LIEBERT-GP-CONDITIONS-MIB

File: LIEBERT-GP-CONDITIONS-MIB.mib (110212 bytes)

Imported modules

SNMPv2-TC SNMPv2-SMI LIEBERT-GP-REGISTRATION-MIB

Imported symbols

DisplayString MODULE-IDENTITY OBJECT-IDENTITY
OBJECT-TYPE Gauge32 TimeTicks
Unsigned32 lgpConditions liebertConditionsModuleReg

Defined Objects

liebertGlobalProductsConditionsModule 1.3.6.1.4.1.476.1.42.1.3.1
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY    

lgpConditionsWellKnown 1.3.6.1.4.1.476.1.42.3.2.1
OBJECT IDENTIFIER    

lgpConditionHighTemperature 1.3.6.1.4.1.476.1.42.3.2.1.1
The temperature has exceeded the high temperature threshold.
OBJECT-IDENTITY    

lgpConditionLowTemperature 1.3.6.1.4.1.476.1.42.3.2.1.2
The temperature is below the low temperature threshold.
OBJECT-IDENTITY    

lgpConditionHighHumidity 1.3.6.1.4.1.476.1.42.3.2.1.3
The humidity has exceeded the high humidity threshold.
OBJECT-IDENTITY    

lgpConditionLowHumidity 1.3.6.1.4.1.476.1.42.3.2.1.4
The humidity is below the low humidity threshold.
OBJECT-IDENTITY    

lgpConditionLossOfAirflow 1.3.6.1.4.1.476.1.42.3.2.1.5
The system has detected a loss of air flow.
OBJECT-IDENTITY    

lgpConditionLossOfAirflow1 1.3.6.1.4.1.476.1.42.3.2.1.5.1
The system has detected a loss of air flow at sensor 1.
OBJECT-IDENTITY    

lgpConditionLossOfAirflow2 1.3.6.1.4.1.476.1.42.3.2.1.5.2
The system has detected a loss of air flow at sensor 2.
OBJECT-IDENTITY    

lgpConditionLossOfAirflowBlower1 1.3.6.1.4.1.476.1.42.3.2.1.5.3
The system has detected a loss of air flow from blower 1.
OBJECT-IDENTITY    

lgpConditionChangeFilter 1.3.6.1.4.1.476.1.42.3.2.1.6
The system has detected a condition indicating the air filter should be changed.
OBJECT-IDENTITY    

lgpConditionCompressorHighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.1.7
This system has detected an excessive head pressure condition.
OBJECT-IDENTITY    

lgpConditionCompressor1HighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.1.7.1
The system has detected excessive head pressure in compressor 1.
OBJECT-IDENTITY    

lgpConditionCompressor2HighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.1.7.2
The system has detected excessive head pressure in compressor 2.
OBJECT-IDENTITY    

lgpConditionCompressor3HighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.1.7.3
The system has detected excessive head pressure in compressor 3.
OBJECT-IDENTITY    

lgpConditionCompressor4HighHeadPressure 1.3.6.1.4.1.476.1.42.3.2.1.7.4
The system has detected excessive head pressure in compressor 4.
OBJECT-IDENTITY    

lgpConditionCompressorOverload 1.3.6.1.4.1.476.1.42.3.2.1.8
This system has detected a compressor overload condition.
OBJECT-IDENTITY    

lgpConditionCompressor1Overload 1.3.6.1.4.1.476.1.42.3.2.1.8.1
The system has detected an overload condition on compressor 1.
OBJECT-IDENTITY    

lgpConditionCompressor2Overload 1.3.6.1.4.1.476.1.42.3.2.1.8.2
The system has detected an overload condition on compressor 2.
OBJECT-IDENTITY    

lgpConditionCompressorShortCycle 1.3.6.1.4.1.476.1.42.3.2.1.9
A compressor has exceeded the maximum number of starts in a minimum time period.
OBJECT-IDENTITY    

lgpConditionCompressor1ShortCycle 1.3.6.1.4.1.476.1.42.3.2.1.9.1
The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time.
OBJECT-IDENTITY    

lgpConditionCompressor2ShortCycle 1.3.6.1.4.1.476.1.42.3.2.1.9.2
The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time.
OBJECT-IDENTITY    

lgpConditionCompressorLowSuctionPressure 1.3.6.1.4.1.476.1.42.3.2.1.10
The pressure at a compressor inlet has dropped below the minimum setting.
OBJECT-IDENTITY    

lgpConditionMainFanOverLoad 1.3.6.1.4.1.476.1.42.3.2.1.11
The system has detected a main fan overload condition.
OBJECT-IDENTITY    

lgpConditionManualOverride 1.3.6.1.4.1.476.1.42.3.2.1.12
The system has detected a manual override condition.
OBJECT-IDENTITY    

lgpConditionStandbyGlycoolPumpOn 1.3.6.1.4.1.476.1.42.3.2.1.13
The standby Glycol or Glycool pump is activated.
OBJECT-IDENTITY    

lgpConditionWaterUnderFloor 1.3.6.1.4.1.476.1.42.3.2.1.14
Moisture has been detected under the floor.
OBJECT-IDENTITY    

lgpConditionHumidifierProblem 1.3.6.1.4.1.476.1.42.3.2.1.15
The system has detected a humidifier problem.
OBJECT-IDENTITY    

lgpConditionLowWaterInHumidifier 1.3.6.1.4.1.476.1.42.3.2.1.16
The system has detected a low water condition in the humidifier reservoir.
OBJECT-IDENTITY    

lgpConditionSmokeDetected 1.3.6.1.4.1.476.1.42.3.2.1.17
The system has detected smoke.
OBJECT-IDENTITY    

lgpConditionLowWaterFlow 1.3.6.1.4.1.476.1.42.3.2.1.18
The system has detected a low water flow rate condition.
OBJECT-IDENTITY    

lgpConditionLostPower 1.3.6.1.4.1.476.1.42.3.2.1.19
The system has lost power before being switched off using the controls. This condition is activated when power is restored.
OBJECT-IDENTITY    

lgpGeneralFault 1.3.6.1.4.1.476.1.42.3.2.1.20
A fault condition has been detected that is not identifed in the well known list.
OBJECT-IDENTITY    

lgpConditionLocalAlarm 1.3.6.1.4.1.476.1.42.3.2.1.21
This system has detected a local, or customer, alarm condition.
OBJECT-IDENTITY    

lgpConditionLocalAlarm1 1.3.6.1.4.1.476.1.42.3.2.1.21.1
The system has detected that customer alarm condition 1 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm2 1.3.6.1.4.1.476.1.42.3.2.1.21.2
The system has detected that customer alarm condition 2 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm3 1.3.6.1.4.1.476.1.42.3.2.1.21.3
The system has detected that customer alarm condition 3 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm4 1.3.6.1.4.1.476.1.42.3.2.1.21.4
The system has detected that customer alarm condition 4 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm5 1.3.6.1.4.1.476.1.42.3.2.1.21.5
The system has detected that customer alarm condition 5 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm6 1.3.6.1.4.1.476.1.42.3.2.1.21.6
The system has detected that customer alarm condition 6 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm7 1.3.6.1.4.1.476.1.42.3.2.1.21.7
The system has detected that customer alarm condition 7 is active.
OBJECT-IDENTITY    

lgpConditionLocalAlarm8 1.3.6.1.4.1.476.1.42.3.2.1.21.8
The system has detected that customer alarm condition 8 is active.
OBJECT-IDENTITY    

lgpConditionStandbyUnitOn 1.3.6.1.4.1.476.1.42.3.2.1.22
The system has detected the standby unit is operating.
OBJECT-IDENTITY    

lgpConditionCompressorLowPressure 1.3.6.1.4.1.476.1.42.3.2.1.23
This system has detected a low head compressor condition.
OBJECT-IDENTITY    

lgpConditionCompressor1LowPressure 1.3.6.1.4.1.476.1.42.3.2.1.23.1
The system has detected low pressure in compressor 1.
OBJECT-IDENTITY    

lgpConditionCompressor2LowPressure 1.3.6.1.4.1.476.1.42.3.2.1.23.2
The system has detected low pressure in compressor 2.
OBJECT-IDENTITY    

lgpConditionCompressor3LowPressure 1.3.6.1.4.1.476.1.42.3.2.1.23.3
The system has detected low pressure in compressor 3.
OBJECT-IDENTITY    

lgpConditionCompressor4LowPressure 1.3.6.1.4.1.476.1.42.3.2.1.23.4
The system has detected low pressure in compressor 4.
OBJECT-IDENTITY    

lgpConditionHighWaterInPan 1.3.6.1.4.1.476.1.42.3.2.1.24
The system has detected a high water condition in the condensor pan.
OBJECT-IDENTITY    

lgpConditionFaultySensor 1.3.6.1.4.1.476.1.42.3.2.1.25
The system has detected a faulty temperature/humidity sensor.
OBJECT-IDENTITY    

lgpConditionServiceCooling 1.3.6.1.4.1.476.1.42.3.2.1.26
The Cooling system requires scheduled maintenance.
OBJECT-IDENTITY    

lgpConditionServiceHumidifier 1.3.6.1.4.1.476.1.42.3.2.1.27
The Humidifier requires scheduled maintenance.
OBJECT-IDENTITY    

lgpConditionSystemControlBatteryLow 1.3.6.1.4.1.476.1.42.3.2.1.28
Charge level of the system control's battery is below the alarm set point.
OBJECT-IDENTITY    

lgpConditionGroundSystemFault 1.3.6.1.4.1.476.1.42.3.2.1.29
The system has detected a ground system fault.
OBJECT-IDENTITY    

lgpConditionGroundFailure 1.3.6.1.4.1.476.1.42.3.2.1.30
The system has detected a ground failure.
OBJECT-IDENTITY    

lgpConditionSecurityBreach 1.3.6.1.4.1.476.1.42.3.2.1.31
The system has detected a security breach.
OBJECT-IDENTITY    

lgpConditionEmergencyShutdown 1.3.6.1.4.1.476.1.42.3.2.1.32
The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency.
OBJECT-IDENTITY    

lgpConditionOnBypass 1.3.6.1.4.1.476.1.42.3.2.1.33
This system has detected the load is being powered by a bypass source.
OBJECT-IDENTITY    

lgpConditionLoadOnBypass 1.3.6.1.4.1.476.1.42.3.2.1.33.1
The load is being powered by a bypass source.
OBJECT-IDENTITY    

lgpConditionLoadOnMaintenceBypass 1.3.6.1.4.1.476.1.42.3.2.1.33.2
The load is being powered by a maintenance bypass source.
OBJECT-IDENTITY    

lgpConditionParallelSysLoadOnBypass 1.3.6.1.4.1.476.1.42.3.2.1.33.3
The parallel system has transferred to bypass.
OBJECT-IDENTITY    

lgpConditionLoadOnBypassByImpact 1.3.6.1.4.1.476.1.42.3.2.1.33.4
The system has dectected a load impact and has transferred the load to the bypass source.
OBJECT-IDENTITY    

lgpConditionLoadTransferedToBypass 1.3.6.1.4.1.476.1.42.3.2.1.33.5
The system has transfered to bypass. The load is being powered by the bypass source.
OBJECT-IDENTITY    

lgpConditionEmergencyTransferToBypass 1.3.6.1.4.1.476.1.42.3.2.1.33.6
The system has performed an emergency transfer to bypass.
OBJECT-IDENTITY    

lgpConditionOutputToLoadVoltTHD 1.3.6.1.4.1.476.1.42.3.2.1.34
The total harmonic distortion of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionLogicFailure 1.3.6.1.4.1.476.1.42.3.2.1.35
The system has detected a control logic failure.
OBJECT-IDENTITY    

lgpConditionPowerSupplyFault 1.3.6.1.4.1.476.1.42.3.2.1.36
This system had detected a power supply fault condition.
OBJECT-IDENTITY    

lgpConditionPowerSupply1Fault 1.3.6.1.4.1.476.1.42.3.2.1.36.1
The system has detected power supply 1 is in a fault condition.
OBJECT-IDENTITY    

lgpConditionPowerSupply2Fault 1.3.6.1.4.1.476.1.42.3.2.1.36.2
The system has detected power supply 2 is in a fault condition.
OBJECT-IDENTITY    

lgpConditionPowerSupplyFailure 1.3.6.1.4.1.476.1.42.3.2.1.37
This system has detected a power supply failure condition.
OBJECT-IDENTITY    

lgpConditionPowerSupply1Failure 1.3.6.1.4.1.476.1.42.3.2.1.37.1
The system has detected power supply 1 has failed.
OBJECT-IDENTITY    

lgpConditionPowerSupply2Failure 1.3.6.1.4.1.476.1.42.3.2.1.37.2
The system has detected power supply 2 has failed.
OBJECT-IDENTITY    

lgpConditionSource1PowerSupplyInputFailure 1.3.6.1.4.1.476.1.42.3.2.1.37.3
The system has detected the source 1 Power supply input has failed.
OBJECT-IDENTITY    

lgpConditionSource2PowerSupplyInputFailure 1.3.6.1.4.1.476.1.42.3.2.1.37.4
The system has detected the source 2 Power supply input has failed.
OBJECT-IDENTITY    

lgpConditionPowerSupplyLogicFailure 1.3.6.1.4.1.476.1.42.3.2.1.37.5
The system has detected a power supply logic failure.
OBJECT-IDENTITY    

lgpConditionCompressorPowerSupplyFailure 1.3.6.1.4.1.476.1.42.3.2.1.37.6
The system has detected the power supply to the compressors has failed.
OBJECT-IDENTITY    

lgpConditionOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38
This system has detected an over voltage condition.
OBJECT-IDENTITY    

lgpConditionSource1OverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.1
The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSource2OverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.2
The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.3
The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionInputOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.4
The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for an specified amount of time.
OBJECT-IDENTITY    

lgpConditionBypassOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.5
The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBypassOverVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.38.6
The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.7
The system has detected a battery over voltage condition.
OBJECT-IDENTITY    

lgpConditionDcBusOverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.8
This system has detected a DC Bus over voltage condition.
OBJECT-IDENTITY    

lgpConditionDcBus1OverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.8.1
The system has detected an over voltage condition on DC Bus 1.
OBJECT-IDENTITY    

lgpConditionDcBus2OverVoltage 1.3.6.1.4.1.476.1.42.3.2.1.38.8.2
The system has detected an over voltage condition on DC Bus 2.
OBJECT-IDENTITY    

lgpConditionDcBus1OverVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.38.8.3
The system has detected an over voltage failure condition on DC Bus 1.
OBJECT-IDENTITY    

lgpConditionDcBus2OverVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.38.8.4
The system has detected an over voltage failure condition on DC Bus 2.
OBJECT-IDENTITY    

lgpConditionUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39
This system has detected an under voltage condition.
OBJECT-IDENTITY    

lgpConditionSource1UnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.1
The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSource2UnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.2
The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionOutputToLoadUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.3
The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSource1UnderVoltageRMS 1.3.6.1.4.1.476.1.42.3.2.1.39.4
The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionSource2UnderVoltageRMS 1.3.6.1.4.1.476.1.42.3.2.1.39.5
The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionInputUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.6
The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBypassUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.7
The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBypassUnderVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.39.8
The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.9
The system has detected a battery under voltage condition.
OBJECT-IDENTITY    

lgpConditionDcBusUnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.10
This system has detected a DC bus under voltage condition
OBJECT-IDENTITY    

lgpConditionDcBus1UnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.10.1
The system has detected an under voltage condition on DC Bus 1.
OBJECT-IDENTITY    

lgpConditionDcBus2UnderVoltage 1.3.6.1.4.1.476.1.42.3.2.1.39.10.2
The system has detected an under voltage condition on DC Bus 2.
OBJECT-IDENTITY    

lgpConditionDcBus1UnderVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.39.10.3
The system has detected an under voltage failure condition on DC Bus 1.
OBJECT-IDENTITY    

lgpConditionDcBus2UnderVoltageFailure 1.3.6.1.4.1.476.1.42.3.2.1.39.10.4
The system has detected an under voltage failure condition on DC Bus 2.
OBJECT-IDENTITY    

lgpConditionOverload 1.3.6.1.4.1.476.1.42.3.2.1.40
This system has detected an overload condition.
OBJECT-IDENTITY    

lgpConditionSource1Overload 1.3.6.1.4.1.476.1.42.3.2.1.40.1
The system has detected a overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSystemOverload 1.3.6.1.4.1.476.1.42.3.2.1.40.2
The system has detected a overload condition.
OBJECT-IDENTITY    

lgpConditionSource1PeakCurrentOverLoad 1.3.6.1.4.1.476.1.42.3.2.1.40.3
The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for an specified amount of time.
OBJECT-IDENTITY    

lgpConditionSource2PeakCurrentOverLoad 1.3.6.1.4.1.476.1.42.3.2.1.40.4
The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for an specified amount of time.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOverLimit 1.3.6.1.4.1.476.1.42.3.2.1.40.5
The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOverload 1.3.6.1.4.1.476.1.42.3.2.1.40.6
The system has detected an output overload condition.
OBJECT-IDENTITY    

lgpConditionParallelSysOverload 1.3.6.1.4.1.476.1.42.3.2.1.40.7
The parallel system has detected an overload condition.
OBJECT-IDENTITY    

lgpConditionScrShort 1.3.6.1.4.1.476.1.42.3.2.1.41
This system has detected a Silicon Controlled Rectifier (SCR) short condition.
OBJECT-IDENTITY    

lgpConditionSource1ScrShort 1.3.6.1.4.1.476.1.42.3.2.1.41.1
The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition.
OBJECT-IDENTITY    

lgpConditionSource2ScrShort 1.3.6.1.4.1.476.1.42.3.2.1.41.2
The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition.
OBJECT-IDENTITY    

lgpConditionBypassScrShort 1.3.6.1.4.1.476.1.42.3.2.1.41.3
The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass.
OBJECT-IDENTITY    

lgpConditionScrOpen 1.3.6.1.4.1.476.1.42.3.2.1.42
This system has detected a Silicon Controlled Rectifier (SCR) open condition.
OBJECT-IDENTITY    

lgpConditionSource1ScrOpen 1.3.6.1.4.1.476.1.42.3.2.1.42.1
The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition.
OBJECT-IDENTITY    

lgpConditionSource2ScrOpen 1.3.6.1.4.1.476.1.42.3.2.1.42.2
The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition.
OBJECT-IDENTITY    

lgpConditionBypassScrOpen 1.3.6.1.4.1.476.1.42.3.2.1.42.3
The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass.
OBJECT-IDENTITY    

lgpConditionFanFailure 1.3.6.1.4.1.476.1.42.3.2.1.43
This system has detected a fan failure condition.
OBJECT-IDENTITY    

lgpConditionFan1Failure 1.3.6.1.4.1.476.1.42.3.2.1.43.1
The system has detected a fan 1 failure condition.
OBJECT-IDENTITY    

lgpConditionTransferInhibited 1.3.6.1.4.1.476.1.42.3.2.1.44
The system is preventing a transfer of the load to the alternate source.
OBJECT-IDENTITY    

lgpConditionAutoReTransferPrimed 1.3.6.1.4.1.476.1.42.3.2.1.45
The system is capable to retransfer to the preferred source.
OBJECT-IDENTITY    

lgpConditionSourcesOutOfSync 1.3.6.1.4.1.476.1.42.3.2.1.46
The system has detected that the input sources are not within the specified phase difference (synchronization window).
OBJECT-IDENTITY    

lgpConditionSourceFailure 1.3.6.1.4.1.476.1.42.3.2.1.47
This system has detected an input source failure condition.
OBJECT-IDENTITY    

lgpConditionSource1Failure 1.3.6.1.4.1.476.1.42.3.2.1.47.1
The system has detected source 1 has failed.
OBJECT-IDENTITY    

lgpConditionSource2Failure 1.3.6.1.4.1.476.1.42.3.2.1.47.2
The system has detected source 2 has failed.
OBJECT-IDENTITY    

lgpConditionAutoReTransferInhibited 1.3.6.1.4.1.476.1.42.3.2.1.48
The system is preventing a transfer of the load back to the prefered source.
OBJECT-IDENTITY    

lgpConditionAutoReTransferFailed 1.3.6.1.4.1.476.1.42.3.2.1.49
The system is failing to automatically retransfer the load back to the preferred source.
OBJECT-IDENTITY    

lgpConditionFuseOpen 1.3.6.1.4.1.476.1.42.3.2.1.50
This system has detected an open fuse condition.
OBJECT-IDENTITY    

lgpConditionControlFuse1Open 1.3.6.1.4.1.476.1.42.3.2.1.50.1
The system has detected a control power fuse 1 open condition.
OBJECT-IDENTITY    

lgpConditionControlFuse2Open 1.3.6.1.4.1.476.1.42.3.2.1.50.2
The system has detected a control power fuse 2 open condition.
OBJECT-IDENTITY    

lgpConditionRectifierFuseOpen 1.3.6.1.4.1.476.1.42.3.2.1.50.3
The system has detected a rectifier fuse open condition.
OBJECT-IDENTITY    

lgpConditionInverterFuseOpen 1.3.6.1.4.1.476.1.42.3.2.1.50.4
The system has detected a inverter fuse open condition.
OBJECT-IDENTITY    

lgpConditionOutputToLoadFuseOpen 1.3.6.1.4.1.476.1.42.3.2.1.50.5
The system has detected an output to load fuse open condition.
OBJECT-IDENTITY    

lgpConditionDcCapacitorFuseOpen 1.3.6.1.4.1.476.1.42.3.2.1.50.6
The system has detected a DC capacitor fuse open condition.
OBJECT-IDENTITY    

lgpConditionDisconnect 1.3.6.1.4.1.476.1.42.3.2.1.51
This system has detected an open/close disconnect condition.
OBJECT-IDENTITY    

lgpConditionSource1DisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.1
The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource2DisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.2
The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource1PduDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.3
The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource2PduDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.4
The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOutputToLoadDisconnect1Open 1.3.6.1.4.1.476.1.42.3.2.1.51.5
The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOutputToLoadDisconnect2Open 1.3.6.1.4.1.476.1.42.3.2.1.51.6
The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource1BypassDisconnectClosed 1.3.6.1.4.1.476.1.42.3.2.1.51.7
The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource2BypassDisconnectClosed 1.3.6.1.4.1.476.1.42.3.2.1.51.8
The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOutputToLoadNeutralDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.9
The system has detected the the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionBatteryDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.10
The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionInputDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.11
The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOutputToLoadDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.12
The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionBypassDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.13
The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionStaticSwitchDisconnectOpen 1.3.6.1.4.1.476.1.42.3.2.1.51.14
The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionFrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.1.52
This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionSource1FrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.1.52.1
The system has detected a frequency deviation condition on source 1. The frequency for source 1 is outside of the pre-determined thresholds for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionSource2FrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.1.52.2
The system has detected a frequency deviation condition on source 2. The frequency for source 2 is outside of the pre-determined thresholds for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionInputFrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.1.52.3
The system has detected a input frequency deviation condition. The frequency for the input is outside of the pre-determined thresholds for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionOutputToLoadFrequencyDeviation 1.3.6.1.4.1.476.1.42.3.2.1.52.4
The system has detected a frequency deviation condition on the output. The frequency for the output is outside of the pre-determined thresholds for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53
This system has detected an current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSource1OverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.1
The system has detected a over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionSource2OverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.2
The system has detected a over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.3
The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionGroundOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.4
A ground source is experiencing a over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionRectifierOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.5
The system has detected a rectifier over current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionInverterOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.6
The system has detected an inverter over current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryConverterOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.7
The system has detected a over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryBalancerOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.8
The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionHumidifierOverCurrent 1.3.6.1.4.1.476.1.42.3.2.1.53.9
The system has detected a over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time.
OBJECT-IDENTITY    

lgpConditionSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54
This system has detected a sensor failure condition.
OBJECT-IDENTITY    

lgpConditionOutputToLoadVoltageSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.1
The system had detected a output to load voltage sensor failure.
OBJECT-IDENTITY    

lgpConditionSource1VoltageSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.2
The system had detected a source 1 voltage sensor failure.
OBJECT-IDENTITY    

lgpConditionSource2VoltageSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.3
The system had detected a source 2 voltage sensor failure.
OBJECT-IDENTITY    

lgpConditionSource1ScrSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.4
The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure.
OBJECT-IDENTITY    

lgpConditionSource2ScrSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.5
The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure.
OBJECT-IDENTITY    

lgpConditionSource1CurrentSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.6
The system has detected a source 1 current sensor failure.
OBJECT-IDENTITY    

lgpConditionSource2CurrentSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.7
The system has detected a source 2 current sensor failure.
OBJECT-IDENTITY    

lgpConditionRoomTempHumiditySensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.8
The system has detected a device temperature and humidity sensor failure.
OBJECT-IDENTITY    

lgpConditionGlycolTempSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.9
The system has detected a glycol temperature sensor failure.
OBJECT-IDENTITY    

lgpConditionLocal1SensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.10
The system has detected a local 1 sensor failure.
OBJECT-IDENTITY    

lgpConditionCompressor1SensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.11
The system has detected a compressor 1 digital scroll sensor failure condition.
OBJECT-IDENTITY    

lgpConditionCompressor2SensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.12
The system has detected a compressor 2 digital scroll sensor failure condtion.
OBJECT-IDENTITY    

lgpConditionSupplySensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.13
The system has detected a supply sensor failure.
OBJECT-IDENTITY    

lgpConditionCabinetTemperatureSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.14
The system has detected a cabinet temperature sensor failure.
OBJECT-IDENTITY    

lgpConditionCabinetHumiditySensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.15
The system has detected a cabinet humidity sensor failure.
OBJECT-IDENTITY    

lgpConditionRoomTempSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.54.16
The system has detected a room temperature sensor failure.
OBJECT-IDENTITY    

lgpConditionInternalCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.1.55
This system has detected an internal communication failure condition.
OBJECT-IDENTITY    

lgpConditionExternalCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.1.56
This system has detected an external communication failure condition.
OBJECT-IDENTITY    

lgpConditionSourceGateDriveFailure 1.3.6.1.4.1.476.1.42.3.2.1.57
This system has detected a source gate drive failure condition.
OBJECT-IDENTITY    

lgpConditionSource1GateDriveFailure 1.3.6.1.4.1.476.1.42.3.2.1.57.1
The system has detected a source 1 gate drive failure.
OBJECT-IDENTITY    

lgpConditionSource2GateDriveFailure 1.3.6.1.4.1.476.1.42.3.2.1.57.2
The system has detected a source 2 gate drive failure.
OBJECT-IDENTITY    

lgpConditionDisconnectFailure 1.3.6.1.4.1.476.1.42.3.2.1.58
This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOutputToLoadNeutralDisconnectFailure 1.3.6.1.4.1.476.1.42.3.2.1.58.1
The system has detected the the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource1DisconnectShuntTripFailure 1.3.6.1.4.1.476.1.42.3.2.1.58.2
The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionSource2DisconnectShuntTripFailure 1.3.6.1.4.1.476.1.42.3.2.1.58.3
The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionInverterDisconnectFailure 1.3.6.1.4.1.476.1.42.3.2.1.58.4
The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionBatteryDisconnectFailure 1.3.6.1.4.1.476.1.42.3.2.1.58.5
The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
OBJECT-IDENTITY    

lgpConditionOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59
This system has detected an over temperature condition.
OBJECT-IDENTITY    

lgpConditionHeatSink1OverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.1
The system has detected a heat sink 1 over temperature condition.
OBJECT-IDENTITY    

lgpConditionAmbient1OverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.2
The system has detected an ambient over temperature condition at location 1.
OBJECT-IDENTITY    

lgpConditionSystemOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.3
The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionTransformerOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.4
The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.5
The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionRectifierOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.6
The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionInverterOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.7
The system has detected an inverter over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionRectifierInductorOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.8
The system has detected an inverter inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionInverterInductorOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.9
The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryConverterOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.10
The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
OBJECT-IDENTITY    

lgpConditionBatteryBalancerInductorOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.11
The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for an specified amount of time.
OBJECT-IDENTITY    

lgpConditionChilledWaterOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.12
The system has detected a chilled water over temperature condition.
OBJECT-IDENTITY    

lgpConditionElectricHeatersOverTemperature 1.3.6.1.4.1.476.1.42.3.2.1.59.13
The system has detected a electric heater over temperature condition.
OBJECT-IDENTITY    

lgpConditionLoadOnAlternateSource 1.3.6.1.4.1.476.1.42.3.2.1.60
The system has detected that the load is being supplied by the alternate source.
OBJECT-IDENTITY    

lgpConditionPhaseRotationError 1.3.6.1.4.1.476.1.42.3.2.1.61
This system has detected a phase rotation error condition.
OBJECT-IDENTITY    

lgpConditionSource1PhaseRotationError 1.3.6.1.4.1.476.1.42.3.2.1.61.1
The system has detected a phase rotation error on source 1.
OBJECT-IDENTITY    

lgpConditionSource2PhaseRotationError 1.3.6.1.4.1.476.1.42.3.2.1.61.2
The system has detected a phase rotation error on source 2.
OBJECT-IDENTITY    

lgpConditionBypassPhaseRotationError 1.3.6.1.4.1.476.1.42.3.2.1.61.3
The system has detected a phase rotation error on the bypass.
OBJECT-IDENTITY    

lgpConditionInputPhaseRotationError 1.3.6.1.4.1.476.1.42.3.2.1.61.4
The system has detected a phase rotation error on the input.
OBJECT-IDENTITY    

lgpConditionControlModuleFailure 1.3.6.1.4.1.476.1.42.3.2.1.62
This system has detected a control module failure condition.
OBJECT-IDENTITY    

lgpConditionControlModule1Failure 1.3.6.1.4.1.476.1.42.3.2.1.62.1
The system has detected a control module 1 failure.
OBJECT-IDENTITY    

lgpConditionHistoryLogFull 1.3.6.1.4.1.476.1.42.3.2.1.63
The system has detected the history log is full.
OBJECT-IDENTITY    

lgpConditionConfigurationModified 1.3.6.1.4.1.476.1.42.3.2.1.64
The system has detected the configuration has been modified.
OBJECT-IDENTITY    

lgpConditionPasswordModified 1.3.6.1.4.1.476.1.42.3.2.1.65
The system has detected the password has been modified.
OBJECT-IDENTITY    

lgpConditionTimeModified 1.3.6.1.4.1.476.1.42.3.2.1.66
The system has detected the time has been modified.
OBJECT-IDENTITY    

lgpConditionDateModified 1.3.6.1.4.1.476.1.42.3.2.1.67
The system has detected the date has been modified.
OBJECT-IDENTITY    

lgpConditionEventLogCleared 1.3.6.1.4.1.476.1.42.3.2.1.68
The system has detected the event log has been cleared.
OBJECT-IDENTITY    

lgpConditionHistoryLogCleared 1.3.6.1.4.1.476.1.42.3.2.1.69
The system has detected the history log has been cleared.
OBJECT-IDENTITY    

lgpConditionUtilityFailure 1.3.6.1.4.1.476.1.42.3.2.1.70
The system has detected a utility failure.
OBJECT-IDENTITY    

lgpConditionBatteryTestInProgress 1.3.6.1.4.1.476.1.42.3.2.1.71
The system is performing a battery test at this time.
OBJECT-IDENTITY    

lgpConditionLoadOnBattery 1.3.6.1.4.1.476.1.42.3.2.1.72
The system load is being supported by the battery.
OBJECT-IDENTITY    

lgpConditionReplaceBattery 1.3.6.1.4.1.476.1.42.3.2.1.74
The system has detected the batteries are due to be replaced.
OBJECT-IDENTITY    

lgpConditionUpsShutdownPending 1.3.6.1.4.1.476.1.42.3.2.1.75
The system is in a shutdown pending condition.
OBJECT-IDENTITY    

lgpConditionBatteryChargerFailed 1.3.6.1.4.1.476.1.42.3.2.1.76
The system has detected the battery charger has failed.
OBJECT-IDENTITY    

lgpConditionBypassVoltageUnqualified 1.3.6.1.4.1.476.1.42.3.2.1.77
The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for an specified amount of time.
OBJECT-IDENTITY    

lgpConditionCheckAirFilter 1.3.6.1.4.1.476.1.42.3.2.1.78
The system has detected it is time to check the air filter.
OBJECT-IDENTITY    

lgpConditionBrownOut 1.3.6.1.4.1.476.1.42.3.2.1.79
The system has detected a brown out condition.
OBJECT-IDENTITY    

lgpConditionMultipleTransferLockout 1.3.6.1.4.1.476.1.42.3.2.1.80
The system has locked out transfers to bypass. Too many transfers have occured over a specified amount of time.
OBJECT-IDENTITY    

lgpConditionBypassPhaseLost 1.3.6.1.4.1.476.1.42.3.2.1.81
The system has detected one or more bypass phases are missing.
OBJECT-IDENTITY    

lgpConditionMaintenceBypassInhibited 1.3.6.1.4.1.476.1.42.3.2.1.82
The system is preventing a transfer of the load to maintence bypass.
OBJECT-IDENTITY    

lgpConditionLoadLockedOnBypass 1.3.6.1.4.1.476.1.42.3.2.1.83
The system has detected an error and been put locked on bypass.
OBJECT-IDENTITY    

lgpConditionOutputToLoadShort 1.3.6.1.4.1.476.1.42.3.2.1.84
The system has detected an output to load short circuit condition.
OBJECT-IDENTITY    

lgpConditionEmergencyTransferToInverter 1.3.6.1.4.1.476.1.42.3.2.1.85
The system has detected an emergency transfer of the load to inverter.
OBJECT-IDENTITY    

lgpConditonEmergencyPowerOff 1.3.6.1.4.1.476.1.42.3.2.1.86
The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system.
OBJECT-IDENTITY    

lgpConditionInverterBackFeed 1.3.6.1.4.1.476.1.42.3.2.1.87
The system has detected an inverter backfeed condition. The inverter is feeding power through the bypass back to the input.
OBJECT-IDENTITY    

lgpConditionDcGroundFault 1.3.6.1.4.1.476.1.42.3.2.1.88
The system has detected a DC ground fault.
OBJECT-IDENTITY    

lgpConditionStaticTransferSwitchInhibited 1.3.6.1.4.1.476.1.42.3.2.1.89
The system is preventing the use of the static transfer switch.
OBJECT-IDENTITY    

lgpConditionBatteryLogFullWarning 1.3.6.1.4.1.476.1.42.3.2.1.90
The system has detected the battery log is approaching the maximum record limit.
OBJECT-IDENTITY    

lgpConditionInputCurrentUnbalanced 1.3.6.1.4.1.476.1.42.3.2.1.91
The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
OBJECT-IDENTITY    

lgpConditionSelfTestFailed 1.3.6.1.4.1.476.1.42.3.2.1.92
The system has detected a self-test failure.
OBJECT-IDENTITY    

lgpConditionInverterOutOfSynchronization 1.3.6.1.4.1.476.1.42.3.2.1.93
The system has detected a Inverter out of sync condition.
OBJECT-IDENTITY    

lgpConditionModuleAlarm 1.3.6.1.4.1.476.1.42.3.2.1.94
This system has detected an alarm within the multi-module system.
OBJECT-IDENTITY    

lgpConditioniModuleUnit1Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.1
The multi-module system has detected an alarm condition on unit 1.
OBJECT-IDENTITY    

lgpConditioniModuleUnit2Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.2
The multi-module system has detected an alarm condition on unit 2.
OBJECT-IDENTITY    

lgpConditioniModuleUnit3Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.3
The multi-module system has detected an alarm condition on unit 3.
OBJECT-IDENTITY    

lgpConditioniModuleUnit4Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.4
The multi-module system has detected an alarm condition on unit 4.
OBJECT-IDENTITY    

lgpConditioniModuleUnit5Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.5
The multi-module system has detected an alarm condition on unit 5.
OBJECT-IDENTITY    

lgpConditioniModuleUnit6Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.6
The multi-module system has detected an alarm condition on unit 6.
OBJECT-IDENTITY    

lgpConditioniModuleUnit7Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.7
The multi-module system has detected an alarm condition on unit 7.
OBJECT-IDENTITY    

lgpConditioniModuleUnit8Alarm 1.3.6.1.4.1.476.1.42.3.2.1.94.8
The multi-module system has detected an alarm condition on unit 8.
OBJECT-IDENTITY    

lgpConditionActiveModuleAlarm 1.3.6.1.4.1.476.1.42.3.2.1.95
The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system.
OBJECT-IDENTITY    

lgpConditionControlFailure 1.3.6.1.4.1.476.1.42.3.2.1.96
This system has detected a control failure condition.
OBJECT-IDENTITY    

lgpConditionMainControlFailure 1.3.6.1.4.1.476.1.42.3.2.1.96.1
The system has detected a main control failure condition.
OBJECT-IDENTITY    

lgpConditionRedundantControlFailure 1.3.6.1.4.1.476.1.42.3.2.1.96.2
The system has detected a redundant control failure condition.
OBJECT-IDENTITY    

lgpConditionParallelSysControlFailure 1.3.6.1.4.1.476.1.42.3.2.1.96.3
The parallel system has detected a control failure condition with one of the controls.
OBJECT-IDENTITY    

lgpConditionControlWarning 1.3.6.1.4.1.476.1.42.3.2.1.97
This system has detected a control warning conditions.
OBJECT-IDENTITY    

lgpConditionMainControlWarning 1.3.6.1.4.1.476.1.42.3.2.1.97.1
The system has detected a main control warning condition.
OBJECT-IDENTITY    

lgpConditionRedundantControlWarning 1.3.6.1.4.1.476.1.42.3.2.1.97.2
The system has detected a redundant control warning condition.
OBJECT-IDENTITY    

lgpConditionUserInterfaceFailure 1.3.6.1.4.1.476.1.42.3.2.1.98
The system has detected a user interface control failure condition.
OBJECT-IDENTITY    

lgpConditionLostPowerRedundancy 1.3.6.1.4.1.476.1.42.3.2.1.99
The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting 'lgpPwrMinimumRedundantPowerModule'.
OBJECT-IDENTITY    

lgpConditionPowerModuleFailure 1.3.6.1.4.1.476.1.42.3.2.1.100
The system has detected a power module failure condition in the system.
OBJECT-IDENTITY    

lgpConditionBatteryModuleFailure 1.3.6.1.4.1.476.1.42.3.2.1.101
The system has detected a battery module failure condition in the system.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOff 1.3.6.1.4.1.476.1.42.3.2.1.102
The system has detected that there is no power being supplied to the load.
OBJECT-IDENTITY    

lgpConditionSystemOff 1.3.6.1.4.1.476.1.42.3.2.1.103
The system is off.
OBJECT-IDENTITY    

lgpConditionRectifierStartupFailure 1.3.6.1.4.1.476.1.42.3.2.1.104
The system has detected a rectifier under voltage start-up failure condition.
OBJECT-IDENTITY    

lgpConditionRectifierFault 1.3.6.1.4.1.476.1.42.3.2.1.105
The system has detected a rectifier fault condition.
OBJECT-IDENTITY    

lgpConditionInverterShutdownLowDc 1.3.6.1.4.1.476.1.42.3.2.1.106
The system has shutdown the inverter due to a DC bus under voltage.
OBJECT-IDENTITY    

lgpConditionInverterFault 1.3.6.1.4.1.476.1.42.3.2.1.107
The system has detected an inverter fault condition.
OBJECT-IDENTITY    

lgpConditionInverterDcOffsetOverrun 1.3.6.1.4.1.476.1.42.3.2.1.108
The system has detected an over run of the inverter DC offset voltage.
OBJECT-IDENTITY    

lgpConditionParallelSysLowBatteryWarning 1.3.6.1.4.1.476.1.42.3.2.1.109
The parallel system has detected a low battery warning condition.
OBJECT-IDENTITY    

lgpConditionParallelSysLoadShareFault 1.3.6.1.4.1.476.1.42.3.2.1.110
The parallel system has detected a load share fault condition.
OBJECT-IDENTITY    

lgpConditionBatteryFault 1.3.6.1.4.1.476.1.42.3.2.1.111
The system has detected a battery fault condition. The battery conductors are either reversed or disconnected.
OBJECT-IDENTITY    

lgpConditionBatteryConverterFailure 1.3.6.1.4.1.476.1.42.3.2.1.112
The system has detected a battery converter failure condition.
OBJECT-IDENTITY    

lgpConditionBatteryBalancerFault 1.3.6.1.4.1.476.1.42.3.2.1.113
The system has detected a battery balancer fault condition.
OBJECT-IDENTITY    

lgpConditionpsUpsOperationFault 1.3.6.1.4.1.476.1.42.3.2.1.114
The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
OBJECT-IDENTITY    

lgpConditionOutputToLoadOnJointMode 1.3.6.1.4.1.476.1.42.3.2.1.115
The system load is being supported by both the battery and rectifier.
OBJECT-IDENTITY    

lgpConditionInputNeutralLost 1.3.6.1.4.1.476.1.42.3.2.1.116
The system had detected the main input neutral is disconnected.
OBJECT-IDENTITY    

lgpConditionLowBatteryWarning 1.3.6.1.4.1.476.1.42.3.2.1.117
The battery's remaining charge is less than or equal to the agent's configured low threshold 'lgpPwrConfigLowBatteryWarningTime'.
OBJECT-IDENTITY    

lgpConditionInternalFault 1.3.6.1.4.1.476.1.42.3.2.1.118
The system has detected an internal fault.
OBJECT-IDENTITY    

lgpConditionBatteryTestFailed 1.3.6.1.4.1.476.1.42.3.2.1.119
The system has detected a battery self-test failure.
OBJECT-IDENTITY    

lgpConditionPowerModuleWarning 1.3.6.1.4.1.476.1.42.3.2.1.120
The system has detected an alarm condition on one, or more, power modules.
OBJECT-IDENTITY    

lgpConditionBatteryModuleWarning 1.3.6.1.4.1.476.1.42.3.2.1.121
The system has detected an alarm condition on one, or more, battery modules.
OBJECT-IDENTITY    

lgpConditionControlModuleWarning 1.3.6.1.4.1.476.1.42.3.2.1.122
The system has detected a control module warning.
OBJECT-IDENTITY    

lgpConditionUpsOperationFault 1.3.6.1.4.1.476.1.42.3.2.1.123
The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
OBJECT-IDENTITY    

lgpConditionActiveAlarm 1.3.6.1.4.1.476.1.42.3.2.1.124
The system has detected an alarm condition.
OBJECT-IDENTITY    

lgpConditionRectifierCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.1.125
The system has detected an internal communication failure condition with the rectifier.
OBJECT-IDENTITY    

lgpConditionInverterCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.1.126
The system has detected an internal communication failure condition with the inverter.
OBJECT-IDENTITY    

lgpConditionParallelSysConnectionFault 1.3.6.1.4.1.476.1.42.3.2.1.127
The parallel system has detected a connection fault. One or more of the devices are not properly connected.
OBJECT-IDENTITY    

lgpConditionParallelSysCommunicationFailure 1.3.6.1.4.1.476.1.42.3.2.1.128
The parallel system has detected a communication failure.
OBJECT-IDENTITY    

lgpConditionLostBatteryRedundancy 1.3.6.1.4.1.476.1.42.3.2.1.129
The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold.
OBJECT-IDENTITY    

lgpConditionCompPumpDownFailure 1.3.6.1.4.1.476.1.42.3.2.1.130
The system has detected that a compressor has failed to pump down.
OBJECT-IDENTITY    

lgpConditionComp1PumpDownFailure 1.3.6.1.4.1.476.1.42.3.2.1.130.1
The system has detected that compressor 1 has failed to pump down.
OBJECT-IDENTITY    

lgpConditionComp2PumpDownFailure 1.3.6.1.4.1.476.1.42.3.2.1.130.2
The system has detected that compressor 2 has failed to pump down.
OBJECT-IDENTITY    

lgpConditionChilledWaterLowWaterFlow 1.3.6.1.4.1.476.1.42.3.2.1.131
The system has detected a chilled water low water flow condition.
OBJECT-IDENTITY    

lgpConditionAirFilterClogged 1.3.6.1.4.1.476.1.42.3.2.1.132
The system has detected a air filter clogged condition.
OBJECT-IDENTITY    

lgpConditionHumidifierFailure 1.3.6.1.4.1.476.1.42.3.2.1.133
The system has detected a humidifier failure condition.
OBJECT-IDENTITY    

lgpConditionRunHoursExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134
The system has detected a pre-determined run hours threshold has been exceeded.
OBJECT-IDENTITY    

lgpConditionUnitRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.1
The system has detected the system run hours has exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionComp1RunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.2
The system has detected the compressor 1 run hours has exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionComp2RunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.3
The system has detected the compressor 2 run hours has exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionFreeCoolRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.4
The system has detected the free cooling run hours has exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionElectricalHeater1RunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.5
The system has detected the electrical heater's run hours have exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionElectricalHeater2RunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.6
The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
OBJECT-IDENTITY    

lgpConditionElectricalHeater3RunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.7
The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
OBJECT-IDENTITY    

lgpConditionHotWaterRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.8
The system has detected the hot water run hours have exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionHotGasRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.9
The system has detected the hot gas run hours have exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionHumidifierRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.10
The system has detected the humidifier run hours have exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionDehumidiferRunHrsExceeded 1.3.6.1.4.1.476.1.42.3.2.1.134.11
The system has detected the dehumidifier run hours have exceeded the pre-determined threshold.
OBJECT-IDENTITY    

lgpConditionCommWarning 1.3.6.1.4.1.476.1.42.3.2.1.135
The system has detected a loss of communications between another module.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit1 1.3.6.1.4.1.476.1.42.3.2.1.135.1
The system has detected a loss of communications with unit 1.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit2 1.3.6.1.4.1.476.1.42.3.2.1.135.2
The system has detected a loss of communications with unit 2.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit3 1.3.6.1.4.1.476.1.42.3.2.1.135.3
The system has detected a loss of communications with unit 3.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit4 1.3.6.1.4.1.476.1.42.3.2.1.135.4
The system has detected a loss of communications with unit 4.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit5 1.3.6.1.4.1.476.1.42.3.2.1.135.5
The system has detected a loss of communications with unit 5.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit6 1.3.6.1.4.1.476.1.42.3.2.1.135.6
The system has detected a loss of communications with unit 6.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit7 1.3.6.1.4.1.476.1.42.3.2.1.135.7
The system has detected a loss of communications with unit 7.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit8 1.3.6.1.4.1.476.1.42.3.2.1.135.8
The system has detected a loss of communications with unit 8.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit9 1.3.6.1.4.1.476.1.42.3.2.1.135.9
The system has detected a loss of communications with unit 9.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit10 1.3.6.1.4.1.476.1.42.3.2.1.135.10
The system has detected a loss of communications with unit 10.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit11 1.3.6.1.4.1.476.1.42.3.2.1.135.11
The system has detected a loss of communications with unit 11.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit12 1.3.6.1.4.1.476.1.42.3.2.1.135.12
The system has detected a loss of communications with unit 12.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit13 1.3.6.1.4.1.476.1.42.3.2.1.135.13
The system has detected a loss of communications with unit 13.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit14 1.3.6.1.4.1.476.1.42.3.2.1.135.14
The system has detected a loss of communications with unit 14.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit15 1.3.6.1.4.1.476.1.42.3.2.1.135.15
The system has detected a loss of communications with unit 15.
OBJECT-IDENTITY    

lgpConditionCommWarningUnit16 1.3.6.1.4.1.476.1.42.3.2.1.135.16
The system has detected a loss of communications with unit 16.
OBJECT-IDENTITY    

lgpConditionUnitOn 1.3.6.1.4.1.476.1.42.3.2.1.136
The unit is on.
OBJECT-IDENTITY    

lgpConditionUnitOff 1.3.6.1.4.1.476.1.42.3.2.1.137
The unit is off.
OBJECT-IDENTITY    

lgpConditionSleepModeOff 1.3.6.1.4.1.476.1.42.3.2.1.138
The system sleep mode operation has been turned off.
OBJECT-IDENTITY    

lgpConditionPowerOn 1.3.6.1.4.1.476.1.42.3.2.1.139
The system power is on.
OBJECT-IDENTITY    

lgpConditionSystemOnStanby 1.3.6.1.4.1.476.1.42.3.2.1.140
The system is on standby.
OBJECT-IDENTITY    

lgpConditionPowerOff 1.3.6.1.4.1.476.1.42.3.2.1.141
The system power is off.
OBJECT-IDENTITY    

lgpConditionHighTemperatureGroup 1.3.6.1.4.1.476.1.42.3.2.1.142
The system has detected a high temperature condition. This group contains various high temperature conditions.
OBJECT-IDENTITY    

lgpConditionHighTemperatureSensor1 1.3.6.1.4.1.476.1.42.3.2.1.142.1
The temperature has exceeded the high temperature threshold for sensor 1.
OBJECT-IDENTITY    

lgpConditionHighTemperatureDigitalScroll1 1.3.6.1.4.1.476.1.42.3.2.1.142.2
The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold.
OBJECT-IDENTITY    

lgpConditionHighTemperatureDigitalScroll2 1.3.6.1.4.1.476.1.42.3.2.1.142.3
The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold.
OBJECT-IDENTITY    

lgpConditionHighTemperatureUser1 1.3.6.1.4.1.476.1.42.3.2.1.142.4
The temperature has exceeded the high temperature threshold for user configured temperature sensor 1.
OBJECT-IDENTITY    

lgpConditionHighTemperatureInternal 1.3.6.1.4.1.476.1.42.3.2.1.142.5
The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold.
OBJECT-IDENTITY    

lgpConditionLowTemperatureGroup 1.3.6.1.4.1.476.1.42.3.2.1.143
The system has detected a low temperature condition. This group contains various low temperature conditions.
OBJECT-IDENTITY    

lgpConditionLowTemperatureSensor1 1.3.6.1.4.1.476.1.42.3.2.1.143.1
The temperature is below the low temperature threshold for sensor 1.
OBJECT-IDENTITY    

lgpConditionLowTemperatureInternal 1.3.6.1.4.1.476.1.42.3.2.1.143.2
The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold.
OBJECT-IDENTITY    

lgpConditionHighHumidityGroup 1.3.6.1.4.1.476.1.42.3.2.1.144
The system has detected a high humidity condition. This group contains various high humidity conditions.
OBJECT-IDENTITY    

lgpConditionHighHumiditySensor1 1.3.6.1.4.1.476.1.42.3.2.1.144.1
The humidity has exceeded the high humidity threshold for sensor 1.
OBJECT-IDENTITY    

lgpConditionLowHumidityGroup 1.3.6.1.4.1.476.1.42.3.2.1.145
The system has detected a low humidity condition. This group contains various high humidity conditions.
OBJECT-IDENTITY    

lgpConditionLowHumiditySensor1 1.3.6.1.4.1.476.1.42.3.2.1.145.1
The humidity is below the low humidity threshold for sensor 1.
OBJECT-IDENTITY    

lgpConditionPeerNetworkNoMaster 1.3.6.1.4.1.476.1.42.3.2.1.146
The system is unable to communicate with the master on the peer to peer network.
OBJECT-IDENTITY    

lgpConditionNoOnOffPermissions 1.3.6.1.4.1.476.1.42.3.2.1.147
The system lacks the permissions to execute the on/off operation.
OBJECT-IDENTITY    

lgpConditionPeerNetworkFailure 1.3.6.1.4.1.476.1.42.3.2.1.148
The system has detected a communication failure on the peer to peer network.
OBJECT-IDENTITY    

lgpConditionUnitDisabled 1.3.6.1.4.1.476.1.42.3.2.1.149
The unit is disabled.
OBJECT-IDENTITY    

lgpConditionUnitShutdown 1.3.6.1.4.1.476.1.42.3.2.1.150
The system has shutdown.
OBJECT-IDENTITY    

lgpConditionPeerNetworkDiscovered 1.3.6.1.4.1.476.1.42.3.2.1.151
The system has established communications on the peer to peer network.
OBJECT-IDENTITY    

lgpConditionLossOfWaterFlow 1.3.6.1.4.1.476.1.42.3.2.1.152
The system has detected a loss of water flow condition.
OBJECT-IDENTITY    

lgpConditionCondensatePumpHighWater 1.3.6.1.4.1.476.1.42.3.2.1.153
The system has detected high water in the condensate pump.
OBJECT-IDENTITY    

lgpConditionGeneralAlarm 1.3.6.1.4.1.476.1.42.3.2.1.154
The system has detected a general alarm condition.
OBJECT-IDENTITY    

lgpConditionProductSpecific 1.3.6.1.4.1.476.1.42.3.2.1.155
The system has detected a product specific condition. This condition is not currently available via the agent card.
OBJECT-IDENTITY    

lgpConditionReheatLockout 1.3.6.1.4.1.476.1.42.3.2.1.156
The system has locked out the electrical reheat operation for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionHumidifierLockout 1.3.6.1.4.1.476.1.42.3.2.1.157
The system has locked out the humidifier operation for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionCompressorsLockout 1.3.6.1.4.1.476.1.42.3.2.1.158
The system has locked out compressor operation for a specified amount of time.
OBJECT-IDENTITY    

lgpConditionCallService 1.3.6.1.4.1.476.1.42.3.2.1.159
The system has detected a condition that requires a service representative be contacted.
OBJECT-IDENTITY    

lgpConditionLowMemoryGroup 1.3.6.1.4.1.476.1.42.3.2.1.160
This group contains various low memory conditions.
OBJECT-IDENTITY    

lgpConditionLowMemory1 1.3.6.1.4.1.476.1.42.3.2.1.160.1
The system has detected a low memory condition. The control board is low in memory resources.
OBJECT-IDENTITY    

lgpConditionMemoryFailureGroup 1.3.6.1.4.1.476.1.42.3.2.1.161
This group contains various memory device failure conditions.
OBJECT-IDENTITY    

lgpConditionMemory1Failure 1.3.6.1.4.1.476.1.42.3.2.1.161.1
The system has detected a memory 1 module failure.
OBJECT-IDENTITY    

lgpConditionMemory2Failure 1.3.6.1.4.1.476.1.42.3.2.1.161.2
The system has detected a memory 2 module failure.
OBJECT-IDENTITY    

lgpConditionUnitCodeErrorGroup 1.3.6.1.4.1.476.1.42.3.2.1.162
This group contains various memory device failure conditions.
OBJECT-IDENTITY    

lgpConditionUnitCodeNotConfigured 1.3.6.1.4.1.476.1.42.3.2.1.162.1
The system has detected the unit code is not configured. The unit code must be configured before system start-up.
OBJECT-IDENTITY    

lgpConditionUnitCode01OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.2
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode02OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.3
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode03OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.4
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode04OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.5
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode05OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.6
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode06OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.7
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode07OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.8
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode08OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.9
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode09OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.10
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode10OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.11
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode11OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.12
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode12OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.13
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode13OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.14
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode14OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.15
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode15OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.16
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode16OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.17
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode17OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.18
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionUnitCode18OutOfRange 1.3.6.1.4.1.476.1.42.3.2.1.162.19
The system has detected a unit code error. This digit of the unit code value is out of range.
OBJECT-IDENTITY    

lgpConditionHighExternalDewPoint 1.3.6.1.4.1.476.1.42.3.2.1.163
The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold.
OBJECT-IDENTITY    

lgpConditionHcbDisconnected 1.3.6.1.4.1.476.1.42.3.2.1.164
The system has detected the humidifier control board is disconnected or not installed.
OBJECT-IDENTITY    

lgpConditionBmsResetTimerExpired 1.3.6.1.4.1.476.1.42.3.2.1.165
The BMS fan speed control reset counter has timed out.
OBJECT-IDENTITY    

lgpConditionAgentFirmwareCorrupt 1.3.6.1.4.1.476.1.42.3.2.1.166
The firmware update to the agent card has failed and the firmware is now corrupt.
OBJECT-IDENTITY    

lgpConditionSystemAccessGroup 1.3.6.1.4.1.476.1.42.3.2.1.175
This group contains various system access conditions. An examples is an open access panel.
OBJECT-IDENTITY    

lgpConditionFrontAccessOpen 1.3.6.1.4.1.476.1.42.3.2.1.175.1
The system has detected the front access panel/door is open.
OBJECT-IDENTITY    

lgpConditionRearAccessOpen 1.3.6.1.4.1.476.1.42.3.2.1.175.2
The system has detected the rear access panel/door is open.
OBJECT-IDENTITY    

lgpConditionsDamperFailure 1.3.6.1.4.1.476.1.42.3.2.1.176
This group contains various damper failure conditions.
OBJECT-IDENTITY    

lgpConditionEmergencyDamperFailure 1.3.6.1.4.1.476.1.42.3.2.1.176.1
The system has detected an emergency damper failure. The damper is in the wrong position.
OBJECT-IDENTITY    

lgpConditionRemoteShutdown 1.3.6.1.4.1.476.1.42.3.2.1.177
A remote shutdown occurred.
OBJECT-IDENTITY    

lgpConditionFireAlarm 1.3.6.1.4.1.476.1.42.3.2.1.178
Fire Alarm.
OBJECT-IDENTITY    

lgpConditionHeatersOverheated 1.3.6.1.4.1.476.1.42.3.2.1.179
Heaters Overheated.
OBJECT-IDENTITY    

lgpConditionCondenserFailureGroup 1.3.6.1.4.1.476.1.42.3.2.1.180
This group contains condenser failure conditions.
OBJECT-IDENTITY    

lgpConditionCondenser1Failure 1.3.6.1.4.1.476.1.42.3.2.1.180.1
Condenser 1 Failure.
OBJECT-IDENTITY    

lgpConditionCondenser2Failure 1.3.6.1.4.1.476.1.42.3.2.1.180.2
Condenser 2 Failure.
OBJECT-IDENTITY    

lgpConditionHumidifierCyclinderWorn 1.3.6.1.4.1.476.1.42.3.2.1.181
The system has detected the humidifier cylinder is worn.
OBJECT-IDENTITY    

lgpConditionUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.1.182
The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent.
OBJECT-IDENTITY    

lgpConditionHumidifierUnderCurrent 1.3.6.1.4.1.476.1.42.3.2.1.182.1
The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time.
OBJECT-IDENTITY    

lgpConditionHeatRejectorGroup 1.3.6.1.4.1.476.1.42.3.2.1.183
This group contains failure conditions for the heat rejection unit.
OBJECT-IDENTITY    

lgpConditionHeatRejectorFanFailure 1.3.6.1.4.1.476.1.42.3.2.1.183.1
The heat rejector fan has failed.
OBJECT-IDENTITY    

lgpConditionHeatRejectorVoltageSuppressionFailure 1.3.6.1.4.1.476.1.42.3.2.1.183.2
The heat rejector voltage suppression has failed and is no longer able to protect the unit from power fluctuations.
OBJECT-IDENTITY    

lgpConditionFreeCoolLockout 1.3.6.1.4.1.476.1.42.3.2.1.184
The free cooling capability has been disabled.
OBJECT-IDENTITY    

lgpConditionWaterLeakSensorFailure 1.3.6.1.4.1.476.1.42.3.2.1.185
The sensor used to detect water leaks is not connected or has failed.
OBJECT-IDENTITY    

lgpConditionNoLoadDetectedWarning 1.3.6.1.4.1.476.1.42.3.2.1.186
There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'
OBJECT-IDENTITY    

lgpConditionsPresent 1.3.6.1.4.1.476.1.42.3.2.2
The present number of conditions.
OBJECT-TYPE    
  Gauge32  

lgpConditionsTable 1.3.6.1.4.1.476.1.42.3.2.3
A list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpConditionEntry

lgpConditionEntry 1.3.6.1.4.1.476.1.42.3.2.3.1
This entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
OBJECT-TYPE    
  LgpConditionEntry  

lgpConditionId 1.3.6.1.4.1.476.1.42.3.2.3.1.1
A unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'.
OBJECT-TYPE    
  Unsigned32  

lgpConditionDescr 1.3.6.1.4.1.476.1.42.3.2.3.1.2
A reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpConditionTime 1.3.6.1.4.1.476.1.42.3.2.3.1.3
The value of sysUpTime when the condition occurred.
OBJECT-TYPE    
  TimeTicks  

lgpConditionControl 1.3.6.1.4.1.476.1.42.3.2.4
OBJECT IDENTIFIER    

lgpConditionControlEventReset 1.3.6.1.4.1.476.1.42.3.2.4.1
Event Reset Command. This command will reset all of the device's events.
OBJECT-TYPE    
  INTEGER noAction(1), resetAll(2)  

lgpConditionControlEventAck 1.3.6.1.4.1.476.1.42.3.2.4.2
Event Acknowledge Command. This command will acknowledge all of the device's events.
OBJECT-TYPE    
  INTEGER noAction(1), ackAll(2)  

lgpConditionDescription 1.3.6.1.4.1.476.1.42.3.2.5
The ascii text description for the condition.
OBJECT-TYPE    
  DisplayString SIZE(255)  

lgpNetworkName 1.3.6.1.4.1.476.1.42.3.2.6
The network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information.
OBJECT-TYPE    
  DisplayString SIZE(255)  

Defined Objects

LgpConditionEntry  
SEQUENCE    
  Unsigned32 as lgpConditionId  
  OBJECT IDENTIFIER as lgpConditionDescr  
  TimeTicks as lgpConditionTime