WEBMON-EDGE-MATRIX-MIB
File:
WEBMON-EDGE-MATRIX-MIB.mib (340266 bytes)
Imported modules
Imported symbols
Defined Types
DescriptionString |
|
A character string used for descriptions. |
TEXTUAL-CONVENTION |
|
|
|
|
OCTET STRING |
Size(0..80) |
|
DigitalState |
|
A type with only two states, used specifically to represent the
state of a digital reading. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
off(0), on(1) |
|
Boolean |
|
A type with only two states. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
false(0), true(1) |
|
ConnectivityState |
|
Used for the state of a connection. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
online(0), offline(1) |
|
AnalogState |
|
Defines states for an analog input. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
highHigh(0), high(1), medium(2), low(3), lowLow(4) |
|
Level |
|
Describes a priority or level. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
normal(0), critical(1), major(2), minor(3), status(4) |
|
SnmpVersion |
|
Defines which version of SNMP is used for traps. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
snmpv1(0), snmpv2c(1), snmpv3(2), snmpv2c-inform(3), snmpv3-inform(4) |
|
CameraStyle |
|
Defines the different types of IP cameras supported. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
d-link-dcs1000(0), sony-snc-rz30n(1), axis-2100(2), d-link-dcs2000(3), d-link-dcs5300(4), axis-210(5), axis-m1103(6) |
|
MeasureStyle |
|
Defines state of measurement style English or Metic. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
english(0), metric(1) |
|
OutputMode |
|
Defines the different ways a control point can be activated. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
manual(0), automatic(1) |
|
OutputState |
|
Defines states for an output. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
open(0), closed(1) |
|
BaudRate |
|
Defines baud rates for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
baud-300(300), baud-600(600), baud-1200(1200), baud-2400(2400), baud-4800(4800), baud-9600(9600), baud-19200(19200), baud-28800(28800), baud-38400(38400) |
|
DataBits |
|
Defines the number of data bits in a byte for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
data-bits-7(7), data-bits-8(8) |
|
Parity |
|
Defines the parity for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
none(0), even-parity(1), odd-parity(2) |
|
StopBits |
|
Defines the number of stop bits in a byte for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
stop-bit-1(1), stop-bits-2(2) |
|
Protocol |
|
Defines different protocols used for communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
none(0), command-line(1), modbus-interrogation(2), configuration-transfer(3), ip-switchboard(4), terminal-server(5), user-login(6), modem-mode(7), ppp-server(8), dcm-responder(9), ascii-log-single-line(10), e2a-host(11), gps-reader(12), port-redirect(13), sensor-reader(14), tl1-responder(15), dcpf-responder(16), lcd-protocol(17), tabs-responder(18), configuration-menu(19), sensor-hub-interrogation(20) |
|
SerialRTS |
|
Defines the different RTS states for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
rts-never-on(0), rts-always-on(1), rts-on-for-transmit(2) |
|
SerialCTS |
|
Defines the different CTS states for serial communication. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
cts-ignore(0), cts-require(1) |
|
SlotId |
|
Defines the different types of slot types available. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
empty(0), discrete-inputs(1), discrete-outputs(2), serial-ports(3), onboard-sensors(4), analog-inputs(5), switch-ports(6), sensor-inputs(7) |
|
ProductType |
|
Defines the type of device. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
webmon-edge(0), webmon-matrix(1) |
|
VoltageRange |
|
Defines the valid voltage ranges. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
plus-minus-100-volts(100), sensor-port(5) |
|
PortType |
|
Defines the type of serial port. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
not-present(0), rs-232(1), rs-485(2), dialup(3), iden(4), e2a(5), cdma(6), gps(7), edge(8), t202(9) |
|
DayOfWeek |
|
Day of the week |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
sunday(0), monday(1), tuesday(2), wednesday(3), thursday(4), friday(5), saturday(6) |
|
TL1Srveff |
|
Service Effecting |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
blank(0), sa(1), nsa(2) |
|
TL1Locn |
|
Location |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
blank(0), nend(1), fend(2), line(3) |
|
TL1Dirn |
|
Direction |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
blank(0), trmt(1), rcv(2), na(3) |
|
TL1Issue |
|
TL1 Issue |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
issue-3(3), issue-5(5) |
|
UseDialout |
|
Use Dialout |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
never(0), always(1), as-backup(2) |
|
SensorType |
|
Sensor Type |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
raw(0), temperature(1), humidity(2) |
|
SNMPVarbindType |
|
Value type |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
integer(2), string(4) |
|
SNMPAccess |
|
Auth/Priv type |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
noauthnopriv(0), authnopriv-md5(1), authpriv-md5(2), authnopriv-sha(3), authpriv-sha(4) |
|
MODBUSCommand |
|
Function code |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
read-holding-register(3), read-input-register(4) |
|
PTrapTargetEntry |
|
SEQUENCE |
|
|
|
|
pTrapTargetDescription |
DescriptionString |
|
|
pTrapTargetConfigured |
Configured |
|
|
pTrapTargetIpAddress |
IpAddress |
|
|
pTrapTargetSnmpVersion |
SnmpVersion |
|
|
pTrapTargetIPPortNum |
Integer32 |
|
|
pTrapTargetBackupIPAddress |
IpAddress |
|
|
pTrapTargetUseDialout |
UseDialout |
|
|
pTrapTargetDialoutTarget |
Integer32 |
|
|
pTrapTargetAuthKey |
DescriptionString |
|
|
pTrapTargetPrivKey |
DescriptionString |
|
|
pTrapTargetSNMPAccess |
SNMPAccess |
|
|
pTrapTargetEngineID |
DescriptionString |
|
|
pTrapTargetIndex |
Integer32 |
1..16 |
PEmailEntry |
|
SEQUENCE |
|
|
|
|
pEmailAddress |
DescriptionString |
|
|
pEmailDescription |
DescriptionString |
|
|
pEmailConfigured |
Configured |
|
|
pEmailIndex |
Integer32 |
1..16 |
PRemoteSensorEntry |
|
SEQUENCE |
|
|
|
|
pRemoteSensorDescription |
DescriptionString |
|
|
pRemoteSensorDesc0 |
DescriptionString |
|
|
pRemoteSensorDesc1 |
DescriptionString |
|
|
pRemoteSensorDesc2 |
DescriptionString |
|
|
pRemoteSensorDesc3 |
DescriptionString |
|
|
pRemoteSensorDesc4 |
DescriptionString |
|
|
pRemoteSensorDesc5 |
DescriptionString |
|
|
pRemoteSensorConfigured |
Configured |
|
|
pRemoteSensorSendEmail |
Boolean |
|
|
pRemoteSensorSendSNMPTrap |
Boolean |
|
|
pRemoteSensorLevel0 |
Level |
|
|
pRemoteSensorLevel1 |
Level |
|
|
pRemoteSensorLevel2 |
Level |
|
|
pRemoteSensorLevel3 |
Level |
|
|
pRemoteSensorLevel4 |
Level |
|
|
pRemoteSensorLevel5 |
Level |
|
|
pRemoteSensorThresh0 |
DescriptionString |
|
|
pRemoteSensorThresh1 |
DescriptionString |
|
|
pRemoteSensorThresh2 |
DescriptionString |
|
|
pRemoteSensorThresh3 |
DescriptionString |
|
|
pRemoteSensorThresh4 |
DescriptionString |
|
|
pRemoteSensorThresh5 |
DescriptionString |
|
|
pRemoteSensorUnits |
DescriptionString |
|
|
pRemoteSensorPollAddress |
Integer32 |
|
|
pRemoteSensorLiveDescription |
DescriptionString |
|
|
pRemoteSensorLiveLevel |
DescriptionString |
|
|
pRemoteSensorLiveRaw |
DescriptionString |
|
|
pRemoteSensorLiveTime |
DescriptionString |
|
|
pRemoteSensorTL1SID |
DescriptionString |
|
|
pRemoteSensorTL1COND |
DescriptionString |
|
|
pRemoteSensorTL1Eqpt |
DescriptionString |
|
|
pRemoteSensorTL1Env |
Boolean |
|
|
pRemoteSensorTL1Srveff |
TL1Srveff |
|
|
pRemoteSensorTL1Locn |
TL1Locn |
|
|
pRemoteSensorTL1Dirn |
TL1Dirn |
|
|
pRemoteSensorMODBUSCommand |
MODBUSCommand |
|
|
pRemoteSensorStartRegister |
Integer32 |
|
|
pRemoteSensorIndex |
Integer32 |
1..32 |
POnboardSensorEntry |
|
SEQUENCE |
|
|
|
|
pOnboardSensorDescription |
DescriptionString |
|
|
pOnboardSensorDesc0 |
DescriptionString |
|
|
pOnboardSensorDesc1 |
DescriptionString |
|
|
pOnboardSensorDesc2 |
DescriptionString |
|
|
pOnboardSensorDesc3 |
DescriptionString |
|
|
pOnboardSensorDesc4 |
DescriptionString |
|
|
pOnboardSensorDesc5 |
DescriptionString |
|
|
pOnboardSensorConfigured |
Configured |
|
|
pOnboardSensorSendEmail |
Boolean |
|
|
pOnboardSensorSendSNMPTrap |
Boolean |
|
|
pOnboardSensorLevel0 |
Level |
|
|
pOnboardSensorLevel1 |
Level |
|
|
pOnboardSensorLevel2 |
Level |
|
|
pOnboardSensorLevel3 |
Level |
|
|
pOnboardSensorLevel4 |
Level |
|
|
pOnboardSensorLevel5 |
Level |
|
|
pOnboardSensorThresh0 |
DescriptionString |
|
|
pOnboardSensorThresh1 |
DescriptionString |
|
|
pOnboardSensorThresh2 |
DescriptionString |
|
|
pOnboardSensorThresh3 |
DescriptionString |
|
|
pOnboardSensorThresh4 |
DescriptionString |
|
|
pOnboardSensorThresh5 |
DescriptionString |
|
|
pOnboardSensorUnits |
DescriptionString |
|
|
pOnboardSensorLiveDescription |
DescriptionString |
|
|
pOnboardSensorLiveLevel |
DescriptionString |
|
|
pOnboardSensorLiveRaw |
DescriptionString |
|
|
pOnboardSensorLiveTime |
DescriptionString |
|
|
pOnboardSensorTL1SID |
DescriptionString |
|
|
pOnboardSensorTL1COND |
DescriptionString |
|
|
pOnboardSensorTL1Eqpt |
DescriptionString |
|
|
pOnboardSensorTL1Env |
Boolean |
|
|
pOnboardSensorTL1Srveff |
TL1Srveff |
|
|
pOnboardSensorTL1Locn |
TL1Locn |
|
|
pOnboardSensorTL1Dirn |
TL1Dirn |
|
|
pOnboardSensorIndex |
Integer32 |
1..2 |
PNetDevicesEntry |
|
SEQUENCE |
|
|
|
|
pNetDevicesDescription |
DescriptionString |
|
|
pNetDevicesDesc0 |
DescriptionString |
|
|
pNetDevicesDesc1 |
DescriptionString |
|
|
pNetDevicesConfigured |
Configured |
|
|
pNetDevicesSendEmail |
Boolean |
|
|
pNetDevicesSendSNMPTrap |
Boolean |
|
|
pNetDevicesIpAddress |
IpAddress |
|
|
pNetDevicesLevel0 |
Level |
|
|
pNetDevicesLevel1 |
Level |
|
|
pNetDevicesLiveDescription |
DescriptionString |
|
|
pNetDevicesLiveLevel |
DescriptionString |
|
|
pNetDevicesLiveRaw |
DescriptionString |
|
|
pNetDevicesLiveTime |
DescriptionString |
|
|
pNetDevicesTL1SID |
DescriptionString |
|
|
pNetDevicesTL1COND |
DescriptionString |
|
|
pNetDevicesTL1Eqpt |
DescriptionString |
|
|
pNetDevicesTL1Env |
Boolean |
|
|
pNetDevicesTL1Srveff |
TL1Srveff |
|
|
pNetDevicesTL1Locn |
TL1Locn |
|
|
pNetDevicesTL1Dirn |
TL1Dirn |
|
|
pNetDevicesIndex |
Integer32 |
1..32 |
PAccountsEntry |
|
SEQUENCE |
|
|
|
|
pAccountsConfigured |
Configured |
|
|
pAccountsName |
DescriptionString |
|
|
pAccountsEncPassword |
DescriptionString |
|
|
pAccountsUserLevel |
Unsigned32 |
|
|
pAccountsUnsecured |
Boolean |
|
|
pAccountsAuthKey |
DescriptionString |
|
|
pAccountsPrivKey |
DescriptionString |
|
|
pAccountsSNMPAccess |
SNMPAccess |
|
|
pAccountsIndex |
Integer32 |
1..16 |
PSerialEntry |
|
SEQUENCE |
|
|
|
|
pSerialDescription |
DescriptionString |
|
|
pSerialConfigured |
Configured |
|
|
pSerialIpAddress |
IpAddress |
|
|
pSerialReadPeriod |
Integer32 |
|
|
pSerialBaudRate |
BaudRate |
|
|
pSerialDataBits |
DataBits |
|
|
pSerialParity |
Parity |
|
|
pSerialStopBits |
StopBits |
|
|
pSerialProtocol |
Protocol |
|
|
pSerialSerialRTS |
SerialRTS |
|
|
pSerialSerialCTS |
SerialCTS |
|
|
pSerialPresent |
Boolean |
|
|
pSerialIPPortNum |
Integer32 |
|
|
pSerialPortType |
PortType |
|
|
pSerialIndex |
Integer32 |
1..5 |
PSelfTestEntry |
|
SEQUENCE |
|
|
|
|
pSelfTestDescription |
DescriptionString |
|
|
pSelfTestConfigured |
Configured |
|
|
pSelfTestIndex |
Integer32 |
1..7 |
PInternalFaultsEntry |
|
SEQUENCE |
|
|
|
|
pInternalFaultsDescription |
DescriptionString |
|
|
pInternalFaultsDesc0 |
DescriptionString |
|
|
pInternalFaultsDesc1 |
DescriptionString |
|
|
pInternalFaultsDesc2 |
DescriptionString |
|
|
pInternalFaultsDesc3 |
DescriptionString |
|
|
pInternalFaultsSendEmail |
Boolean |
|
|
pInternalFaultsSendSNMPTrap |
Boolean |
|
|
pInternalFaultsLevel0 |
Level |
|
|
pInternalFaultsLevel1 |
Level |
|
|
pInternalFaultsLevel2 |
Level |
|
|
pInternalFaultsLevel3 |
Level |
|
|
pInternalFaultsIgnoreOff |
Boolean |
|
|
pInternalFaultsLiveDescription |
DescriptionString |
|
|
pInternalFaultsLiveLevel |
DescriptionString |
|
|
pInternalFaultsLiveTime |
DescriptionString |
|
|
pInternalFaultsIndex |
Integer32 |
1..11 |
PSlotInfoEntry |
|
SEQUENCE |
|
|
|
|
pSlotInfoDescription |
DescriptionString |
|
|
pSlotInfoRecord |
Integer32 |
|
|
pSlotInfoPresent |
Boolean |
|
|
pSlotInfoSlotId |
SlotId |
|
|
pSlotInfoIndex |
Integer32 |
1..6 |
PNetPortsEntry |
|
SEQUENCE |
|
|
|
|
pNetPortsDescription |
DescriptionString |
|
|
pNetPortsIPPortNum |
Integer32 |
|
|
pNetPortsIndex |
Integer32 |
1..5 |
PDCMProtocolEntry |
|
SEQUENCE |
|
|
|
|
pDCMProtocolDescription |
DescriptionString |
|
|
pDCMProtocolConfigured |
Configured |
|
|
pDCMProtocolBaseDCMAddress |
Integer32 |
|
|
pDCMProtocolIndex |
Integer32 |
1..27 |
PdialOutEntry |
|
SEQUENCE |
|
|
|
|
pdialOutConfigured |
Configured |
|
|
pdialOutName |
DescriptionString |
|
|
pdialOutPassword |
DescriptionString |
|
|
pdialOutDialOutNumber |
DescriptionString |
|
|
pdialOutIndex |
Integer32 |
1..4 |
PderivedDiscreteEntry |
|
SEQUENCE |
|
|
|
|
pderivedDiscreteDescription |
DescriptionString |
|
|
pderivedDiscreteDesc0 |
DescriptionString |
|
|
pderivedDiscreteDesc1 |
DescriptionString |
|
|
pderivedDiscreteConfigured |
Configured |
|
|
pderivedDiscreteSendEmail |
Boolean |
|
|
pderivedDiscreteSendSNMPTrap |
Boolean |
|
|
pderivedDiscreteLevel0 |
Level |
|
|
pderivedDiscreteLevel1 |
Level |
|
|
pderivedDiscreteLiveDescription |
DescriptionString |
|
|
pderivedDiscreteLiveLevel |
DescriptionString |
|
|
pderivedDiscreteLiveTime |
DescriptionString |
|
|
pderivedDiscreteElementAPkg |
Integer32 |
|
|
pderivedDiscreteElementAPoint |
Integer32 |
|
|
pderivedDiscreteElementBPkg |
Integer32 |
|
|
pderivedDiscreteElementBPoint |
Integer32 |
|
|
pderivedDiscreteDiscreteFormula |
DiscreteFormula |
|
|
pderivedDiscreteTL1SID |
DescriptionString |
|
|
pderivedDiscreteTL1COND |
DescriptionString |
|
|
pderivedDiscreteTL1Eqpt |
DescriptionString |
|
|
pderivedDiscreteTL1Env |
Boolean |
|
|
pderivedDiscreteTL1Srveff |
TL1Srveff |
|
|
pderivedDiscreteTL1Locn |
TL1Locn |
|
|
pderivedDiscreteTL1Dirn |
TL1Dirn |
|
|
pderivedDiscreteIndex |
Integer32 |
1..16 |
Pe2aHostEntry |
|
SEQUENCE |
|
|
|
|
pe2aHostDescription |
DescriptionString |
|
|
pe2aHostConfigured |
Configured |
|
|
pe2aHostIpAddress |
IpAddress |
|
|
pe2aHostLevel0 |
Level |
|
|
pe2aHostLevel1 |
Level |
|
|
pe2aHostLevel2 |
Level |
|
|
pe2aHostRosterID |
Integer32 |
|
|
pe2aHostPollAddress |
Integer32 |
|
|
pe2aHostIPPortNum |
Integer32 |
|
|
pe2aHostTL1SID |
DescriptionString |
|
|
pe2aHostTL1COND |
DescriptionString |
|
|
pe2aHostTL1Eqpt |
DescriptionString |
|
|
pe2aHostTL1Env |
Boolean |
|
|
pe2aHostTL1Srveff |
TL1Srveff |
|
|
pe2aHostTL1Locn |
TL1Locn |
|
|
pe2aHostTL1Dirn |
TL1Dirn |
|
|
pe2aHostIndex |
Integer32 |
1..256 |
PderivedAnalogEntry |
|
SEQUENCE |
|
|
|
|
pderivedAnalogDescription |
DescriptionString |
|
|
pderivedAnalogDesc0 |
DescriptionString |
|
|
pderivedAnalogDesc1 |
DescriptionString |
|
|
pderivedAnalogDesc2 |
DescriptionString |
|
|
pderivedAnalogDesc3 |
DescriptionString |
|
|
pderivedAnalogDesc4 |
DescriptionString |
|
|
pderivedAnalogConfigured |
Configured |
|
|
pderivedAnalogSendEmail |
Boolean |
|
|
pderivedAnalogSendSNMPTrap |
Boolean |
|
|
pderivedAnalogLevel0 |
Level |
|
|
pderivedAnalogLevel1 |
Level |
|
|
pderivedAnalogLevel2 |
Level |
|
|
pderivedAnalogLevel3 |
Level |
|
|
pderivedAnalogLevel4 |
Level |
|
|
pderivedAnalogThresh0 |
DescriptionString |
|
|
pderivedAnalogThresh1 |
DescriptionString |
|
|
pderivedAnalogThresh2 |
DescriptionString |
|
|
pderivedAnalogThresh3 |
DescriptionString |
|
|
pderivedAnalogThresh4 |
DescriptionString |
|
|
pderivedAnalogThresh5 |
DescriptionString |
|
|
pderivedAnalogUnits |
DescriptionString |
|
|
pderivedAnalogLiveDescription |
DescriptionString |
|
|
pderivedAnalogLiveLevel |
DescriptionString |
|
|
pderivedAnalogLiveRaw |
DescriptionString |
|
|
pderivedAnalogLiveTime |
DescriptionString |
|
|
pderivedAnalogElementAPkg |
Integer32 |
|
|
pderivedAnalogElementAPoint |
Integer32 |
|
|
pderivedAnalogElementBPkg |
Integer32 |
|
|
pderivedAnalogElementBPoint |
Integer32 |
|
|
pderivedAnalogFormula |
DescriptionString |
|
|
pderivedAnalogTL1SID |
DescriptionString |
|
|
pderivedAnalogTL1COND |
DescriptionString |
|
|
pderivedAnalogTL1Eqpt |
DescriptionString |
|
|
pderivedAnalogTL1Env |
Boolean |
|
|
pderivedAnalogTL1Srveff |
TL1Srveff |
|
|
pderivedAnalogTL1Locn |
TL1Locn |
|
|
pderivedAnalogTL1Dirn |
TL1Dirn |
|
|
pderivedAnalogIndex |
Integer32 |
1..16 |
PgpsEntry |
|
SEQUENCE |
|
|
|
|
pgpsDescription |
DescriptionString |
|
|
pgpsDesc0 |
DescriptionString |
|
|
pgpsDesc1 |
DescriptionString |
|
|
pgpsDesc2 |
DescriptionString |
|
|
pgpsDesc3 |
DescriptionString |
|
|
pgpsDesc4 |
DescriptionString |
|
|
pgpsConfigured |
Configured |
|
|
pgpsSendEmail |
Boolean |
|
|
pgpsSendSNMPTrap |
Boolean |
|
|
pgpsLevel0 |
Level |
|
|
pgpsLevel1 |
Level |
|
|
pgpsLevel2 |
Level |
|
|
pgpsLevel3 |
Level |
|
|
pgpsLevel4 |
Level |
|
|
pgpsThresh0 |
DescriptionString |
|
|
pgpsThresh1 |
DescriptionString |
|
|
pgpsThresh2 |
DescriptionString |
|
|
pgpsThresh3 |
DescriptionString |
|
|
pgpsThresh4 |
DescriptionString |
|
|
pgpsThresh5 |
DescriptionString |
|
|
pgpsUnits |
DescriptionString |
|
|
pgpsLiveDescription |
DescriptionString |
|
|
pgpsLiveLevel |
DescriptionString |
|
|
pgpsLiveRaw |
DescriptionString |
|
|
pgpsLiveTime |
DescriptionString |
|
|
pgpsTL1SID |
DescriptionString |
|
|
pgpsTL1COND |
DescriptionString |
|
|
pgpsTL1Eqpt |
DescriptionString |
|
|
pgpsTL1Env |
Boolean |
|
|
pgpsTL1Srveff |
TL1Srveff |
|
|
pgpsTL1Locn |
TL1Locn |
|
|
pgpsTL1Dirn |
TL1Dirn |
|
|
pgpsIndex |
Integer32 |
1..3 |
PportRedirectEntry |
|
SEQUENCE |
|
|
|
|
pportRedirectDescription |
DescriptionString |
|
|
pportRedirectConfigured |
Configured |
|
|
pportRedirectIpAddress |
IpAddress |
|
|
pportRedirectReadPeriod |
Integer32 |
|
|
pportRedirectRosterID |
Integer32 |
|
|
pportRedirectIPPortNum |
Integer32 |
|
|
pportRedirectIndex |
Integer32 |
1..16 |
PscheduleAEntry |
|
SEQUENCE |
|
|
|
|
pscheduleADayOfWeek |
DayOfWeek |
|
|
pscheduleAConfiguredState |
ConfiguredState |
|
|
pscheduleAConfigured1 |
ConfiguredState |
|
|
pscheduleAConfigured2 |
ConfiguredState |
|
|
pscheduleAConfigured3 |
ConfiguredState |
|
|
pscheduleAConfigured4 |
ConfiguredState |
|
|
pscheduleATime0 |
DescriptionString |
|
|
pscheduleATime1 |
DescriptionString |
|
|
pscheduleATime2 |
DescriptionString |
|
|
pscheduleATime3 |
DescriptionString |
|
|
pscheduleATime4 |
DescriptionString |
|
|
pscheduleATime5 |
DescriptionString |
|
|
pscheduleAIndex |
Integer32 |
1..7 |
PscheduleBEntry |
|
SEQUENCE |
|
|
|
|
pscheduleBDayOfWeek |
DayOfWeek |
|
|
pscheduleBConfiguredState |
ConfiguredState |
|
|
pscheduleBConfigured1 |
ConfiguredState |
|
|
pscheduleBConfigured2 |
ConfiguredState |
|
|
pscheduleBConfigured3 |
ConfiguredState |
|
|
pscheduleBConfigured4 |
ConfiguredState |
|
|
pscheduleBTime0 |
DescriptionString |
|
|
pscheduleBTime1 |
DescriptionString |
|
|
pscheduleBTime2 |
DescriptionString |
|
|
pscheduleBTime3 |
DescriptionString |
|
|
pscheduleBTime4 |
DescriptionString |
|
|
pscheduleBTime5 |
DescriptionString |
|
|
pscheduleBIndex |
Integer32 |
1..7 |
PscheduleCEntry |
|
SEQUENCE |
|
|
|
|
pscheduleCDayOfWeek |
DayOfWeek |
|
|
pscheduleCConfiguredState |
ConfiguredState |
|
|
pscheduleCConfigured1 |
ConfiguredState |
|
|
pscheduleCConfigured2 |
ConfiguredState |
|
|
pscheduleCConfigured3 |
ConfiguredState |
|
|
pscheduleCConfigured4 |
ConfiguredState |
|
|
pscheduleCTime0 |
DescriptionString |
|
|
pscheduleCTime1 |
DescriptionString |
|
|
pscheduleCTime2 |
DescriptionString |
|
|
pscheduleCTime3 |
DescriptionString |
|
|
pscheduleCTime4 |
DescriptionString |
|
|
pscheduleCTime5 |
DescriptionString |
|
|
pscheduleCIndex |
Integer32 |
1..7 |
PscheduleDEntry |
|
SEQUENCE |
|
|
|
|
pscheduleDDayOfWeek |
DayOfWeek |
|
|
pscheduleDConfiguredState |
ConfiguredState |
|
|
pscheduleDConfigured1 |
ConfiguredState |
|
|
pscheduleDConfigured2 |
ConfiguredState |
|
|
pscheduleDConfigured3 |
ConfiguredState |
|
|
pscheduleDConfigured4 |
ConfiguredState |
|
|
pscheduleDTime0 |
DescriptionString |
|
|
pscheduleDTime1 |
DescriptionString |
|
|
pscheduleDTime2 |
DescriptionString |
|
|
pscheduleDTime3 |
DescriptionString |
|
|
pscheduleDTime4 |
DescriptionString |
|
|
pscheduleDTime5 |
DescriptionString |
|
|
pscheduleDIndex |
Integer32 |
1..7 |
PDCPFProtocolEntry |
|
SEQUENCE |
|
|
|
|
pDCPFProtocolDescription |
DescriptionString |
|
|
pDCPFProtocolConfigured |
Configured |
|
|
pDCPFProtocolBaseDCPFDisplay |
Integer32 |
|
|
pDCPFProtocolIndex |
Integer32 |
1..27 |
PTABSProtocolEntry |
|
SEQUENCE |
|
|
|
|
pTABSProtocolDescription |
DescriptionString |
|
|
pTABSProtocolConfigured |
Configured |
|
|
pTABSProtocolBaseTABSDisplay |
Integer32 |
|
|
pTABSProtocolIndex |
Integer32 |
1..27 |
PsnmpCommandsEntry |
|
SEQUENCE |
|
|
|
|
psnmpCommandsDescription |
DescriptionString |
|
|
psnmpCommandsConfigured |
Configured |
|
|
psnmpCommandsIpAddress |
IpAddress |
|
|
psnmpCommandsGet |
DescriptionString |
|
|
psnmpCommandsSnmpVersion |
SnmpVersion |
|
|
psnmpCommandsOutputAuto |
Integer32 |
|
|
psnmpCommandsOutputAutoPkg |
Integer32 |
|
|
psnmpCommandsIPPortNum |
Integer32 |
|
|
psnmpCommandsOID |
DescriptionString |
|
|
psnmpCommandsSNMPVarbindType |
SNMPVarbindType |
|
|
psnmpCommandsTextNormal |
DescriptionString |
|
|
psnmpCommandsTextCritical |
DescriptionString |
|
|
psnmpCommandsTextMajor |
DescriptionString |
|
|
psnmpCommandsTextMinor |
DescriptionString |
|
|
psnmpCommandsTextStatus |
DescriptionString |
|
|
psnmpCommandsIndex |
Integer32 |
1..16 |
PBankInfoEntry |
|
SEQUENCE |
|
|
|
|
pBankInfoDescription |
DescriptionString |
|
|
pBankInfoConfigured |
Configured |
|
|
pBankInfoPresent |
Boolean |
|
|
pBankInfoSlotId |
SlotId |
|
|
pBankInfoIOFormat |
IOFormat |
|
|
pBankInfoIndex |
Integer32 |
1..16 |
PSlot1Entry |
|
SEQUENCE |
|
|
|
|
pSlot1Description |
DescriptionString |
|
|
pSlot1Desc0 |
DescriptionString |
|
|
pSlot1Desc1 |
DescriptionString |
|
|
pSlot1Desc2 |
DescriptionString |
|
|
pSlot1Desc3 |
DescriptionString |
|
|
pSlot1Desc4 |
DescriptionString |
|
|
pSlot1Desc5 |
DescriptionString |
|
|
pSlot1Configured |
Configured |
|
|
pSlot1SendEmail |
Boolean |
|
|
pSlot1SendSNMPTrap |
Boolean |
|
|
pSlot1IpAddress |
IpAddress |
|
|
pSlot1Level0 |
Level |
|
|
pSlot1Level1 |
Level |
|
|
pSlot1Level2 |
Level |
|
|
pSlot1Level3 |
Level |
|
|
pSlot1Level4 |
Level |
|
|
pSlot1Level5 |
Level |
|
|
pSlot1ReadPeriod |
Integer32 |
|
|
pSlot1Thresh0 |
DescriptionString |
|
|
pSlot1Thresh1 |
DescriptionString |
|
|
pSlot1Thresh2 |
DescriptionString |
|
|
pSlot1Thresh3 |
DescriptionString |
|
|
pSlot1Thresh4 |
DescriptionString |
|
|
pSlot1Thresh5 |
DescriptionString |
|
|
pSlot1ContactStyle |
ContactStyle |
|
|
pSlot1Units |
DescriptionString |
|
|
pSlot1OutputMode |
OutputMode |
|
|
pSlot1OutputState |
OutputState |
|
|
pSlot1OutputAuto |
Integer32 |
|
|
pSlot1BaudRate |
BaudRate |
|
|
pSlot1DataBits |
DataBits |
|
|
pSlot1Parity |
Parity |
|
|
pSlot1StopBits |
StopBits |
|
|
pSlot1Protocol |
Protocol |
|
|
pSlot1SerialRTS |
SerialRTS |
|
|
pSlot1SerialCTS |
SerialCTS |
|
|
pSlot1LiveDescription |
DescriptionString |
|
|
pSlot1LiveLevel |
DescriptionString |
|
|
pSlot1LiveRaw |
DescriptionString |
|
|
pSlot1LiveTime |
DescriptionString |
|
|
pSlot1Present |
Boolean |
|
|
pSlot1OutputAutoPkg |
Integer32 |
|
|
pSlot1VoltageRange |
VoltageRange |
|
|
pSlot1IPPortNum |
Integer32 |
|
|
pSlot1IOFormat |
IOFormat |
|
|
pSlot1PortType |
PortType |
|
|
pSlot1TL1SID |
DescriptionString |
|
|
pSlot1TL1COND |
DescriptionString |
|
|
pSlot1TL1Eqpt |
DescriptionString |
|
|
pSlot1TL1Env |
Boolean |
|
|
pSlot1TL1Srveff |
TL1Srveff |
|
|
pSlot1TL1Locn |
TL1Locn |
|
|
pSlot1TL1Dirn |
TL1Dirn |
|
|
pSlot1SensorType |
SensorType |
|
|
pSlot1Index |
Integer32 |
1..32 |
PSlot2Entry |
|
SEQUENCE |
|
|
|
|
pSlot2Description |
DescriptionString |
|
|
pSlot2Desc0 |
DescriptionString |
|
|
pSlot2Desc1 |
DescriptionString |
|
|
pSlot2Desc2 |
DescriptionString |
|
|
pSlot2Desc3 |
DescriptionString |
|
|
pSlot2Desc4 |
DescriptionString |
|
|
pSlot2Desc5 |
DescriptionString |
|
|
pSlot2Configured |
Configured |
|
|
pSlot2SendEmail |
Boolean |
|
|
pSlot2SendSNMPTrap |
Boolean |
|
|
pSlot2IpAddress |
IpAddress |
|
|
pSlot2Level0 |
Level |
|
|
pSlot2Level1 |
Level |
|
|
pSlot2Level2 |
Level |
|
|
pSlot2Level3 |
Level |
|
|
pSlot2Level4 |
Level |
|
|
pSlot2Level5 |
Level |
|
|
pSlot2ReadPeriod |
Integer32 |
|
|
pSlot2Thresh0 |
DescriptionString |
|
|
pSlot2Thresh1 |
DescriptionString |
|
|
pSlot2Thresh2 |
DescriptionString |
|
|
pSlot2Thresh3 |
DescriptionString |
|
|
pSlot2Thresh4 |
DescriptionString |
|
|
pSlot2Thresh5 |
DescriptionString |
|
|
pSlot2ContactStyle |
ContactStyle |
|
|
pSlot2Units |
DescriptionString |
|
|
pSlot2OutputMode |
OutputMode |
|
|
pSlot2OutputState |
OutputState |
|
|
pSlot2OutputAuto |
Integer32 |
|
|
pSlot2BaudRate |
BaudRate |
|
|
pSlot2DataBits |
DataBits |
|
|
pSlot2Parity |
Parity |
|
|
pSlot2StopBits |
StopBits |
|
|
pSlot2Protocol |
Protocol |
|
|
pSlot2SerialRTS |
SerialRTS |
|
|
pSlot2SerialCTS |
SerialCTS |
|
|
pSlot2LiveDescription |
DescriptionString |
|
|
pSlot2LiveLevel |
DescriptionString |
|
|
pSlot2LiveRaw |
DescriptionString |
|
|
pSlot2LiveTime |
DescriptionString |
|
|
pSlot2Present |
Boolean |
|
|
pSlot2OutputAutoPkg |
Integer32 |
|
|
pSlot2VoltageRange |
VoltageRange |
|
|
pSlot2IPPortNum |
Integer32 |
|
|
pSlot2IOFormat |
IOFormat |
|
|
pSlot2PortType |
PortType |
|
|
pSlot2TL1SID |
DescriptionString |
|
|
pSlot2TL1COND |
DescriptionString |
|
|
pSlot2TL1Eqpt |
DescriptionString |
|
|
pSlot2TL1Env |
Boolean |
|
|
pSlot2TL1Srveff |
TL1Srveff |
|
|
pSlot2TL1Locn |
TL1Locn |
|
|
pSlot2TL1Dirn |
TL1Dirn |
|
|
pSlot2SensorType |
SensorType |
|
|
pSlot2Index |
Integer32 |
1..32 |
PSlot3Entry |
|
SEQUENCE |
|
|
|
|
pSlot3Description |
DescriptionString |
|
|
pSlot3Desc0 |
DescriptionString |
|
|
pSlot3Desc1 |
DescriptionString |
|
|
pSlot3Desc2 |
DescriptionString |
|
|
pSlot3Desc3 |
DescriptionString |
|
|
pSlot3Desc4 |
DescriptionString |
|
|
pSlot3Desc5 |
DescriptionString |
|
|
pSlot3Configured |
Configured |
|
|
pSlot3SendEmail |
Boolean |
|
|
pSlot3SendSNMPTrap |
Boolean |
|
|
pSlot3IpAddress |
IpAddress |
|
|
pSlot3Level0 |
Level |
|
|
pSlot3Level1 |
Level |
|
|
pSlot3Level2 |
Level |
|
|
pSlot3Level3 |
Level |
|
|
pSlot3Level4 |
Level |
|
|
pSlot3Level5 |
Level |
|
|
pSlot3ReadPeriod |
Integer32 |
|
|
pSlot3Thresh0 |
DescriptionString |
|
|
pSlot3Thresh1 |
DescriptionString |
|
|
pSlot3Thresh2 |
DescriptionString |
|
|
pSlot3Thresh3 |
DescriptionString |
|
|
pSlot3Thresh4 |
DescriptionString |
|
|
pSlot3Thresh5 |
DescriptionString |
|
|
pSlot3ContactStyle |
ContactStyle |
|
|
pSlot3Units |
DescriptionString |
|
|
pSlot3OutputMode |
OutputMode |
|
|
pSlot3OutputState |
OutputState |
|
|
pSlot3OutputAuto |
Integer32 |
|
|
pSlot3BaudRate |
BaudRate |
|
|
pSlot3DataBits |
DataBits |
|
|
pSlot3Parity |
Parity |
|
|
pSlot3StopBits |
StopBits |
|
|
pSlot3Protocol |
Protocol |
|
|
pSlot3SerialRTS |
SerialRTS |
|
|
pSlot3SerialCTS |
SerialCTS |
|
|
pSlot3LiveDescription |
DescriptionString |
|
|
pSlot3LiveLevel |
DescriptionString |
|
|
pSlot3LiveRaw |
DescriptionString |
|
|
pSlot3LiveTime |
DescriptionString |
|
|
pSlot3Present |
Boolean |
|
|
pSlot3OutputAutoPkg |
Integer32 |
|
|
pSlot3VoltageRange |
VoltageRange |
|
|
pSlot3IPPortNum |
Integer32 |
|
|
pSlot3IOFormat |
IOFormat |
|
|
pSlot3PortType |
PortType |
|
|
pSlot3TL1SID |
DescriptionString |
|
|
pSlot3TL1COND |
DescriptionString |
|
|
pSlot3TL1Eqpt |
DescriptionString |
|
|
pSlot3TL1Env |
Boolean |
|
|
pSlot3TL1Srveff |
TL1Srveff |
|
|
pSlot3TL1Locn |
TL1Locn |
|
|
pSlot3TL1Dirn |
TL1Dirn |
|
|
pSlot3SensorType |
SensorType |
|
|
pSlot3Index |
Integer32 |
1..32 |
PSlot4Entry |
|
SEQUENCE |
|
|
|
|
pSlot4Description |
DescriptionString |
|
|
pSlot4Desc0 |
DescriptionString |
|
|
pSlot4Desc1 |
DescriptionString |
|
|
pSlot4Desc2 |
DescriptionString |
|
|
pSlot4Desc3 |
DescriptionString |
|
|
pSlot4Desc4 |
DescriptionString |
|
|
pSlot4Desc5 |
DescriptionString |
|
|
pSlot4Configured |
Configured |
|
|
pSlot4SendEmail |
Boolean |
|
|
pSlot4SendSNMPTrap |
Boolean |
|
|
pSlot4IpAddress |
IpAddress |
|
|
pSlot4Level0 |
Level |
|
|
pSlot4Level1 |
Level |
|
|
pSlot4Level2 |
Level |
|
|
pSlot4Level3 |
Level |
|
|
pSlot4Level4 |
Level |
|
|
pSlot4Level5 |
Level |
|
|
pSlot4ReadPeriod |
Integer32 |
|
|
pSlot4Thresh0 |
DescriptionString |
|
|
pSlot4Thresh1 |
DescriptionString |
|
|
pSlot4Thresh2 |
DescriptionString |
|
|
pSlot4Thresh3 |
DescriptionString |
|
|
pSlot4Thresh4 |
DescriptionString |
|
|
pSlot4Thresh5 |
DescriptionString |
|
|
pSlot4ContactStyle |
ContactStyle |
|
|
pSlot4Units |
DescriptionString |
|
|
pSlot4OutputMode |
OutputMode |
|
|
pSlot4OutputState |
OutputState |
|
|
pSlot4OutputAuto |
Integer32 |
|
|
pSlot4BaudRate |
BaudRate |
|
|
pSlot4DataBits |
DataBits |
|
|
pSlot4Parity |
Parity |
|
|
pSlot4StopBits |
StopBits |
|
|
pSlot4Protocol |
Protocol |
|
|
pSlot4SerialRTS |
SerialRTS |
|
|
pSlot4SerialCTS |
SerialCTS |
|
|
pSlot4LiveDescription |
DescriptionString |
|
|
pSlot4LiveLevel |
DescriptionString |
|
|
pSlot4LiveRaw |
DescriptionString |
|
|
pSlot4LiveTime |
DescriptionString |
|
|
pSlot4Present |
Boolean |
|
|
pSlot4OutputAutoPkg |
Integer32 |
|
|
pSlot4VoltageRange |
VoltageRange |
|
|
pSlot4IPPortNum |
Integer32 |
|
|
pSlot4IOFormat |
IOFormat |
|
|
pSlot4PortType |
PortType |
|
|
pSlot4TL1SID |
DescriptionString |
|
|
pSlot4TL1COND |
DescriptionString |
|
|
pSlot4TL1Eqpt |
DescriptionString |
|
|
pSlot4TL1Env |
Boolean |
|
|
pSlot4TL1Srveff |
TL1Srveff |
|
|
pSlot4TL1Locn |
TL1Locn |
|
|
pSlot4TL1Dirn |
TL1Dirn |
|
|
pSlot4SensorType |
SensorType |
|
|
pSlot4Index |
Integer32 |
1..32 |
PSlot5Entry |
|
SEQUENCE |
|
|
|
|
pSlot5Description |
DescriptionString |
|
|
pSlot5Desc0 |
DescriptionString |
|
|
pSlot5Desc1 |
DescriptionString |
|
|
pSlot5Desc2 |
DescriptionString |
|
|
pSlot5Desc3 |
DescriptionString |
|
|
pSlot5Desc4 |
DescriptionString |
|
|
pSlot5Desc5 |
DescriptionString |
|
|
pSlot5Configured |
Configured |
|
|
pSlot5SendEmail |
Boolean |
|
|
pSlot5SendSNMPTrap |
Boolean |
|
|
pSlot5IpAddress |
IpAddress |
|
|
pSlot5Level0 |
Level |
|
|
pSlot5Level1 |
Level |
|
|
pSlot5Level2 |
Level |
|
|
pSlot5Level3 |
Level |
|
|
pSlot5Level4 |
Level |
|
|
pSlot5Level5 |
Level |
|
|
pSlot5ReadPeriod |
Integer32 |
|
|
pSlot5Thresh0 |
DescriptionString |
|
|
pSlot5Thresh1 |
DescriptionString |
|
|
pSlot5Thresh2 |
DescriptionString |
|
|
pSlot5Thresh3 |
DescriptionString |
|
|
pSlot5Thresh4 |
DescriptionString |
|
|
pSlot5Thresh5 |
DescriptionString |
|
|
pSlot5ContactStyle |
ContactStyle |
|
|
pSlot5Units |
DescriptionString |
|
|
pSlot5OutputMode |
OutputMode |
|
|
pSlot5OutputState |
OutputState |
|
|
pSlot5OutputAuto |
Integer32 |
|
|
pSlot5BaudRate |
BaudRate |
|
|
pSlot5DataBits |
DataBits |
|
|
pSlot5Parity |
Parity |
|
|
pSlot5StopBits |
StopBits |
|
|
pSlot5Protocol |
Protocol |
|
|
pSlot5SerialRTS |
SerialRTS |
|
|
pSlot5SerialCTS |
SerialCTS |
|
|
pSlot5LiveDescription |
DescriptionString |
|
|
pSlot5LiveLevel |
DescriptionString |
|
|
pSlot5LiveRaw |
DescriptionString |
|
|
pSlot5LiveTime |
DescriptionString |
|
|
pSlot5Present |
Boolean |
|
|
pSlot5OutputAutoPkg |
Integer32 |
|
|
pSlot5VoltageRange |
VoltageRange |
|
|
pSlot5IPPortNum |
Integer32 |
|
|
pSlot5IOFormat |
IOFormat |
|
|
pSlot5PortType |
PortType |
|
|
pSlot5TL1SID |
DescriptionString |
|
|
pSlot5TL1COND |
DescriptionString |
|
|
pSlot5TL1Eqpt |
DescriptionString |
|
|
pSlot5TL1Env |
Boolean |
|
|
pSlot5TL1Srveff |
TL1Srveff |
|
|
pSlot5TL1Locn |
TL1Locn |
|
|
pSlot5TL1Dirn |
TL1Dirn |
|
|
pSlot5SensorType |
SensorType |
|
|
pSlot5Index |
Integer32 |
1..32 |
PSlot6Entry |
|
SEQUENCE |
|
|
|
|
pSlot6Description |
DescriptionString |
|
|
pSlot6Desc0 |
DescriptionString |
|
|
pSlot6Desc1 |
DescriptionString |
|
|
pSlot6Desc2 |
DescriptionString |
|
|
pSlot6Desc3 |
DescriptionString |
|
|
pSlot6Desc4 |
DescriptionString |
|
|
pSlot6Desc5 |
DescriptionString |
|
|
pSlot6Configured |
Configured |
|
|
pSlot6SendEmail |
Boolean |
|
|
pSlot6SendSNMPTrap |
Boolean |
|
|
pSlot6IpAddress |
IpAddress |
|
|
pSlot6Level0 |
Level |
|
|
pSlot6Level1 |
Level |
|
|
pSlot6Level2 |
Level |
|
|
pSlot6Level3 |
Level |
|
|
pSlot6Level4 |
Level |
|
|
pSlot6Level5 |
Level |
|
|
pSlot6ReadPeriod |
Integer32 |
|
|
pSlot6Thresh0 |
DescriptionString |
|
|
pSlot6Thresh1 |
DescriptionString |
|
|
pSlot6Thresh2 |
DescriptionString |
|
|
pSlot6Thresh3 |
DescriptionString |
|
|
pSlot6Thresh4 |
DescriptionString |
|
|
pSlot6Thresh5 |
DescriptionString |
|
|
pSlot6ContactStyle |
ContactStyle |
|
|
pSlot6Units |
DescriptionString |
|
|
pSlot6OutputMode |
OutputMode |
|
|
pSlot6OutputState |
OutputState |
|
|
pSlot6OutputAuto |
Integer32 |
|
|
pSlot6BaudRate |
BaudRate |
|
|
pSlot6DataBits |
DataBits |
|
|
pSlot6Parity |
Parity |
|
|
pSlot6StopBits |
StopBits |
|
|
pSlot6Protocol |
Protocol |
|
|
pSlot6SerialRTS |
SerialRTS |
|
|
pSlot6SerialCTS |
SerialCTS |
|
|
pSlot6LiveDescription |
DescriptionString |
|
|
pSlot6LiveLevel |
DescriptionString |
|
|
pSlot6LiveRaw |
DescriptionString |
|
|
pSlot6LiveTime |
DescriptionString |
|
|
pSlot6Present |
Boolean |
|
|
pSlot6OutputAutoPkg |
Integer32 |
|
|
pSlot6VoltageRange |
VoltageRange |
|
|
pSlot6IPPortNum |
Integer32 |
|
|
pSlot6IOFormat |
IOFormat |
|
|
pSlot6PortType |
PortType |
|
|
pSlot6TL1SID |
DescriptionString |
|
|
pSlot6TL1COND |
DescriptionString |
|
|
pSlot6TL1Eqpt |
DescriptionString |
|
|
pSlot6TL1Env |
Boolean |
|
|
pSlot6TL1Srveff |
TL1Srveff |
|
|
pSlot6TL1Locn |
TL1Locn |
|
|
pSlot6TL1Dirn |
TL1Dirn |
|
|
pSlot6SensorType |
SensorType |
|
|
pSlot6Index |
Integer32 |
1..32 |
Defined Values
moduleIdentity |
1.3.6.1.4.1.994.3.4.3 |
WebMon Edge-Matrix MIB. |
MODULE-IDENTITY |
|
|
|
dantel |
1.3.6.1.4.1.994 |
OBJECT IDENTIFIER |
|
|
|
webMon |
1.3.6.1.4.1.994.3.4 |
The parent node representing the WebMon device. |
Status: current |
Access: read-write |
OBJECT-IDENTITY |
|
|
|
triggers |
1.3.6.1.4.1.994.3.4.8 |
OBJECT IDENTIFIER |
|
|
|
resetDevice |
1.3.6.1.4.1.994.3.4.8.1 |
Setting this item to true will cause a reset of the device.
Setting this item to false will have no effect. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
commitAccountChanges |
1.3.6.1.4.1.994.3.4.8.2 |
Setting this item to true will cause any user account changes to go into effect immediatly.
Setting this item to false will have no effect. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
resendEvents |
1.3.6.1.4.1.994.3.4.8.3 |
Setting this item to true will cause the device to resend traps for any standing alarms.
Setting this item to false will have no effect. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
systemGeneralIpAddress |
1.3.6.1.4.1.994.3.4.7.1.14 |
IP Address of the device. If changed, the new IP address
will only take effect after a reset. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
systemGeneralSubnetMask |
1.3.6.1.4.1.994.3.4.7.1.15 |
Subnet Mask of the device. If changed, the new IP address
will only take effect after a reset. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
systemGeneralGatewayAddress |
1.3.6.1.4.1.994.3.4.7.1.16 |
Gateway Address of the device. If changed, the new IP address
will only take effect after a reset. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
systemGeneralIPPortNum |
1.3.6.1.4.1.994.3.4.7.1.73 |
IP port number to use when connecting to the web page (HTTP). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pTrapTargetEntry |
1.3.6.1.4.1.994.3.4.7.2.1 |
Entry for configuration table of TrapTarget |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PTrapTargetEntry |
|
|
pTrapTargetIpAddress |
1.3.6.1.4.1.994.3.4.7.2.1.14 |
SNMP traps are sent to this IP address. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pTrapTargetIPPortNum |
1.3.6.1.4.1.994.3.4.7.2.1.73 |
SNMP traps are sent to this network port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pTrapTargetUseDialout |
1.3.6.1.4.1.994.3.4.7.2.1.125 |
Determines if traps will be sent only when dialed out. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
UseDialout |
|
|
pTrapTargetDialoutTarget |
1.3.6.1.4.1.994.3.4.7.2.1.126 |
Determines which target to dial out to when sending traps. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pEmailTable |
1.3.6.1.4.1.994.3.4.7.3 |
Table for configuration of Email |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PEmailEntry |
|
pEmailEntry |
1.3.6.1.4.1.994.3.4.7.3.1 |
Entry for configuration table of Email |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PEmailEntry |
|
|
pEmailIndex |
1.3.6.1.4.1.994.3.4.7.3.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..16 |
|
pRemoteSensorEntry |
1.3.6.1.4.1.994.3.4.7.5.1 |
Entry for configuration table of RemoteSensor |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PRemoteSensorEntry |
|
|
pRemoteSensorDesc0 |
1.3.6.1.4.1.994.3.4.7.5.1.4 |
The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorDesc1 |
1.3.6.1.4.1.994.3.4.7.5.1.5 |
The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorDesc2 |
1.3.6.1.4.1.994.3.4.7.5.1.6 |
The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorDesc3 |
1.3.6.1.4.1.994.3.4.7.5.1.7 |
The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorDesc4 |
1.3.6.1.4.1.994.3.4.7.5.1.8 |
The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorDesc5 |
1.3.6.1.4.1.994.3.4.7.5.1.9 |
Description for a communications failure to the remote analog device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorSendEmail |
1.3.6.1.4.1.994.3.4.7.5.1.11 |
If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pRemoteSensorSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.5.1.12 |
If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pRemoteSensorLevel0 |
1.3.6.1.4.1.994.3.4.7.5.1.17 |
The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLevel1 |
1.3.6.1.4.1.994.3.4.7.5.1.18 |
The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLevel2 |
1.3.6.1.4.1.994.3.4.7.5.1.19 |
The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLevel3 |
1.3.6.1.4.1.994.3.4.7.5.1.20 |
The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLevel4 |
1.3.6.1.4.1.994.3.4.7.5.1.21 |
The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLevel5 |
1.3.6.1.4.1.994.3.4.7.5.1.22 |
Level of a communications failure to the remote analog device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pRemoteSensorLiveRaw |
1.3.6.1.4.1.994.3.4.7.5.1.66 |
The current reading from the analog device. This value will always
be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pRemoteSensorTL1Env |
1.3.6.1.4.1.994.3.4.7.5.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pRemoteSensorTL1Srveff |
1.3.6.1.4.1.994.3.4.7.5.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pRemoteSensorTL1Locn |
1.3.6.1.4.1.994.3.4.7.5.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pRemoteSensorTL1Dirn |
1.3.6.1.4.1.994.3.4.7.5.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pOnboardSensorEntry |
1.3.6.1.4.1.994.3.4.7.6.1 |
Entry for configuration table of OnboardSensor |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
POnboardSensorEntry |
|
|
pOnboardSensorSendEmail |
1.3.6.1.4.1.994.3.4.7.6.1.11 |
If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pOnboardSensorSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.6.1.12 |
If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pOnboardSensorLevel0 |
1.3.6.1.4.1.994.3.4.7.6.1.17 |
The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLevel1 |
1.3.6.1.4.1.994.3.4.7.6.1.18 |
The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLevel2 |
1.3.6.1.4.1.994.3.4.7.6.1.19 |
The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLevel3 |
1.3.6.1.4.1.994.3.4.7.6.1.20 |
The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLevel4 |
1.3.6.1.4.1.994.3.4.7.6.1.21 |
The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLevel5 |
1.3.6.1.4.1.994.3.4.7.6.1.22 |
Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pOnboardSensorLiveRaw |
1.3.6.1.4.1.994.3.4.7.6.1.66 |
The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pOnboardSensorTL1Env |
1.3.6.1.4.1.994.3.4.7.6.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pOnboardSensorTL1Srveff |
1.3.6.1.4.1.994.3.4.7.6.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pOnboardSensorTL1Locn |
1.3.6.1.4.1.994.3.4.7.6.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pOnboardSensorTL1Dirn |
1.3.6.1.4.1.994.3.4.7.6.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pNetDevicesEntry |
1.3.6.1.4.1.994.3.4.7.7.1 |
Entry for configuration table of NetDevices |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PNetDevicesEntry |
|
|
pNetDevicesSendEmail |
1.3.6.1.4.1.994.3.4.7.7.1.11 |
If set to true, an email will be sent when a change of state is detected.
If set to false, no email will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pNetDevicesSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.7.1.12 |
If set to true, an SNMP trap will be sent when a change of state is detected.
If set to false, no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pNetDevicesIpAddress |
1.3.6.1.4.1.994.3.4.7.7.1.14 |
The IP address of the net device to ping. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pNetDevicesLevel0 |
1.3.6.1.4.1.994.3.4.7.7.1.17 |
Alarm level associated with the online state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pNetDevicesLevel1 |
1.3.6.1.4.1.994.3.4.7.7.1.18 |
Alarm level associated with the offline state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pNetDevicesLiveRaw |
1.3.6.1.4.1.994.3.4.7.7.1.66 |
The current reading from the net device. This value will always
be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pNetDevicesTL1Env |
1.3.6.1.4.1.994.3.4.7.7.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pNetDevicesTL1Srveff |
1.3.6.1.4.1.994.3.4.7.7.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pNetDevicesTL1Locn |
1.3.6.1.4.1.994.3.4.7.7.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pNetDevicesTL1Dirn |
1.3.6.1.4.1.994.3.4.7.7.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pAccountsTable |
1.3.6.1.4.1.994.3.4.7.9 |
Table for configuration of Accounts |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PAccountsEntry |
|
pAccountsEntry |
1.3.6.1.4.1.994.3.4.7.9.1 |
Entry for configuration table of Accounts |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PAccountsEntry |
|
|
pAccountsEncPassword |
1.3.6.1.4.1.994.3.4.7.9.1.27 |
Password for this account. When reading, an encrypted version of password
will be displayed. When writing, use plain text. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pAccountsUserLevel |
1.3.6.1.4.1.994.3.4.7.9.1.55 |
The user level for this account.
One of the following masks from each group are used:
No FTP access 0x0000 0
FTP read-only 0x0001 1
FTP Full access 0x0003 3
No Web access 0x0000 0
Monitor 0x0010 16
Config 0x0030 48
Config + Accounts 0x00B0 176
The masks are added together to create a permission value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Unsigned32 |
|
|
pAccountsUnsecured |
1.3.6.1.4.1.994.3.4.7.9.1.77 |
Allow secured configuration for SNMP through this account. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
camera |
1.3.6.1.4.1.994.3.4.7.10 |
OBJECT IDENTIFIER |
|
|
|
cameraIpAddress |
1.3.6.1.4.1.994.3.4.7.10.14 |
IP address of the camera. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
snmpGeneralReadPeriod |
1.3.6.1.4.1.994.3.4.7.12.23 |
Period in minutes between resend of standing alarms |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
snmpGeneralIPPortNum |
1.3.6.1.4.1.994.3.4.7.12.73 |
SNMP configuration is done on this network port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSerialTable |
1.3.6.1.4.1.994.3.4.7.14 |
Table for configuration of Serial |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSerialEntry |
|
pSerialEntry |
1.3.6.1.4.1.994.3.4.7.14.1 |
Entry for configuration table of Serial |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSerialEntry |
|
|
pSerialIpAddress |
1.3.6.1.4.1.994.3.4.7.14.1.14 |
IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSerialReadPeriod |
1.3.6.1.4.1.994.3.4.7.14.1.23 |
Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSerialBaudRate |
1.3.6.1.4.1.994.3.4.7.14.1.57 |
Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSerialDataBits |
1.3.6.1.4.1.994.3.4.7.14.1.58 |
Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSerialParity |
1.3.6.1.4.1.994.3.4.7.14.1.59 |
Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSerialStopBits |
1.3.6.1.4.1.994.3.4.7.14.1.60 |
Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSerialProtocol |
1.3.6.1.4.1.994.3.4.7.14.1.61 |
Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSerialSerialRTS |
1.3.6.1.4.1.994.3.4.7.14.1.62 |
Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSerialSerialCTS |
1.3.6.1.4.1.994.3.4.7.14.1.63 |
Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSerialPresent |
1.3.6.1.4.1.994.3.4.7.14.1.68 |
If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSerialIPPortNum |
1.3.6.1.4.1.994.3.4.7.14.1.73 |
IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSerialPortType |
1.3.6.1.4.1.994.3.4.7.14.1.76 |
The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSerialIndex |
1.3.6.1.4.1.994.3.4.7.14.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..5 |
|
pSelfTestTable |
1.3.6.1.4.1.994.3.4.7.15 |
Table for configuration of SelfTest |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSelfTestEntry |
|
pSelfTestEntry |
1.3.6.1.4.1.994.3.4.7.15.1 |
Entry for configuration table of SelfTest |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSelfTestEntry |
|
|
pInternalFaultsEntry |
1.3.6.1.4.1.994.3.4.7.16.1 |
Entry for configuration table of InternalFaults |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PInternalFaultsEntry |
|
|
pInternalFaultsSendEmail |
1.3.6.1.4.1.994.3.4.7.16.1.11 |
If set to true an email event will be set when a change occurs.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pInternalFaultsSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.16.1.12 |
If set to true an SNMP trap will be set when a change occurs.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pInternalFaultsLevel0 |
1.3.6.1.4.1.994.3.4.7.16.1.17 |
Alarm level associated with the healthy state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pInternalFaultsLevel1 |
1.3.6.1.4.1.994.3.4.7.16.1.18 |
Alarm level associated with this non-normal state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pInternalFaultsLevel2 |
1.3.6.1.4.1.994.3.4.7.16.1.19 |
Alarm level associated with this non-normal state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pInternalFaultsLevel3 |
1.3.6.1.4.1.994.3.4.7.16.1.20 |
Alarm level associated with this non-normal state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pInternalFaultsIgnoreOff |
1.3.6.1.4.1.994.3.4.7.16.1.50 |
If true, no event is generated for a change to the healty state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlotInfoTable |
1.3.6.1.4.1.994.3.4.7.17 |
Table for configuration of SlotInfo |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlotInfoEntry |
|
pSlotInfoEntry |
1.3.6.1.4.1.994.3.4.7.17.1 |
Entry for configuration table of SlotInfo |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlotInfoEntry |
|
|
pSlotInfoRecord |
1.3.6.1.4.1.994.3.4.7.17.1.35 |
The number of records for this slot. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlotInfoPresent |
1.3.6.1.4.1.994.3.4.7.17.1.68 |
If true indicates a card is in the slot.
If false indicates that no card is present in the slot. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlotInfoSlotId |
1.3.6.1.4.1.994.3.4.7.17.1.69 |
Identifies the type of card in slot. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
SlotId |
|
|
pNetPortsTable |
1.3.6.1.4.1.994.3.4.7.24 |
Table for configuration of NetPorts |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PNetPortsEntry |
|
pNetPortsEntry |
1.3.6.1.4.1.994.3.4.7.24.1 |
Entry for configuration table of NetPorts |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PNetPortsEntry |
|
|
pNetPortsIPPortNum |
1.3.6.1.4.1.994.3.4.7.24.1.73 |
IP port number to use when connecting to this network port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
wirelessModemSecondary |
1.3.6.1.4.1.994.3.4.7.25.115 |
Determines if the modem can use accept a dynamic (local) IP. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
webmonSecurityUserLevel |
1.3.6.1.4.1.994.3.4.7.26.55 |
This is the default user level. Anyone who has access to this
device will have these permissions without logging in.
One of the following masks from each group are used:
No FTP access 0x0000 0
FTP read-only 0x0001 1
FTP Full access 0x0003 3
No Web access 0x0000 0
Monitor 0x0010 16
Config 0x0030 48
Config + Accounts 0x00B0 176
The masks are added together to create a permission value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Unsigned32 |
|
|
dateTime |
1.3.6.1.4.1.994.3.4.7.27 |
OBJECT IDENTIFIER |
|
|
|
dateTimeDaylightSaving |
1.3.6.1.4.1.994.3.4.7.27.53 |
Determines if Daylight Savings is automatically adjusted. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
dateTimeNegOffset |
1.3.6.1.4.1.994.3.4.7.27.88 |
True if a negative offset from UTC is desired |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pDCMProtocolEntry |
1.3.6.1.4.1.994.3.4.7.28.1 |
Entry for configuration table of DCMProtocol |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PDCMProtocolEntry |
|
|
pdialOutTable |
1.3.6.1.4.1.994.3.4.7.29 |
Table for configuration of dialOut |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PdialOutEntry |
|
pdialOutEntry |
1.3.6.1.4.1.994.3.4.7.29.1 |
Entry for configuration table of dialOut |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PdialOutEntry |
|
|
pdialOutIndex |
1.3.6.1.4.1.994.3.4.7.29.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..4 |
|
pderivedDiscreteEntry |
1.3.6.1.4.1.994.3.4.7.30.1 |
Entry for configuration table of derivedDiscrete |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PderivedDiscreteEntry |
|
|
pderivedDiscreteSendEmail |
1.3.6.1.4.1.994.3.4.7.30.1.11 |
If set to true, an email will be sent on a change of state.
If false, no email will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedDiscreteSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.30.1.12 |
If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedDiscreteTL1Env |
1.3.6.1.4.1.994.3.4.7.30.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedDiscreteTL1Srveff |
1.3.6.1.4.1.994.3.4.7.30.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pderivedDiscreteTL1Locn |
1.3.6.1.4.1.994.3.4.7.30.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pderivedDiscreteTL1Dirn |
1.3.6.1.4.1.994.3.4.7.30.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
license |
1.3.6.1.4.1.994.3.4.7.31 |
OBJECT IDENTIFIER |
|
|
|
licenseExpires |
1.3.6.1.4.1.994.3.4.7.31.85 |
This is the date the current License will expire. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
licenseAllowTL1 |
1.3.6.1.4.1.994.3.4.7.31.124 |
This describes the status of TL1 support in the license |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pe2aHostTable |
1.3.6.1.4.1.994.3.4.7.32 |
Table for configuration of e2aHost |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
Pe2aHostEntry |
|
pe2aHostEntry |
1.3.6.1.4.1.994.3.4.7.32.1 |
Entry for configuration table of e2aHost |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Pe2aHostEntry |
|
|
pe2aHostIpAddress |
1.3.6.1.4.1.994.3.4.7.32.1.14 |
The IP address of the remote device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pe2aHostLevel0 |
1.3.6.1.4.1.994.3.4.7.32.1.17 |
Alarm level associated with the online state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pe2aHostLevel1 |
1.3.6.1.4.1.994.3.4.7.32.1.18 |
Alarm level associated with the offline state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pe2aHostLevel2 |
1.3.6.1.4.1.994.3.4.7.32.1.19 |
Alarm level associated with the connecting state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pe2aHostRosterID |
1.3.6.1.4.1.994.3.4.7.32.1.37 |
Serial port number to use when connecting to WebMon. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pe2aHostPollAddress |
1.3.6.1.4.1.994.3.4.7.32.1.56 |
The E2A address of the remote device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pe2aHostIPPortNum |
1.3.6.1.4.1.994.3.4.7.32.1.73 |
IP port number to use when connecting to the remote device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pe2aHostTL1Env |
1.3.6.1.4.1.994.3.4.7.32.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pe2aHostTL1Srveff |
1.3.6.1.4.1.994.3.4.7.32.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pe2aHostTL1Locn |
1.3.6.1.4.1.994.3.4.7.32.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pe2aHostTL1Dirn |
1.3.6.1.4.1.994.3.4.7.32.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pe2aHostIndex |
1.3.6.1.4.1.994.3.4.7.32.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..256 |
|
pderivedAnalogEntry |
1.3.6.1.4.1.994.3.4.7.33.1 |
Entry for configuration table of derivedAnalog |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PderivedAnalogEntry |
|
|
pderivedAnalogDesc0 |
1.3.6.1.4.1.994.3.4.7.33.1.4 |
The description for derived values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogDesc1 |
1.3.6.1.4.1.994.3.4.7.33.1.5 |
The description for derived values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogDesc2 |
1.3.6.1.4.1.994.3.4.7.33.1.6 |
The description for derived values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogDesc3 |
1.3.6.1.4.1.994.3.4.7.33.1.7 |
The description for derived values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogDesc4 |
1.3.6.1.4.1.994.3.4.7.33.1.8 |
The description for derived values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogSendEmail |
1.3.6.1.4.1.994.3.4.7.33.1.11 |
If set to true, an email will be sent on a change of state.
If false, no email will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedAnalogSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.33.1.12 |
If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedAnalogLevel0 |
1.3.6.1.4.1.994.3.4.7.33.1.17 |
The level for derived values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pderivedAnalogLevel1 |
1.3.6.1.4.1.994.3.4.7.33.1.18 |
The level for derived values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pderivedAnalogLevel2 |
1.3.6.1.4.1.994.3.4.7.33.1.19 |
The level for derived values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pderivedAnalogLevel3 |
1.3.6.1.4.1.994.3.4.7.33.1.20 |
The level for derived values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pderivedAnalogLevel4 |
1.3.6.1.4.1.994.3.4.7.33.1.21 |
The level for derived values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pderivedAnalogLiveRaw |
1.3.6.1.4.1.994.3.4.7.33.1.66 |
The current derived reading from the analog devices. This value
will alwaysbe between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pderivedAnalogTL1Env |
1.3.6.1.4.1.994.3.4.7.33.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pderivedAnalogTL1Srveff |
1.3.6.1.4.1.994.3.4.7.33.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pderivedAnalogTL1Locn |
1.3.6.1.4.1.994.3.4.7.33.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pderivedAnalogTL1Dirn |
1.3.6.1.4.1.994.3.4.7.33.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pgpsTable |
1.3.6.1.4.1.994.3.4.7.34 |
Table for configuration of gps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PgpsEntry |
|
pgpsEntry |
1.3.6.1.4.1.994.3.4.7.34.1 |
Entry for configuration table of gps |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PgpsEntry |
|
|
pgpsDesc0 |
1.3.6.1.4.1.994.3.4.7.34.1.4 |
The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsDesc1 |
1.3.6.1.4.1.994.3.4.7.34.1.5 |
The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsDesc2 |
1.3.6.1.4.1.994.3.4.7.34.1.6 |
The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsDesc3 |
1.3.6.1.4.1.994.3.4.7.34.1.7 |
The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsDesc4 |
1.3.6.1.4.1.994.3.4.7.34.1.8 |
The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsSendEmail |
1.3.6.1.4.1.994.3.4.7.34.1.11 |
If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pgpsSendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.34.1.12 |
If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pgpsLevel0 |
1.3.6.1.4.1.994.3.4.7.34.1.17 |
The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pgpsLevel1 |
1.3.6.1.4.1.994.3.4.7.34.1.18 |
The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pgpsLevel2 |
1.3.6.1.4.1.994.3.4.7.34.1.19 |
The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pgpsLevel3 |
1.3.6.1.4.1.994.3.4.7.34.1.20 |
The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pgpsLevel4 |
1.3.6.1.4.1.994.3.4.7.34.1.21 |
The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pgpsThresh1 |
1.3.6.1.4.1.994.3.4.7.34.1.29 |
This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsThresh2 |
1.3.6.1.4.1.994.3.4.7.34.1.30 |
This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsThresh3 |
1.3.6.1.4.1.994.3.4.7.34.1.31 |
This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsThresh4 |
1.3.6.1.4.1.994.3.4.7.34.1.32 |
This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsThresh5 |
1.3.6.1.4.1.994.3.4.7.34.1.33 |
This is the maximum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsUnits |
1.3.6.1.4.1.994.3.4.7.34.1.46 |
Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsLiveLevel |
1.3.6.1.4.1.994.3.4.7.34.1.65 |
The level of the current state of the onboard sensor. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsLiveRaw |
1.3.6.1.4.1.994.3.4.7.34.1.66 |
The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsTL1SID |
1.3.6.1.4.1.994.3.4.7.34.1.116 |
(TL1) System ID associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsTL1COND |
1.3.6.1.4.1.994.3.4.7.34.1.117 |
(TL1) Condition text associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsTL1Eqpt |
1.3.6.1.4.1.994.3.4.7.34.1.118 |
(TL1) EQPT field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pgpsTL1Env |
1.3.6.1.4.1.994.3.4.7.34.1.119 |
(TL1) Environmental field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pgpsTL1Srveff |
1.3.6.1.4.1.994.3.4.7.34.1.120 |
(TL1) Service Effecting field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pgpsTL1Locn |
1.3.6.1.4.1.994.3.4.7.34.1.121 |
(TL1) Location field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pgpsTL1Dirn |
1.3.6.1.4.1.994.3.4.7.34.1.122 |
(TL1) Direction field associated with this item. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pgpsIndex |
1.3.6.1.4.1.994.3.4.7.34.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..3 |
|
pportRedirectEntry |
1.3.6.1.4.1.994.3.4.7.35.1 |
Entry for configuration table of portRedirect |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PportRedirectEntry |
|
|
pportRedirectRosterID |
1.3.6.1.4.1.994.3.4.7.35.1.37 |
IP port number to use when connecting to the remote device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pportRedirectIPPortNum |
1.3.6.1.4.1.994.3.4.7.35.1.73 |
IP port number to use when connecting to WebMon. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pscheduleATable |
1.3.6.1.4.1.994.3.4.7.36 |
Table for configuration of scheduleA |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PscheduleAEntry |
|
pscheduleAEntry |
1.3.6.1.4.1.994.3.4.7.36.1 |
Entry for configuration table of scheduleA |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PscheduleAEntry |
|
|
pscheduleBTable |
1.3.6.1.4.1.994.3.4.7.37 |
Table for configuration of scheduleB |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PscheduleBEntry |
|
pscheduleBEntry |
1.3.6.1.4.1.994.3.4.7.37.1 |
Entry for configuration table of scheduleB |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PscheduleBEntry |
|
|
pscheduleCTable |
1.3.6.1.4.1.994.3.4.7.38 |
Table for configuration of scheduleC |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PscheduleCEntry |
|
pscheduleCEntry |
1.3.6.1.4.1.994.3.4.7.38.1 |
Entry for configuration table of scheduleC |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PscheduleCEntry |
|
|
pscheduleDTable |
1.3.6.1.4.1.994.3.4.7.39 |
Table for configuration of scheduleD |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PscheduleDEntry |
|
pscheduleDEntry |
1.3.6.1.4.1.994.3.4.7.39.1 |
Entry for configuration table of scheduleD |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PscheduleDEntry |
|
|
tl1SettingsTL1Issue |
1.3.6.1.4.1.994.3.4.7.40.123 |
(TL1) TL1 issue associated with this device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Issue |
|
|
pDCPFProtocolEntry |
1.3.6.1.4.1.994.3.4.7.41.1 |
Entry for configuration table of DCPFProtocol |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PDCPFProtocolEntry |
|
|
pTABSProtocolEntry |
1.3.6.1.4.1.994.3.4.7.43.1 |
Entry for configuration table of TABSProtocol |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PTABSProtocolEntry |
|
|
psnmpCommandsEntry |
1.3.6.1.4.1.994.3.4.7.45.1 |
Entry for configuration table of snmpCommands |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PsnmpCommandsEntry |
|
|
psnmpCommandsIpAddress |
1.3.6.1.4.1.994.3.4.7.45.1.14 |
Target (receiver) IP address of this SNMP command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
psnmpCommandsIPPortNum |
1.3.6.1.4.1.994.3.4.7.45.1.73 |
Target (receiver) IP port of this SNMP command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
psnmpCommandsTextNormal |
1.3.6.1.4.1.994.3.4.7.45.1.135 |
Value sent to target for normal condition for a set command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
psnmpCommandsTextCritical |
1.3.6.1.4.1.994.3.4.7.45.1.136 |
Value sent to target for critical condition for a set command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
psnmpCommandsTextMajor |
1.3.6.1.4.1.994.3.4.7.45.1.137 |
Value sent to target for major condition for a set command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
psnmpCommandsTextMinor |
1.3.6.1.4.1.994.3.4.7.45.1.138 |
Value sent to target for minor condition for a set command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
psnmpCommandsTextStatus |
1.3.6.1.4.1.994.3.4.7.45.1.139 |
Value sent to target for status condition for a set command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
battMon |
1.3.6.1.4.1.994.3.4.7.46 |
OBJECT IDENTIFIER |
|
|
|
battMonOutputAuto |
1.3.6.1.4.1.994.3.4.7.46.49 |
Source alarm point for this SNMP command. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
battMonOutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.46.71 |
Package where the source alarm point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pBankInfoTable |
1.3.6.1.4.1.994.3.4.7.47 |
Table for configuration of BankInfo |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PBankInfoEntry |
|
pBankInfoEntry |
1.3.6.1.4.1.994.3.4.7.47.1 |
Entry for configuration table of BankInfo |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PBankInfoEntry |
|
|
pBankInfoPresent |
1.3.6.1.4.1.994.3.4.7.47.1.68 |
If true indicates the bank is connected to the WebMon.
If false indicates that the bank is not connected. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pBankInfoSlotId |
1.3.6.1.4.1.994.3.4.7.47.1.69 |
Identifies the type of card in slot. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SlotId |
|
|
pSlot1Table |
1.3.6.1.4.1.994.3.4.7.18 |
Table for configuration of Slot1 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot1Entry |
|
pSlot1Entry |
1.3.6.1.4.1.994.3.4.7.18.1 |
Entry for configuration table of Slot1 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot1Entry |
|
|
pSlot1Description |
1.3.6.1.4.1.994.3.4.7.18.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc0 |
1.3.6.1.4.1.994.3.4.7.18.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc1 |
1.3.6.1.4.1.994.3.4.7.18.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc2 |
1.3.6.1.4.1.994.3.4.7.18.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc3 |
1.3.6.1.4.1.994.3.4.7.18.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc4 |
1.3.6.1.4.1.994.3.4.7.18.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Desc5 |
1.3.6.1.4.1.994.3.4.7.18.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1SendEmail |
1.3.6.1.4.1.994.3.4.7.18.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot1SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.18.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot1IpAddress |
1.3.6.1.4.1.994.3.4.7.18.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot1Level0 |
1.3.6.1.4.1.994.3.4.7.18.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1Level1 |
1.3.6.1.4.1.994.3.4.7.18.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1Level2 |
1.3.6.1.4.1.994.3.4.7.18.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1Level3 |
1.3.6.1.4.1.994.3.4.7.18.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1Level4 |
1.3.6.1.4.1.994.3.4.7.18.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1Level5 |
1.3.6.1.4.1.994.3.4.7.18.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot1ReadPeriod |
1.3.6.1.4.1.994.3.4.7.18.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot1Thresh0 |
1.3.6.1.4.1.994.3.4.7.18.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Thresh1 |
1.3.6.1.4.1.994.3.4.7.18.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Thresh2 |
1.3.6.1.4.1.994.3.4.7.18.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Thresh3 |
1.3.6.1.4.1.994.3.4.7.18.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Thresh4 |
1.3.6.1.4.1.994.3.4.7.18.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Thresh5 |
1.3.6.1.4.1.994.3.4.7.18.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Units |
1.3.6.1.4.1.994.3.4.7.18.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1OutputMode |
1.3.6.1.4.1.994.3.4.7.18.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot1OutputState |
1.3.6.1.4.1.994.3.4.7.18.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot1OutputAuto |
1.3.6.1.4.1.994.3.4.7.18.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot1BaudRate |
1.3.6.1.4.1.994.3.4.7.18.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot1DataBits |
1.3.6.1.4.1.994.3.4.7.18.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot1Parity |
1.3.6.1.4.1.994.3.4.7.18.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot1StopBits |
1.3.6.1.4.1.994.3.4.7.18.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot1Protocol |
1.3.6.1.4.1.994.3.4.7.18.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot1SerialRTS |
1.3.6.1.4.1.994.3.4.7.18.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot1SerialCTS |
1.3.6.1.4.1.994.3.4.7.18.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot1LiveDescription |
1.3.6.1.4.1.994.3.4.7.18.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1LiveLevel |
1.3.6.1.4.1.994.3.4.7.18.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1LiveRaw |
1.3.6.1.4.1.994.3.4.7.18.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1LiveTime |
1.3.6.1.4.1.994.3.4.7.18.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1Present |
1.3.6.1.4.1.994.3.4.7.18.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot1OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.18.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot1VoltageRange |
1.3.6.1.4.1.994.3.4.7.18.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot1IPPortNum |
1.3.6.1.4.1.994.3.4.7.18.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot1PortType |
1.3.6.1.4.1.994.3.4.7.18.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot1TL1SID |
1.3.6.1.4.1.994.3.4.7.18.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1TL1COND |
1.3.6.1.4.1.994.3.4.7.18.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.18.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot1TL1Env |
1.3.6.1.4.1.994.3.4.7.18.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot1TL1Srveff |
1.3.6.1.4.1.994.3.4.7.18.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot1TL1Locn |
1.3.6.1.4.1.994.3.4.7.18.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot1TL1Dirn |
1.3.6.1.4.1.994.3.4.7.18.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot1SensorType |
1.3.6.1.4.1.994.3.4.7.18.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot1Index |
1.3.6.1.4.1.994.3.4.7.18.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
pSlot2Table |
1.3.6.1.4.1.994.3.4.7.19 |
Table for configuration of Slot2 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot2Entry |
|
pSlot2Entry |
1.3.6.1.4.1.994.3.4.7.19.1 |
Entry for configuration table of Slot2 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot2Entry |
|
|
pSlot2Description |
1.3.6.1.4.1.994.3.4.7.19.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc0 |
1.3.6.1.4.1.994.3.4.7.19.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc1 |
1.3.6.1.4.1.994.3.4.7.19.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc2 |
1.3.6.1.4.1.994.3.4.7.19.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc3 |
1.3.6.1.4.1.994.3.4.7.19.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc4 |
1.3.6.1.4.1.994.3.4.7.19.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Desc5 |
1.3.6.1.4.1.994.3.4.7.19.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2SendEmail |
1.3.6.1.4.1.994.3.4.7.19.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot2SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.19.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot2IpAddress |
1.3.6.1.4.1.994.3.4.7.19.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot2Level0 |
1.3.6.1.4.1.994.3.4.7.19.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2Level1 |
1.3.6.1.4.1.994.3.4.7.19.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2Level2 |
1.3.6.1.4.1.994.3.4.7.19.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2Level3 |
1.3.6.1.4.1.994.3.4.7.19.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2Level4 |
1.3.6.1.4.1.994.3.4.7.19.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2Level5 |
1.3.6.1.4.1.994.3.4.7.19.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot2ReadPeriod |
1.3.6.1.4.1.994.3.4.7.19.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot2Thresh0 |
1.3.6.1.4.1.994.3.4.7.19.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Thresh1 |
1.3.6.1.4.1.994.3.4.7.19.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Thresh2 |
1.3.6.1.4.1.994.3.4.7.19.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Thresh3 |
1.3.6.1.4.1.994.3.4.7.19.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Thresh4 |
1.3.6.1.4.1.994.3.4.7.19.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Thresh5 |
1.3.6.1.4.1.994.3.4.7.19.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Units |
1.3.6.1.4.1.994.3.4.7.19.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2OutputMode |
1.3.6.1.4.1.994.3.4.7.19.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot2OutputState |
1.3.6.1.4.1.994.3.4.7.19.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot2OutputAuto |
1.3.6.1.4.1.994.3.4.7.19.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot2BaudRate |
1.3.6.1.4.1.994.3.4.7.19.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot2DataBits |
1.3.6.1.4.1.994.3.4.7.19.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot2Parity |
1.3.6.1.4.1.994.3.4.7.19.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot2StopBits |
1.3.6.1.4.1.994.3.4.7.19.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot2Protocol |
1.3.6.1.4.1.994.3.4.7.19.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot2SerialRTS |
1.3.6.1.4.1.994.3.4.7.19.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot2SerialCTS |
1.3.6.1.4.1.994.3.4.7.19.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot2LiveDescription |
1.3.6.1.4.1.994.3.4.7.19.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2LiveLevel |
1.3.6.1.4.1.994.3.4.7.19.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2LiveRaw |
1.3.6.1.4.1.994.3.4.7.19.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2LiveTime |
1.3.6.1.4.1.994.3.4.7.19.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2Present |
1.3.6.1.4.1.994.3.4.7.19.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot2OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.19.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot2VoltageRange |
1.3.6.1.4.1.994.3.4.7.19.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot2IPPortNum |
1.3.6.1.4.1.994.3.4.7.19.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot2PortType |
1.3.6.1.4.1.994.3.4.7.19.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot2TL1SID |
1.3.6.1.4.1.994.3.4.7.19.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2TL1COND |
1.3.6.1.4.1.994.3.4.7.19.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.19.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot2TL1Env |
1.3.6.1.4.1.994.3.4.7.19.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot2TL1Srveff |
1.3.6.1.4.1.994.3.4.7.19.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot2TL1Locn |
1.3.6.1.4.1.994.3.4.7.19.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot2TL1Dirn |
1.3.6.1.4.1.994.3.4.7.19.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot2SensorType |
1.3.6.1.4.1.994.3.4.7.19.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot2Index |
1.3.6.1.4.1.994.3.4.7.19.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
pSlot3Table |
1.3.6.1.4.1.994.3.4.7.20 |
Table for configuration of Slot3 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot3Entry |
|
pSlot3Entry |
1.3.6.1.4.1.994.3.4.7.20.1 |
Entry for configuration table of Slot3 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot3Entry |
|
|
pSlot3Description |
1.3.6.1.4.1.994.3.4.7.20.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc0 |
1.3.6.1.4.1.994.3.4.7.20.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc1 |
1.3.6.1.4.1.994.3.4.7.20.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc2 |
1.3.6.1.4.1.994.3.4.7.20.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc3 |
1.3.6.1.4.1.994.3.4.7.20.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc4 |
1.3.6.1.4.1.994.3.4.7.20.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Desc5 |
1.3.6.1.4.1.994.3.4.7.20.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3SendEmail |
1.3.6.1.4.1.994.3.4.7.20.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot3SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.20.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot3IpAddress |
1.3.6.1.4.1.994.3.4.7.20.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot3Level0 |
1.3.6.1.4.1.994.3.4.7.20.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3Level1 |
1.3.6.1.4.1.994.3.4.7.20.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3Level2 |
1.3.6.1.4.1.994.3.4.7.20.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3Level3 |
1.3.6.1.4.1.994.3.4.7.20.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3Level4 |
1.3.6.1.4.1.994.3.4.7.20.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3Level5 |
1.3.6.1.4.1.994.3.4.7.20.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot3ReadPeriod |
1.3.6.1.4.1.994.3.4.7.20.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot3Thresh0 |
1.3.6.1.4.1.994.3.4.7.20.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Thresh1 |
1.3.6.1.4.1.994.3.4.7.20.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Thresh2 |
1.3.6.1.4.1.994.3.4.7.20.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Thresh3 |
1.3.6.1.4.1.994.3.4.7.20.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Thresh4 |
1.3.6.1.4.1.994.3.4.7.20.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Thresh5 |
1.3.6.1.4.1.994.3.4.7.20.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Units |
1.3.6.1.4.1.994.3.4.7.20.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3OutputMode |
1.3.6.1.4.1.994.3.4.7.20.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot3OutputState |
1.3.6.1.4.1.994.3.4.7.20.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot3OutputAuto |
1.3.6.1.4.1.994.3.4.7.20.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot3BaudRate |
1.3.6.1.4.1.994.3.4.7.20.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot3DataBits |
1.3.6.1.4.1.994.3.4.7.20.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot3Parity |
1.3.6.1.4.1.994.3.4.7.20.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot3StopBits |
1.3.6.1.4.1.994.3.4.7.20.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot3Protocol |
1.3.6.1.4.1.994.3.4.7.20.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot3SerialRTS |
1.3.6.1.4.1.994.3.4.7.20.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot3SerialCTS |
1.3.6.1.4.1.994.3.4.7.20.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot3LiveDescription |
1.3.6.1.4.1.994.3.4.7.20.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3LiveLevel |
1.3.6.1.4.1.994.3.4.7.20.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3LiveRaw |
1.3.6.1.4.1.994.3.4.7.20.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3LiveTime |
1.3.6.1.4.1.994.3.4.7.20.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3Present |
1.3.6.1.4.1.994.3.4.7.20.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot3OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.20.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot3VoltageRange |
1.3.6.1.4.1.994.3.4.7.20.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot3IPPortNum |
1.3.6.1.4.1.994.3.4.7.20.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot3PortType |
1.3.6.1.4.1.994.3.4.7.20.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot3TL1SID |
1.3.6.1.4.1.994.3.4.7.20.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3TL1COND |
1.3.6.1.4.1.994.3.4.7.20.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.20.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot3TL1Env |
1.3.6.1.4.1.994.3.4.7.20.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot3TL1Srveff |
1.3.6.1.4.1.994.3.4.7.20.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot3TL1Locn |
1.3.6.1.4.1.994.3.4.7.20.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot3TL1Dirn |
1.3.6.1.4.1.994.3.4.7.20.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot3SensorType |
1.3.6.1.4.1.994.3.4.7.20.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot3Index |
1.3.6.1.4.1.994.3.4.7.20.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
pSlot4Table |
1.3.6.1.4.1.994.3.4.7.21 |
Table for configuration of Slot4 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot4Entry |
|
pSlot4Entry |
1.3.6.1.4.1.994.3.4.7.21.1 |
Entry for configuration table of Slot4 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot4Entry |
|
|
pSlot4Description |
1.3.6.1.4.1.994.3.4.7.21.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc0 |
1.3.6.1.4.1.994.3.4.7.21.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc1 |
1.3.6.1.4.1.994.3.4.7.21.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc2 |
1.3.6.1.4.1.994.3.4.7.21.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc3 |
1.3.6.1.4.1.994.3.4.7.21.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc4 |
1.3.6.1.4.1.994.3.4.7.21.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Desc5 |
1.3.6.1.4.1.994.3.4.7.21.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4SendEmail |
1.3.6.1.4.1.994.3.4.7.21.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot4SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.21.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot4IpAddress |
1.3.6.1.4.1.994.3.4.7.21.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot4Level0 |
1.3.6.1.4.1.994.3.4.7.21.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4Level1 |
1.3.6.1.4.1.994.3.4.7.21.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4Level2 |
1.3.6.1.4.1.994.3.4.7.21.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4Level3 |
1.3.6.1.4.1.994.3.4.7.21.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4Level4 |
1.3.6.1.4.1.994.3.4.7.21.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4Level5 |
1.3.6.1.4.1.994.3.4.7.21.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot4ReadPeriod |
1.3.6.1.4.1.994.3.4.7.21.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot4Thresh0 |
1.3.6.1.4.1.994.3.4.7.21.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Thresh1 |
1.3.6.1.4.1.994.3.4.7.21.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Thresh2 |
1.3.6.1.4.1.994.3.4.7.21.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Thresh3 |
1.3.6.1.4.1.994.3.4.7.21.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Thresh4 |
1.3.6.1.4.1.994.3.4.7.21.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Thresh5 |
1.3.6.1.4.1.994.3.4.7.21.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Units |
1.3.6.1.4.1.994.3.4.7.21.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4OutputMode |
1.3.6.1.4.1.994.3.4.7.21.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot4OutputState |
1.3.6.1.4.1.994.3.4.7.21.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot4OutputAuto |
1.3.6.1.4.1.994.3.4.7.21.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot4BaudRate |
1.3.6.1.4.1.994.3.4.7.21.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot4DataBits |
1.3.6.1.4.1.994.3.4.7.21.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot4Parity |
1.3.6.1.4.1.994.3.4.7.21.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot4StopBits |
1.3.6.1.4.1.994.3.4.7.21.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot4Protocol |
1.3.6.1.4.1.994.3.4.7.21.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot4SerialRTS |
1.3.6.1.4.1.994.3.4.7.21.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot4SerialCTS |
1.3.6.1.4.1.994.3.4.7.21.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot4LiveDescription |
1.3.6.1.4.1.994.3.4.7.21.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4LiveLevel |
1.3.6.1.4.1.994.3.4.7.21.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4LiveRaw |
1.3.6.1.4.1.994.3.4.7.21.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4LiveTime |
1.3.6.1.4.1.994.3.4.7.21.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4Present |
1.3.6.1.4.1.994.3.4.7.21.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot4OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.21.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot4VoltageRange |
1.3.6.1.4.1.994.3.4.7.21.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot4IPPortNum |
1.3.6.1.4.1.994.3.4.7.21.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot4PortType |
1.3.6.1.4.1.994.3.4.7.21.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot4TL1SID |
1.3.6.1.4.1.994.3.4.7.21.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4TL1COND |
1.3.6.1.4.1.994.3.4.7.21.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.21.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot4TL1Env |
1.3.6.1.4.1.994.3.4.7.21.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot4TL1Srveff |
1.3.6.1.4.1.994.3.4.7.21.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot4TL1Locn |
1.3.6.1.4.1.994.3.4.7.21.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot4TL1Dirn |
1.3.6.1.4.1.994.3.4.7.21.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot4SensorType |
1.3.6.1.4.1.994.3.4.7.21.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot4Index |
1.3.6.1.4.1.994.3.4.7.21.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
pSlot5Table |
1.3.6.1.4.1.994.3.4.7.22 |
Table for configuration of Slot5 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot5Entry |
|
pSlot5Entry |
1.3.6.1.4.1.994.3.4.7.22.1 |
Entry for configuration table of Slot5 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot5Entry |
|
|
pSlot5Description |
1.3.6.1.4.1.994.3.4.7.22.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc0 |
1.3.6.1.4.1.994.3.4.7.22.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc1 |
1.3.6.1.4.1.994.3.4.7.22.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc2 |
1.3.6.1.4.1.994.3.4.7.22.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc3 |
1.3.6.1.4.1.994.3.4.7.22.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc4 |
1.3.6.1.4.1.994.3.4.7.22.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Desc5 |
1.3.6.1.4.1.994.3.4.7.22.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5SendEmail |
1.3.6.1.4.1.994.3.4.7.22.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot5SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.22.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot5IpAddress |
1.3.6.1.4.1.994.3.4.7.22.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot5Level0 |
1.3.6.1.4.1.994.3.4.7.22.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5Level1 |
1.3.6.1.4.1.994.3.4.7.22.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5Level2 |
1.3.6.1.4.1.994.3.4.7.22.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5Level3 |
1.3.6.1.4.1.994.3.4.7.22.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5Level4 |
1.3.6.1.4.1.994.3.4.7.22.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5Level5 |
1.3.6.1.4.1.994.3.4.7.22.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot5ReadPeriod |
1.3.6.1.4.1.994.3.4.7.22.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot5Thresh0 |
1.3.6.1.4.1.994.3.4.7.22.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Thresh1 |
1.3.6.1.4.1.994.3.4.7.22.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Thresh2 |
1.3.6.1.4.1.994.3.4.7.22.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Thresh3 |
1.3.6.1.4.1.994.3.4.7.22.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Thresh4 |
1.3.6.1.4.1.994.3.4.7.22.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Thresh5 |
1.3.6.1.4.1.994.3.4.7.22.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Units |
1.3.6.1.4.1.994.3.4.7.22.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5OutputMode |
1.3.6.1.4.1.994.3.4.7.22.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot5OutputState |
1.3.6.1.4.1.994.3.4.7.22.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot5OutputAuto |
1.3.6.1.4.1.994.3.4.7.22.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot5BaudRate |
1.3.6.1.4.1.994.3.4.7.22.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot5DataBits |
1.3.6.1.4.1.994.3.4.7.22.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot5Parity |
1.3.6.1.4.1.994.3.4.7.22.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot5StopBits |
1.3.6.1.4.1.994.3.4.7.22.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot5Protocol |
1.3.6.1.4.1.994.3.4.7.22.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot5SerialRTS |
1.3.6.1.4.1.994.3.4.7.22.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot5SerialCTS |
1.3.6.1.4.1.994.3.4.7.22.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot5LiveDescription |
1.3.6.1.4.1.994.3.4.7.22.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5LiveLevel |
1.3.6.1.4.1.994.3.4.7.22.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5LiveRaw |
1.3.6.1.4.1.994.3.4.7.22.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5LiveTime |
1.3.6.1.4.1.994.3.4.7.22.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5Present |
1.3.6.1.4.1.994.3.4.7.22.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot5OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.22.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot5VoltageRange |
1.3.6.1.4.1.994.3.4.7.22.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot5IPPortNum |
1.3.6.1.4.1.994.3.4.7.22.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot5PortType |
1.3.6.1.4.1.994.3.4.7.22.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot5TL1SID |
1.3.6.1.4.1.994.3.4.7.22.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5TL1COND |
1.3.6.1.4.1.994.3.4.7.22.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.22.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot5TL1Env |
1.3.6.1.4.1.994.3.4.7.22.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot5TL1Srveff |
1.3.6.1.4.1.994.3.4.7.22.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot5TL1Locn |
1.3.6.1.4.1.994.3.4.7.22.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot5TL1Dirn |
1.3.6.1.4.1.994.3.4.7.22.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot5SensorType |
1.3.6.1.4.1.994.3.4.7.22.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot5Index |
1.3.6.1.4.1.994.3.4.7.22.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
pSlot6Table |
1.3.6.1.4.1.994.3.4.7.23 |
Table for configuration of Slot6 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
PSlot6Entry |
|
pSlot6Entry |
1.3.6.1.4.1.994.3.4.7.23.1 |
Entry for configuration table of Slot6 |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
PSlot6Entry |
|
|
pSlot6Description |
1.3.6.1.4.1.994.3.4.7.23.1.3 |
This field is used in the following card types:
discrete-inputs - Description of the alarm point.
discrete-outputs - Description of the control point.
serial-ports - Description of the serial port.
onboard-sensors - Description of the onboard device.
analog-Inputs - Description of the analog input device.
analog-Sensors - Description of the sensor input device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc0 |
1.3.6.1.4.1.994.3.4.7.23.1.4 |
This field is used in the following card types:
discrete-inputs - Description of the off state.
discrete-outputs - Description when the control point is open.
onboard-sensors - The description for values between threshold 0 and threshold 1.
analog-Inputs - The description for values between threshold 0 and threshold 1.
analog-Sensors - The description for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc1 |
1.3.6.1.4.1.994.3.4.7.23.1.5 |
This field is used in the following card types:
discrete-inputs - Description of the on state.
discrete-outputs - Description when the control point is closed.
onboard-sensors - The description for values between threshold 1 and threshold 2.
analog-Inputs - The description for values between threshold 1 and threshold 2.
analog-Sensors - The description for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc2 |
1.3.6.1.4.1.994.3.4.7.23.1.6 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 2 and threshold 3.
analog-Inputs - The description for values between threshold 2 and threshold 3.
analog-Sensors - The description for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc3 |
1.3.6.1.4.1.994.3.4.7.23.1.7 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 3 and threshold 4.
analog-Inputs - The description for values between threshold 3 and threshold 4.
analog-Sensors - The description for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc4 |
1.3.6.1.4.1.994.3.4.7.23.1.8 |
This field is used in the following card types:
onboard-sensors - The description for values between threshold 4 and threshold 5.
analog-Inputs - The description for values between threshold 4 and threshold 5.
analog-Sensors - The description for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Desc5 |
1.3.6.1.4.1.994.3.4.7.23.1.9 |
This field is used in the following card types:
analog-Inputs - Description for a communications failure to the sensor.
analog-Sensors - Description for a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6SendEmail |
1.3.6.1.4.1.994.3.4.7.23.1.11 |
This field is used in the following card types:
discrete-inputs - If set to true, an email will be sent on a change of state.
If false, no email will be sent.
onboard-sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Inputs - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent.
analog-Sensors - If set to true an email event will be set when a threshold is crossed.
If set to false no email event will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot6SendSNMPTrap |
1.3.6.1.4.1.994.3.4.7.23.1.12 |
This field is used in the following card types:
discrete-inputs - If set to true, an SNMP trap will be sent on a change of state.
If false, no SNMP trap will be sent.
onboard-sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Inputs - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent.
analog-Sensors - If set to true an SNMP trap will be set when a threshold is crossed.
If set to false no SNMP trap will be sent. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot6IpAddress |
1.3.6.1.4.1.994.3.4.7.23.1.14 |
This field is used in the following card types:
serial-ports - IP Address of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
pSlot6Level0 |
1.3.6.1.4.1.994.3.4.7.23.1.17 |
This field is used in the following card types:
discrete-inputs - Level of the off state.
discrete-outputs - Level of the control point when open.
onboard-sensors - The level for values between threshold 0 and threshold 1.
analog-Inputs - The level for values between threshold 0 and threshold 1.
analog-Sensors - The level for values between threshold 0 and threshold 1. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6Level1 |
1.3.6.1.4.1.994.3.4.7.23.1.18 |
This field is used in the following card types:
discrete-inputs - Level of the on state.
discrete-outputs - Level of the control point when closed.
onboard-sensors - The level for values between threshold 1 and threshold 2.
analog-Inputs - The level for values between threshold 1 and threshold 2.
analog-Sensors - The level for values between threshold 1 and threshold 2. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6Level2 |
1.3.6.1.4.1.994.3.4.7.23.1.19 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 2 and threshold 3.
analog-Inputs - The level for values between threshold 2 and threshold 3.
analog-Sensors - The level for values between threshold 2 and threshold 3. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6Level3 |
1.3.6.1.4.1.994.3.4.7.23.1.20 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 3 and threshold 4.
analog-Inputs - The level for values between threshold 3 and threshold 4.
analog-Sensors - The level for values between threshold 3 and threshold 4. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6Level4 |
1.3.6.1.4.1.994.3.4.7.23.1.21 |
This field is used in the following card types:
onboard-sensors - The level for values between threshold 4 and threshold 5.
analog-Inputs - The level for values between threshold 4 and threshold 5.
analog-Sensors - The level for values between threshold 4 and threshold 5. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6Level5 |
1.3.6.1.4.1.994.3.4.7.23.1.22 |
This field is used in the following card types:
analog-Inputs - Level of a communications failure to the sensor.
analog-Sensors - Level of a communications failure to the sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
pSlot6ReadPeriod |
1.3.6.1.4.1.994.3.4.7.23.1.23 |
This field is used in the following card types:
serial-ports - Inactivity timeout (in minutes). |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot6Thresh0 |
1.3.6.1.4.1.994.3.4.7.23.1.28 |
This field is used in the following card types:
onboard-sensors - This is the minimun analog value.
analog-Inputs - This is the maximum analog value.
analog-Sensors - This is the maximum analog value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Thresh1 |
1.3.6.1.4.1.994.3.4.7.23.1.29 |
This field is used in the following card types:
onboard-sensors - This is the first threshold value.
analog-Inputs - This is the first threshold value.
analog-Sensors - This is the first threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Thresh2 |
1.3.6.1.4.1.994.3.4.7.23.1.30 |
This field is used in the following card types:
onboard-sensors - This is the second threshold value.
analog-Inputs - This is the second threshold value.
analog-Sensors - This is the second threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Thresh3 |
1.3.6.1.4.1.994.3.4.7.23.1.31 |
This field is used in the following card types:
onboard-sensors - This is the third threshold value.
analog-Inputs - This is the third threshold value.
analog-Sensors - This is the third threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Thresh4 |
1.3.6.1.4.1.994.3.4.7.23.1.32 |
This field is used in the following card types:
onboard-sensors - This is the fourth threshold value.
analog-Inputs - This is the fourth threshold value.
analog-Sensors - This is the fourth threshold value. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Thresh5 |
1.3.6.1.4.1.994.3.4.7.23.1.33 |
This field is used in the following card types:
onboard-sensors - This is the maximum threshold value.
analog-Inputs - This is the minimum threshold value.
analog-Sensors - This is the minimum threshold value. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Units |
1.3.6.1.4.1.994.3.4.7.23.1.46 |
This field is used in the following card types:
onboard-sensors - Description of the units of measurement.
analog-Inputs - Description of the units of measurement.
analog-Sensors - Description of the units of measurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6OutputMode |
1.3.6.1.4.1.994.3.4.7.23.1.47 |
This field is used in the following card types:
discrete-outputs - Defines the different ways a control point can be activated. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputMode |
|
|
pSlot6OutputState |
1.3.6.1.4.1.994.3.4.7.23.1.48 |
This field is used in the following card types:
discrete-outputs - A value of 0 will open the control point.
A value of 1 will close the control point. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
OutputState |
|
|
pSlot6OutputAuto |
1.3.6.1.4.1.994.3.4.7.23.1.49 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this alarm point will change state
to the on state. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot6BaudRate |
1.3.6.1.4.1.994.3.4.7.23.1.57 |
This field is used in the following card types:
serial-ports - Baud rate of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
BaudRate |
|
|
pSlot6DataBits |
1.3.6.1.4.1.994.3.4.7.23.1.58 |
This field is used in the following card types:
serial-ports - Number of data bit for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DataBits |
|
|
pSlot6Parity |
1.3.6.1.4.1.994.3.4.7.23.1.59 |
This field is used in the following card types:
serial-ports - Parity of the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Parity |
|
|
pSlot6StopBits |
1.3.6.1.4.1.994.3.4.7.23.1.60 |
This field is used in the following card types:
serial-ports - Number of stop bits for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
StopBits |
|
|
pSlot6Protocol |
1.3.6.1.4.1.994.3.4.7.23.1.61 |
This field is used in the following card types:
serial-ports - Protocol the serial port is speaking. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Protocol |
|
|
pSlot6SerialRTS |
1.3.6.1.4.1.994.3.4.7.23.1.62 |
This field is used in the following card types:
serial-ports - Request To Send (RTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialRTS |
|
|
pSlot6SerialCTS |
1.3.6.1.4.1.994.3.4.7.23.1.63 |
This field is used in the following card types:
serial-ports - Clear To Send (CTS) setting for the serial port. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SerialCTS |
|
|
pSlot6LiveDescription |
1.3.6.1.4.1.994.3.4.7.23.1.64 |
This field is used in the following card types:
discrete-inputs - The current description of the alarm state.
onboard-sensors - The description of the current state of the onboard sensor
analog-Inputs - The description of the current state of the analog input.
analog-Sensors - The description of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6LiveLevel |
1.3.6.1.4.1.994.3.4.7.23.1.65 |
This field is used in the following card types:
discrete-inputs - The current level of the alarm.
onboard-sensors - The level of the current state of the onboard sensor.
analog-Inputs - The level of the current state of the analog input.
analog-Sensors - The level of the current state of the sensor input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6LiveRaw |
1.3.6.1.4.1.994.3.4.7.23.1.66 |
This field is used in the following card types:
onboard-sensors - The current reading from the onboard sensor. This value
will always be between the threshold 0 and threshold 5 values.
analog-Inputs - The current reading from the analog input. This value
will always be between the threshold 0 and threshold 5 values.
analog-Sensors - The current reading from the sensor input. This value
will always be between the threshold 0 and threshold 5 values. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6LiveTime |
1.3.6.1.4.1.994.3.4.7.23.1.67 |
This field is used in the following card types:
discrete-inputs - The time of the last change of state.
onboard-sensors - The time of the last event.
analog-Inputs - The time of the last event.
analog-Sensors - The time of the last event. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6Present |
1.3.6.1.4.1.994.3.4.7.23.1.68 |
This field is used in the following card types:
serial-ports - If set to true, the serial port exists.
If set to false the serial port does not exist. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot6OutputAutoPkg |
1.3.6.1.4.1.994.3.4.7.23.1.71 |
This field is used in the following card types:
discrete-outputs - When this control point is opened, this is the package that the alarm
point is located. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot6VoltageRange |
1.3.6.1.4.1.994.3.4.7.23.1.72 |
This field is used in the following card types:
onboard-sensors - The voltage range.
analog-Inputs - The voltage range.
analog-Sensors - The voltage range. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
VoltageRange |
|
|
pSlot6IPPortNum |
1.3.6.1.4.1.994.3.4.7.23.1.73 |
This field is used in the following card types:
serial-ports - IP port number of the target device. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
pSlot6PortType |
1.3.6.1.4.1.994.3.4.7.23.1.76 |
This field is used in the following card types:
serial-ports - The type of serial port. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
PortType |
|
|
pSlot6TL1SID |
1.3.6.1.4.1.994.3.4.7.23.1.116 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6TL1COND |
1.3.6.1.4.1.994.3.4.7.23.1.117 |
This field is used in the following card types:
discrete-inputs -
discrete-outputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6TL1Eqpt |
1.3.6.1.4.1.994.3.4.7.23.1.118 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
pSlot6TL1Env |
1.3.6.1.4.1.994.3.4.7.23.1.119 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
pSlot6TL1Srveff |
1.3.6.1.4.1.994.3.4.7.23.1.120 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Srveff |
|
|
pSlot6TL1Locn |
1.3.6.1.4.1.994.3.4.7.23.1.121 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Locn |
|
|
pSlot6TL1Dirn |
1.3.6.1.4.1.994.3.4.7.23.1.122 |
This field is used in the following card types:
discrete-inputs -
onboard-sensors -
analog-Inputs -
analog-Sensors - |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
TL1Dirn |
|
|
pSlot6SensorType |
1.3.6.1.4.1.994.3.4.7.23.1.131 |
This field is used in the following card types:
analog-Inputs - The type of sensor.
analog-Sensors - The type of sensor. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
SensorType |
|
|
pSlot6Index |
1.3.6.1.4.1.994.3.4.7.23.1.999 |
Index. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Integer32 |
1..32 |
|
configObjectGroup |
1.3.6.1.4.1.994.3.4.7.999 |
Description. |
Status: current |
Access: read-only |
OBJECT-GROUP |
|
|
|
notificationGroup |
1.3.6.1.4.1.994.3.4.4 |
Group containing all the notification types. |
Status: current |
Access: read-only |
NOTIFICATION-GROUP |
|
|
|
objectGroup |
1.3.6.1.4.1.994.3.4.5 |
Group containing all the objects. |
Status: current |
Access: read-only |
OBJECT-GROUP |
|
|
|
traps |
1.3.6.1.4.1.994.3.4.6 |
Category containing all the traps. Each trap has sibling data nodes
that contain the data associated with the most recently sent trap
of that particular type. A GET-REQUEST sent to the WebMon for those
data nodes will allow you to verify the data received in a recent
trap. |
Status: current |
Access: read-only |
OBJECT-IDENTITY |
|
|
|
analogEventTrap |
1.3.6.1.4.1.994.3.4.6.1.1 |
Notification sent upon an analog input reading crossing a
threshold. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
analogLiveLevel |
1.3.6.1.4.1.994.3.4.6.1.3 |
The level associated with the analogLiveReading for this input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
analogLiveReading |
1.3.6.1.4.1.994.3.4.6.1.5 |
The reading from the analog input described by
analogInputDescription at the time the trap was sent. It is in the
units described in analogUnitsOfMeasurement. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DescriptionString |
|
|
analogLiveState |
1.3.6.1.4.1.994.3.4.6.1.7 |
The state associated with analogLiveReading. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
AnalogState |
|
|
analogAlarmState |
1.3.6.1.4.1.994.3.4.6.1.9 |
If true this field indicates the alarmed state.
If false this field indicates the not alarmed state. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
analogSourceIndex |
1.3.6.1.4.1.994.3.4.6.1.102 |
Index of the event source. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|
digitalEventTrap |
1.3.6.1.4.1.994.3.4.6.2.1 |
Notification sent upon change of state on a digital input. |
Status: current |
Access: not-accessible |
NOTIFICATION-TYPE |
|
|
|
digitalLiveLevel |
1.3.6.1.4.1.994.3.4.6.2.3 |
The level associated with digitalLiveState for this input. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
digitalLiveState |
1.3.6.1.4.1.994.3.4.6.2.4 |
The state of the digital input described by digitalInputDescription
at the time the trap was sent. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DigitalState |
|
|
digitalAlarmState |
1.3.6.1.4.1.994.3.4.6.2.6 |
If true this field indicates the alarmed state.
If false this field indicates the not alarmed state. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
remoteDevices |
1.3.6.1.4.1.994.3.4.6.3 |
Subtree containing trap and associated data for monitored remote
devices.
Remote devices are monitored for network connectivity. The device's
live state is always either online or offline. Traps are sent on
events, which are defined as a change in the live state. |
Status: current |
Access: not-accessible |
OBJECT-IDENTITY |
|
|
|
remoteDeviceEventTrap |
1.3.6.1.4.1.994.3.4.6.3.1 |
Notification sent upon change of state of a remote device. |
Status: current |
Access: not-accessible |
NOTIFICATION-TYPE |
|
|
|
remoteDeviceLiveLevel |
1.3.6.1.4.1.994.3.4.6.3.3 |
The level associated with remoteDeviceLiveState. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
remoteDeviceLiveState |
1.3.6.1.4.1.994.3.4.6.3.4 |
The state of the remote device described by remoteDeviceDescription
at the time the trap was sent. Online indicates connected, offline
indicates not connected. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
ConnectivityState |
|
|
remoteDeviceAlarmState |
1.3.6.1.4.1.994.3.4.6.3.5 |
If true this field indicates the alarmed state.
If false this field indicates the not alarmed state. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
faults |
1.3.6.1.4.1.994.3.4.6.4 |
Subtree containing trap and associated data for faults.
Faults are conditions internal to the WebMon. The only data
associated with this trap is a string that describes the condition. |
Status: current |
Access: not-accessible |
OBJECT-IDENTITY |
|
|
|
faultTrap |
1.3.6.1.4.1.994.3.4.6.4.1 |
Notification sent when a fault is encountered. |
Status: current |
Access: not-accessible |
NOTIFICATION-TYPE |
|
|
|
faultLiveLevel |
1.3.6.1.4.1.994.3.4.6.4.3 |
The level associated with faultStateDescription. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Level |
|
|
faultAlarmState |
1.3.6.1.4.1.994.3.4.6.4.5 |
If true this field indicates the alarmed state.
If false this field indicates the not alarmed state. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Boolean |
|
|
faultSourceIndex |
1.3.6.1.4.1.994.3.4.6.4.102 |
Index of the event source. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
Integer32 |
|
|