DAMOCLES-MIB

File: DAMOCLES-MIB.mib (13518 bytes)

Imported modules

RFC-1212 RFC1155-SMI SNMPv2-SMI
RFC1213-MIB RFC-1215

Imported symbols

OBJECT-TYPE TimeTicks Gauge
enterprises Gauge32 DisplayString
TRAP-TYPE

Defined Objects

hwgroup 1.3.6.1.4.1.21796
OBJECT IDENTIFIER    

charonII 1.3.6.1.4.1.21796.3
OBJECT IDENTIFIER    

damocles 1.3.6.1.4.1.21796.3.4
OBJECT IDENTIFIER    

inpTable 1.3.6.1.4.1.21796.3.4.1
A list of binary input entries.
OBJECT-TYPE    
  SEQUENCE OF  
    InpEntry

inpChange 1.3.6.1.4.1.21796.3.4.1
Input changed.
TRAP-TYPE    
  inpName  
  inpState  
  inpAlarmState  

inpEntry 1.3.6.1.4.1.21796.3.4.1.1
An entry containing information applicable to a particular binary input.
OBJECT-TYPE    
  InpEntry  

inpIndex 1.3.6.1.4.1.21796.3.4.1.1.1
The binary input index.
OBJECT-TYPE    
  PositiveInteger  

inpState 1.3.6.1.4.1.21796.3.4.1.1.2
The binary input state.
OBJECT-TYPE    
  OnOff  

inpName 1.3.6.1.4.1.21796.3.4.1.1.3
The binary input name.
OBJECT-TYPE    
  IOName  

inpAlarmSetup 1.3.6.1.4.1.21796.3.4.1.1.4
You can enable alarm for this binary input. Alarm can be inactive or active for ON/OFF state.
OBJECT-TYPE    
  InputAlarmSetup  

inpAlarmState 1.3.6.1.4.1.21796.3.4.1.1.5
The binary input alarm state.
OBJECT-TYPE    
  InputAlarmState  

inpCounter 1.3.6.1.4.1.21796.3.4.1.1.6
Number of pulses on this input. Entering edge is used to increment this counter. Only pulses longer than sampling interval are counted.
OBJECT-TYPE    
  NonNegativeInteger  

outTable 1.3.6.1.4.1.21796.3.4.2
A list of binary output entries.
OBJECT-TYPE    
  SEQUENCE OF  
    OutEntry

sensStateChanged 1.3.6.1.4.1.21796.3.4.2
Sensor n changed its state.
TRAP-TYPE    
  sensName  
  sensID  
  sensState  
  sensValue  
  sensUnit  

outEntry 1.3.6.1.4.1.21796.3.4.2.1
An entry containing information applicable to a particular binary output.
OBJECT-TYPE    
  OutEntry  

outIndex 1.3.6.1.4.1.21796.3.4.2.1.1
The binary output index.
OBJECT-TYPE    
  PositiveInteger  

outState 1.3.6.1.4.1.21796.3.4.2.1.2
The binary output state. 0 off(open), 1 on(close), 2 off if any alarm, 3 on if any alarm
OBJECT-TYPE    
  OnOff  

outName 1.3.6.1.4.1.21796.3.4.2.1.3
The binary output name.
OBJECT-TYPE    
  IOName  

outType 1.3.6.1.4.1.21796.3.4.2.1.4
The binary output type. 0 relay (off, on), 1 rts (-10,+10v), 2 dtr (0,10v)
OBJECT-TYPE    
  OutputType  

sensTable 1.3.6.1.4.1.21796.3.4.3
A list of sensor table entries. The number of entries corresponds with number of detected sensors.
OBJECT-TYPE    
  SEQUENCE OF  
    SensEntry

tsTrapNewAlarm 1.3.6.1.4.1.21796.3.4.3
This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for powerFailure.
TRAP-TYPE    
  tsAlarmId  
  tsAlarmDescr  

sensEntry 1.3.6.1.4.1.21796.3.4.3.1
An entry containing information applicable to a particular sensor.
OBJECT-TYPE    
  SensEntry  

sensIndex 1.3.6.1.4.1.21796.3.4.3.1.1
The sensor index.
OBJECT-TYPE    
  PositiveInteger  

sensName 1.3.6.1.4.1.21796.3.4.3.1.2
The sensor name.
OBJECT-TYPE    
  SensorName  

sensState 1.3.6.1.4.1.21796.3.4.3.1.4
The sensor state.
OBJECT-TYPE    
  SensorState  

sensString 1.3.6.1.4.1.21796.3.4.3.1.5
The string representation of sensor value.
OBJECT-TYPE    
  SensorString  

sensValue 1.3.6.1.4.1.21796.3.4.3.1.6
The integer (decimal * 10) representation of sensor value.
OBJECT-TYPE    
  SensorValue  

sensValueRaw 1.3.6.1.4.1.21796.3.4.3.1.7
The original raw value of sensor (it differs for each sensor type, especially 1-Wire sensors have different precisions).
OBJECT-TYPE    
  SensorValue  

sensID 1.3.6.1.4.1.21796.3.4.3.1.8
The sensor ID.
OBJECT-TYPE    
  SensorID  

sensUnit 1.3.6.1.4.1.21796.3.4.3.1.9
The sensor unit.
OBJECT-TYPE    
  UnitType  

tsTrapAlarmEnd 1.3.6.1.4.1.21796.3.4.4
This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms.
TRAP-TYPE    
  tsAlarmId  
  tsAlarmDescr  

tsAlarm 1.3.6.1.4.1.21796.3.4.50
OBJECT IDENTIFIER    

tsAlarmsPresent 1.3.6.1.4.1.21796.3.4.50.1
The present number of active alarm conditions.
OBJECT-TYPE    
  Gauge32  

tsAlarmTable 1.3.6.1.4.1.21796.3.4.50.2
A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with tsAlarmId equal to 1, and increments the value of tsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of tsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because tsAlarmId might have wrapped. The number of rows in the table at any given time is reflected by the value of tsAlarmsPresent.
OBJECT-TYPE    
  SEQUENCE OF  
    TsAlarmEntry

tsAlarmEntry 1.3.6.1.4.1.21796.3.4.50.2.1
An entry containing information applicable to a particular alarm.
OBJECT-TYPE    
  TsAlarmEntry  

tsAlarmIdx 1.3.6.1.4.1.21796.3.4.50.2.1.1
An index to alarm table.
OBJECT-TYPE    
  PositiveInteger  

tsAlarmId 1.3.6.1.4.1.21796.3.4.50.2.1.2
A unique identifier for an alarm condition. This value must remain constant.
OBJECT-TYPE    
  PositiveInteger  

tsAlarmDescr 1.3.6.1.4.1.21796.3.4.50.2.1.3
Description of the alarm condition.
OBJECT-TYPE    
  INTEGER inputStateAlarm(1), temperatureOutOfRange(2), maskStateAlarm(3)  

tsAlarmSensName 1.3.6.1.4.1.21796.3.4.50.2.1.4
Name of sensor with alarm condition.
OBJECT-TYPE    
  SensorName  

tsAlarmTime 1.3.6.1.4.1.21796.3.4.50.2.1.5
The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of tsAlarmTime shall equal 0.
OBJECT-TYPE    
  TimeStamp  

setup 1.3.6.1.4.1.21796.3.4.99
OBJECT IDENTIFIER    

sensSetup 1.3.6.1.4.1.21796.3.4.99.1
OBJECT IDENTIFIER    

unitType 1.3.6.1.4.1.21796.3.4.99.1.1
Units for displayed values. All setup values are fixed in Celsius
OBJECT-TYPE    
  UnitType  

sensSetupTable 1.3.6.1.4.1.21796.3.4.99.1.2
A list of sensor table setup entries. The number of entries corresponds with number of detected sensors.
OBJECT-TYPE    
  SEQUENCE OF  
    SensSetupEntry

sensSetupEntry 1.3.6.1.4.1.21796.3.4.99.1.2.1
An entry containing setup information for a particular sensor.
OBJECT-TYPE    
  SensSetupEntry  

sensSetupIndex 1.3.6.1.4.1.21796.3.4.99.1.2.1.1
The sensor setup table index.
OBJECT-TYPE    
  PositiveInteger  

sensSetupName 1.3.6.1.4.1.21796.3.4.99.1.2.1.2
The sensor name.
OBJECT-TYPE    
  SensorName  

sensFlags 1.3.6.1.4.1.21796.3.4.99.1.2.1.5
The behaviour of sensor - 0x01: range or level detection - 0x02: enable trap sending -- 0x04: output set (thermostat) - 0x08: sensor enabled - 0x10: enable SMS sending - 0x20: enable email sending.
OBJECT-TYPE    
  SensorFlags  

sensLimitMin 1.3.6.1.4.1.21796.3.4.99.1.2.1.6
The sensor low limit.
OBJECT-TYPE    
  SensorValue  

sensLimitMax 1.3.6.1.4.1.21796.3.4.99.1.2.1.7
The sensor high limit.
OBJECT-TYPE    
  SensorValue  

sensHysteresis 1.3.6.1.4.1.21796.3.4.99.1.2.1.8
The sensor hysteresis.
OBJECT-TYPE    
  SensorValue  

Defined Objects

PositiveInteger  
INTEGER 1..2147483647    

NonNegativeInteger  
INTEGER 0..2147483647    

OnOff  
INTEGER off(1), on(2)    

OutputType  
INTEGER onOff(0), rts(1), dtr(2)    

UnitType  
INTEGER celsius(0), fahrenheit(1), kelvin(2), percent(3), volt(4), miliamper(5), nounit(6), pulse(7), switch(8)    

InputAlarmSetup  
INTEGER inactive(0), activeOff(1), activeOn(2)    

InputAlarmState  
INTEGER normal(1), alarm(2)    

SensorState  
INTEGER invalid(0), normal(1), alarmstate(2), alarm(3)    

SensorID  
INTEGER 0..65535    

IOName  
DisplayString SIZE(0..12)    

SensorName  
DisplayString SIZE(0..16)    

SensorValue  
INTEGER    

SensorString  
DisplayString SIZE(0..10)    

SensorFlags  
INTEGER    

TimeStamp  
TimeTicks    

InpEntry  
SEQUENCE    
  PositiveInteger as inpIndex  
  OnOff as inpState  
  IOName as inpName  
  InputAlarmSetup as inpAlarmSetup  
  InputAlarmState as inpAlarmState  
  NonNegativeInteger as inpCounter  

OutEntry  
SEQUENCE    
  PositiveInteger as outIndex  
  OnOff as outState  
  IOName as outName  
  OutputType as outType  

SensEntry  
SEQUENCE    
  PositiveInteger as sensIndex  
  SensorName as sensName  
  SensorState as sensState  
  SensorString as sensString  
  SensorValue as sensValue  
  SensorValue as sensValueRaw  
  SensorID as sensID  
  UnitType as sensUnit  

TsAlarmEntry  
SEQUENCE    
  PositiveInteger as tsAlarmIdx  
  PositiveInteger as tsAlarmId  
  INTEGER as tsAlarmDescr  
  SensorName as tsAlarmSensName  
  TimeStamp as tsAlarmTime  

SensSetupEntry  
SEQUENCE    
  PositiveInteger as sensSetupIndex  
  SensorName as sensSetupName  
  SensorFlags as sensFlags  
  SensorValue as sensLimitMin  
  SensorValue as sensLimitMax  
  SensorValue as sensHysteresis