CPQPOWER-MIB

File: CPQPOWER-MIB.mib (69254 bytes)

Imported modules

CPQHOST-MIB RFC1155-SMI RFC1213-MIB
RFC-1212 RFC-1215

Imported symbols

compaq TimeTicks Gauge
Counter DisplayString ifIndex
ifDescr sysName sysDescr
sysContact sysLocation OBJECT-TYPE
TRAP-TYPE

Defined Objects

cpqPower 1.3.6.1.4.1.232.165
OBJECT IDENTIFIER    

powerDevice 1.3.6.1.4.1.232.165.1
OBJECT IDENTIFIER    

trapCritical 1.3.6.1.4.1.232.165.1
A critical alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  trapCode  
  trapDescription  
  trapDeviceName  
  trapDeviceDetails  
  trapDeviceMgmtUrl  

trapInfo 1.3.6.1.4.1.232.165.1.1
OBJECT IDENTIFIER    

trapCode 1.3.6.1.4.1.232.165.1.1.1
A number identifying the event for the trap that was sent. Mapped unique trap code per unique event to be used by ISEE's decoder ring.
OBJECT-TYPE    
  INTEGER  

trapDescription 1.3.6.1.4.1.232.165.1.1.2
A string identifying the event for that last trap that was sent.
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

trapDeviceMgmtUrl 1.3.6.1.4.1.232.165.1.1.3
A string contains the URL for the management software.
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

trapDeviceDetails 1.3.6.1.4.1.232.165.1.1.4
A string details information about the device, including model, serial number, part number, etc....
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

trapDeviceName 1.3.6.1.4.1.232.165.1.1.5
A string contains the name of the device.
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

managementModuleIdent 1.3.6.1.4.1.232.165.1.2
OBJECT IDENTIFIER    

deviceManufacturer 1.3.6.1.4.1.232.165.1.2.1
The device manufacturer.
OBJECT-TYPE    
  DisplayString  

deviceModel 1.3.6.1.4.1.232.165.1.2.2
The device model.
OBJECT-TYPE    
  DisplayString  

deviceFirmwareVersion 1.3.6.1.4.1.232.165.1.2.3
The device firmware version(s).
OBJECT-TYPE    
  DisplayString  

deviceHardwareVersion 1.3.6.1.4.1.232.165.1.2.4
The device hardware version.
OBJECT-TYPE    
  DisplayString  

deviceIdentName 1.3.6.1.4.1.232.165.1.2.5
A string identifying the device.
OBJECT-TYPE    
  DisplayString  

devicePartNumber 1.3.6.1.4.1.232.165.1.2.6
The device part number.
OBJECT-TYPE    
  DisplayString  

deviceSerialNumber 1.3.6.1.4.1.232.165.1.2.7
The device serial number.
OBJECT-TYPE    
  DisplayString  

deviceMACAddress 1.3.6.1.4.1.232.165.1.2.8
The device MAC address.
OBJECT-TYPE    
  DisplayString  

pdu 1.3.6.1.4.1.232.165.2
OBJECT IDENTIFIER    

trapWarning 1.3.6.1.4.1.232.165.2
A warning alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  trapCode  
  trapDescription  
  trapDeviceName  
  trapDeviceDetails  
  trapDeviceMgmtUrl  

pduIdent 1.3.6.1.4.1.232.165.2.1
OBJECT IDENTIFIER    

numOfPdu 1.3.6.1.4.1.232.165.2.1.1
The number of PDUs.
OBJECT-TYPE    
  INTEGER 0..63  

pduIdentTable 1.3.6.1.4.1.232.165.2.1.2
The Aggregate Object with number of entries equal to NumOfPdu and including the PduIdent group.
OBJECT-TYPE    
  SEQUENCE OF  
    PduIdentEntry

pduIdentEntry 1.3.6.1.4.1.232.165.2.1.2.1
The ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
OBJECT-TYPE    
  PduIdentEntry  

pduIdentIndex 1.3.6.1.4.1.232.165.2.1.2.1.1
Index for the PduIdentEntry table.
OBJECT-TYPE    
  INTEGER  

pduName 1.3.6.1.4.1.232.165.2.1.2.1.2
The string identify the device.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduModel 1.3.6.1.4.1.232.165.2.1.2.1.3
The Device Model.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduManufacturer 1.3.6.1.4.1.232.165.2.1.2.1.4
The Device Manufacturer Name (e.g. Hewlett-Packard).
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduFirmwareVersion 1.3.6.1.4.1.232.165.2.1.2.1.5
The firmware revision level of the device.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduPartNumber 1.3.6.1.4.1.232.165.2.1.2.1.6
The device part number.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduSerialNumber 1.3.6.1.4.1.232.165.2.1.2.1.7
The deice serial number.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pduStatus 1.3.6.1.4.1.232.165.2.1.2.1.8
The overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the device is operating with critical indicators.
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4)  

pduControllable 1.3.6.1.4.1.232.165.2.1.2.1.9
This object indicates whether or not the device is controllable.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

pduInput 1.3.6.1.4.1.232.165.2.2
OBJECT IDENTIFIER    

pduInputTable 1.3.6.1.4.1.232.165.2.2.1
The Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
OBJECT-TYPE    
  SEQUENCE OF  
    PduInputEntry

pduInputEntry 1.3.6.1.4.1.232.165.2.2.1.1
The input table entry containing the voltage and current for the PDU
OBJECT-TYPE    
  PduInputEntry  

pduInputIndex 1.3.6.1.4.1.232.165.2.2.1.1.1
Index for the PduInputEntry table.
OBJECT-TYPE    
  INTEGER  

inputVoltage 1.3.6.1.4.1.232.165.2.2.1.1.2
The measured input voltage from the PDU meters in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

inputCurrent 1.3.6.1.4.1.232.165.2.2.1.1.3
The measured input current from the PDU meters in amps.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pduOutput 1.3.6.1.4.1.232.165.2.3
OBJECT IDENTIFIER    

pduOutputTable 1.3.6.1.4.1.232.165.2.3.1
The Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutputEntry

pduOutputEntry 1.3.6.1.4.1.232.165.2.3.1.1
The input table entry containing the name, heat load, current load, power load, firmware, etc.
OBJECT-TYPE    
  PduOutputEntry  

pduOutputIndex 1.3.6.1.4.1.232.165.2.3.1.1.1
Index for the PduOutputEntry table.
OBJECT-TYPE    
  INTEGER  

pduOutputLoad 1.3.6.1.4.1.232.165.2.3.1.1.2
The device output load in percent of rated capacity. A value of -1 will be returned if the heat load is unable to be measured.
OBJECT-TYPE    
  INTEGER 0..200  

pduOutputHeat 1.3.6.1.4.1.232.165.2.3.1.1.3
The total heat load measured on the PDU in BTUs. A value of -1 will be returned if the heat load is unable to be measured.
OBJECT-TYPE    
  INTEGER  

pduOutputPower 1.3.6.1.4.1.232.165.2.3.1.1.4
The total power load measured on the PDU in watts. A value of -1 will be returned if the power load is unable to be measured.
OBJECT-TYPE    
  INTEGER  

pduOutputNumBreakers 1.3.6.1.4.1.232.165.2.3.1.1.5
The number of breakers for the device. This variable indicates the number of rows in the breakers table.
OBJECT-TYPE    
  INTEGER  

pduOutputBreakerTable 1.3.6.1.4.1.232.165.2.3.2
List of breaker table entries. The number of entries is given by pduOutputNumBreakers .
OBJECT-TYPE    
  SEQUENCE OF  
    PduOutputBreakerEntry

pduOutputBreakerEntry 1.3.6.1.4.1.232.165.2.3.2.1
An entry containing information applicable to an breaker.
OBJECT-TYPE    
  PduOutputBreakerEntry  

breakerIndex 1.3.6.1.4.1.232.165.2.3.2.1.1
The breaker identifier.
OBJECT-TYPE    
  INTEGER  

breakerVoltage 1.3.6.1.4.1.232.165.2.3.2.1.2
The breaker voltage in volts.
OBJECT-TYPE    
  INTEGER  

breakerCurrent 1.3.6.1.4.1.232.165.2.3.2.1.3
The breaker current draw in Amps.
OBJECT-TYPE    
  INTEGER  

breakerPercentLoad 1.3.6.1.4.1.232.165.2.3.2.1.4
The breaker load in percent.
OBJECT-TYPE    
  INTEGER  

breakerStatus 1.3.6.1.4.1.232.165.2.3.2.1.5
This object indicates the status of the breaker. A value of normal(1) indicates the breaker is operating normally. A value of overloadWarning(2) indicates the breaker has an overload warning. A value of overloadCritical(3) indicates the breaker is overloaded. A value of voltageRangeWarning(4) indicates the breaker voltage is out of tolerance by 10-20%. A value of voltageRangeCritical(5) indicates the breaker voltage is out of tolerance by more than 20%. Note: Overload status has priority over voltage tolerance status.
OBJECT-TYPE    
  INTEGER normal(1), overloadWarning(2), overloadCritical(3), voltageRangeWarning(4), voltageRangeCritical(5)  

ups 1.3.6.1.4.1.232.165.3
OBJECT IDENTIFIER    

trapInformation 1.3.6.1.4.1.232.165.3
An informational alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  trapCode  
  trapDescription  
  trapDeviceName  
  trapDeviceDetails  
  trapDeviceMgmtUrl  

upsIdent 1.3.6.1.4.1.232.165.3.1
OBJECT IDENTIFIER    

upsIdentManufacturer 1.3.6.1.4.1.232.165.3.1.1
The UPS Manufacturer Name (e.g. Hewlett-Packard).
OBJECT-TYPE    
  DisplayString SIZE(0..31)  

upsIdentModel 1.3.6.1.4.1.232.165.3.1.2
The UPS Model;Part number;Serial number (e.g. HP R5500 XR;204451-B21;B00123456W).
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

upsIdentSoftwareVersions 1.3.6.1.4.1.232.165.3.1.3
The firmware revision level(s) of the UPS microcontroller(s).
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

upsIdentOemCode 1.3.6.1.4.1.232.165.3.1.4
A binary code indicating vendor. This should be a ?0x0c? for HP
OBJECT-TYPE    
  INTEGER 0..255  

upsBattery 1.3.6.1.4.1.232.165.3.2
OBJECT IDENTIFIER    

upsBatTimeRemaining 1.3.6.1.4.1.232.165.3.2.1
Battery run time in seconds before UPS turns off due to low battery.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsBatVoltage 1.3.6.1.4.1.232.165.3.2.2
Battery voltage as reported by the UPS meters.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsBatCurrent 1.3.6.1.4.1.232.165.3.2.3
Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
OBJECT-TYPE    
  INTEGER -2147483648..2147483647  

upsBatCapacity 1.3.6.1.4.1.232.165.3.2.4
Battery percent charge.
OBJECT-TYPE    
  INTEGER 0..100  

upsBatteryAbmStatus 1.3.6.1.4.1.232.165.3.2.5
Gives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done.
OBJECT-TYPE    
  INTEGER batteryCharging(1), batteryDischarging(2), batteryFloating(3), batteryResting(4), unknown(5)  

upsInput 1.3.6.1.4.1.232.165.3.3
OBJECT IDENTIFIER    

upsInputFrequency 1.3.6.1.4.1.232.165.3.3.1
The utility line frequency in tenths of Hz.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsInputLineBads 1.3.6.1.4.1.232.165.3.3.2
The number of times the Input was out of tolerance in voltage or frequency.
OBJECT-TYPE    
  Counter  

upsInputNumPhases 1.3.6.1.4.1.232.165.3.3.3
OBJECT-TYPE    
  INTEGER 0..6  

upsInputTable 1.3.6.1.4.1.232.165.3.3.4
The Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
OBJECT-TYPE    
  SEQUENCE OF  
    UpsInputEntry

upsInputEntry 1.3.6.1.4.1.232.165.3.3.4.1
The input table entry containing the current, voltage, etc.
OBJECT-TYPE    
  UpsInputEntry  

upsInputPhase 1.3.6.1.4.1.232.165.3.3.4.1.1
The number of the phase. Serves as index for input table.
OBJECT-TYPE    
  INTEGER 0..6  

upsInputVoltage 1.3.6.1.4.1.232.165.3.3.4.1.2
The measured input voltage from the UPS meters in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsInputCurrent 1.3.6.1.4.1.232.165.3.3.4.1.3
The measured input current from the UPS meters in amps.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsInputWatts 1.3.6.1.4.1.232.165.3.3.4.1.4
The measured input real power in watts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsInputSource 1.3.6.1.4.1.232.165.3.3.5
The present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an internal source). The bypassFeed(4) can only be used when the Bypass source is known to be a separate utility feed than the primaryUtility(3).
OBJECT-TYPE    
  INTEGER other(1), none(2), primaryUtility(3), bypassFeed(4), secondaryUtility(5), generator(6), flywheel(7), fuelcell(8)  

upsOutput 1.3.6.1.4.1.232.165.3.4
OBJECT IDENTIFIER    

upsOutputLoad 1.3.6.1.4.1.232.165.3.4.1
The UPS output load in percent of rated capacity.
OBJECT-TYPE    
  INTEGER 0..200  

upsOutputFrequency 1.3.6.1.4.1.232.165.3.4.2
The measured UPS output frequency in tenths of Hz.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsOutputNumPhases 1.3.6.1.4.1.232.165.3.4.3
The number of metered output phases, serves as the table index.
OBJECT-TYPE    
  INTEGER 0..6  

upsOutputTable 1.3.6.1.4.1.232.165.3.4.4
The Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
OBJECT-TYPE    
  SEQUENCE OF  
    UpsOutputEntry

upsOutputEntry 1.3.6.1.4.1.232.165.3.4.4.1
Output Table Entry containing voltage, current, etc.
OBJECT-TYPE    
  UpsOutputEntry  

upsOutputPhase 1.3.6.1.4.1.232.165.3.4.4.1.1
The number {1..3} of the output phase.
OBJECT-TYPE    
  INTEGER 0..6  

upsOutputVoltage 1.3.6.1.4.1.232.165.3.4.4.1.2
The measured output voltage from the UPS metering in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsOutputCurrent 1.3.6.1.4.1.232.165.3.4.4.1.3
The measured UPS output current in amps.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsOutputWatts 1.3.6.1.4.1.232.165.3.4.4.1.4
The measured real output power in watts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsOutputSource 1.3.6.1.4.1.232.165.3.4.5
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
OBJECT-TYPE    
  INTEGER other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), parallelCapacity(8), parallelRedundant(9), highEfficiencyMode(10)  

upsBypass 1.3.6.1.4.1.232.165.3.5
OBJECT IDENTIFIER    

upsBypassFrequency 1.3.6.1.4.1.232.165.3.5.1
The bypass frequency in tenths of Hz.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsBypassNumPhases 1.3.6.1.4.1.232.165.3.5.2
The number of lines in the UPS bypass table.
OBJECT-TYPE    
  INTEGER 0..6  

upsBypassTable 1.3.6.1.4.1.232.165.3.5.3
OBJECT-TYPE    
  SEQUENCE OF  
    UpsBypassEntry

upsBypassEntry 1.3.6.1.4.1.232.165.3.5.3.1
Entry in the UpsBypassTable.
OBJECT-TYPE    
  UpsBypassEntry  

upsBypassPhase 1.3.6.1.4.1.232.165.3.5.3.1.1
The Bypass Phase, index for the table.
OBJECT-TYPE    
  INTEGER 0..6  

upsBypassVoltage 1.3.6.1.4.1.232.165.3.5.3.1.2
The measured UPS bypass voltage in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsEnvironment 1.3.6.1.4.1.232.165.3.6
OBJECT IDENTIFIER    

upsEnvAmbientTemp 1.3.6.1.4.1.232.165.3.6.1
The reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvAmbientLowerLimit 1.3.6.1.4.1.232.165.3.6.2
The Lower Limit of the ambient temperature; if UpsEnvAmbientTemp falls below this value, the UpsAmbientTempBad alarm will occur.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvAmbientUpperLimit 1.3.6.1.4.1.232.165.3.6.3
The Upper Limit of the ambient temperature; if UpsEnvAmbientTemp rises above this value, the UpsAmbientTempBad alarm will occur. This value should be greater than UpsEnvAmbientLowerLimit.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvAmbientHumidity 1.3.6.1.4.1.232.165.3.6.4
The reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
OBJECT-TYPE    
  INTEGER 0..100  

upsEnvRemoteTemp 1.3.6.1.4.1.232.165.3.6.5
The reading of a remote temperature sensor connected to the UPS or SNMP agent.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvRemoteHumidity 1.3.6.1.4.1.232.165.3.6.6
The reading of a remote humidity sensor connected to the UPS or SNMP agent.
OBJECT-TYPE    
  INTEGER 0..100  

upsEnvNumContacts 1.3.6.1.4.1.232.165.3.6.7
The number of Contacts in the UpsContactsTable. This object indicates the number of rows in the UpsContactsTable.
OBJECT-TYPE    
  INTEGER 1..1024  

upsContactsTable 1.3.6.1.4.1.232.165.3.6.8
A list of Contact Sensing table entries. The number of entries is given by the value of UpsEnvNumContacts.
OBJECT-TYPE    
  SEQUENCE OF  
    UpsContactsTableEntry

upsContactsTableEntry 1.3.6.1.4.1.232.165.3.6.8.1
An entry containing information applicable to a particular Contact input.
OBJECT-TYPE    
  UpsContactsTableEntry  

upsContactIndex 1.3.6.1.4.1.232.165.3.6.8.1.1
The Contact identifier; identical to the Contact Number.
OBJECT-TYPE    
  INTEGER 1..1024  

upsContactType 1.3.6.1.4.1.232.165.3.6.8.1.2
The normal state for this contact. The 'other' state is the Active state for generating the UpstdContactActiveNotice trap. If anyChange(3) is selected, then this trap is sent any time the contact changes to either Open or Closed. No traps are sent if the Contact is set to notUsed(4). In many cases, the configuration for Contacts may be done by other means, so this object may be read-only.
OBJECT-TYPE    
  INTEGER normallyOpen(1), normallyClosed(2), anyChange(3), notUsed(4)  

upsContactState 1.3.6.1.4.1.232.165.3.6.8.1.3
The current state of the Contact input; the value is based on the open/closed input state and the setting for UpsContactType. When entering the openWithNotice(3) and closedWithNotice(4) states, no entries added to the UpsAlarmTable, but the UpstdContactActiveNotice trap is sent.
OBJECT-TYPE    
  INTEGER open(1), closed(2), openWithNotice(3), closedWithNotice(4)  

upsContactDescr 1.3.6.1.4.1.232.165.3.6.8.1.4
A label identifying the Contact. This object should be set by the administrator.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

upsEnvRemoteTempLowerLimit 1.3.6.1.4.1.232.165.3.6.9
The Lower Limit of the remote temperature; if UpsEnvRemoteTemp falls below this value, the UpsRemoteTempBad alarm will occur.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvRemoteTempUpperLimit 1.3.6.1.4.1.232.165.3.6.10
The Upper Limit of the remote temperature; if UpsEnvRemoteTemp rises above this value, the UpsRemoteTempBad alarm will occur. This value should be greater than UpsEnvRemoteTempLowerLimit.
OBJECT-TYPE    
  INTEGER -100..200  

upsEnvRemoteHumidityLowerLimit 1.3.6.1.4.1.232.165.3.6.11
The Lower Limit of the remote humidity reading; if UpsEnvRemoteHumidity falls below this value, the UpsRemoteHumidityBad alarm will occur.
OBJECT-TYPE    
  INTEGER 0..100  

upsEnvRemoteHumidityUpperLimit 1.3.6.1.4.1.232.165.3.6.12
The Upper Limit of the remote humidity reading; if UpsEnvRemoteHumidity rises above this value, the UpsRemoteHumidityBad alarm will occur. This value should be greater than UpsEnvRemoteHumidityLowerLimit.
OBJECT-TYPE    
  INTEGER 0..100  

upsTest 1.3.6.1.4.1.232.165.3.7
OBJECT IDENTIFIER    

upsTestBattery 1.3.6.1.4.1.232.165.3.7.1
Setting this variable to startTest initiates the battery test. All other set values are invalid.
OBJECT-TYPE    
  INTEGER startTest(1)  

upsTestBatteryStatus 1.3.6.1.4.1.232.165.3.7.2
Reading this enumerated value gives an indication of the UPS Battery test status.
OBJECT-TYPE    
  INTEGER unknown(1), passed(2), failed(3), inProgress(4), notSupported(5), inhibited(6), scheduled(7)  

upsTestTrap 1.3.6.1.4.1.232.165.3.7.3
Setting this variable to startTestTrap initiates a TrapTest is sent out from HPMM. All other set values are invalid.
OBJECT-TYPE    
  INTEGER startTestTrap(1)  

upsControl 1.3.6.1.4.1.232.165.3.8
OBJECT IDENTIFIER    

upsControlOutputOffDelay 1.3.6.1.4.1.232.165.3.8.1
Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsControlOutputOnDelay 1.3.6.1.4.1.232.165.3.8.2
Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsControlOutputOffTrapDelay 1.3.6.1.4.1.232.165.3.8.3
When UpsControlOutputOffDelay reaches this value, a trap will be sent.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsControlOutputOnTrapDelay 1.3.6.1.4.1.232.165.3.8.4
When UpsControlOutputOnDelay reaches this value, a UpsOutputOff trap will be sent.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsControlToBypassDelay 1.3.6.1.4.1.232.165.3.8.5
Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsLoadShedSecsWithRestart 1.3.6.1.4.1.232.165.3.8.6
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike UpsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfig 1.3.6.1.4.1.232.165.3.9
OBJECT IDENTIFIER    

upsConfigOutputVoltage 1.3.6.1.4.1.232.165.3.9.1
The nominal UPS Output voltage per phase in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfigInputVoltage 1.3.6.1.4.1.232.165.3.9.2
The nominal UPS Input voltage per phase in volts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfigOutputWatts 1.3.6.1.4.1.232.165.3.9.3
The nominal UPS available real power output in watts.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfigOutputFreq 1.3.6.1.4.1.232.165.3.9.4
The nominal output frequency in tenths of Hz.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfigDateAndTime 1.3.6.1.4.1.232.165.3.9.5
Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS.
OBJECT-TYPE    
  DisplayString SIZE(0..22)  

upsConfigLowOutputVoltageLimit 1.3.6.1.4.1.232.165.3.9.6
The Lower limit for acceptable Output Voltage, per the UPS specifications.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsConfigHighOutputVoltageLimit 1.3.6.1.4.1.232.165.3.9.7
The Upper limit for acceptable Output Voltage, per the UPS specifications.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsRecep 1.3.6.1.4.1.232.165.3.10
OBJECT IDENTIFIER    

upsNumReceptacles 1.3.6.1.4.1.232.165.3.10.1
The number of independently controllable Receptacles, as described in the UpsRecepTable.
OBJECT-TYPE    
  INTEGER 0..64  

upsRecepTable 1.3.6.1.4.1.232.165.3.10.2
The Aggregate Object with number of entries equal to NumReceptacles and including the UpsRecep group.
OBJECT-TYPE    
  SEQUENCE OF  
    UpsRecepEntry

upsRecepEntry 1.3.6.1.4.1.232.165.3.10.2.1
The Recep table entry, etc.
OBJECT-TYPE    
  UpsRecepEntry  

upsRecepIndex 1.3.6.1.4.1.232.165.3.10.2.1.1
The number of the Receptacle. Serves as index for Receptacle table.
OBJECT-TYPE    
  INTEGER 1..64  

upsRecepStatus 1.3.6.1.4.1.232.165.3.10.2.1.2
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown.
OBJECT-TYPE    
  INTEGER on(1), off(2), pendingOff(3), pendingOn(4), unknown(5)  

upsRecepOffDelaySecs 1.3.6.1.4.1.232.165.3.10.2.1.3
The Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object is set while the UPS is On Battery, it is not necessary to set UpsRecepOnDelaySecs, since the outlet will turn back on automatically when power is available again.
OBJECT-TYPE    
  INTEGER -1..2147483647  

upsRecepOnDelaySecs 1.3.6.1.4.1.232.165.3.10.2.1.4
The Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart.
OBJECT-TYPE    
  INTEGER -1..2147483647  

upsRecepAutoOffDelay 1.3.6.1.4.1.232.165.3.10.2.1.5
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
OBJECT-TYPE    
  INTEGER -1..32767  

upsRecepAutoOnDelay 1.3.6.1.4.1.232.165.3.10.2.1.6
Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Receptacle should come On immediately at power-up or for an On command.
OBJECT-TYPE    
  INTEGER -1..32767  

upsRecepShedSecsWithRestart 1.3.6.1.4.1.232.165.3.10.2.1.7
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike UpsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted.
OBJECT-TYPE    
  INTEGER 0..2147483647  

upsTopology 1.3.6.1.4.1.232.165.3.11
OBJECT IDENTIFIER    

upsTopologyType 1.3.6.1.4.1.232.165.3.11.1
Value which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
OBJECT-TYPE    
  INTEGER 0..32767  

upsTopoMachineCode 1.3.6.1.4.1.232.165.3.11.2
ID Value which denotes the Compaq/HP model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
OBJECT-TYPE    
  INTEGER 0..32767  

upsTopoUnitNumber 1.3.6.1.4.1.232.165.3.11.3
Identifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a value of 0, since they are the 'full system' view. A value of 1 or higher indicates the number of the module in the system which is reporting only its own data in the HP MIB objects.
OBJECT-TYPE    
  INTEGER 0..64  

upsTopoPowerStrategy 1.3.6.1.4.1.232.165.3.11.4
Value which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize its power-protection levels. This mode will be held for at most 24 hours. standard(2) - Balanced, normal power protection strategy. UPS will not enter HE operating mode from this setting. enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to optimize its operating state to maximize its efficiency, when conditions change to permit it (as determined by the UPS). forceHighEfficiency(4) - If this value is permitted to be Set for this UPS, and if conditions permit, requires the UPS to enter High Efficiency mode now, without delay (for as long as utility conditions permit). After successfully set to forceHighEfficiency(4), UpsTopoPowerStrategy changes to value enableHighEfficiency(3). UpsOutputSource will indicate if the UPS status is actually operating in High Efficiency mode.
OBJECT-TYPE    
  INTEGER highAlert(1), standard(2), enableHighEfficiency(3), immediateHighEfficiency(4)  

pdr 1.3.6.1.4.1.232.165.4
OBJECT IDENTIFIER    

trapCleared 1.3.6.1.4.1.232.165.4
An alarm has cleared. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  trapCode  
  trapDescription  
  trapDeviceName  
  trapDeviceDetails  
  trapDeviceMgmtUrl  

pdrIdent 1.3.6.1.4.1.232.165.4.1
OBJECT IDENTIFIER    

pdrName 1.3.6.1.4.1.232.165.4.1.1
The string identify the device.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrModel 1.3.6.1.4.1.232.165.4.1.2
The Device Model.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrManufacturer 1.3.6.1.4.1.232.165.4.1.3
The Device Manufacturer Name (e.g. Hewlett-Packard).
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrFirmwareVersion 1.3.6.1.4.1.232.165.4.1.4
The firmware revision level of the device.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrPartNumber 1.3.6.1.4.1.232.165.4.1.5
The device part number.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrSerialNumber 1.3.6.1.4.1.232.165.4.1.6
The PDR's serial number.
OBJECT-TYPE    
  DisplayString SIZE(0..63)  

pdrVARating 1.3.6.1.4.1.232.165.4.1.7
The VA Rating of this PDR (all phases)
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrNominalOutputVoltage 1.3.6.1.4.1.232.165.4.1.8
The nominal Output Voltage may differ from the nominal Input Voltage if the PDR has an input transformer
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrNumPhases 1.3.6.1.4.1.232.165.4.1.9
The number of phases for this PDR
OBJECT-TYPE    
  INTEGER 1..3  

pdrNumPanels 1.3.6.1.4.1.232.165.4.1.10
The number of panels or subfeeds in this PDR
OBJECT-TYPE    
  INTEGER 0..100  

pdrNumBreakers 1.3.6.1.4.1.232.165.4.1.11
The number of breakers in this PDR
OBJECT-TYPE    
  INTEGER 0..100  

pdrPanel 1.3.6.1.4.1.232.165.4.2
OBJECT IDENTIFIER    

pdrPanelTable 1.3.6.1.4.1.232.165.4.2.1
Aggregate Object with number of entries equal to pdrNumPanels
OBJECT-TYPE    
  SEQUENCE OF  
    PdrPanelEntry

pdrPanelEntry 1.3.6.1.4.1.232.165.4.2.1.1
The panel table entry containing all power parameters for each panel.
OBJECT-TYPE    
  PdrPanelEntry  

pdrPanelIndex 1.3.6.1.4.1.232.165.4.2.1.1.1
Index for the pdrPanelEntry table.
OBJECT-TYPE    
  INTEGER  

pdrPanelFrequency 1.3.6.1.4.1.232.165.4.2.1.1.2
The present frequency reading for the panel voltage.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelPower 1.3.6.1.4.1.232.165.4.2.1.1.3
The present power of the panel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelRatedCurrent 1.3.6.1.4.1.232.165.4.2.1.1.4
The present rated current of the panel.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelMonthlyKWH 1.3.6.1.4.1.232.165.4.2.1.1.5
The accumulated KWH for this panel since the beginning of this calendar month or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelYearlyKWH 1.3.6.1.4.1.232.165.4.2.1.1.6
The accumulated KWH for this panel since the beginning of this calendar year or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelTotalKWH 1.3.6.1.4.1.232.165.4.2.1.1.7
The accumulated KWH for this panel since it was put into service or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelVoltageA 1.3.6.1.4.1.232.165.4.2.1.1.8
The measured panel output voltage.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelVoltageB 1.3.6.1.4.1.232.165.4.2.1.1.9
The measured panel output voltage.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelVoltageC 1.3.6.1.4.1.232.165.4.2.1.1.10
The measured panel output voltage.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelCurrentA 1.3.6.1.4.1.232.165.4.2.1.1.11
The measured panel output current.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelCurrentB 1.3.6.1.4.1.232.165.4.2.1.1.12
The measured panel output current.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelCurrentC 1.3.6.1.4.1.232.165.4.2.1.1.13
The measured panel output current.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrPanelLoadA 1.3.6.1.4.1.232.165.4.2.1.1.14
The percentage of load is the ratio of each output current to the rated output current to the panel.
OBJECT-TYPE    
  INTEGER 0..200  

pdrPanelLoadB 1.3.6.1.4.1.232.165.4.2.1.1.15
The percentage of load is the ratio of each output current to the rated output current to the panel.
OBJECT-TYPE    
  INTEGER 0..200  

pdrPanelLoadC 1.3.6.1.4.1.232.165.4.2.1.1.16
The percentage of load is the ratio of each output current to the rated output current to the panel.
OBJECT-TYPE    
  INTEGER 0..200  

pdrBreaker 1.3.6.1.4.1.232.165.4.3
OBJECT IDENTIFIER    

pdrBreakerTable 1.3.6.1.4.1.232.165.4.3.1
List of breaker table entries. The number of entries is given by pdrNumBreakers for this panel.
OBJECT-TYPE    
  SEQUENCE OF  
    PdrBreakerEntry

pdrBreakerEntry 1.3.6.1.4.1.232.165.4.3.1.1
An entry containing information applicable to a particular output breaker of a particular panel.
OBJECT-TYPE    
  PdrBreakerEntry  

pdrBreakerIndex 1.3.6.1.4.1.232.165.4.3.1.1.1
The index of breakers. 42 breakers in each panel, arranged in odd and even columns
OBJECT-TYPE    
  INTEGER  

pdrBreakerPanel 1.3.6.1.4.1.232.165.4.3.1.1.2
The index of panel that these breakers are installed on.
OBJECT-TYPE    
  INTEGER  

pdrBreakerNumPosition 1.3.6.1.4.1.232.165.4.3.1.1.3
The position of this breaker in the panel, 1-phase breaker or n-m breaker for 2-phase or n-m-k breaker for 3-phase.
OBJECT-TYPE    
  INTEGER  

pdrBreakerNumPhases 1.3.6.1.4.1.232.165.4.3.1.1.4
The number of phase for this particular breaker.
OBJECT-TYPE    
  INTEGER  

pdrBreakerNumSequence 1.3.6.1.4.1.232.165.4.3.1.1.5
The sequence of this breaker. i.e. 1 for single phase 1,2 for 2-phase or 1,2,3 for 3-phase.
OBJECT-TYPE    
  INTEGER  

pdrBreakerRatedCurrent 1.3.6.1.4.1.232.165.4.3.1.1.6
The rated current in Amps for this particular breaker.
OBJECT-TYPE    
  INTEGER  

pdrBreakerMonthlyKWH 1.3.6.1.4.1.232.165.4.3.1.1.7
The accumulated KWH for this breaker since the beginning of this calendar month or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrBreakerYearlyKWH 1.3.6.1.4.1.232.165.4.3.1.1.8
The accumulated KWH for this breaker since the beginning of this calendar year or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrBreakerTotalKWH 1.3.6.1.4.1.232.165.4.3.1.1.9
The accumulated KWH for this breaker since it was put into service or since the last reset.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrBreakerCurrent 1.3.6.1.4.1.232.165.4.3.1.1.10
The measured output current for this breaker Current.
OBJECT-TYPE    
  INTEGER 0..2147483647  

pdrBreakerCurrentPercent 1.3.6.1.4.1.232.165.4.3.1.1.11
The ratio of output current over rated current for each breaker.
OBJECT-TYPE    
  INTEGER 0..200  

pdrBreakerPower 1.3.6.1.4.1.232.165.4.3.1.1.12
The power for this breaker.
OBJECT-TYPE    
  INTEGER  

pdrBreakerPercentWarning 1.3.6.1.4.1.232.165.4.3.1.1.13
The percentage of Warning set for this breaker.
OBJECT-TYPE    
  INTEGER 0..200  

pdrBreakerPercentOverload 1.3.6.1.4.1.232.165.4.3.1.1.14
The percentage of Overload set for this breaker.
OBJECT-TYPE    
  INTEGER  

trapTest 1.3.6.1.4.1.232.165.5
Test trap sent to a trap receiver to check proper reception of traps
TRAP-TYPE    
  sysName  
  trapCode  
  trapDescription  
  trapDeviceName  
  trapDeviceDetails  
  trapDeviceMgmtUrl  

deviceTrapInitialization 1.3.6.1.4.1.232.165.6
This trap is sent each time a power device is initialized.
TRAP-TYPE    
  sysName  
  deviceIdentName  

Defined Objects

PduIdentEntry  
SEQUENCE    
  INTEGER as pduIdentIndex  
  DisplayString as pduName  
  DisplayString as pduModel  
  DisplayString as pduManufacturer  
  DisplayString as pduFirmwareVersion  
  DisplayString as pduPartNumber  
  DisplayString as pduSerialNumber  
  INTEGER as pduStatus  
  INTEGER as pduControllable  

PduInputEntry  
SEQUENCE    
  INTEGER as pduInputIndex  
  INTEGER as inputVoltage  
  INTEGER as inputCurrent  

PduOutputEntry  
SEQUENCE    
  INTEGER as pduOutputIndex  
  INTEGER as pduOutputLoad  
  INTEGER as pduOutputHeat  
  INTEGER as pduOutputPower  
  INTEGER as pduOutputNumBreakers  

PduOutputBreakerEntry  
SEQUENCE    
  INTEGER as breakerIndex  
  INTEGER as breakerVoltage  
  INTEGER as breakerCurrent  
  INTEGER as breakerPercentLoad  
  INTEGER as breakerStatus  

UpsInputEntry  
SEQUENCE    
  INTEGER as upsInputPhase  
  INTEGER as upsInputVoltage  
  INTEGER as upsInputCurrent  
  INTEGER as upsInputWatts  

UpsOutputEntry  
SEQUENCE    
  INTEGER as upsOutputPhase  
  INTEGER as upsOutputVoltage  
  INTEGER as upsOutputCurrent  
  INTEGER as upsOutputWatts  

UpsBypassEntry  
SEQUENCE    
  INTEGER as upsBypassPhase  
  INTEGER as upsBypassVoltage  

UpsContactsTableEntry  
SEQUENCE    
  INTEGER as upsContactIndex  
  INTEGER as upsContactType  
  INTEGER as upsContactState  
  DisplayString as upsContactDescr  

UpsRecepEntry  
SEQUENCE    
  INTEGER as upsRecepIndex  
  INTEGER as upsRecepStatus  
  INTEGER as upsRecepOffDelaySecs  
  INTEGER as upsRecepOnDelaySecs  
  INTEGER as upsRecepAutoOffDelay  
  INTEGER as upsRecepAutoOnDelay  
  INTEGER as upsRecepShedSecsWithRestart  

PdrPanelEntry  
SEQUENCE    
  INTEGER as pdrPanelIndex  
  INTEGER as pdrPanelFrequency  
  INTEGER as pdrPanelPower  
  INTEGER as pdrPanelRatedCurrent  
  INTEGER as pdrPanelMonthlyKWH  
  INTEGER as pdrPanelYearlyKWH  
  INTEGER as pdrPanelTotalKWH  
  INTEGER as pdrPanelVoltageA  
  INTEGER as pdrPanelVoltageB  
  INTEGER as pdrPanelVoltageC  
  INTEGER as pdrPanelCurrentA  
  INTEGER as pdrPanelCurrentB  
  INTEGER as pdrPanelCurrentC  
  INTEGER as pdrPanelLoadA  
  INTEGER as pdrPanelLoadB  
  INTEGER as pdrPanelLoadC  

PdrBreakerEntry  
SEQUENCE    
  INTEGER as pdrBreakerIndex  
  INTEGER as pdrBreakerPanel  
  INTEGER as pdrBreakerNumPosition  
  INTEGER as pdrBreakerNumPhases  
  INTEGER as pdrBreakerNumSequence  
  INTEGER as pdrBreakerRatedCurrent  
  INTEGER as pdrBreakerMonthlyKWH  
  INTEGER as pdrBreakerYearlyKWH  
  INTEGER as pdrBreakerTotalKWH  
  INTEGER as pdrBreakerCurrent  
  INTEGER as pdrBreakerCurrentPercent  
  INTEGER as pdrBreakerPower  
  INTEGER as pdrBreakerPercentWarning  
  INTEGER as pdrBreakerPercentOverload