnitEventConfigEntry |
1.3.6.1.4.1.1718.4.1.2.4.1 |
Event configuration objects for a particular unit. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4UnitEventConfigEntry |
|
|
st4LineConfigEntry |
1.3.6.1.4.1.1718.4.1.4.2.1 |
Configuration objects for a particular line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4LineConfigEntry |
|
|
st4LineMonitorEntry |
1.3.6.1.4.1.1718.4.1.4.3.1 |
Objects to monitor for a particular line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4LineMonitorEntry |
|
|
st4LineEventConfigEntry |
1.3.6.1.4.1.1718.4.1.4.4.1 |
Event configuration objects for a particular line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4LineEventConfigEntry |
|
|
st4PhaseConfigEntry |
1.3.6.1.4.1.1718.4.1.5.2.1 |
Configuration objects for a particular phase. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4PhaseConfigEntry |
|
|
st4PhaseMonitorEntry |
1.3.6.1.4.1.1718.4.1.5.3.1 |
Objects to monitor for a particular phase. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4PhaseMonitorEntry |
|
|
st4PhaseEventConfigEntry |
1.3.6.1.4.1.1718.4.1.5.4.1 |
Event configuration objects for a particular phase. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4PhaseEventConfigEntry |
|
|
st4OcpConfigEntry |
1.3.6.1.4.1.1718.4.1.6.2.1 |
Configuration objects for a particular over-current protector. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OcpConfigEntry |
|
|
st4OcpMonitorEntry |
1.3.6.1.4.1.1718.4.1.6.3.1 |
Objects to monitor for a particular over-current protector. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OcpMonitorEntry |
|
|
st4OcpEventConfigEntry |
1.3.6.1.4.1.1718.4.1.6.4.1 |
Event configuration objects for a particular over-current
protector. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OcpEventConfigEntry |
|
|
st4BranchConfigEntry |
1.3.6.1.4.1.1718.4.1.7.2.1 |
Configuration objects for a particular branch. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4BranchConfigEntry |
|
|
st4BranchMonitorEntry |
1.3.6.1.4.1.1718.4.1.7.3.1 |
Objects to monitor for a particular branch. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4BranchMonitorEntry |
|
|
st4BranchEventConfigEntry |
1.3.6.1.4.1.1718.4.1.7.4.1 |
Event configuration objects for a particular branch. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4BranchEventConfigEntry |
|
|
st4OutletConfigEntry |
1.3.6.1.4.1.1718.4.1.8.2.1 |
Configuration objects for a particular outlet. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OutletConfigEntry |
|
|
st4OutletPostOnDelay |
1.3.6.1.4.1.1718.4.1.8.2.1.21 |
The post-on delay of the outlet in seconds. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
0..900 |
|
st4OutletMonitorEntry |
1.3.6.1.4.1.1718.4.1.8.3.1 |
Objects to monitor for a particular outlet. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OutletMonitorEntry |
|
|
st4OutletEventConfigEntry |
1.3.6.1.4.1.1718.4.1.8.4.1 |
Event configuration objects for a particular outlet. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OutletEventConfigEntry |
|
|
st4OutletControlEntry |
1.3.6.1.4.1.1718.4.1.8.5.1 |
Objects for control of a particular outlet. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4OutletControlEntry |
|
|
st4OutletControlState |
1.3.6.1.4.1.1718.4.1.8.5.1.1 |
The control state of the outlet. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
notSet(0), fixedOn(1), idleOff(2), idleOn(3), wakeOff(4), wakeOn(5), ocpOff(6), ocpOn(7), pendOn(8), pendOff(9), off(10), on(11), reboot(12), shutdown(13), lockedOff(14), lockedOn(15), eventOff(16), eventOn(17), eventReboot(18), eventShutdown(19) |
|
st4TempSensorConfigEntry |
1.3.6.1.4.1.1718.4.1.9.2.1 |
Configuration objects for a particular temperature sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4TempSensorConfigEntry |
|
|
st4TempSensorMonitorEntry |
1.3.6.1.4.1.1718.4.1.9.3.1 |
Objects to monitor for a particular temperature sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4TempSensorMonitorEntry |
|
|
st4TempSensorEventConfigEntry |
1.3.6.1.4.1.1718.4.1.9.4.1 |
Event configuration objects for a particular temperature sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4TempSensorEventConfigEntry |
|
|
st4HumidSensorConfigEntry |
1.3.6.1.4.1.1718.4.1.10.2.1 |
Configuration objects for a particular humidity sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4HumidSensorConfigEntry |
|
|
st4HumidSensorMonitorEntry |
1.3.6.1.4.1.1718.4.1.10.3.1 |
Objects to monitor for a particular humidity sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4HumidSensorMonitorEntry |
|
|
st4HumidSensorEventConfigEntry |
1.3.6.1.4.1.1718.4.1.10.4.1 |
Event configuration objects for a particular humidity sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4HumidSensorEventConfigEntry |
|
|
st4WaterSensorConfigEntry |
1.3.6.1.4.1.1718.4.1.11.2.1 |
Configuration objects for a particular water sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4WaterSensorConfigEntry |
|
|
st4WaterSensorMonitorEntry |
1.3.6.1.4.1.1718.4.1.11.3.1 |
Objects to monitor for a particular water sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4WaterSensorMonitorEntry |
|
|
st4WaterSensorEventConfigEntry |
1.3.6.1.4.1.1718.4.1.11.4.1 |
Event configuration objects for a particular water sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4WaterSensorEventConfigEntry |
|
|
st4CcSensorConfigEntry |
1.3.6.1.4.1.1718.4.1.12.2.1 |
Configuration objects for a particular contact closure sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4CcSensorConfigEntry |
|
|
st4CcSensorMonitorEntry |
1.3.6.1.4.1.1718.4.1.12.3.1 |
Objects to monitor for a particular contact closure sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4CcSensorMonitorEntry |
|
|
st4CcSensorEventConfigEntry |
1.3.6.1.4.1.1718.4.1.12.4.1 |
Event configuration objects for a particular contact closure
sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4CcSensorEventConfigEntry |
|
|
st4AdcSensorConfigEntry |
1.3.6.1.4.1.1718.4.1.13.2.1 |
Configuration objects for a particular analog-to-digital
converter sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4AdcSensorConfigEntry |
|
|
st4AdcSensorMonitorEntry |
1.3.6.1.4.1.1718.4.1.13.3.1 |
Objects to monitor for a particular analog-to-digital converter
sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4AdcSensorMonitorEntry |
|
|
st4AdcSensorEventConfigEntry |
1.3.6.1.4.1.1718.4.1.13.4.1 |
Event configuration objects for a particular
analog-to-digital converter sensor. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
St4AdcSensorEventConfigEntry |
|
|
st4EventStatusText |
1.3.6.1.4.1.1718.4.1.99.1 |
The text representation of the enumerated integer value of
the most-relevant status or state object included in a trap.
The value of this object is set only when sent with a trap.
A read of this object will return a NULL string. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..20) |
|