CPQRPM-MIB

File: CPQRPM-MIB.mib (85188 bytes)

Imported modules

CPQHOST-MIB RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

compaq DisplayString OBJECT-TYPE
TRAP-TYPE sysName

Defined Objects

cpqRPM 1.3.6.1.4.1.232.154
OBJECT IDENTIFIER    

cpqRPMTrapInfo 1.3.6.1.4.1.232.154.1
OBJECT IDENTIFIER    

cpqRPMTrapDescription 1.3.6.1.4.1.232.154.1.1
Text description of the event that caused the trap.
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

cpqRPMTrapDeviceId 1.3.6.1.4.1.232.154.1.2
A unique numeric identifier for the device that caused the trap.
OBJECT-TYPE    
  INTEGER 0..2147483647  

cpqRPMTrapDeviceName 1.3.6.1.4.1.232.154.1.3
The text name for the device.
OBJECT-TYPE    
  DisplayString SIZE(0..50)  

cpqRPMTrapDeviceAddress 1.3.6.1.4.1.232.154.1.4
The hostname or ip address for the device.
OBJECT-TYPE    
  DisplayString SIZE(0..50)  

cpqRPMTrapType 1.3.6.1.4.1.232.154.1.5
Indicates the type of the event that caused the trap.
OBJECT-TYPE    
  INTEGER system(1), event(2), change(3), power(4), environment(5)  

cpqRPMTrapSeverity 1.3.6.1.4.1.232.154.1.6
Indicates the severity of the event that caused the trap.
OBJECT-TYPE    
  INTEGER unknown(1), information(2), normal(3), minor(4), major(5), critical(6)  

cpqRPMTrapCode 1.3.6.1.4.1.232.154.1.7
A unique identifier for the alarm.
OBJECT-TYPE    
  INTEGER 0..2147483647  

cpqRPMTrapURL 1.3.6.1.4.1.232.154.1.8
The URL for the management software.
OBJECT-TYPE    
  DisplayString SIZE(0..255)  

cpqRPMTraps 1.3.6.1.4.1.232.154.2
OBJECT IDENTIFIER    

cpqRPMTrapDeviceConnected 1.3.6.1.4.1.232.154.2.1
A UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapConnectionLost 1.3.6.1.4.1.232.154.2.2
A UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapLookupFailed 1.3.6.1.4.1.232.154.2.3
CRPM failed to find an IP address for the device hostname.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapConnectionFailed 1.3.6.1.4.1.232.154.2.4
CRPM failed to connect to a device.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapDeviceSettingsChanged 1.3.6.1.4.1.232.154.2.5
Device settings have been changed by a user.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp1BelowMin 1.3.6.1.4.1.232.154.2.10001
A CMC device is reporting temperature 1 below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp1AboveWarn 1.3.6.1.4.1.232.154.2.10002
A CMC device is reporting temperature 1 above warning threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp1AboveMax 1.3.6.1.4.1.232.154.2.10003
A CMC device is reporting temperature 1 above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp1Normal 1.3.6.1.4.1.232.154.2.10004
A CMC device is reporting temperature 1 has returned to a normal temperature.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp2BelowMin 1.3.6.1.4.1.232.154.2.10005
A CMC device is reporting temperature 2 below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp2AboveWarn 1.3.6.1.4.1.232.154.2.10006
A CMC device is reporting temperature 2 above warning threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp2AboveMax 1.3.6.1.4.1.232.154.2.10007
A CMC device is reporting temperature 2 above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCTemp2Normal 1.3.6.1.4.1.232.154.2.10008
A CMC device is reporting temperature 2 has returned to a normal temperature.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCVoltUnder 1.3.6.1.4.1.232.154.2.10011
A CMC device is reporting voltage below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCVoltOver 1.3.6.1.4.1.232.154.2.10012
A CMC device is reporting voltage above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCVoltNormal 1.3.6.1.4.1.232.154.2.10013
A CMC device is reporting voltage has returned to normal.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCHmdtUnder 1.3.6.1.4.1.232.154.2.10021
A CMC device is reporting humidity below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCHmdtOver 1.3.6.1.4.1.232.154.2.10022
A CMC device is reporting humidity above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCHmdtNormal 1.3.6.1.4.1.232.154.2.10023
A CMC device is reporting humidity has returned to normal.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCSmokeDetected 1.3.6.1.4.1.232.154.2.10031
A CMC device is reporting smoke detected.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCSmokeCleared 1.3.6.1.4.1.232.154.2.10032
A CMC device is reporting smoke cleared.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCShockDetected 1.3.6.1.4.1.232.154.2.10041
A CMC device is reporting shock detected.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCShockCleared 1.3.6.1.4.1.232.154.2.10042
A CMC device is reporting shock cleared.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCAux1Alarm 1.3.6.1.4.1.232.154.2.10051
A CMC device has entered an alarm condition for auxiliary input 1.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCAux1Cleared 1.3.6.1.4.1.232.154.2.10052
A CMC device is reporting auxiliary input 1 alarm cleared.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCAux2Alarm 1.3.6.1.4.1.232.154.2.10053
A CMC device has entered an alarm condition for auxiliary input 2.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCAux2Cleared 1.3.6.1.4.1.232.154.2.10054
A CMC device is reporting auxiliary input 2 alarm cleared.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput1Opened 1.3.6.1.4.1.232.154.2.10101
A CMC device is reporting input 1 has been opened.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput1Closed 1.3.6.1.4.1.232.154.2.10102
A CMC device is reporting input 1 has been closed.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput2Opened 1.3.6.1.4.1.232.154.2.10103
A CMC device is reporting input 2 has been opened.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput2Closed 1.3.6.1.4.1.232.154.2.10104
A CMC device is reporting input 2 has been closed.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput3Opened 1.3.6.1.4.1.232.154.2.10105
A CMC device is reporting input 3 has been opened.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput3Closed 1.3.6.1.4.1.232.154.2.10106
A CMC device is reporting input 3 has been closed.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput4Opened 1.3.6.1.4.1.232.154.2.10107
A CMC device is reporting input 4 has been opened.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCInput4Closed 1.3.6.1.4.1.232.154.2.10108
A CMC device is reporting input 4 has been closed.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset1Unlocked 1.3.6.1.4.1.232.154.2.10111
A CMC device is reporting lockset 1 has been unlocked.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset1FailedToLock 1.3.6.1.4.1.232.154.2.10112
A CMC device is reporting lockset 1 has failed to lock.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset1Error 1.3.6.1.4.1.232.154.2.10113
A CMC device is reporting an error with lockset 1.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset1Locked 1.3.6.1.4.1.232.154.2.10114
A CMC device is reporting lockset 1 has been locked.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset2Unlocked 1.3.6.1.4.1.232.154.2.10116
A CMC device is reporting lockset 2 has been unlocked.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset2FailedToLock 1.3.6.1.4.1.232.154.2.10117
A CMC device is reporting lockset 2 has failed to lock.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset2Error 1.3.6.1.4.1.232.154.2.10118
A CMC device is reporting an error with lockset 2.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset2Locked 1.3.6.1.4.1.232.154.2.10119
A CMC device is reporting lockset 2 has been locked.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset1Normal 1.3.6.1.4.1.232.154.2.10134
A CMC device is reporting lockset 2 is normal.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapCMCLockset2Normal 1.3.6.1.4.1.232.154.2.10135
A CMC device is reporting lockset 2 is normal.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSInputVoltageBelowMin 1.3.6.1.4.1.232.154.2.20001
A UPS device is reporting input voltage below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSInputVoltageAboveMax 1.3.6.1.4.1.232.154.2.20002
A UPS device is reporting input voltage above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSInputVoltageNormal 1.3.6.1.4.1.232.154.2.20003
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOutputVoltageBelowMin 1.3.6.1.4.1.232.154.2.20011
A UPS device is reporting output voltage below minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSOutputVoltageAboveMax 1.3.6.1.4.1.232.154.2.20012
A UPS device is reporting output voltage above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSOutputOverload 1.3.6.1.4.1.232.154.2.20014
A UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOutputOverloadCleared 1.3.6.1.4.1.232.154.2.20015
A UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryDepleted 1.3.6.1.4.1.232.154.2.20022
A UPS device is a depleted battery.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSBatteryLevelNormal 1.3.6.1.4.1.232.154.2.20023
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOnBypass 1.3.6.1.4.1.232.154.2.20032
A UPS device is being bypassed.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSTemperatureLow 1.3.6.1.4.1.232.154.2.20101
A UPS device is reporting temperature blow minimum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSTemperatureHigh 1.3.6.1.4.1.232.154.2.20102
A UPS device is reporting temperature above maximum threshold.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSTemperatureNormal 1.3.6.1.4.1.232.154.2.20103
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSInternalFailure 1.3.6.1.4.1.232.154.2.20111
A UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSInternalFailureCleared 1.3.6.1.4.1.232.154.2.20112
A UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryFailure 1.3.6.1.4.1.232.154.2.20121
A UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryFailureCleared 1.3.6.1.4.1.232.154.2.20122
A UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSDiagnosticTestFailed 1.3.6.1.4.1.232.154.2.20131
A UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSDiagnosticTestSucceeded 1.3.6.1.4.1.232.154.2.20132
A UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSInputUnderOverFreq 1.3.6.1.4.1.232.154.2.20141
Input (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSInputUnderOverFreqCleared 1.3.6.1.4.1.232.154.2.20142
Measured input frequency is normal
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cppqRPMtrapUPSStartedOnBattery 1.3.6.1.4.1.232.154.2.20151
A UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cppqRPMtrapUPSStartedOnBatteryCleared 1.3.6.1.4.1.232.154.2.20152
A UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBypassNotAvailable 1.3.6.1.4.1.232.154.2.20161
A UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBypassNotAvailableCleared 1.3.6.1.4.1.232.154.2.20162
A UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSUtilityFail 1.3.6.1.4.1.232.154.2.20171
Indicates that the utility input power is not within predetermined limits. This could be, but is not limited to, over voltage, under voltage, over frequency, under frequency or over current.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSUtilityFailCleared 1.3.6.1.4.1.232.154.2.20172
Indicates that the utility input power is within predetermined limits.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSUtilityNotPresent 1.3.6.1.4.1.232.154.2.20181
Indicates that the utility input is not present. This differs from alarm #57 in that the detected voltage is zero in this case.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSUtilityNotPresentCleared 1.3.6.1.4.1.232.154.2.20182
Indicates that the utility input is present.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSBypassManualTurnedOn 1.3.6.1.4.1.232.154.2.20191
The bypass has been given a manual turn on command.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSBypassManualTurnedOff 1.3.6.1.4.1.232.154.2.20192
The bypass has been given a manual turn off command.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSSiteWiringFault 1.3.6.1.4.1.232.154.2.20201
A UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSSiteWiringNormal 1.3.6.1.4.1.232.154.2.20202
A UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSTemperatureOutOfRange 1.3.6.1.4.1.232.154.2.21007
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSTemperatureOutOfRangeCleared 1.3.6.1.4.1.232.154.2.21008
A UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSShutdownPending 1.3.6.1.4.1.232.154.2.21011
A UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSShutdownPendingCleared 1.3.6.1.4.1.232.154.2.21012
A UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSShutdownImminent 1.3.6.1.4.1.232.154.2.21013
A UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSShutdownImminentCleared 1.3.6.1.4.1.232.154.2.21014
A UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSOutputoutofRange 1.3.6.1.4.1.232.154.2.21019
A UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOutputVoltageNormal 1.3.6.1.4.1.232.154.2.21020
A UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSInputOutofRange 1.3.6.1.4.1.232.154.2.21021
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSInputOutofRangeCleared 1.3.6.1.4.1.232.154.2.21022
A UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSLossOfRedundancy 1.3.6.1.4.1.232.154.2.21023
A UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSLossOfRedundancyCleared 1.3.6.1.4.1.232.154.2.21024
A UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOnBuck 1.3.6.1.4.1.232.154.2.21029
A UPS device is reporting an On Buck condition due to the following. 1. Utility power has increased above recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSOnBoost 1.3.6.1.4.1.232.154.2.21031
A UPS device is reporting an On Boost condition due to the following. 1. Utility power has dropped below recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSManualLoadDumped 1.3.6.1.4.1.232.154.2.21033
The UPS has been powered off with user interaction.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSManualLoadDumpedCleared 1.3.6.1.4.1.232.154.2.21034
The UPS has been powered off with user interaction.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSFanFailure 1.3.6.1.4.1.232.154.2.21035
A UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSFanFailureCleared 1.3.6.1.4.1.232.154.2.21036
A UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSEPOInitiated 1.3.6.1.4.1.232.154.2.21037
A UPS device is reporting an Emergency Power Off (EPO) command has been received to shutdown the UPS immediately with out delay. This command may come from a local control panel or from a remote source. Recommendations: 1. Turn the UPS on to reapply power to attached equipment.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSCheckBreaker 1.3.6.1.4.1.232.154.2.21041
A UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSCheckBreakerCleared 1.3.6.1.4.1.232.154.2.21042
A UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSCabinetDoorOpen 1.3.6.1.4.1.232.154.2.21045
A UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSCabinetDoorOpenCleared 1.3.6.1.4.1.232.154.2.21046
A UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSBypassOnAuto 1.3.6.1.4.1.232.154.2.21047
A UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSBypassOnAutoCleared 1.3.6.1.4.1.232.154.2.21048
A UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteriesDisconnected 1.3.6.1.4.1.232.154.2.21053
A UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteriesDisconnectedCleared 1.3.6.1.4.1.232.154.2.21054
A UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryLow 1.3.6.1.4.1.232.154.2.21055
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryLowCleared 1.3.6.1.4.1.232.154.2.21056
A UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryDischarged 1.3.6.1.4.1.232.154.2.21057
A UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSBatteryDischargedCleared 1.3.6.1.4.1.232.154.2.21058
A UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSBypassONManual 1.3.6.1.4.1.232.154.2.21059
A UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMtrapUPSBypassOffManual 1.3.6.1.4.1.232.154.2.21060
A UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOnBattery 1.3.6.1.4.1.232.154.2.21063
A UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSOnUtilityPower 1.3.6.1.4.1.232.154.2.21064
A UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  
  cpqRPMTrapURL  

cpqRPMTrapUPSDCStartOccurred 1.3.6.1.4.1.232.154.2.29998
The UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTrapUPSDCStartOccurredCleared 1.3.6.1.4.1.232.154.2.29999
The UPS has been started on utility while AC input power is present.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqRPMTestTrap 1.3.6.1.4.1.232.154.2.50001
This trap is sent to test SNMP setup.
TRAP-TYPE    
  sysName  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceId  
  cpqRPMTrapDeviceName  
  cpqRPMTrapDeviceAddress  
  cpqRPMTrapType  
  cpqRPMTrapSeverity  

cpqPMTraps 1.3.6.1.4.1.232.154.3
OBJECT IDENTIFIER    

cpqPMTrapCritical 1.3.6.1.4.1.232.154.3.1
A critical alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  cpqRPMTrapCode  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceName  
  cpqRPMTrapURL  

cpqPMTrapWarning 1.3.6.1.4.1.232.154.3.2
A warning alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  cpqRPMTrapCode  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceName  
  cpqRPMTrapURL  

cpqPMTrapInformation 1.3.6.1.4.1.232.154.3.3
An information alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  cpqRPMTrapCode  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceName  
  cpqRPMTrapURL  

cpqPMTrapCleared 1.3.6.1.4.1.232.154.3.4
An alarm has cleared. Action: Check the Trap Details for more information.
TRAP-TYPE    
  sysName  
  cpqRPMTrapCode  
  cpqRPMTrapDescription  
  cpqRPMTrapDeviceName  
  cpqRPMTrapURL