TIC-RMTI4-G9000-G2020-MIB
File:
TIC-RMTI4-G9000-G2020-MIB.mib (57098 bytes)
Imported modules
Imported symbols
Defined Types
Defined Values
toshiba |
1.3.6.1.4.1.186 |
OBJECT IDENTIFIER |
|
|
|
equ |
1.3.6.1.4.1.186.1 |
OBJECT IDENTIFIER |
|
|
|
equUPS |
1.3.6.1.4.1.186.1.19 |
OBJECT IDENTIFIER |
|
|
|
ticUPS |
1.3.6.1.4.1.186.1.19.2 |
OBJECT IDENTIFIER |
|
|
|
rmti4 |
1.3.6.1.4.1.186.1.19.2.5 |
OBJECT IDENTIFIER |
|
|
|
upsIdent |
1.3.6.1.4.1.186.1.19.2.5.1.1 |
OBJECT IDENTIFIER |
|
|
|
upsOutput |
1.3.6.1.4.1.186.1.19.2.5.1.3 |
OBJECT IDENTIFIER |
|
|
|
upsBypass |
1.3.6.1.4.1.186.1.19.2.5.1.4 |
OBJECT IDENTIFIER |
|
|
|
upsBattery |
1.3.6.1.4.1.186.1.19.2.5.1.5 |
OBJECT IDENTIFIER |
|
|
|
upsAlarm |
1.3.6.1.4.1.186.1.19.2.5.1.6 |
OBJECT IDENTIFIER |
|
|
|
upsConfig |
1.3.6.1.4.1.186.1.19.2.5.1.7 |
OBJECT IDENTIFIER |
|
|
|
upsTime |
1.3.6.1.4.1.186.1.19.2.5.1.8 |
OBJECT IDENTIFIER |
|
|
|
upsTrap |
1.3.6.1.4.1.186.1.19.2.5.1.9 |
OBJECT IDENTIFIER |
|
|
|
upsIdentSysName |
1.3.6.1.4.1.186.1.19.2.5.1.1.4 |
A string identifying the UPS. This object is
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
upsIdentAttachedDevices |
1.3.6.1.4.1.186.1.19.2.5.1.1.5 |
A string identifying the devices attached to the
output(s) of the UPS. This object is set by
the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
upsOutputSource |
1.3.6.1.4.1.186.1.19.2.5.1.3.1 |
The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
other(1), none(2), normal(3), bypass(4), battery(5) |
|
upsOutputCurrentPercentA |
1.3.6.1.4.1.186.1.19.2.5.1.3.10 |
The output current for phase A in percent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputCurrentPercentB |
1.3.6.1.4.1.186.1.19.2.5.1.3.11 |
The output current for phase B in percent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputCurrentPercentC |
1.3.6.1.4.1.186.1.19.2.5.1.3.12 |
The output current for phase C in percent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryStatus |
1.3.6.1.4.1.186.1.19.2.5.1.5.1 |
The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6) |
|
upsElapsedTimeOnBatteryPower |
1.3.6.1.4.1.186.1.19.2.5.1.5.2 |
If the unit is on battery power, the elapsed time
since the UPS on battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsEstimatedBatteryRuntime |
1.3.6.1.4.1.186.1.19.2.5.1.5.3 |
An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
upsBatteryEstimatedCharge |
1.3.6.1.4.1.186.1.19.2.5.1.5.6 |
An estimate of the charge to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
upsBatteryModel |
1.3.6.1.4.1.186.1.19.2.5.1.5.9 |
The Battery manufacturer. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..15) |
|
upsAlarmsPresent |
1.3.6.1.4.1.186.1.19.2.5.1.6.1 |
The present number of active alarm conditions. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge32 |
|
|
upsAlarmTable |
1.3.6.1.4.1.186.1.19.2.5.1.6.2 |
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsAlarmEntry |
|
upsAlarmEntry |
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1 |
An entry containing information applicable to a
particular alarm. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsAlarmEntry |
|
|
upsAlarmId |
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1 |
A unique identifier for an alarm condition. This
value must remain constant. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PositiveInteger |
|
|
upsAlarmDescr |
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2 |
A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AutonomousType |
|
|
upsAlarmTime |
1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3 |
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal 0. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
TimeStamp |
|
|
upsAlarmFault |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.1 |
Fault: A UPS fault/Alarm condition exists. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOnBattery |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.2 |
Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryLow |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.3 |
Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryDepleted |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.4 |
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryOverheat |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.5 |
Fault: Detection of over temperature at the batteries. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmBatteryVoltageAbnormal |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.6 |
Fault: Battery voltage is abnormality. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmUPSOverheat |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.7 |
Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmPowerFailure |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.8 |
Info: Power Failure. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmUPSOverload |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.9 |
Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmUserDefinedOverloadWarning |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.10 |
Warning: The inverter output load % is greater than the user defined overload set point (default: 110%). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOnBypass |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.11 |
Warning: The UPS is in Stop (Bypass) mode. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOff |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.12 |
Info: The UPS output is off. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmAsyncOperation |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.13 |
Warning: Async Operation |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusOverCurrent |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.14 |
Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusOverVoltage |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.15 |
Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusUnderVoltage |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.16 |
Fault: UPS is reporting a DC bus undervoltage condition. Contact your
Toshiba authorized service center for examination of a DCUV fault. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDCBusImbalanced |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.17 |
Fault: The DC imbalanced alarm detection. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputUnderVoltage |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.18 |
Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmOutputOverVoltage |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.19 |
Fault: UPS is reporting an output overvoltage condition. Contact your
Toshiba authorized service center for examination of a INVOV fault. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmInverterOverload |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.20 |
Fault: Short time over-current has been detected. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmInverterOvercurrent |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.21 |
Fault: Detection of inverter overcurrent. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmRemotEyeCommError |
1.3.6.1.4.1.186.1.19.2.5.1.6.3.22 |
Warning: Communication error between the RemotEye 4 and the UPS. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsConfigModelIDString |
1.3.6.1.4.1.186.1.19.2.5.1.7.1 |
UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..63) |
|
upsConfigRatedOutputFrequency |
1.3.6.1.4.1.186.1.19.2.5.1.7.8 |
The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
bad Value for SNMPv1, or inconsistent Value for SNMPv2. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsConfigRatedOutputLLVoltage |
1.3.6.1.4.1.186.1.19.2.5.1.7.9 |
The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., bad Value for SNMPv1,
or inconsistent Value for SNMPv2. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
NonNegativeInteger |
|
|
upsConfigSysName |
1.3.6.1.4.1.186.1.19.2.5.1.7.24 |
A string identifying the UPS. This object is
set by the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsConfigAttachedDevices |
1.3.6.1.4.1.186.1.19.2.5.1.7.25 |
A string identifying the devices attached to the
output(s) of the UPS. This object is set by
the administrator. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsTimeRealDate |
1.3.6.1.4.1.186.1.19.2.5.1.8.1 |
Present date: year-month-date-day of the week. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsTimeRealTime |
1.3.6.1.4.1.186.1.19.2.5.1.8.2 |
Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..31) |
|
upsTrapFault |
1 |
Alarm: One or more fault/status alarm(s) reported. |
TRAP-TYPE |
|
|
|
upsTrapBatteryDepleted |
7 |
Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load. |
TRAP-TYPE |
|
|
|
upsTrapBatteryDepletedClear |
8 |
Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.. |
TRAP-TYPE |
|
|
|
upsTrapUPSOverheat |
13 |
Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapUPSOverheatClear |
14 |
Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapUPSOverload |
17 |
Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load. |
TRAP-TYPE |
|
|
|
upsTrapUPSOverloadClear |
18 |
Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverCurrent |
27 |
Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverCurrentClear |
28 |
Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverVoltage |
29 |
Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusOverVoltageClear |
30 |
Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusUnderVoltage |
31 |
Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusImbalance |
33 |
Fault: DC Unbalance. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapDCBusImbalanceClear |
34 |
Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputUnderVoltage |
35 |
Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputOverVoltage |
37 |
Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapOutputOverVoltageClear |
38 |
Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|
upsTrapInverterOverload |
39 |
Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. |
TRAP-TYPE |
|
|
|
upsTrapInverterOverloadClear |
40 |
Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. |
TRAP-TYPE |
|
|
|
upsTrapInverterOvercurrent |
41 |
Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination. |
TRAP-TYPE |
|
|
|