Sentry4-MIB

File: Sentry4-MIB.mib (155468 bytes)

Imported modules

SNMPv2-SMI SNMPv2-CONF SNMPv2-TC

Imported symbols

MODULE-IDENTITY enterprises Integer32
OBJECT-TYPE NOTIFICATION-TYPE OBJECT-GROUP
NOTIFICATION-GROUP MODULE-COMPLIANCE TEXTUAL-CONVENTION
DisplayString

Defined Types

DeviceStatus  
Status returned by devices.
TEXTUAL-CONVENTION    
  INTEGER normal(0), disabled(1), purged(2), reading(5), settle(6), notFound(7), lost(8), readError(9), noComm(10), pwrError(11), breakerTripped(12), fuseBlown(13), lowAlarm(14), lowWarning(15), highWarning(16), highAlarm(17), alarm(18), underLimit(19), overLimit(20), nvmFail(21), profileError(22), conflict(23)  

DeviceState  
On or off state of devices.
TEXTUAL-CONVENTION    
  INTEGER unknown(0), on(1), off(2)  

EventNotificationMethods  
Bits to enable event notification methods.
TEXTUAL-CONVENTION    
  BITS snmpTrap(0), email(1)  

St4UnitConfigEntry  
SEQUENCE    
  st4UnitIndex Integer32
  st4UnitID DisplayString
  st4UnitName DisplayString
  st4UnitProductSN DisplayString
  st4UnitModel DisplayString
  st4UnitAssetTag DisplayString
  st4UnitType INTEGER
  st4UnitCapabilities BITS
  st4UnitProductMfrDate DisplayString
  st4UnitDisplayOrientation INTEGER
  st4UnitOutletSequenceOrder INTEGER
  st4UnitInputCordCount Integer32
  st4UnitTempSensorCount Integer32
  st4UnitHumidSensorCount Integer32
  st4UnitWaterSensorCount Integer32
  st4UnitCcSensorCount Integer32
  st4UnitAdcSensorCount Integer32

St4UnitMonitorEntry  
SEQUENCE    
  st4UnitStatus DeviceStatus

St4UnitEventConfigEntry  
SEQUENCE    
  st4UnitNotifications EventNotificationMethods

St4InputCordConfigEntry  
SEQUENCE    
  st4InputCordIndex Integer32
  st4InputCordID DisplayString
  st4InputCordName DisplayString
  st4InputCordInletType DisplayString
  st4InputCordNominalVoltage Integer32
  st4InputCordNominalVoltageMin Integer32
  st4InputCordNominalVoltageMax Integer32
  st4InputCordCurrentCapacity Integer32
  st4InputCordCurrentCapacityMax Integer32
  st4InputCordPowerCapacity Integer32
  st4InputCordNominalPowerFactor Integer32
  st4InputCordLineCount Integer32
  st4InputCordPhaseCount Integer32
  st4InputCordOcpCount Integer32
  st4InputCordBranchCount Integer32
  st4InputCordOutletCount Integer32

St4InputCordMonitorEntry  
SEQUENCE    
  st4InputCordState DeviceState
  st4InputCordStatus DeviceStatus
  st4InputCordActivePower Integer32
  st4InputCordActivePowerStatus DeviceStatus
  st4InputCordApparentPower Integer32
  st4InputCordApparentPowerStatus DeviceStatus
  st4InputCordPowerUtilized Integer32
  st4InputCordPowerFactor Integer32
  st4InputCordPowerFactorStatus DeviceStatus
  st4InputCordEnergy Integer32
  st4InputCordFrequency Integer32
  st4InputCordOutOfBalance Integer32
  st4InputCordOutOfBalanceStatus DeviceStatus

St4InputCordEventConfigEntry  
SEQUENCE    
  st4InputCordNotifications EventNotificationMethods
  st4InputCordActivePowerLowAlarm Integer32
  st4InputCordActivePowerLowWarning Integer32
  st4InputCordActivePowerHighWarning Integer32
  st4InputCordActivePowerHighAlarm Integer32
  st4InputCordApparentPowerLowAlarm Integer32
  st4InputCordApparentPowerLowWarning Integer32
  st4InputCordApparentPowerHighWarning Integer32
  st4InputCordApparentPowerHighAlarm Integer32
  st4InputCordPowerFactorLowAlarm Integer32
  st4InputCordPowerFactorLowWarning Integer32
  st4InputCordOutOfBalanceHighWarning Integer32
  st4InputCordOutOfBalanceHighAlarm Integer32

St4LineConfigEntry  
SEQUENCE    
  st4LineIndex Integer32
  st4LineID DisplayString
  st4LineLabel DisplayString
  st4LineCurrentCapacity Integer32

St4LineMonitorEntry  
SEQUENCE    
  st4LineState DeviceState
  st4LineStatus DeviceStatus
  st4LineCurrent Integer32
  st4LineCurrentStatus DeviceStatus
  st4LineCurrentUtilized Integer32

St4LineEventConfigEntry  
SEQUENCE    
  st4LineNotifications EventNotificationMethods
  st4LineCurrentLowAlarm Integer32
  st4LineCurrentLowWarning Integer32
  st4LineCurrentHighWarning Integer32
  st4LineCurrentHighAlarm Integer32

St4PhaseConfigEntry  
SEQUENCE    
  st4PhaseIndex Integer32
  st4PhaseID DisplayString
  st4PhaseLabel DisplayString
  st4PhaseNominalVoltage Integer32
  st4PhaseBranchCount Integer32
  st4PhaseOutletCount Integer32

St4PhaseMonitorEntry  
SEQUENCE    
  st4PhaseState DeviceState
  st4PhaseStatus DeviceStatus
  st4PhaseVoltage Integer32
  st4PhaseVoltageStatus DeviceStatus
  st4PhaseVoltageDeviation Integer32
  st4PhaseCurrent Integer32
  st4PhaseCurrentCrestFactor Integer32
  st4PhaseActivePower Integer32
  st4PhaseApparentPower Integer32
  st4PhasePowerFactor Integer32
  st4PhasePowerFactorStatus DeviceStatus
  st4PhaseReactance Integer32
  st4PhaseEnergy Integer32

St4PhaseEventConfigEntry  
SEQUENCE    
  st4PhaseNotifications EventNotificationMethods
  st4PhaseVoltageLowAlarm Integer32
  st4PhaseVoltageLowWarning Integer32
  st4PhaseVoltageHighWarning Integer32
  st4PhaseVoltageHighAlarm Integer32
  st4PhasePowerFactorLowAlarm Integer32
  st4PhasePowerFactorLowWarning Integer32

St4OcpConfigEntry  
SEQUENCE    
  st4OcpIndex Integer32
  st4OcpID DisplayString
  st4OcpLabel DisplayString
  st4OcpType INTEGER
  st4OcpCurrentCapacity Integer32
  st4OcpCurrentCapacityMax Integer32
  st4OcpBranchCount Integer32
  st4OcpOutletCount Integer32

St4OcpMonitorEntry  
SEQUENCE    
  st4OcpStatus DeviceStatus

St4OcpEventConfigEntry  
SEQUENCE    
  st4OcpNotifications EventNotificationMethods

St4BranchConfigEntry  
SEQUENCE    
  st4BranchIndex Integer32
  st4BranchID DisplayString
  st4BranchLabel DisplayString
  st4BranchCurrentCapacity Integer32
  st4BranchPhaseID DisplayString
  st4BranchOcpID DisplayString
  st4BranchOutletCount Integer32

St4BranchMonitorEntry  
SEQUENCE    
  st4BranchState DeviceState
  st4BranchStatus DeviceStatus
  st4BranchCurrent Integer32
  st4BranchCurrentStatus DeviceStatus
  st4BranchCurrentUtilized Integer32

St4BranchEventConfigEntry  
SEQUENCE    
  st4BranchNotifications EventNotificationMethods
  st4BranchCurrentLowAlarm Integer32
  st4BranchCurrentLowWarning Integer32
  st4BranchCurrentHighWarning Integer32
  st4BranchCurrentHighAlarm Integer32

St4OutletConfigEntry  
SEQUENCE    
  st4OutletIndex Integer32
  st4OutletID DisplayString
  st4OutletName DisplayString
  st4OutletCapabilities BITS
  st4OutletSocketType DisplayString
  st4OutletCurrentCapacity Integer32
  st4OutletPowerCapacity Integer32
  st4OutletWakeupState INTEGER
  st4OutletPostOnDelay Integer32
  st4OutletPhaseID DisplayString
  st4OutletOcpID DisplayString
  st4OutletBranchID DisplayString

St4OutletMonitorEntry  
SEQUENCE    
  st4OutletState DeviceState
  st4OutletStatus DeviceStatus
  st4OutletCurrent Integer32
  st4OutletCurrentStatus DeviceStatus
  st4OutletCurrentUtilized Integer32
  st4OutletVoltage Integer32
  st4OutletActivePower Integer32
  st4OutletActivePowerStatus DeviceStatus
  st4OutletApparentPower Integer32
  st4OutletPowerFactor Integer32
  st4OutletPowerFactorStatus DeviceStatus
  st4OutletCurrentCrestFactor Integer32
  st4OutletReactance INTEGER
  st4OutletEnergy Integer32

St4OutletEventConfigEntry  
SEQUENCE    
  st4OutletNotifications EventNotificationMethods
  st4OutletCurrentLowAlarm Integer32
  st4OutletCurrentLowWarning Integer32
  st4OutletCurrentHighWarning Integer32
  st4OutletCurrentHighAlarm Integer32
  st4OutletActivePowerLowAlarm Integer32
  st4OutletActivePowerLowWarning Integer32
  st4OutletActivePowerHighWarning Integer32
  st4OutletActivePowerHighAlarm Integer32
  st4OutletPowerFactorLowAlarm Integer32
  st4OutletPowerFactorLowWarning Integer32

St4OutletControlEntry  
SEQUENCE    
  st4OutletControlState INTEGER
  st4OutletControlAction INTEGER

St4TempSensorConfigEntry  
SEQUENCE    
  st4TempSensorIndex Integer32
  st4TempSensorID DisplayString
  st4TempSensorName DisplayString
  st4TempSensorValueMin Integer32
  st4TempSensorValueMax Integer32

St4TempSensorMonitorEntry  
SEQUENCE    
  st4TempSensorValue Integer32
  st4TempSensorStatus DeviceStatus

St4TempSensorEventConfigEntry  
SEQUENCE    
  st4TempSensorNotifications EventNotificationMethods
  st4TempSensorLowAlarm Integer32
  st4TempSensorLowWarning Integer32
  st4TempSensorHighWarning Integer32
  st4TempSensorHighAlarm Integer32

St4HumidSensorConfigEntry  
SEQUENCE    
  st4HumidSensorIndex Integer32
  st4HumidSensorID DisplayString
  st4HumidSensorName DisplayString

St4HumidSensorMonitorEntry  
SEQUENCE    
  st4HumidSensorValue Integer32
  st4HumidSensorStatus DeviceStatus

St4HumidSensorEventConfigEntry  
SEQUENCE    
  st4HumidSensorNotifications EventNotificationMethods
  st4HumidSensorLowAlarm Integer32
  st4HumidSensorLowWarning Integer32
  st4HumidSensorHighWarning Integer32
  st4HumidSensorHighAlarm Integer32

St4WaterSensorConfigEntry  
SEQUENCE    
  st4WaterSensorIndex Integer32
  st4WaterSensorID DisplayString
  st4WaterSensorName DisplayString

St4WaterSensorMonitorEntry  
SEQUENCE    
  st4WaterSensorStatus DeviceStatus

St4WaterSensorEventConfigEntry  
SEQUENCE    
  st4WaterSensorNotifications EventNotificationMethods

St4CcSensorConfigEntry  
SEQUENCE    
  st4CcSensorIndex Integer32
  st4CcSensorID DisplayString
  st4CcSensorName DisplayString

St4CcSensorMonitorEntry  
SEQUENCE    
  st4CcSensorStatus DeviceStatus

St4CcSensorEventConfigEntry  
SEQUENCE    
  st4CcSensorNotifications EventNotificationMethods

St4AdcSensorConfigEntry  
SEQUENCE    
  st4AdcSensorIndex Integer32
  st4AdcSensorID DisplayString
  st4AdcSensorName DisplayString

St4AdcSensorMonitorEntry  
SEQUENCE    
  st4AdcSensorValue Integer32
  st4AdcSensorStatus DeviceStatus

St4AdcSensorEventConfigEntry  
SEQUENCE    
  st4AdcSensorNotifications EventNotificationMethods
  st4AdcSensorLowAlarm Integer32
  st4AdcSensorLowWarning Integer32
  st4AdcSensorHighWarning Integer32
  st4AdcSensorHighAlarm Integer32

Defined Values

sentry4 1.3.6.1.4.1.1718.4
This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Cabinet Distribution Unit (CDU) and Power Distribution Unit (PDU) products.
MODULE-IDENTITY    

serverTech 1.3.6.1.4.1.1718
OBJECT IDENTIFIER    

st4Objects 1.3.6.1.4.1.1718.4.1
OBJECT IDENTIFIER    

st4System 1.3.6.1.4.1.1718.4.1.1
OBJECT IDENTIFIER    

st4SystemConfig 1.3.6.1.4.1.1718.4.1.1.1
OBJECT IDENTIFIER    

st4SystemProductName 1.3.6.1.4.1.1718.4.1.1.1.1
The product name.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

st4SystemLocation 1.3.6.1.4.1.1718.4.1.1.1.2
The location of the system.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..63)  

st4SystemFirmwareVersion 1.3.6.1.4.1.1718.4.1.1.1.3
The firmware version.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

st4SystemFirmwareBuildInfo 1.3.6.1.4.1.1718.4.1.1.1.4
The firmware build information.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

st4SystemNICSerialNumber 1.3.6.1.4.1.1718.4.1.1.1.5
The serial number of the network interface card.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

st4SystemNICHardwareInfo 1.3.6.1.4.1.1718.4.1.1.1.6
Hardware information about the network interface card.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..63)  

st4SystemProductSeries 1.3.6.1.4.1.1718.4.1.1.1.7
The product series.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER pro1(0), pro2(1)  

st4SystemFeatures 1.3.6.1.4.1.1718.4.1.1.1.10
The key-activated features enabled in the system.
Status: current Access: read-only
OBJECT-TYPE    
  BITS smartLoadShedding(0), reserved(1), outletControlInhibit(2)  

st4SystemFeatureKey 1.3.6.1.4.1.1718.4.1.1.1.11
A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..19)  

st4SystemConfigModifiedCount 1.3.6.1.4.1.1718.4.1.1.1.20
The total number of times the system configuration has changed.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..2147483647  

st4SystemUnitCount 1.3.6.1.4.1.1718.4.1.1.1.21
The number of units in the system.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..8  

st4Units 1.3.6.1.4.1.1718.4.1.2
OBJECT IDENTIFIER    

st4UnitCommonConfig 1.3.6.1.4.1.1718.4.1.2.1
OBJECT IDENTIFIER    

st4UnitConfigTable 1.3.6.1.4.1.1718.4.1.2.2
Unit configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4UnitConfigEntry

st4UnitConfigEntry 1.3.6.1.4.1.1718.4.1.2.2.1
Configuration objects for a particular unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4UnitConfigEntry  

st4UnitIndex 1.3.6.1.4.1.1718.4.1.2.2.1.1
Unit index. A=1, B=2, C=3, D=4, E=5, F=6.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..6  

st4UnitID 1.3.6.1.4.1.1718.4.1.2.2.1.2
The internal ID of the unit. Format=A.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1)  

st4UnitName 1.3.6.1.4.1.1718.4.1.2.2.1.3
The name of the unit.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4UnitProductSN 1.3.6.1.4.1.1718.4.1.2.2.1.4
The product serial number of the unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4UnitModel 1.3.6.1.4.1.1718.4.1.2.2.1.5
The model of the unit.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4UnitAssetTag 1.3.6.1.4.1.1718.4.1.2.2.1.6
The asset tag of the unit.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4UnitType 1.3.6.1.4.1.1718.4.1.2.2.1.7
The type of the unit.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER masterPdu(0), linkPdu(1), controller(2), emcu(3)  

st4UnitCapabilities 1.3.6.1.4.1.1718.4.1.2.2.1.8
The capabilities of the unit.
Status: current Access: read-only
OBJECT-TYPE    
  BITS dc(0), phase3(1), wye(2), delta(3)  

st4UnitProductMfrDate 1.3.6.1.4.1.1718.4.1.2.2.1.9
The product manufacture date in YYYY-MM-DD (ISO 8601 format).
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..10)  

st4UnitDisplayOrientation 1.3.6.1.4.1.1718.4.1.2.2.1.20
The orientation of all displays in the unit.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(0), inverted(1), auto(2)  

st4UnitOutletSequenceOrder 1.3.6.1.4.1.1718.4.1.2.2.1.21
The sequencing order of all outlets in the unit.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER normal(0), reversed(1)  

st4UnitInputCordCount 1.3.6.1.4.1.1718.4.1.2.2.1.30
The number of power input cords into the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

st4UnitTempSensorCount 1.3.6.1.4.1.1718.4.1.2.2.1.31
The number of external temperature sensors supported by the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..2  

st4UnitHumidSensorCount 1.3.6.1.4.1.1718.4.1.2.2.1.32
The number of external humidity sensors supported by the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..2  

st4UnitWaterSensorCount 1.3.6.1.4.1.1718.4.1.2.2.1.33
The number of external water sensors supported by the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

st4UnitCcSensorCount 1.3.6.1.4.1.1718.4.1.2.2.1.34
The number of external contact closure sensors supported by the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

st4UnitAdcSensorCount 1.3.6.1.4.1.1718.4.1.2.2.1.35
The number of analog-to-digital converter sensors supported by the unit.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..1  

st4UnitMonitorTable 1.3.6.1.4.1.1718.4.1.2.3
Unit monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4UnitMonitorEntry

st4UnitMonitorEntry 1.3.6.1.4.1.1718.4.1.2.3.1
Objects to monitor for a particular unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4UnitMonitorEntry  

st4UnitStatus 1.3.6.1.4.1.1718.4.1.2.3.1.1
The status of the unit.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4UnitEventConfigTable 1.3.6.1.4.1.1718.4.1.2.4
Unit event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4UnitEventConfigEntry

st4UnitEventConfigEntry 1.3.6.1.4.1.1718.4.1.2.4.1
Event configuration objects for a particular unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4UnitEventConfigEntry  

st4UnitNotifications 1.3.6.1.4.1.1718.4.1.2.4.1.1
The notification methods enabled for unit events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4InputCords 1.3.6.1.4.1.1718.4.1.3
OBJECT IDENTIFIER    

st4InputCordCommonConfig 1.3.6.1.4.1.1718.4.1.3.1
OBJECT IDENTIFIER    

st4InputCordActivePowerHysteresis 1.3.6.1.4.1.1718.4.1.3.1.1
The active power hysteresis of the input cord in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1000  

st4InputCordApparentPowerHysteresis 1.3.6.1.4.1.1718.4.1.3.1.2
The apparent power hysteresis of the input cord in Volt-Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1000  

st4InputCordPowerFactorHysteresis 1.3.6.1.4.1.1718.4.1.3.1.3
The power factor hysteresis of the input cord in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..20  

st4InputCordOutOfBalanceHysteresis 1.3.6.1.4.1.1718.4.1.3.1.4
The 3 phase out-of-balance hysteresis of the input cord in percent.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10  

st4InputCordConfigTable 1.3.6.1.4.1.1718.4.1.3.2
Input cord configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4InputCordConfigEntry

st4InputCordConfigEntry 1.3.6.1.4.1.1718.4.1.3.2.1
Configuration objects for a particular input cord.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4InputCordConfigEntry  

st4InputCordIndex 1.3.6.1.4.1.1718.4.1.3.2.1.1
Input cord index. A=1, B=2, C=3, D=4.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

st4InputCordID 1.3.6.1.4.1.1718.4.1.3.2.1.2
The internal ID of the input cord. Format=AA.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4InputCordName 1.3.6.1.4.1.1718.4.1.3.2.1.3
The name of the input cord.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4InputCordInletType 1.3.6.1.4.1.1718.4.1.3.2.1.6
The type of plug on the input cord, or socket for the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4InputCordNominalVoltage 1.3.6.1.4.1.1718.4.1.3.2.1.7
The user-configured nominal voltage of the input cord in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4InputCordNominalVoltageMin 1.3.6.1.4.1.1718.4.1.3.2.1.8
The factory-set minimum allowed for the user-configured nominal voltage of the input cord in Volts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..600  

st4InputCordNominalVoltageMax 1.3.6.1.4.1.1718.4.1.3.2.1.9
The factory-set maximum allowed for the user-configured nominal voltage of the input cord in Volts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..600  

st4InputCordCurrentCapacity 1.3.6.1.4.1.1718.4.1.3.2.1.10
The user-configured current capacity of the input cord in Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..600  

st4InputCordCurrentCapacityMax 1.3.6.1.4.1.1718.4.1.3.2.1.11
The factory-set maximum allowed for the user-configured current capacity of the input cord in Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..600  

st4InputCordPowerCapacity 1.3.6.1.4.1.1718.4.1.3.2.1.12
The power capacity of the input cord in Volt-Amps. For DC products, this is identical to power capacity in Watts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordNominalPowerFactor 1.3.6.1.4.1.1718.4.1.3.2.1.13
The user-configured estimated nominal power factor of the input cord in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4InputCordLineCount 1.3.6.1.4.1.1718.4.1.3.2.1.20
The number of current-carrying lines in the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..4  

st4InputCordPhaseCount 1.3.6.1.4.1.1718.4.1.3.2.1.21
The number of active phases from the lines in the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..6  

st4InputCordOcpCount 1.3.6.1.4.1.1718.4.1.3.2.1.22
The number of over-current protectors downstream from the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..12  

st4InputCordBranchCount 1.3.6.1.4.1.1718.4.1.3.2.1.23
The number of branches downstream from the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..12  

st4InputCordOutletCount 1.3.6.1.4.1.1718.4.1.3.2.1.24
The number of outlets powered from the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..128  

st4InputCordMonitorTable 1.3.6.1.4.1.1718.4.1.3.3
Input cord monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4InputCordMonitorEntry

st4InputCordMonitorEntry 1.3.6.1.4.1.1718.4.1.3.3.1
Objects to monitor for a particular input cord.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4InputCordMonitorEntry  

st4InputCordState 1.3.6.1.4.1.1718.4.1.3.3.1.1
The on/off state of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceState  

st4InputCordStatus 1.3.6.1.4.1.1718.4.1.3.3.1.2
The status of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4InputCordActivePower 1.3.6.1.4.1.1718.4.1.3.3.1.3
The measured active power of the input cord in Watts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..50000  

st4InputCordActivePowerStatus 1.3.6.1.4.1.1718.4.1.3.3.1.4
The status of the measured active power of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4InputCordApparentPower 1.3.6.1.4.1.1718.4.1.3.3.1.5
The measured apparent power of the input cord in Volt-Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..50000  

st4InputCordApparentPowerStatus 1.3.6.1.4.1.1718.4.1.3.3.1.6
The status of the measured apparent power of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4InputCordPowerUtilized 1.3.6.1.4.1.1718.4.1.3.3.1.7
The amount of the input cord power capacity used in tenth percent. For AC products, this is the ratio of the apparent power to the power capacity. For DC products, this is the ratio of the active power to the power capacity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..1200  

st4InputCordPowerFactor 1.3.6.1.4.1.1718.4.1.3.3.1.8
The measured power factor of the input cord in hundredths.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..100  

st4InputCordPowerFactorStatus 1.3.6.1.4.1.1718.4.1.3.3.1.9
The status of the measured power factor of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4InputCordEnergy 1.3.6.1.4.1.1718.4.1.3.3.1.10
The total energy consumption of loads through the input cord in tenth Kilowatt-Hours.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..2147483647  

st4InputCordFrequency 1.3.6.1.4.1.1718.4.1.3.3.1.11
The frequency of the input cord voltage in tenth Hertz.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..1000  

st4InputCordOutOfBalance 1.3.6.1.4.1.1718.4.1.3.3.1.12
The current imbalance on the lines of the input cord in tenth percent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..2000  

st4InputCordOutOfBalanceStatus 1.3.6.1.4.1.1718.4.1.3.3.1.13
The status of the current imbalance on the lines of the input cord.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4InputCordEventConfigTable 1.3.6.1.4.1.1718.4.1.3.4
Input cord event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4InputCordEventConfigEntry

st4InputCordEventConfigEntry 1.3.6.1.4.1.1718.4.1.3.4.1
Event configuration objects for a particular input cord.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4InputCordEventConfigEntry  

st4InputCordNotifications 1.3.6.1.4.1.1718.4.1.3.4.1.1
The notification methods enabled for input cord events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4InputCordActivePowerLowAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.2
The active power low alarm threshold of the input cord in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordActivePowerLowWarning 1.3.6.1.4.1.1718.4.1.3.4.1.3
The active power low warning threshold of the input cord in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordActivePowerHighWarning 1.3.6.1.4.1.1718.4.1.3.4.1.4
The active power high warning threshold of the input cord in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordActivePowerHighAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.5
The active power high alarm threshold of the input cord in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordApparentPowerLowAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.6
The apparent power low alarm threshold of the input cord in Volt-Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordApparentPowerLowWarning 1.3.6.1.4.1.1718.4.1.3.4.1.7
The apparent power low warning threshold of the input cord in Volt-Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordApparentPowerHighWarning 1.3.6.1.4.1.1718.4.1.3.4.1.8
The apparent power high warning threshold of the input cord in Volt-Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordApparentPowerHighAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.9
The apparent power high alarm threshold of the input cord in Volt-Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..50000  

st4InputCordPowerFactorLowAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.10
The power factor low alarm threshold of the input cord in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4InputCordPowerFactorLowWarning 1.3.6.1.4.1.1718.4.1.3.4.1.11
The power factor low warning threshold of the input cord in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4InputCordOutOfBalanceHighWarning 1.3.6.1.4.1.1718.4.1.3.4.1.12
The 3 phase out-of-balance high warning threshold of the input cord in percent.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4InputCordOutOfBalanceHighAlarm 1.3.6.1.4.1.1718.4.1.3.4.1.13
The 3 phase out-of-balance high alarm threshold of the input cord in percent.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4Lines 1.3.6.1.4.1.1718.4.1.4
OBJECT IDENTIFIER    

st4LineCommonConfig 1.3.6.1.4.1.1718.4.1.4.1
OBJECT IDENTIFIER    

st4LineCurrentHysteresis 1.3.6.1.4.1.1718.4.1.4.1.1
The current hysteresis of the line in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4LineConfigTable 1.3.6.1.4.1.1718.4.1.4.2
Line configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4LineConfigEntry

st4LineConfigEntry 1.3.6.1.4.1.1718.4.1.4.2.1
Configuration objects for a particular line.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4LineConfigEntry  

st4LineIndex 1.3.6.1.4.1.1718.4.1.4.2.1.1
Line index. L1=1, L2=2, L3=3, N=4.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..4  

st4LineID 1.3.6.1.4.1.1718.4.1.4.2.1.2
The internal ID of the line. Format=AAN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3)  

st4LineLabel 1.3.6.1.4.1.1718.4.1.4.2.1.4
The system label assigned to the line for identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4LineCurrentCapacity 1.3.6.1.4.1.1718.4.1.4.2.1.6
The current capacity of the line in Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..600  

st4LineMonitorTable 1.3.6.1.4.1.1718.4.1.4.3
Line monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4LineMonitorEntry

st4LineMonitorEntry 1.3.6.1.4.1.1718.4.1.4.3.1
Objects to monitor for a particular line.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4LineMonitorEntry  

st4LineState 1.3.6.1.4.1.1718.4.1.4.3.1.1
The on/off state of the line.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceState  

st4LineStatus 1.3.6.1.4.1.1718.4.1.4.3.1.2
The status of the line.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4LineCurrent 1.3.6.1.4.1.1718.4.1.4.3.1.3
The measured current on the line in hundredth Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..60000  

st4LineCurrentStatus 1.3.6.1.4.1.1718.4.1.4.3.1.4
The status of the measured current on the line.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4LineCurrentUtilized 1.3.6.1.4.1.1718.4.1.4.3.1.5
The amount of the line current capacity used in tenth percent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..1200  

st4LineEventConfigTable 1.3.6.1.4.1.1718.4.1.4.4
Line event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4LineEventConfigEntry

st4LineEventConfigEntry 1.3.6.1.4.1.1718.4.1.4.4.1
Event configuration objects for a particular line.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4LineEventConfigEntry  

st4LineNotifications 1.3.6.1.4.1.1718.4.1.4.4.1.1
The notification methods enabled for line events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4LineCurrentLowAlarm 1.3.6.1.4.1.1718.4.1.4.4.1.2
The current low alarm threshold of the line in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4LineCurrentLowWarning 1.3.6.1.4.1.1718.4.1.4.4.1.3
The current low warning threshold of the line in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4LineCurrentHighWarning 1.3.6.1.4.1.1718.4.1.4.4.1.4
The current high warning threshold of the line in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4LineCurrentHighAlarm 1.3.6.1.4.1.1718.4.1.4.4.1.5
The current high alarm threshold of the line in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4Phases 1.3.6.1.4.1.1718.4.1.5
OBJECT IDENTIFIER    

st4PhaseCommonConfig 1.3.6.1.4.1.1718.4.1.5.1
OBJECT IDENTIFIER    

st4PhaseVoltageHysteresis 1.3.6.1.4.1.1718.4.1.5.1.1
The voltage hysteresis of the phase in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..200  

st4PhasePowerFactorHysteresis 1.3.6.1.4.1.1718.4.1.5.1.2
The power factor hysteresis of the phase in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..20  

st4PhaseConfigTable 1.3.6.1.4.1.1718.4.1.5.2
Phase configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4PhaseConfigEntry

st4PhaseConfigEntry 1.3.6.1.4.1.1718.4.1.5.2.1
Configuration objects for a particular phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4PhaseConfigEntry  

st4PhaseIndex 1.3.6.1.4.1.1718.4.1.5.2.1.1
Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3; Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase: L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2, L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..6  

st4PhaseID 1.3.6.1.4.1.1718.4.1.5.2.1.2
The internal ID of the phase. Format=AAN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3)  

st4PhaseLabel 1.3.6.1.4.1.1718.4.1.5.2.1.4
The system label assigned to the phase for identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4PhaseNominalVoltage 1.3.6.1.4.1.1718.4.1.5.2.1.6
The nominal voltage of the phase in tenth Volts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..6000  

st4PhaseBranchCount 1.3.6.1.4.1.1718.4.1.5.2.1.20
The number of branches downstream from the phase.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..12  

st4PhaseOutletCount 1.3.6.1.4.1.1718.4.1.5.2.1.21
The number of outlets powered from the phase.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..128  

st4PhaseMonitorTable 1.3.6.1.4.1.1718.4.1.5.3
Phase monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4PhaseMonitorEntry

st4PhaseMonitorEntry 1.3.6.1.4.1.1718.4.1.5.3.1
Objects to monitor for a particular phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4PhaseMonitorEntry  

st4PhaseState 1.3.6.1.4.1.1718.4.1.5.3.1.1
The on/off state of the phase.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceState  

st4PhaseStatus 1.3.6.1.4.1.1718.4.1.5.3.1.2
The status of the phase.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4PhaseVoltage 1.3.6.1.4.1.1718.4.1.5.3.1.3
The measured voltage on the phase in tenth Volts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..6000  

st4PhaseVoltageStatus 1.3.6.1.4.1.1718.4.1.5.3.1.4
The status of the measured voltage on the phase.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4PhaseVoltageDeviation 1.3.6.1.4.1.1718.4.1.5.3.1.5
The deviation from the nominal voltage on the phase in tenth percent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1000..1000  

st4PhaseCurrent 1.3.6.1.4.1.1718.4.1.5.3.1.6
The measured current on the phase in hundredth Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..30000  

st4PhaseCurrentCrestFactor 1.3.6.1.4.1.1718.4.1.5.3.1.7
The measured crest factor of the current waveform on the phase in tenths.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..250  

st4PhaseActivePower 1.3.6.1.4.1.1718.4.1.5.3.1.8
The measured active power on the phase in Watts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..25000  

st4PhaseApparentPower 1.3.6.1.4.1.1718.4.1.5.3.1.9
The measured apparent power on the phase in Volt-Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..25000  

st4PhasePowerFactor 1.3.6.1.4.1.1718.4.1.5.3.1.10
The measured power factor on the phase in hundredths.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..100  

st4PhasePowerFactorStatus 1.3.6.1.4.1.1718.4.1.5.3.1.11
The status of the measured power factor on the phase.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4PhaseReactance 1.3.6.1.4.1.1718.4.1.5.3.1.12
The status of the measured reactance of the phase.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(0), capacitive(1), inductive(2), resistive(3)  

st4PhaseEnergy 1.3.6.1.4.1.1718.4.1.5.3.1.13
The total energy consumption of loads through the phase in tenth Kilowatt-Hours.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..2147483647  

st4PhaseEventConfigTable 1.3.6.1.4.1.1718.4.1.5.4
Phase event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4PhaseEventConfigEntry

st4PhaseEventConfigEntry 1.3.6.1.4.1.1718.4.1.5.4.1
Event configuration objects for a particular phase.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4PhaseEventConfigEntry  

st4PhaseNotifications 1.3.6.1.4.1.1718.4.1.5.4.1.1
The notification methods enabled for phase events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4PhaseVoltageLowAlarm 1.3.6.1.4.1.1718.4.1.5.4.1.2
The current low alarm threshold of the phase in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4PhaseVoltageLowWarning 1.3.6.1.4.1.1718.4.1.5.4.1.3
The current low warning threshold of the phase in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4PhaseVoltageHighWarning 1.3.6.1.4.1.1718.4.1.5.4.1.4
The current high warning threshold of the phase in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4PhaseVoltageHighAlarm 1.3.6.1.4.1.1718.4.1.5.4.1.5
The current high alarm threshold of the phase in tenth Volts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..6000  

st4PhasePowerFactorLowAlarm 1.3.6.1.4.1.1718.4.1.5.4.1.6
The low power factor alarm threshold of the phase in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4PhasePowerFactorLowWarning 1.3.6.1.4.1.1718.4.1.5.4.1.7
The low power factor warning threshold of the phase in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4OverCurrentProtectors 1.3.6.1.4.1.1718.4.1.6
OBJECT IDENTIFIER    

st4OcpCommonConfig 1.3.6.1.4.1.1718.4.1.6.1
OBJECT IDENTIFIER    

st4OcpConfigTable 1.3.6.1.4.1.1718.4.1.6.2
Over-current protector configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OcpConfigEntry

st4OcpConfigEntry 1.3.6.1.4.1.1718.4.1.6.2.1
Configuration objects for a particular over-current protector.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OcpConfigEntry  

st4OcpIndex 1.3.6.1.4.1.1718.4.1.6.2.1.1
Over-current protector index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..64  

st4OcpID 1.3.6.1.4.1.1718.4.1.6.2.1.2
The internal ID of the over-current protector. Format=AAN[N].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..4)  

st4OcpLabel 1.3.6.1.4.1.1718.4.1.6.2.1.4
The system label assigned to the over-current protector for identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4OcpType 1.3.6.1.4.1.1718.4.1.6.2.1.6
The type of over-current protector.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER fuse(0), breaker(1)  

st4OcpCurrentCapacity 1.3.6.1.4.1.1718.4.1.6.2.1.7
The user-configured current capacity of the over-current protector in Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..125  

st4OcpCurrentCapacityMax 1.3.6.1.4.1.1718.4.1.6.2.1.8
The factory-set maximum allowed for the user-configured current capacity of the over-current protector in Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..125  

st4OcpBranchCount 1.3.6.1.4.1.1718.4.1.6.2.1.20
The number of branches downstream from the over-current protector.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..12  

st4OcpOutletCount 1.3.6.1.4.1.1718.4.1.6.2.1.21
The number of outlets powered from the over-current protector.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..128  

st4OcpMonitorTable 1.3.6.1.4.1.1718.4.1.6.3
Over-current protector monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OcpMonitorEntry

st4OcpMonitorEntry 1.3.6.1.4.1.1718.4.1.6.3.1
Objects to monitor for a particular over-current protector.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OcpMonitorEntry  

st4OcpStatus 1.3.6.1.4.1.1718.4.1.6.3.1.1
The status of the over-current protector.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4OcpEventConfigTable 1.3.6.1.4.1.1718.4.1.6.4
Over-current protector event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OcpEventConfigEntry

st4OcpEventConfigEntry 1.3.6.1.4.1.1718.4.1.6.4.1
Event configuration objects for a particular over-current protector.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OcpEventConfigEntry  

st4OcpNotifications 1.3.6.1.4.1.1718.4.1.6.4.1.1
The notification methods enabled for over-current protector events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4Branches 1.3.6.1.4.1.1718.4.1.7
OBJECT IDENTIFIER    

st4BranchCommonConfig 1.3.6.1.4.1.1718.4.1.7.1
OBJECT IDENTIFIER    

st4BranchCurrentHysteresis 1.3.6.1.4.1.1718.4.1.7.1.1
The current hysteresis of the branch in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4BranchConfigTable 1.3.6.1.4.1.1718.4.1.7.2
Branch configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4BranchConfigEntry

st4BranchConfigEntry 1.3.6.1.4.1.1718.4.1.7.2.1
Configuration objects for a particular branch.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4BranchConfigEntry  

st4BranchIndex 1.3.6.1.4.1.1718.4.1.7.2.1.1
Branch index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..64  

st4BranchID 1.3.6.1.4.1.1718.4.1.7.2.1.2
The internal ID of the branch. Format=AAN[N].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..4)  

st4BranchLabel 1.3.6.1.4.1.1718.4.1.7.2.1.4
The system label assigned to the branch for identification.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4BranchCurrentCapacity 1.3.6.1.4.1.1718.4.1.7.2.1.6
The current capacity of the branch in Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..125  

st4BranchPhaseID 1.3.6.1.4.1.1718.4.1.7.2.1.20
The internal ID of the phase powering this branch. Format=AAN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3)  

st4BranchOcpID 1.3.6.1.4.1.1718.4.1.7.2.1.21
The internal ID of the over-current protector powering this outlet. Format=AAN[N].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..4)  

st4BranchOutletCount 1.3.6.1.4.1.1718.4.1.7.2.1.30
The number of outlets powered from the branch.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..128  

st4BranchMonitorTable 1.3.6.1.4.1.1718.4.1.7.3
Branch monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4BranchMonitorEntry

st4BranchMonitorEntry 1.3.6.1.4.1.1718.4.1.7.3.1
Objects to monitor for a particular branch.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4BranchMonitorEntry  

st4BranchState 1.3.6.1.4.1.1718.4.1.7.3.1.1
The on/off state of the branch.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceState  

st4BranchStatus 1.3.6.1.4.1.1718.4.1.7.3.1.2
The status of the branch.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4BranchCurrent 1.3.6.1.4.1.1718.4.1.7.3.1.3
The measured current on the branch in hundredth Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..12500  

st4BranchCurrentStatus 1.3.6.1.4.1.1718.4.1.7.3.1.4
The status of the measured current on the branch.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4BranchCurrentUtilized 1.3.6.1.4.1.1718.4.1.7.3.1.5
The amount of the branch current capacity used in tenth percent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..1200  

st4BranchEventConfigTable 1.3.6.1.4.1.1718.4.1.7.4
Branch event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4BranchEventConfigEntry

st4BranchEventConfigEntry 1.3.6.1.4.1.1718.4.1.7.4.1
Event configuration objects for a particular branch.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4BranchEventConfigEntry  

st4BranchNotifications 1.3.6.1.4.1.1718.4.1.7.4.1.1
The notification methods enabled for branch events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4BranchCurrentLowAlarm 1.3.6.1.4.1.1718.4.1.7.4.1.2
The current low alarm threshold of the branch in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4BranchCurrentLowWarning 1.3.6.1.4.1.1718.4.1.7.4.1.3
The current low warning threshold of the branch in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4BranchCurrentHighWarning 1.3.6.1.4.1.1718.4.1.7.4.1.4
The current high warning threshold of the branch in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4BranchCurrentHighAlarm 1.3.6.1.4.1.1718.4.1.7.4.1.5
The current high alarm threshold of the branch in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4Outlets 1.3.6.1.4.1.1718.4.1.8
OBJECT IDENTIFIER    

st4OutletCommonConfig 1.3.6.1.4.1.1718.4.1.8.1
OBJECT IDENTIFIER    

st4OutletCurrentHysteresis 1.3.6.1.4.1.1718.4.1.8.1.1
The current hysteresis of the outlet in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4OutletActivePowerHysteresis 1.3.6.1.4.1.1718.4.1.8.1.2
The power hysteresis of the outlet in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1000  

st4OutletPowerFactorHysteresis 1.3.6.1.4.1.1718.4.1.8.1.3
The power factor hysteresis of the outlet in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..20  

st4OutletSequenceInterval 1.3.6.1.4.1.1718.4.1.8.1.10
The power-on sequencing interval for all outlets in seconds.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..15  

st4OutletRebootDelay 1.3.6.1.4.1.1718.4.1.8.1.11
The reboot delay for all outlets in seconds.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 5..600  

st4OutletStateChangeLogging 1.3.6.1.4.1.1718.4.1.8.1.12
Enables or disables informational Outlet State Change event logging.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER disabled(0), enabled(1)  

st4OutletConfigTable 1.3.6.1.4.1.1718.4.1.8.2
Outlet configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OutletConfigEntry

st4OutletConfigEntry 1.3.6.1.4.1.1718.4.1.8.2.1
Configuration objects for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OutletConfigEntry  

st4OutletIndex 1.3.6.1.4.1.1718.4.1.8.2.1.1
Outlet index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 1..128  

st4OutletID 1.3.6.1.4.1.1718.4.1.8.2.1.2
The internal ID of the outlet. Format=AAN[N[N]].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..5)  

st4OutletName 1.3.6.1.4.1.1718.4.1.8.2.1.3
The name of the outlet.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4OutletCapabilities 1.3.6.1.4.1.1718.4.1.8.2.1.5
The capabilities of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  BITS switched(0), pops(1)  

st4OutletSocketType 1.3.6.1.4.1.1718.4.1.8.2.1.6
The socket type of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4OutletCurrentCapacity 1.3.6.1.4.1.1718.4.1.8.2.1.7
The current capacity of the outlet in Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..125  

st4OutletPowerCapacity 1.3.6.1.4.1.1718.4.1.8.2.1.8
The power capacity of the outlet in Volt-Amps. For DC products, this is identical to power capacity in Watts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 0..10000  

st4OutletWakeupState 1.3.6.1.4.1.1718.4.1.8.2.1.20
The wakeup state of the outlet.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER on(0), off(1), last(2)  

st4OutletPostOnDelay 1.3.6.1.4.1.1718.4.1.8.2.1.21
The post-on delay of the outlet in seconds.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..900  

st4OutletPhaseID 1.3.6.1.4.1.1718.4.1.8.2.1.30
The internal ID of the phase powering this outlet. Format=AAN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3)  

st4OutletOcpID 1.3.6.1.4.1.1718.4.1.8.2.1.31
The internal ID of the over-current protector powering this outlet. Format=AAN[N].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..4)  

st4OutletBranchID 1.3.6.1.4.1.1718.4.1.8.2.1.32
The internal ID of the branch powering this outlet. Format=AAN[N].
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(3..4)  

st4OutletMonitorTable 1.3.6.1.4.1.1718.4.1.8.3
Outlet monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OutletMonitorEntry

st4OutletMonitorEntry 1.3.6.1.4.1.1718.4.1.8.3.1
Objects to monitor for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OutletMonitorEntry  

st4OutletState 1.3.6.1.4.1.1718.4.1.8.3.1.1
The on/off state of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceState  

st4OutletStatus 1.3.6.1.4.1.1718.4.1.8.3.1.2
The status of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4OutletCurrent 1.3.6.1.4.1.1718.4.1.8.3.1.3
The measured current on the outlet in hundredth Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..12500  

st4OutletCurrentStatus 1.3.6.1.4.1.1718.4.1.8.3.1.4
The status of the measured current on the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4OutletCurrentUtilized 1.3.6.1.4.1.1718.4.1.8.3.1.5
The amount of the outlet current capacity used in tenth percent.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..1200  

st4OutletVoltage 1.3.6.1.4.1.1718.4.1.8.3.1.6
The measured voltage of the outlet in tenth Volts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..6000  

st4OutletActivePower 1.3.6.1.4.1.1718.4.1.8.3.1.7
The measured active power of the outlet in Watts.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..10000  

st4OutletActivePowerStatus 1.3.6.1.4.1.1718.4.1.8.3.1.8
The status of the measured active power of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4OutletApparentPower 1.3.6.1.4.1.1718.4.1.8.3.1.9
The measured apparent power of the outlet in Volt-Amps.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..10000  

st4OutletPowerFactor 1.3.6.1.4.1.1718.4.1.8.3.1.10
The measured power factor of the outlet in hundredths.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..100  

st4OutletPowerFactorStatus 1.3.6.1.4.1.1718.4.1.8.3.1.11
The status of the measured power factor of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4OutletCurrentCrestFactor 1.3.6.1.4.1.1718.4.1.8.3.1.12
The measured crest factor of the outlet in tenths.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..250  

st4OutletReactance 1.3.6.1.4.1.1718.4.1.8.3.1.13
The status of the measured reactance of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(0), capacitive(1), inductive(2), resistive(3)  

st4OutletEnergy 1.3.6.1.4.1.1718.4.1.8.3.1.14
The total energy consumption of the device plugged into the outlet in Watt-Hours.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..2147483647  

st4OutletEventConfigTable 1.3.6.1.4.1.1718.4.1.8.4
Outlet event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OutletEventConfigEntry

st4OutletEventConfigEntry 1.3.6.1.4.1.1718.4.1.8.4.1
Event configuration objects for a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OutletEventConfigEntry  

st4OutletNotifications 1.3.6.1.4.1.1718.4.1.8.4.1.1
The notification methods enabled for outlet events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4OutletCurrentLowAlarm 1.3.6.1.4.1.1718.4.1.8.4.1.2
The current low alarm threshold of the outlet in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4OutletCurrentLowWarning 1.3.6.1.4.1.1718.4.1.8.4.1.3
The current low warning threshold of the outlet in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4OutletCurrentHighWarning 1.3.6.1.4.1.1718.4.1.8.4.1.4
The current high warning threshold of the outlet in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4OutletCurrentHighAlarm 1.3.6.1.4.1.1718.4.1.8.4.1.5
The current high alarm threshold of the outlet in tenth Amps.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..1250  

st4OutletActivePowerLowAlarm 1.3.6.1.4.1.1718.4.1.8.4.1.6
The active power low alarm threshold of the outlet in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10000  

st4OutletActivePowerLowWarning 1.3.6.1.4.1.1718.4.1.8.4.1.7
The active power low warning threshold of the outlet in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10000  

st4OutletActivePowerHighWarning 1.3.6.1.4.1.1718.4.1.8.4.1.8
The active power high warning threshold of the outlet in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10000  

st4OutletActivePowerHighAlarm 1.3.6.1.4.1.1718.4.1.8.4.1.9
The active power high alarm threshold of the outlet in Watts.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..10000  

st4OutletPowerFactorLowAlarm 1.3.6.1.4.1.1718.4.1.8.4.1.10
The low power factor alarm threshold of the outlet in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4OutletPowerFactorLowWarning 1.3.6.1.4.1.1718.4.1.8.4.1.11
The low power factor warning threshold of the outlet in hundredths.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4OutletControlTable 1.3.6.1.4.1.1718.4.1.8.5
Outlet control table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4OutletControlEntry

st4OutletControlEntry 1.3.6.1.4.1.1718.4.1.8.5.1
Objects for control of a particular outlet.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4OutletControlEntry  

st4OutletControlState 1.3.6.1.4.1.1718.4.1.8.5.1.1
The control state of the outlet.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER notSet(0), fixedOn(1), idleOff(2), idleOn(3), wakeOff(4), wakeOn(5), ocpOff(6), ocpOn(7), pendOn(8), pendOff(9), off(10), on(11), reboot(12), shutdown(13), lockedOff(14), lockedOn(15), eventOff(16), eventOn(17), eventReboot(18), eventShutdown(19)  

st4OutletControlAction 1.3.6.1.4.1.1718.4.1.8.5.1.2
An action to change the control state of the outlet, or to queue an action.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER none(0), on(1), off(2), reboot(3), queueOn(4), queueOff(5), queueReboot(6)  

st4OutletCommonControl 1.3.6.1.4.1.1718.4.1.8.6
OBJECT IDENTIFIER    

st4OutletQueueControl 1.3.6.1.4.1.1718.4.1.8.6.1
An action to clear or commit queued outlet control actions. A read of this object returns clear(0) if queue is empty, and commit(1) if the queue is not empty.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER clear(0), commit(1)  

st4TemperatureSensors 1.3.6.1.4.1.1718.4.1.9
OBJECT IDENTIFIER    

st4TempSensorCommonConfig 1.3.6.1.4.1.1718.4.1.9.1
OBJECT IDENTIFIER    

st4TempSensorHysteresis 1.3.6.1.4.1.1718.4.1.9.1.1
The temperature hysteresis of the sensor in degrees, using the scale selected by st4TempSensorScale.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..54  

st4TempSensorScale 1.3.6.1.4.1.1718.4.1.9.1.10
The current scale used for all temperature values.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER celsius(0), fahrenheit(1)  

st4TempSensorConfigTable 1.3.6.1.4.1.1718.4.1.9.2
Temperature sensor configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4TempSensorConfigEntry

st4TempSensorConfigEntry 1.3.6.1.4.1.1718.4.1.9.2.1
Configuration objects for a particular temperature sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4TempSensorConfigEntry  

st4TempSensorIndex 1.3.6.1.4.1.1718.4.1.9.2.1.1
Temperature sensor index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..2  

st4TempSensorID 1.3.6.1.4.1.1718.4.1.9.2.1.2
The internal ID of the temperature sensor. Format=AN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4TempSensorName 1.3.6.1.4.1.1718.4.1.9.2.1.3
The name of the temperature sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4TempSensorValueMin 1.3.6.1.4.1.1718.4.1.9.2.1.4
The minimum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -40..253  

st4TempSensorValueMax 1.3.6.1.4.1.1718.4.1.9.2.1.5
The maximum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -40..253  

st4TempSensorMonitorTable 1.3.6.1.4.1.1718.4.1.9.3
Temperature sensor monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4TempSensorMonitorEntry

st4TempSensorMonitorEntry 1.3.6.1.4.1.1718.4.1.9.3.1
Objects to monitor for a particular temperature sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4TempSensorMonitorEntry  

st4TempSensorValue 1.3.6.1.4.1.1718.4.1.9.3.1.1
The measured temperature on the sensor in tenth degrees using the scale selected by st4TempSensorScale. -410 means the temperature reading is invalid.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -410..2540  

st4TempSensorStatus 1.3.6.1.4.1.1718.4.1.9.3.1.2
The status of the temperature sensor.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4TempSensorEventConfigTable 1.3.6.1.4.1.1718.4.1.9.4
Temperature sensor event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4TempSensorEventConfigEntry

st4TempSensorEventConfigEntry 1.3.6.1.4.1.1718.4.1.9.4.1
Event configuration objects for a particular temperature sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4TempSensorEventConfigEntry  

st4TempSensorNotifications 1.3.6.1.4.1.1718.4.1.9.4.1.1
The notification methods enabled for temperature sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4TempSensorLowAlarm 1.3.6.1.4.1.1718.4.1.9.4.1.2
The low alarm threshold of the temperature sensor in degrees.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -40..253  

st4TempSensorLowWarning 1.3.6.1.4.1.1718.4.1.9.4.1.3
The low warning threshold of the temperature sensor in degrees.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -40..253  

st4TempSensorHighWarning 1.3.6.1.4.1.1718.4.1.9.4.1.4
The high warning threshold of the temperature sensor in degrees.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -40..253  

st4TempSensorHighAlarm 1.3.6.1.4.1.1718.4.1.9.4.1.5
The high alarm threshold of the temperature sensor in degrees.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 -40..253  

st4HumiditySensors 1.3.6.1.4.1.1718.4.1.10
OBJECT IDENTIFIER    

st4HumidSensorCommonConfig 1.3.6.1.4.1.1718.4.1.10.1
OBJECT IDENTIFIER    

st4HumidSensorHysteresis 1.3.6.1.4.1.1718.4.1.10.1.1
The humidity hysteresis of the sensor in percent relative humidity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..20  

st4HumidSensorConfigTable 1.3.6.1.4.1.1718.4.1.10.2
Humidity sensor configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4HumidSensorConfigEntry

st4HumidSensorConfigEntry 1.3.6.1.4.1.1718.4.1.10.2.1
Configuration objects for a particular humidity sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4HumidSensorConfigEntry  

st4HumidSensorIndex 1.3.6.1.4.1.1718.4.1.10.2.1.1
Humidity sensor index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..2  

st4HumidSensorID 1.3.6.1.4.1.1718.4.1.10.2.1.2
The internal ID of the humidity sensor. Format=AN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4HumidSensorName 1.3.6.1.4.1.1718.4.1.10.2.1.3
The name of the humidity sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4HumidSensorMonitorTable 1.3.6.1.4.1.1718.4.1.10.3
Humidity sensor monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4HumidSensorMonitorEntry

st4HumidSensorMonitorEntry 1.3.6.1.4.1.1718.4.1.10.3.1
Objects to monitor for a particular humidity sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4HumidSensorMonitorEntry  

st4HumidSensorValue 1.3.6.1.4.1.1718.4.1.10.3.1.1
The measured humidity on the sensor in percentage relative humidity.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..100  

st4HumidSensorStatus 1.3.6.1.4.1.1718.4.1.10.3.1.2
The status of the humidity sensor.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4HumidSensorEventConfigTable 1.3.6.1.4.1.1718.4.1.10.4
Humidity sensor event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4HumidSensorEventConfigEntry

st4HumidSensorEventConfigEntry 1.3.6.1.4.1.1718.4.1.10.4.1
Event configuration objects for a particular humidity sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4HumidSensorEventConfigEntry  

st4HumidSensorNotifications 1.3.6.1.4.1.1718.4.1.10.4.1.1
The notification methods enabled for humidity sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4HumidSensorLowAlarm 1.3.6.1.4.1.1718.4.1.10.4.1.2
The low alarm threshold of the humidity sensor in percentage relative humidity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4HumidSensorLowWarning 1.3.6.1.4.1.1718.4.1.10.4.1.3
The low warning threshold of the humidity sensor in percentage relative humidity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4HumidSensorHighWarning 1.3.6.1.4.1.1718.4.1.10.4.1.4
The high warning threshold of the humidity sensor in percentage relative humidity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4HumidSensorHighAlarm 1.3.6.1.4.1.1718.4.1.10.4.1.5
The high alarm threshold of the humidity sensor in percentage relative humidity.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..100  

st4WaterSensors 1.3.6.1.4.1.1718.4.1.11
OBJECT IDENTIFIER    

st4WaterSensorCommonConfig 1.3.6.1.4.1.1718.4.1.11.1
OBJECT IDENTIFIER    

st4WaterSensorConfigTable 1.3.6.1.4.1.1718.4.1.11.2
Water sensor configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4WaterSensorConfigEntry

st4WaterSensorConfigEntry 1.3.6.1.4.1.1718.4.1.11.2.1
Configuration objects for a particular water sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4WaterSensorConfigEntry  

st4WaterSensorIndex 1.3.6.1.4.1.1718.4.1.11.2.1.1
Water sensor index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..1  

st4WaterSensorID 1.3.6.1.4.1.1718.4.1.11.2.1.2
The internal ID of the water sensor. Format=AN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4WaterSensorName 1.3.6.1.4.1.1718.4.1.11.2.1.3
The name of the water sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4WaterSensorMonitorTable 1.3.6.1.4.1.1718.4.1.11.3
Water sensor monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4WaterSensorMonitorEntry

st4WaterSensorMonitorEntry 1.3.6.1.4.1.1718.4.1.11.3.1
Objects to monitor for a particular water sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4WaterSensorMonitorEntry  

st4WaterSensorStatus 1.3.6.1.4.1.1718.4.1.11.3.1.1
The status of the water sensor.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4WaterSensorEventConfigTable 1.3.6.1.4.1.1718.4.1.11.4
Water sensor event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4WaterSensorEventConfigEntry

st4WaterSensorEventConfigEntry 1.3.6.1.4.1.1718.4.1.11.4.1
Event configuration objects for a particular water sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4WaterSensorEventConfigEntry  

st4WaterSensorNotifications 1.3.6.1.4.1.1718.4.1.11.4.1.1
The notification methods enabled for water sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4ContactClosureSensors 1.3.6.1.4.1.1718.4.1.12
OBJECT IDENTIFIER    

st4CcSensorCommonConfig 1.3.6.1.4.1.1718.4.1.12.1
OBJECT IDENTIFIER    

st4CcSensorConfigTable 1.3.6.1.4.1.1718.4.1.12.2
Contact closure sensor configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4CcSensorConfigEntry

st4CcSensorConfigEntry 1.3.6.1.4.1.1718.4.1.12.2.1
Configuration objects for a particular contact closure sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4CcSensorConfigEntry  

st4CcSensorIndex 1.3.6.1.4.1.1718.4.1.12.2.1.1
Contact closure sensor index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..4  

st4CcSensorID 1.3.6.1.4.1.1718.4.1.12.2.1.2
The internal ID of the contact closure sensor. Format=AN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4CcSensorName 1.3.6.1.4.1.1718.4.1.12.2.1.3
The name of the contact closure sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4CcSensorMonitorTable 1.3.6.1.4.1.1718.4.1.12.3
Contact closure sensor monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4CcSensorMonitorEntry

st4CcSensorMonitorEntry 1.3.6.1.4.1.1718.4.1.12.3.1
Objects to monitor for a particular contact closure sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4CcSensorMonitorEntry  

st4CcSensorStatus 1.3.6.1.4.1.1718.4.1.12.3.1.1
The status of the contact closure.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4CcSensorEventConfigTable 1.3.6.1.4.1.1718.4.1.12.4
Contact closure sensor event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4CcSensorEventConfigEntry

st4CcSensorEventConfigEntry 1.3.6.1.4.1.1718.4.1.12.4.1
Event configuration objects for a particular contact closure sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4CcSensorEventConfigEntry  

st4CcSensorNotifications 1.3.6.1.4.1.1718.4.1.12.4.1.1
The notification methods enabled for contact closure sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4AnalogToDigitalConvSensors 1.3.6.1.4.1.1718.4.1.13
OBJECT IDENTIFIER    

st4AdcSensorCommonConfig 1.3.6.1.4.1.1718.4.1.13.1
OBJECT IDENTIFIER    

st4AdcSensorHysteresis 1.3.6.1.4.1.1718.4.1.13.1.1
The 8-bit count hysteresis of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..20  

st4AdcSensorConfigTable 1.3.6.1.4.1.1718.4.1.13.2
Analog-to-digital converter sensor configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4AdcSensorConfigEntry

st4AdcSensorConfigEntry 1.3.6.1.4.1.1718.4.1.13.2.1
Configuration objects for a particular analog-to-digital converter sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4AdcSensorConfigEntry  

st4AdcSensorIndex 1.3.6.1.4.1.1718.4.1.13.2.1.1
Analog-to-digital converter sensor index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Integer32 0..1  

st4AdcSensorID 1.3.6.1.4.1.1718.4.1.13.2.1.2
The internal ID of the analog-to-digital converter sensor. Format=AN.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(2)  

st4AdcSensorName 1.3.6.1.4.1.1718.4.1.13.2.1.3
The name of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..32)  

st4AdcSensorMonitorTable 1.3.6.1.4.1.1718.4.1.13.3
Analog-to-digital converter sensor monitor table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4AdcSensorMonitorEntry

st4AdcSensorMonitorEntry 1.3.6.1.4.1.1718.4.1.13.3.1
Objects to monitor for a particular analog-to-digital converter sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4AdcSensorMonitorEntry  

st4AdcSensorValue 1.3.6.1.4.1.1718.4.1.13.3.1.1
The 8-bit value from the analog-to-digital converter sensor.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32 -1..255  

st4AdcSensorStatus 1.3.6.1.4.1.1718.4.1.13.3.1.2
The status of the analog-to-digital converter sensor.
Status: current Access: read-only
OBJECT-TYPE    
  DeviceStatus  

st4AdcSensorEventConfigTable 1.3.6.1.4.1.1718.4.1.13.4
Analog-to-digital converter sensor event configuration table.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    St4AdcSensorEventConfigEntry

st4AdcSensorEventConfigEntry 1.3.6.1.4.1.1718.4.1.13.4.1
Event configuration objects for a particular analog-to-digital converter sensor.
Status: current Access: not-accessible
OBJECT-TYPE    
  St4AdcSensorEventConfigEntry  

st4AdcSensorNotifications 1.3.6.1.4.1.1718.4.1.13.4.1.1
The notification methods enabled for analog-to-digital converter sensor events.
Status: current Access: read-write
OBJECT-TYPE    
  EventNotificationMethods  

st4AdcSensorLowAlarm 1.3.6.1.4.1.1718.4.1.13.4.1.2
The 8-bit value for the low alarm threshold of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

st4AdcSensorLowWarning 1.3.6.1.4.1.1718.4.1.13.4.1.3
The 8-bit value for the low warning threshold of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

st4AdcSensorHighWarning 1.3.6.1.4.1.1718.4.1.13.4.1.4
The 8-bit value for the high warning threshold of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

st4AdcSensorHighAlarm 1.3.6.1.4.1.1718.4.1.13.4.1.5
The 8-bit value for the high alarm threshold of the analog-to-digital converter sensor.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32 0..255  

st4EventInformation 1.3.6.1.4.1.1718.4.1.99
OBJECT IDENTIFIER    

st4EventStatusText 1.3.6.1.4.1.1718.4.1.99.1
The text representation of the enumerated integer value of the most-relevant status or state object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return a NULL string.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..20)  

st4EventStatusCondition 1.3.6.1.4.1.1718.4.1.99.2
The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return zero.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER nonError(0), error(1)  

st4Notifications 1.3.6.1.4.1.1718.4.100
OBJECT IDENTIFIER    

st4Events 1.3.6.1.4.1.1718.4.100.0
OBJECT IDENTIFIER    

st4UnitStatusEvent 1.3.6.1.4.1.1718.4.100.0.1
Unit status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4InputCordStatusEvent 1.3.6.1.4.1.1718.4.100.0.2
Input cord status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4InputCordActivePowerEvent 1.3.6.1.4.1.1718.4.100.0.3
Input cord active power event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4InputCordApparentPowerEvent 1.3.6.1.4.1.1718.4.100.0.4
Input cord apparent power event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4InputCordPowerFactorEvent 1.3.6.1.4.1.1718.4.100.0.5
Input cord power factor event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4InputCordOutOfBalanceEvent 1.3.6.1.4.1.1718.4.100.0.6
Input cord out-of-balance event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4LineStatusEvent 1.3.6.1.4.1.1718.4.100.0.7
Line status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4LineCurrentEvent 1.3.6.1.4.1.1718.4.100.0.8
Line current event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4PhaseStatusEvent 1.3.6.1.4.1.1718.4.100.0.9
Phase status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4PhaseVoltageEvent 1.3.6.1.4.1.1718.4.100.0.10
Phase voltage event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4PhasePowerFactorEvent 1.3.6.1.4.1.1718.4.100.0.11
Phase voltage event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OcpStatusEvent 1.3.6.1.4.1.1718.4.100.0.12
Over-current protector status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4BranchStatusEvent 1.3.6.1.4.1.1718.4.100.0.13
Branch status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4BranchCurrentEvent 1.3.6.1.4.1.1718.4.100.0.14
Branch current event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OutletStatusEvent 1.3.6.1.4.1.1718.4.100.0.15
Outlet status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OutletStateChangeEvent 1.3.6.1.4.1.1718.4.100.0.16
Outlet state change event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OutletCurrentEvent 1.3.6.1.4.1.1718.4.100.0.17
Outlet current event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OutletActivePowerEvent 1.3.6.1.4.1.1718.4.100.0.18
Outlet active power event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4OutletPowerFactorEvent 1.3.6.1.4.1.1718.4.100.0.19
Outlet power factor event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4TempSensorEvent 1.3.6.1.4.1.1718.4.100.0.20
Temperature sensor event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4HumidSensorEvent 1.3.6.1.4.1.1718.4.100.0.21
Humidity sensor event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4WaterSensorStatusEvent 1.3.6.1.4.1.1718.4.100.0.22
Water sensor status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4CcSensorStatusEvent 1.3.6.1.4.1.1718.4.100.0.23
Contact closure sensor status event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4AdcSensorEvent 1.3.6.1.4.1.1718.4.100.0.24
Analog-to-digital converter sensor event.
Status: current Access: read-only
NOTIFICATION-TYPE    

st4Conformance 1.3.6.1.4.1.1718.4.200
OBJECT IDENTIFIER    

st4Groups 1.3.6.1.4.1.1718.4.200.1
OBJECT IDENTIFIER    

st4SystemObjectsGroup 1.3.6.1.4.1.1718.4.200.1.1
System objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4UnitObjectsGroup 1.3.6.1.4.1.1718.4.200.1.2
Unit objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4InputCordObjectsGroup 1.3.6.1.4.1.1718.4.200.1.3
Input cord objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4LineObjectsGroup 1.3.6.1.4.1.1718.4.200.1.4
Line objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4PhaseObjectsGroup 1.3.6.1.4.1.1718.4.200.1.5
Phase objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4OcpObjectsGroup 1.3.6.1.4.1.1718.4.200.1.6
Over-current protector objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4BranchObjectsGroup 1.3.6.1.4.1.1718.4.200.1.7
Branch objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4OutletObjectsGroup 1.3.6.1.4.1.1718.4.200.1.8
Outlet objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4TempSensorObjectsGroup 1.3.6.1.4.1.1718.4.200.1.9
Temperature sensor objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4HumidSensorObjectsGroup 1.3.6.1.4.1.1718.4.200.1.10
Humidity sensor objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4WaterSensorObjectsGroup 1.3.6.1.4.1.1718.4.200.1.11
Water sensor objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4CcSensorObjectsGroup 1.3.6.1.4.1.1718.4.200.1.12
Contact closure sensor objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4AdcSensorObjectsGroup 1.3.6.1.4.1.1718.4.200.1.13
Analog-to-digital converter sensor objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4EventInfoObjectsGroup 1.3.6.1.4.1.1718.4.200.1.99
Event information objects group.
Status: current Access: read-only
OBJECT-GROUP    

st4EventNotificationsGroup 1.3.6.1.4.1.1718.4.200.1.100
Event notifications group.
Status: current Access: read-only
NOTIFICATION-GROUP    

st4Compliances 1.3.6.1.4.1.1718.4.200.2
OBJECT IDENTIFIER    

st4ModuleCompliances 1.3.6.1.4.1.1718.4.200.2.1
The requirements for conformance to the Sentry4-MIB.
Status: current Access: read-only
MODULE-COMPLIANCE