T3511-MIB

File: T3511-MIB.mib (7831 bytes)

Imported modules

RFC1155-SMI RFC-1212

Imported symbols

enterprises OBJECT-TYPE

Defined Types

DisplayString  
OCTET STRING    

HistoryEntry  
SEQUENCE    
  histtemperature INTEGER
  histhumidity INTEGER
  histcomputedValue INTEGER

Defined Values

comet 1.3.6.1.4.1.22626
OBJECT IDENTIFIER    

products 1.3.6.1.4.1.22626.1
OBJECT IDENTIFIER    

t3511 1.3.6.1.4.1.22626.1.2
OBJECT IDENTIFIER    

readings 1.3.6.1.4.1.22626.1.2.1
OBJECT IDENTIFIER    

settings 1.3.6.1.4.1.22626.1.2.2
OBJECT IDENTIFIER    

readingsint 1.3.6.1.4.1.22626.1.2.3
OBJECT IDENTIFIER    

settingsint 1.3.6.1.4.1.22626.1.2.4
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.22626.1.2.5
OBJECT IDENTIFIER    

tables 1.3.6.1.4.1.22626.1.2.6
OBJECT IDENTIFIER    

temperature 1.3.6.1.4.1.22626.1.2.1.1
Temperature
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

humidity 1.3.6.1.4.1.22626.1.2.1.2
Humidity
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

computedValue 1.3.6.1.4.1.22626.1.2.1.3
Computed value
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

templow 1.3.6.1.4.1.22626.1.2.2.1
Temperature Limit Low
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

temphigh 1.3.6.1.4.1.22626.1.2.2.2
Temperature Limit High
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

humiditylow 1.3.6.1.4.1.22626.1.2.2.3
Humidity Limit Low
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

humidityhigh 1.3.6.1.4.1.22626.1.2.2.4
Humidity Limit High
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

cvlow 1.3.6.1.4.1.22626.1.2.2.5
Computed Value Limit Low
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

cvhigh 1.3.6.1.4.1.22626.1.2.2.6
Computed Value Limit High
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

temptime 1.3.6.1.4.1.22626.1.2.2.7
Temperature alaram delay
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

humidityTime 1.3.6.1.4.1.22626.1.2.2.8
Humidity alaram delay
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

cvTime 1.3.6.1.4.1.22626.1.2.2.9
Computed value alaram delay
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

tempHyst 1.3.6.1.4.1.22626.1.2.2.10
Temperature hysteresis
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

humidityHyst 1.3.6.1.4.1.22626.1.2.2.11
Humidity hysteresis
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

cvHyst 1.3.6.1.4.1.22626.1.2.2.12
Computed value hysteresis
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..8)  

temperaturei 1.3.6.1.4.1.22626.1.2.3.1
Temperature *10
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -2000..6000  

humidityi 1.3.6.1.4.1.22626.1.2.3.2
Humidity *10
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..1000  

cvi 1.3.6.1.4.1.22626.1.2.3.3
Computed Value *10
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -2000..6000  

templowi 1.3.6.1.4.1.22626.1.2.4.1
Temperature Limit Low *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

temphighi 1.3.6.1.4.1.22626.1.2.4.2
Temperature Limit High *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

humiditylowi 1.3.6.1.4.1.22626.1.2.4.3
Humidity Limit Low *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

humidityhighi 1.3.6.1.4.1.22626.1.2.4.4
Humidity Limit High *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

cvlowi 1.3.6.1.4.1.22626.1.2.4.5
Computed value Limit Low *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

cvhighi 1.3.6.1.4.1.22626.1.2.4.6
Computed value Limit High *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

temptimei 1.3.6.1.4.1.22626.1.2.4.7
Temperature alaram delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

humidityTimei 1.3.6.1.4.1.22626.1.2.4.8
Humidity alaram delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

cvTimei 1.3.6.1.4.1.22626.1.2.4.9
Computed value alaram delay
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

tempHysti 1.3.6.1.4.1.22626.1.2.4.10
Temperature hysteresis *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

humidityHysti 1.3.6.1.4.1.22626.1.2.4.11
Humidity hysteresis *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

cvHysti 1.3.6.1.4.1.22626.1.2.4.12
Computed value hysteresis *10
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -2000..6000  

messageString 1.3.6.1.4.1.22626.1.2.5.1
Message giving more detailed information on alarms.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..30)  

alarmTemperature 1.3.6.1.4.1.22626.1.2.5.2
Temperature alarm 0 = temperature OK 1 = temperature too high 2 = temperature too low
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2  

alarmhumidity 1.3.6.1.4.1.22626.1.2.5.3
Humidity alarm 0 = humidity OK 1 = humidity too high 2 = humidity too low
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2  

alarmCv 1.3.6.1.4.1.22626.1.2.5.4
Computed value alarm 0 = Computed value OK 1 = Computed value too high 2 = Computed value too low
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..2  

historyTable 1.3.6.1.4.1.22626.1.2.6.1
Table of the history values.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    HistoryEntry

historyEntry 1.3.6.1.4.1.22626.1.2.6.1.1
History values entries.
Status: optional Access: not-accessible
OBJECT-TYPE    
  HistoryEntry  

histtemperature 1.3.6.1.4.1.22626.1.2.6.1.1.1
Temperature reading.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

histhumidity 1.3.6.1.4.1.22626.1.2.6.1.1.2
Humidity reading.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

histcomputedValue 1.3.6.1.4.1.22626.1.2.6.1.1.3
Computed value reading.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535