CPQWCRM-MIB

File: CPQWCRM-MIB.mib (69247 bytes)

Imported modules

CPQHOST-MIB RFC-1212 RFC1213-MIB
RFC-1215

Imported symbols

compaq OBJECT-TYPE DisplayString
sysName sysDescr sysContact
sysLocation TRAP-TYPE

Defined Objects

cpqWcrm 1.3.6.1.4.1.232.167
OBJECT IDENTIFIER    

cpqWcrmMibRev 1.3.6.1.4.1.232.167.1
OBJECT IDENTIFIER    

alarmSensorInternal 1.3.6.1.4.1.232.167.1
Internal Sensor Alarm
TRAP-TYPE    
  sysContact  
  sysName  
  sysLocation  
  internalMsgIndex  
  internalMsgText  
  internalMsgStatus  
  internalSensorValue  
  cpqWcrmURL  

cpqWcrmMibMajRev 1.3.6.1.4.1.232.167.1.1
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
OBJECT-TYPE    
  INTEGER 1..65535  

cpqWcrmMibMinRev 1.3.6.1.4.1.232.167.1.2
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
OBJECT-TYPE    
  INTEGER 0..65535  

cpqWcrmMibCondition 1.3.6.1.4.1.232.167.1.3
The overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on Environmental Controller) (4) a major problem (red LED on Environmental Controller) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on Environmental Controller)
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4), configChanged(5)  

cpqWcrmStatus 1.3.6.1.4.1.232.167.2
OBJECT IDENTIFIER    

alarmSensorWaterCoolUnit 1.3.6.1.4.1.232.167.2
Water Cool Unit Sensor Alarm
TRAP-TYPE    
  sysContact  
  sysName  
  sysLocation  
  waterCoolUnitMsgIndex  
  waterCoolUnitMsgText  
  waterCoolUnitMsgStatus  
  waterCoolUnitSensorValue  
  cpqWcrmURL  

cpqWcrmStatusDeviceEnvironmentalController 1.3.6.1.4.1.232.167.2.1
General Status of Environmental Controller unit itself (1) failed (2) OK
OBJECT-TYPE    
  INTEGER failed(1), ok(2)  

cpqWcrmUnitsConnected 1.3.6.1.4.1.232.167.2.2
Number of sensor units connected to the Environmental Controller, Port 1 to 2
OBJECT-TYPE    
  INTEGER  

cpqWcrmStatusSensorInternal 1.3.6.1.4.1.232.167.2.3
OBJECT IDENTIFIER    

cpqWcrmInternalTypeOfDevice 1.3.6.1.4.1.232.167.2.3.1
Type of sensor unit connected to port 1
OBJECT-TYPE    
  INTEGER notAvail(1), unitWcrm(2), unitIO(3)  

cpqWcrmInternalText 1.3.6.1.4.1.232.167.2.3.2
Descriptional text for sensor unit connected to port 1
OBJECT-TYPE    
  DisplayString SIZE(0..10)  

cpqWcrmInternalSerial 1.3.6.1.4.1.232.167.2.3.3
Serialnumber of sensor unit connected to port 1
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalStatus 1.3.6.1.4.1.232.167.2.3.4
General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), reset(4), timeout(5), detected(6), notAvail(7), lowPower(8)  

cpqWcrmStatusInternalSensors 1.3.6.1.4.1.232.167.2.3.5
OBJECT IDENTIFIER    

cpqWcrmInternalNumberOfSensors 1.3.6.1.4.1.232.167.2.3.5.1
Number of sensors connected to sensor unit 1
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalSensorTable 1.3.6.1.4.1.232.167.2.3.5.2
Headline of sensor table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalSensorEntry

cpqWcrmInternalSensorEntry 1.3.6.1.4.1.232.167.2.3.5.2.1
Entries of sensor table
OBJECT-TYPE    
  CpqWcrmInternalSensorEntry  

internalSensorIndex 1.3.6.1.4.1.232.167.2.3.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfSensors.
OBJECT-TYPE    
  INTEGER 1..65535  

internalSensorType 1.3.6.1.4.1.232.167.2.3.5.2.1.2
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from Environmental Controller-FAS-Unit 20: leakage sensor
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), access(4), vibration(5), motion(6), smoke(7), airFlow(8), type6(9), temperature(10), current4to20(11), humidity(12), userNO(13), userNC(14), voltOK(17), voltage(18), fanOK(19), leakage(20)  

internalSensorText 1.3.6.1.4.1.232.167.2.3.5.2.1.3
Descriptional text for each sensor (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

internalSensorStatus 1.3.6.1.4.1.232.167.2.3.5.2.1.4
Actual status of the sensor
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)  

internalSensorValue 1.3.6.1.4.1.232.167.2.3.5.2.1.5
Value of sensor
OBJECT-TYPE    
  INTEGER  

internalSensorSetHigh 1.3.6.1.4.1.232.167.2.3.5.2.1.6
Value for high setpoint of sensor
OBJECT-TYPE    
  INTEGER  

internalSensorSetLow 1.3.6.1.4.1.232.167.2.3.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
OBJECT-TYPE    
  INTEGER  

internalSensorSetWarn 1.3.6.1.4.1.232.167.2.3.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
OBJECT-TYPE    
  INTEGER  

cpqWcrmStatusInternalOutputs 1.3.6.1.4.1.232.167.2.3.6
OBJECT IDENTIFIER    

cpqWcrmInternalNumberOfOutputs 1.3.6.1.4.1.232.167.2.3.6.1
Number of outputs available on internal sensor
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalOutputTable 1.3.6.1.4.1.232.167.2.3.6.2
Headline of output table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalOutputEntry

cpqWcrmInternalOutputEntry 1.3.6.1.4.1.232.167.2.3.6.2.1
Entries of output table
OBJECT-TYPE    
  CpqWcrmInternalOutputEntry  

internalOutputIndex 1.3.6.1.4.1.232.167.2.3.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfOutputs.
OBJECT-TYPE    
  INTEGER 1..65535  

internalOutputType 1.3.6.1.4.1.232.167.2.3.6.2.1.2
Type of output which is connected to internal sensor to output[internalOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 6, universal relay output 5: output type 8, power output
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), universalOut(4), powerOut(5)  

internalOutputText 1.3.6.1.4.1.232.167.2.3.6.2.1.3
Descriptional text for each output (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

internalOutputStatus 1.3.6.1.4.1.232.167.2.3.6.2.1.4
Actual status of the output
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

internalOutputValue 1.3.6.1.4.1.232.167.2.3.6.2.1.5
Value for output
OBJECT-TYPE    
  INTEGER  

internalOutputSet 1.3.6.1.4.1.232.167.2.3.6.2.1.6
Command for output
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

internalOutputConfig 1.3.6.1.4.1.232.167.2.3.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

internalOutputDelay 1.3.6.1.4.1.232.167.2.3.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
OBJECT-TYPE    
  INTEGER  

internalOutputTimeoutAction 1.3.6.1.4.1.232.167.2.3.6.2.1.9
State for output if timeout (RS422) occurs
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cpqWcrmStatusInternalMsg 1.3.6.1.4.1.232.167.2.3.7
OBJECT IDENTIFIER    

cpqWcrmInternalNumberOfMsgs 1.3.6.1.4.1.232.167.2.3.7.1
Number of messages that can be created with internal sensor
OBJECT-TYPE    
  INTEGER  

cpqWcrmInternalMsgTable 1.3.6.1.4.1.232.167.2.3.7.2
Headline of message table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmInternalMsgEntry

cpqWcrmInternalMsgEntry 1.3.6.1.4.1.232.167.2.3.7.2.1
Entries of message table
OBJECT-TYPE    
  CpqWcrmInternalMsgEntry  

internalMsgIndex 1.3.6.1.4.1.232.167.2.3.7.2.1.1
Index for the list of message entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfMsgs.
OBJECT-TYPE    
  INTEGER 1..65535  

internalMsgText 1.3.6.1.4.1.232.167.2.3.7.2.1.2
Descriptional text for each message (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

internalMsgStatus 1.3.6.1.4.1.232.167.2.3.7.2.1.3
Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to ON 10: output is set to OFF
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10)  

internalMsgRelay 1.3.6.1.4.1.232.167.2.3.7.2.1.4
Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgBeeper 1.3.6.1.4.1.232.167.2.3.7.2.1.5
Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap1 1.3.6.1.4.1.232.167.2.3.7.2.1.6
Trap receiver 1 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap2 1.3.6.1.4.1.232.167.2.3.7.2.1.7
Trap receiver 2 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap3 1.3.6.1.4.1.232.167.2.3.7.2.1.8
Trap receiver 3 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgTrap4 1.3.6.1.4.1.232.167.2.3.7.2.1.9
Trap receiver 4 and Event Logging activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

internalMsgReset 1.3.6.1.4.1.232.167.2.3.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

cpqWcrmStatusSensorWaterCoolUnit 1.3.6.1.4.1.232.167.2.4
OBJECT IDENTIFIER    

cpqWcrmWaterCoolUnitTypeOfDevice 1.3.6.1.4.1.232.167.2.4.1
Type of sensor unit connected to port 2
OBJECT-TYPE    
  INTEGER notAvail(1), unitWcrm(2), unitIO(3)  

cpqWcrmWaterCoolUnitText 1.3.6.1.4.1.232.167.2.4.2
Descriptional text for sensor unit connected to port 2
OBJECT-TYPE    
  DisplayString SIZE(0..10)  

cpqWcrmWaterCoolUnitSerial 1.3.6.1.4.1.232.167.2.4.3
Serialnumber of sensor unit connected to port 2
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitStatus 1.3.6.1.4.1.232.167.2.4.4
General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low
OBJECT-TYPE    
  INTEGER ok(1), error(2), changed(3), reset(4), timeout(5), detected(6), notAvail(7), lowPower(8)  

cpqWcrmStatusWaterCoolUnitSensors 1.3.6.1.4.1.232.167.2.4.5
OBJECT IDENTIFIER    

cpqWcrmWaterCoolUnitNumberOfSensors 1.3.6.1.4.1.232.167.2.4.5.1
Number of sensors connected to water cool unit
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitSensorTable 1.3.6.1.4.1.232.167.2.4.5.2
Headline of sensor table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitSensorEntry

cpqWcrmWaterCoolUnitSensorEntry 1.3.6.1.4.1.232.167.2.4.5.2.1
Entries of sensor table
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitSensorEntry  

waterCoolUnitSensorIndex 1.3.6.1.4.1.232.167.2.4.5.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors.
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitSensorType 1.3.6.1.4.1.232.167.2.4.5.2.1.2
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: average temperature of air inlet to rack, average or max/min from each HEX 5: average temperature of air outlet from rack, average or max/min from each HEX 6: heatflow sensor 7: alarm: Bit 0: Leakage Bit 1: IIC Failure 8: warning: Bit 0..2: Fan Tach 1..3 Bit 3,4: Temp. sensor HEX1 In,Out Bit 5,6: Temp. sensor HEX2 In,Out Bit 7,8: Temp. sensor HEX3 In,Out Bit 9: Air temp. sensor Bit 10..12: IIC failure, HEX1..3 Bit 13: Waterflow low Bit 14,15: Watertemp. In,Out Bit 16: Waterflow sensor fail. Bit 17: Magnetic valve fail. Bit 18: Leakdetector fail. Bit 19: Uneven heat load Bit 20: Condensation Pump Cycles > Max Bit 21: Condensation Pump Running Time > Max 9: rpm speed of Fan1 10: rpm speed of Fan2 11: rpm speed of Fan3 12: fanSpeed setpoint, calculated from average temperatures 13: temperature air inlet to rack, HEX 1 14: temperature air outlet from rack, HEX 1 15: temperature air inlet to rack, HEX 1 16: temperature air outlet from rack, HEX 1 17: temperature air inlet to rack, HEX 1 18: temperature air outlet from rack, HEX 1 19: water temperature In 20: water temperature Out 21: water Flow 22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%) 23: status: Bit 0..Bit 2: fan module 1..3 available Bit 3: water module available 24: condensation pump number of seconds on counter (last operating time) 25: condensation pump on/off cycle counter 26: rpm speed of Fan4 27: rpm speed of Fan5 28: rpm speed of Fan6 29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2 30: water valve actual value (%)
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), tempIn(4), tempOut(5), heatFlow(6), alarm(7), warning(8), rpmFan1(9), rpmFan2(10), rpmFan3(11), fanSpeed(12), tempIn1(13), tempOut1(14), tempIn2(15), tempOut2(16), tempIn3(17), tempOut3(18), tempWaterIn(19), tempWaterOut(20), waterFlow(21), valve(22), status(23), condensateDuration(24), condensateCycles(25), rpmFan4(26), rpmFan5(27), rpmFan6(28), transfSwitch(29), valveActValue(30)  

waterCoolUnitSensorText 1.3.6.1.4.1.232.167.2.4.5.2.1.3
Descriptional text for each sensor (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

waterCoolUnitSensorStatus 1.3.6.1.4.1.232.167.2.4.5.2.1.4
Actual status of the sensor
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), warning(7), tooLow(8), tooHigh(9)  

waterCoolUnitSensorValue 1.3.6.1.4.1.232.167.2.4.5.2.1.5
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex) If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperature. If msg index = 2: This value represents the bit coded warning condition Bit 0: Top Fan Module Failed Bit 1: Middle Fan Module Failed Bit 2: Bottom Fan Module Failed Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed Bit 9: Air Temperature Sensor Failed Bit 10: Top Fan not installed Bit 11: Middle Fan not installed Bit 12: Bottom Fan not installed Bit 13: Waterflow low Bit 14: Water Unit Temperature Input Out of Range Bit 15: Water Unit Temperature Output Out of Range Bit 16: Waterflow Sensor Value Out of Range Bit 17: Water Valve Failed Bit 18: Leakdetector Failed Bit 19: Heat Load Warning Bit 20: The Condensation Pump has exceeded the max. number of cycles Bit 21: The Condensation Pump has exceeded the max. Running Time If msg index = 3: This value represents the bit coded alarm condition Bit 0: Leakage Detected Bit 1: Comm. Failure IIC
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetHigh 1.3.6.1.4.1.232.167.2.4.5.2.1.6
Value for high setpoint of sensor
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetLow 1.3.6.1.4.1.232.167.2.4.5.2.1.7
Value for low setpoint of sensor, also used as alarm delay
OBJECT-TYPE    
  INTEGER  

waterCoolUnitSensorSetWarn 1.3.6.1.4.1.232.167.2.4.5.2.1.8
Value for warning setpoint of sensor, also used as fan threshold
OBJECT-TYPE    
  INTEGER  

cpqWcrmStatusWaterCoolUnitOutputs 1.3.6.1.4.1.232.167.2.4.6
OBJECT IDENTIFIER    

cpqWcrmWaterCoolUnitNumberOfOutputs 1.3.6.1.4.1.232.167.2.4.6.1
Number of outputs available on sensor water cool unit
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitOutputTable 1.3.6.1.4.1.232.167.2.4.6.2
Headline of output table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitOutputEntry

cpqWcrmWaterCoolUnitOutputEntry 1.3.6.1.4.1.232.167.2.4.6.2.1
Entries of output table
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitOutputEntry  

waterCoolUnitOutputIndex 1.3.6.1.4.1.232.167.2.4.6.2.1.1
Index for the list of output entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs.
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitOutputType 1.3.6.1.4.1.232.167.2.4.6.2.1.2
Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: water valve setpoint 5: water valve hysteresis 6: command for manual control 7: Flow Meter Model, 0=SIKA, 1=Chemline 8: minimum fan speed 9: min delta T, used for fan control 10: max delta T, used for fan control 11: specific heat capacity 12: setpoint heatload warning 13: setpoint Water Flow Loss Emergency Door Opening 14: setpoint High Temperature Emergency Door Opening 15: setpoint Condensation Pump Cycles (Warning) 16: setpoint Condensation Pump Running Time (Warning) 17: command for door opening, 0=lock door, 1=unlock door 18: KP parameter for PID controller 19: KI parameter for PID controller 20: KD parameter for PID controller 21: sampling time PID controller
OBJECT-TYPE    
  INTEGER notAvail(1), failure(2), overflow(3), setpoint(4), hysteresis(5), command(6), controlMode(7), fanSpeedMin(8), dTmin(9), dTmax(10), cpWatert(11), setHeatload(12), setEdoFlow(13), setEdoHeat(14), setCondCycles(15), setCondRun(16), doorControl(17), pidContrKP(18), pidContrKI(19), pidContrKD(20), pidSampleTime(21)  

waterCoolUnitOutputText 1.3.6.1.4.1.232.167.2.4.6.2.1.3
Descriptional text for each output (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

waterCoolUnitOutputStatus 1.3.6.1.4.1.232.167.2.4.6.2.1.4
Actual status of the output
OBJECT-TYPE    
  INTEGER notAvail(1), lost(2), changed(3), ok(4), off(5), on(6), setOff(7), setOn(8)  

waterCoolUnitOutputValue 1.3.6.1.4.1.232.167.2.4.6.2.1.5
Signed value for output
OBJECT-TYPE    
  INTEGER  

waterCoolUnitOutputSet 1.3.6.1.4.1.232.167.2.4.6.2.1.6
Command for output
OBJECT-TYPE    
  INTEGER off(1), on(2), lock(3), unlock(4), unlockDelay(5)  

waterCoolUnitOutputConfig 1.3.6.1.4.1.232.167.2.4.6.2.1.7
Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
OBJECT-TYPE    
  INTEGER disRemote(1), enRemote(2)  

waterCoolUnitOutputDelay 1.3.6.1.4.1.232.167.2.4.6.2.1.8
Unsigned Value for delay, after this time the output will fall into the previous state
OBJECT-TYPE    
  INTEGER  

waterCoolUnitOutputTimeoutAction 1.3.6.1.4.1.232.167.2.4.6.2.1.9
State for output if timeout (RS422) occurs
OBJECT-TYPE    
  INTEGER stay(1), off(2), on(3)  

cpqWcrmStatusWaterCoolUnitMsg 1.3.6.1.4.1.232.167.2.4.7
OBJECT IDENTIFIER    

cpqWcrmWaterCoolUnitNumberOfMsgs 1.3.6.1.4.1.232.167.2.4.7.1
Number of alarms that can be created with water cool unit
OBJECT-TYPE    
  INTEGER  

cpqWcrmWaterCoolUnitMsgTable 1.3.6.1.4.1.232.167.2.4.7.2
Headline of message table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmWaterCoolUnitMsgEntry

cpqWcrmWaterCoolUnitMsgEntry 1.3.6.1.4.1.232.167.2.4.7.2.1
Entries of message table
OBJECT-TYPE    
  CpqWcrmWaterCoolUnitMsgEntry  

waterCoolUnitMsgIndex 1.3.6.1.4.1.232.167.2.4.7.2.1.1
Index for the list of alarm entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs.
OBJECT-TYPE    
  INTEGER 1..65535  

waterCoolUnitMsgText 1.3.6.1.4.1.232.167.2.4.7.2.1.2
Descriptional text for each message (entry in the table)
OBJECT-TYPE    
  DisplayString SIZE(0..20)  

waterCoolUnitMsgStatus 1.3.6.1.4.1.232.167.2.4.7.2.1.3
Actual message status 4: OK 5: alarm 6: warning 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold
OBJECT-TYPE    
  INTEGER notAvail(1), configChanged(2), error(3), ok(4), alarm(5), warning(6), tooLow(7), tooHigh(8), setOff(9), setOn(10)  

waterCoolUnitMsgRelay 1.3.6.1.4.1.232.167.2.4.7.2.1.4
Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgBeeper 1.3.6.1.4.1.232.167.2.4.7.2.1.5
Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap1 1.3.6.1.4.1.232.167.2.4.7.2.1.6
Trap receiver 1 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap2 1.3.6.1.4.1.232.167.2.4.7.2.1.7
Trap receiver 2 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap3 1.3.6.1.4.1.232.167.2.4.7.2.1.8
Trap receiver 3 activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgTrap4 1.3.6.1.4.1.232.167.2.4.7.2.1.9
Trap receiver 4 and Event Logging activated
OBJECT-TYPE    
  INTEGER disable(1), enable(2)  

waterCoolUnitMsgReset 1.3.6.1.4.1.232.167.2.4.7.2.1.10
Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
OBJECT-TYPE    
  INTEGER auto(1), manual(2)  

cpqWcrmURL 1.3.6.1.4.1.232.167.2.7
URL of the management interface in the format http[s]://ipaddr[:port#][/page]
OBJECT-TYPE    
  DisplayString SIZE(0..80)  

cpqWcrmSetup 1.3.6.1.4.1.232.167.3
OBJECT IDENTIFIER    

cpqWcrmSetupGeneral 1.3.6.1.4.1.232.167.3.1
OBJECT IDENTIFIER    

cpqWcrmSetTempUnit 1.3.6.1.4.1.232.167.3.1.1
Unit of all temperature values and setpoints, Celsius or Fahrenheit
OBJECT-TYPE    
  INTEGER celsius(1), fahrenheit(2)  

cpqWcrmSetBeeper 1.3.6.1.4.1.232.167.3.1.2
Audible alarm in Environmental Controller unit: (2): beeper is on (1): beeper is off (general)
OBJECT-TYPE    
  INTEGER off(1), on(2)  

cpqWcrmResetRelay 1.3.6.1.4.1.232.167.3.1.3
Enable or disable acknowledging currently active alarm relay (with 'C' on Environmental Controller).
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cpqWcrmLogicRelay 1.3.6.1.4.1.232.167.3.1.4
Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
OBJECT-TYPE    
  INTEGER closeAtAlarm(1), openAtAlarm(2), off(3)  

cpqWcrmWebAccess 1.3.6.1.4.1.232.167.3.1.5
Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
OBJECT-TYPE    
  INTEGER viewOnly(1), fullAccess(2), off(3)  

cpqWcrmSetupDate 1.3.6.1.4.1.232.167.3.1.6
actual Date in format DD.MM.YYYY
OBJECT-TYPE    
  DisplayString SIZE(0..10)  

cpqWcrmSetupTime 1.3.6.1.4.1.232.167.3.1.7
actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
OBJECT-TYPE    
  DisplayString SIZE(0..8)  

cpqWcrmTimerTable1 1.3.6.1.4.1.232.167.3.1.8
OBJECT IDENTIFIER    

cpqWcrmTimerNumber 1.3.6.1.4.1.232.167.3.1.8.1
Number of value-table entries=number of outlets available on this unit
OBJECT-TYPE    
  INTEGER  

cpqWcrmTimerTable 1.3.6.1.4.1.232.167.3.1.8.2
Headline of status-table
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmTimerEntry

cpqWcrmTimerEntry 1.3.6.1.4.1.232.167.3.1.8.2.1
Entries of timer-table
OBJECT-TYPE    
  CpqWcrmTimerEntry  

cpqWcrmTimerIndex 1.3.6.1.4.1.232.167.3.1.8.2.1.1
Index for the list of timer entries. Its value ranges between 1 and the value of cpqWcrmTimerNumber.
OBJECT-TYPE    
  INTEGER 1..65535  

cpqWcrmTimerStatus 1.3.6.1.4.1.232.167.3.1.8.2.1.2
Actual status of the timer
OBJECT-TYPE    
  INTEGER switchedOff(1), switchedOn(2), noTime(3)  

cpqWcrmTimerDayOfWeek 1.3.6.1.4.1.232.167.3.1.8.2.1.3
Selection of day of week for timer to switch
OBJECT-TYPE    
  INTEGER sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat-sun(8), mon-fri(9), mon-sun(10)  

cpqWcrmTimeOn 1.3.6.1.4.1.232.167.3.1.8.2.1.4
Time to switch on current function, Format: HH:MM
OBJECT-TYPE    
  DisplayString SIZE(0..5)  

cpqWcrmTimeOff 1.3.6.1.4.1.232.167.3.1.8.2.1.5
Time to switch off current function, Format: HH:MM
OBJECT-TYPE    
  DisplayString SIZE(0..5)  

cpqWcrmTimeControl 1.3.6.1.4.1.232.167.3.1.8.2.1.6
Control via RTC
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

cpqWcrmTimerFunction 1.3.6.1.4.1.232.167.3.1.8.2.1.7
Function which is controlled via timer 1-4: sending Traps to this Trap receiver will be disabled 5 - 8: scheduled alarm off
OBJECT-TYPE    
  INTEGER disTrapRec1(1), disTrapRec2(2), disTrapRec3(3), disTrapRec4(4), schedule1(5), schedule2(6), schedule3(7), schedule4(8)  

cpqWcrmSetFlowUnit 1.3.6.1.4.1.232.167.3.1.9
Unit of Water Flow, Liter/min or Gallon/min
OBJECT-TYPE    
  INTEGER literMin(1), gallonMin(2)  

cpqWcrmTrapControl 1.3.6.1.4.1.232.167.4
OBJECT IDENTIFIER    

cpqWcrmTraps 1.3.6.1.4.1.232.167.4.7
OBJECT IDENTIFIER    

cpqWcrmTraptableNumber 1.3.6.1.4.1.232.167.4.7.1
Number of trapTable entries. The number of trap-receiver
OBJECT-TYPE    
  INTEGER  

cpqWcrmTrapTableTable 1.3.6.1.4.1.232.167.4.7.2
A list of trap-receiver entries
OBJECT-TYPE    
  SEQUENCE OF  
    CpqWcrmTrapTableEntry

cpqWcrmTrapTableEntry 1.3.6.1.4.1.232.167.4.7.2.1
Entries of trapTable
OBJECT-TYPE    
  CpqWcrmTrapTableEntry  

trapIndex 1.3.6.1.4.1.232.167.4.7.2.1.1
Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
OBJECT-TYPE    
  INTEGER 1..65535  

trapStatus 1.3.6.1.4.1.232.167.4.7.2.1.2
Enable or disable trap receiver
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

trapIPaddress 1.3.6.1.4.1.232.167.4.7.2.1.3
IP-address of trap-receiver
OBJECT-TYPE    
  DisplayString SIZE(0..15)  

cpqWcrmControl 1.3.6.1.4.1.232.167.5
OBJECT IDENTIFIER    

alarmInternal 1.3.6.1.4.1.232.167.5
Internal Unit Alarm
TRAP-TYPE    
  sysContact  
  sysName  
  sysLocation  
  cpqWcrmInternalText  
  cpqWcrmInternalStatus  
  cpqWcrmURL  

cpqWcrmResetUnit 1.3.6.1.4.1.232.167.5.1
Command to reset (acknowledge) alarms of Environmental Controller unit. Setting to 'reset' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noReset' (1).
OBJECT-TYPE    
  INTEGER noReset(1), reset(2)  

alarmWaterCoolUnit 1.3.6.1.4.1.232.167.6
Water Cool Unit System Alarm
TRAP-TYPE    
  sysContact  
  sysName  
  sysLocation  
  cpqWcrmWaterCoolUnitText  
  cpqWcrmWaterCoolUnitStatus  
  cpqWcrmURL  

testTrap 1.3.6.1.4.1.232.167.10
Test trap sent to a trap receiver to check proper reception of traps
TRAP-TYPE    
  sysContact  
  sysName  
  sysLocation  
  cpqWcrmURL  

Defined Objects

CpqWcrmInternalSensorEntry  
SEQUENCE    
  INTEGER as internalSensorIndex  
  INTEGER as internalSensorType  
  DisplayString as internalSensorText SIZE(0..20)  
  INTEGER as internalSensorStatus  
  INTEGER as internalSensorValue  
  INTEGER as internalSensorSetHigh  
  INTEGER as internalSensorSetLow  
  INTEGER as internalSensorSetWarn  

CpqWcrmInternalOutputEntry  
SEQUENCE    
  INTEGER as internalOutputIndex  
  INTEGER as internalOutputType  
  DisplayString as internalOutputText SIZE(0..20)  
  INTEGER as internalOutputStatus  
  INTEGER as internalOutputValue  
  INTEGER as internalOutputSet  
  INTEGER as internalOutputConfig  
  INTEGER as internalOutputDelay  
  INTEGER as internalOutputTimeoutAction  

CpqWcrmInternalMsgEntry  
SEQUENCE    
  INTEGER as internalMsgIndex  
  DisplayString as internalMsgText SIZE(0..20)  
  INTEGER as internalMsgStatus  
  INTEGER as internalMsgRelay  
  INTEGER as internalMsgBeeper  
  INTEGER as internalMsgTrap1  
  INTEGER as internalMsgTrap2  
  INTEGER as internalMsgTrap3  
  INTEGER as internalMsgTrap4  
  INTEGER as internalMsgReset  

CpqWcrmWaterCoolUnitSensorEntry  
SEQUENCE    
  INTEGER as waterCoolUnitSensorIndex  
  INTEGER as waterCoolUnitSensorType  
  DisplayString as waterCoolUnitSensorText SIZE(0..20)  
  INTEGER as waterCoolUnitSensorStatus  
  INTEGER as waterCoolUnitSensorValue  
  INTEGER as waterCoolUnitSensorSetHigh  
  INTEGER as waterCoolUnitSensorSetLow  
  INTEGER as waterCoolUnitSensorSetWarn  

CpqWcrmWaterCoolUnitOutputEntry  
SEQUENCE    
  INTEGER as waterCoolUnitOutputIndex  
  INTEGER as waterCoolUnitOutputType  
  DisplayString as waterCoolUnitOutputText SIZE(0..20)  
  INTEGER as waterCoolUnitOutputStatus  
  INTEGER as waterCoolUnitOutputValue  
  INTEGER as waterCoolUnitOutputSet  
  INTEGER as waterCoolUnitOutputConfig  
  INTEGER as waterCoolUnitOutputDelay  
  INTEGER as waterCoolUnitOutputTimeoutAction  

CpqWcrmWaterCoolUnitMsgEntry  
SEQUENCE    
  INTEGER as waterCoolUnitMsgIndex  
  DisplayString as waterCoolUnitMsgText SIZE(0..20)  
  INTEGER as waterCoolUnitMsgStatus  
  INTEGER as waterCoolUnitMsgRelay  
  INTEGER as waterCoolUnitMsgBeeper  
  INTEGER as waterCoolUnitMsgTrap1  
  INTEGER as waterCoolUnitMsgTrap2  
  INTEGER as waterCoolUnitMsgTrap3  
  INTEGER as waterCoolUnitMsgTrap4  
  INTEGER as waterCoolUnitMsgReset  

CpqWcrmTimerEntry  
SEQUENCE    
  INTEGER as cpqWcrmTimerIndex  
  INTEGER as cpqWcrmTimerStatus  
  INTEGER as cpqWcrmTimerDayOfWeek  
  DisplayString as cpqWcrmTimeOn SIZE(0..5)  
  DisplayString as cpqWcrmTimeOff SIZE(0..5)  
  INTEGER as cpqWcrmTimeControl  
  INTEGER as cpqWcrmTimerFunction  

CpqWcrmTrapTableEntry  
SEQUENCE    
  INTEGER as trapIndex  
  INTEGER as trapStatus  
  DisplayString as trapIPaddress