| SNMPv2-TC | SNMPv2-SMI | LIEBERT-GP-REGISTRATION-MIB |
| DisplayString | MODULE-IDENTITY | OBJECT-IDENTITY |
| OBJECT-TYPE | Gauge32 | TimeTicks |
| Unsigned32 | lgpConditions | liebertConditionsModuleReg |
| liebertGlobalProductsConditionsModule | 1.3.6.1.4.1.476.1.42.1.3.1 | ||
| The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. | |||
| MODULE-IDENTITY | |||
| lgpConditionsWellKnown | 1.3.6.1.4.1.476.1.42.3.2.1 | ||
| OBJECT IDENTIFIER | |||
| lgpConditionHighTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.1 | ||
| The temperature has exceeded the high temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.2 | ||
| The temperature is below the low temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighHumidity | 1.3.6.1.4.1.476.1.42.3.2.1.3 | ||
| The humidity has exceeded the high humidity threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowHumidity | 1.3.6.1.4.1.476.1.42.3.2.1.4 | ||
| The humidity is below the low humidity threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLossOfAirflow | 1.3.6.1.4.1.476.1.42.3.2.1.5 | ||
| The system has detected a loss of air flow. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLossOfAirflow1 | 1.3.6.1.4.1.476.1.42.3.2.1.5.1 | ||
| The system has detected a loss of air flow at sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLossOfAirflow2 | 1.3.6.1.4.1.476.1.42.3.2.1.5.2 | ||
| The system has detected a loss of air flow at sensor 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLossOfAirflowBlower1 | 1.3.6.1.4.1.476.1.42.3.2.1.5.3 | ||
| The system has detected a loss of air flow from blower 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionChangeFilter | 1.3.6.1.4.1.476.1.42.3.2.1.6 | ||
| The system has detected a condition indicating the air filter should be changed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.1.7 | ||
| This system has detected an excessive head pressure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor1HighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.1.7.1 | ||
| The system has detected excessive head pressure in compressor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor2HighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.1.7.2 | ||
| The system has detected excessive head pressure in compressor 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor3HighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.1.7.3 | ||
| The system has detected excessive head pressure in compressor 3. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor4HighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.1.7.4 | ||
| The system has detected excessive head pressure in compressor 4. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorOverload | 1.3.6.1.4.1.476.1.42.3.2.1.8 | ||
| This system has detected a compressor overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor1Overload | 1.3.6.1.4.1.476.1.42.3.2.1.8.1 | ||
| The system has detected an overload condition on compressor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor2Overload | 1.3.6.1.4.1.476.1.42.3.2.1.8.2 | ||
| The system has detected an overload condition on compressor 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorShortCycle | 1.3.6.1.4.1.476.1.42.3.2.1.9 | ||
| A compressor has exceeded the maximum number of starts in a minimum time period. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor1ShortCycle | 1.3.6.1.4.1.476.1.42.3.2.1.9.1 | ||
| The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor2ShortCycle | 1.3.6.1.4.1.476.1.42.3.2.1.9.2 | ||
| The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorLowSuctionPressure | 1.3.6.1.4.1.476.1.42.3.2.1.10 | ||
| The pressure at a compressor inlet has dropped below the minimum setting. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMainFanOverLoad | 1.3.6.1.4.1.476.1.42.3.2.1.11 | ||
| The system has detected a main fan overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionManualOverride | 1.3.6.1.4.1.476.1.42.3.2.1.12 | ||
| The system has detected a manual override condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionStandbyGlycoolPumpOn | 1.3.6.1.4.1.476.1.42.3.2.1.13 | ||
| The standby Glycol or Glycool pump is activated. | |||
| OBJECT-IDENTITY | |||
| lgpConditionWaterUnderFloor | 1.3.6.1.4.1.476.1.42.3.2.1.14 | ||
| Moisture has been detected under the floor. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierProblem | 1.3.6.1.4.1.476.1.42.3.2.1.15 | ||
| The system has detected a humidifier problem. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowWaterInHumidifier | 1.3.6.1.4.1.476.1.42.3.2.1.16 | ||
| The system has detected a low water condition in the humidifier reservoir. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSmokeDetected | 1.3.6.1.4.1.476.1.42.3.2.1.17 | ||
| The system has detected smoke. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowWaterFlow | 1.3.6.1.4.1.476.1.42.3.2.1.18 | ||
| The system has detected a low water flow rate condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLostPower | 1.3.6.1.4.1.476.1.42.3.2.1.19 | ||
| The system has lost power before being switched off using the controls. This condition is activated when power is restored. | |||
| OBJECT-IDENTITY | |||
| lgpGeneralFault | 1.3.6.1.4.1.476.1.42.3.2.1.20 | ||
| A fault condition has been detected that is not identifed in the well known list. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.21 | ||
| This system has detected a local, or customer, alarm condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm1 | 1.3.6.1.4.1.476.1.42.3.2.1.21.1 | ||
| The system has detected that customer alarm condition 1 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm2 | 1.3.6.1.4.1.476.1.42.3.2.1.21.2 | ||
| The system has detected that customer alarm condition 2 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm3 | 1.3.6.1.4.1.476.1.42.3.2.1.21.3 | ||
| The system has detected that customer alarm condition 3 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm4 | 1.3.6.1.4.1.476.1.42.3.2.1.21.4 | ||
| The system has detected that customer alarm condition 4 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm5 | 1.3.6.1.4.1.476.1.42.3.2.1.21.5 | ||
| The system has detected that customer alarm condition 5 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm6 | 1.3.6.1.4.1.476.1.42.3.2.1.21.6 | ||
| The system has detected that customer alarm condition 6 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm7 | 1.3.6.1.4.1.476.1.42.3.2.1.21.7 | ||
| The system has detected that customer alarm condition 7 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocalAlarm8 | 1.3.6.1.4.1.476.1.42.3.2.1.21.8 | ||
| The system has detected that customer alarm condition 8 is active. | |||
| OBJECT-IDENTITY | |||
| lgpConditionStandbyUnitOn | 1.3.6.1.4.1.476.1.42.3.2.1.22 | ||
| The system has detected the standby unit is operating. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorLowPressure | 1.3.6.1.4.1.476.1.42.3.2.1.23 | ||
| This system has detected a low head compressor condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor1LowPressure | 1.3.6.1.4.1.476.1.42.3.2.1.23.1 | ||
| The system has detected low pressure in compressor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor2LowPressure | 1.3.6.1.4.1.476.1.42.3.2.1.23.2 | ||
| The system has detected low pressure in compressor 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor3LowPressure | 1.3.6.1.4.1.476.1.42.3.2.1.23.3 | ||
| The system has detected low pressure in compressor 3. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor4LowPressure | 1.3.6.1.4.1.476.1.42.3.2.1.23.4 | ||
| The system has detected low pressure in compressor 4. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighWaterInPan | 1.3.6.1.4.1.476.1.42.3.2.1.24 | ||
| The system has detected a high water condition in the condensor pan. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFaultySensor | 1.3.6.1.4.1.476.1.42.3.2.1.25 | ||
| The system has detected a faulty temperature/humidity sensor. | |||
| OBJECT-IDENTITY | |||
| lgpConditionServiceCooling | 1.3.6.1.4.1.476.1.42.3.2.1.26 | ||
| The Cooling system requires scheduled maintenance. | |||
| OBJECT-IDENTITY | |||
| lgpConditionServiceHumidifier | 1.3.6.1.4.1.476.1.42.3.2.1.27 | ||
| The Humidifier requires scheduled maintenance. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemControlBatteryLow | 1.3.6.1.4.1.476.1.42.3.2.1.28 | ||
| Charge level of the system control's battery is below the alarm set point. | |||
| OBJECT-IDENTITY | |||
| lgpConditionGroundSystemFault | 1.3.6.1.4.1.476.1.42.3.2.1.29 | ||
| The system has detected a ground system fault. | |||
| OBJECT-IDENTITY | |||
| lgpConditionGroundFailure | 1.3.6.1.4.1.476.1.42.3.2.1.30 | ||
| The system has detected a ground failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSecurityBreach | 1.3.6.1.4.1.476.1.42.3.2.1.31 | ||
| The system has detected a security breach. | |||
| OBJECT-IDENTITY | |||
| lgpConditionEmergencyShutdown | 1.3.6.1.4.1.476.1.42.3.2.1.32 | ||
| The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOnBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33 | ||
| This system has detected the load is being powered by a bypass source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadOnBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33.1 | ||
| The load is being powered by a bypass source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadOnMaintenceBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33.2 | ||
| The load is being powered by a maintenance bypass source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysLoadOnBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33.3 | ||
| The parallel system has transferred to bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadOnBypassByImpact | 1.3.6.1.4.1.476.1.42.3.2.1.33.4 | ||
| The system has dectected a load impact and has transferred the load to the bypass source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadTransferedToBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33.5 | ||
| The system has transfered to bypass. The load is being powered by the bypass source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionEmergencyTransferToBypass | 1.3.6.1.4.1.476.1.42.3.2.1.33.6 | ||
| The system has performed an emergency transfer to bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadVoltTHD | 1.3.6.1.4.1.476.1.42.3.2.1.34 | ||
| The total harmonic distortion of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLogicFailure | 1.3.6.1.4.1.476.1.42.3.2.1.35 | ||
| The system has detected a control logic failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupplyFault | 1.3.6.1.4.1.476.1.42.3.2.1.36 | ||
| This system had detected a power supply fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupply1Fault | 1.3.6.1.4.1.476.1.42.3.2.1.36.1 | ||
| The system has detected power supply 1 is in a fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupply2Fault | 1.3.6.1.4.1.476.1.42.3.2.1.36.2 | ||
| The system has detected power supply 2 is in a fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.1.37 | ||
| This system has detected a power supply failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupply1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.37.1 | ||
| The system has detected power supply 1 has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupply2Failure | 1.3.6.1.4.1.476.1.42.3.2.1.37.2 | ||
| The system has detected power supply 2 has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1PowerSupplyInputFailure | 1.3.6.1.4.1.476.1.42.3.2.1.37.3 | ||
| The system has detected the source 1 Power supply input has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2PowerSupplyInputFailure | 1.3.6.1.4.1.476.1.42.3.2.1.37.4 | ||
| The system has detected the source 2 Power supply input has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerSupplyLogicFailure | 1.3.6.1.4.1.476.1.42.3.2.1.37.5 | ||
| The system has detected a power supply logic failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.1.37.6 | ||
| The system has detected the power supply to the compressors has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38 | ||
| This system has detected an over voltage condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1OverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.1 | ||
| The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2OverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.2 | ||
| The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.3 | ||
| The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.4 | ||
| The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for an specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.5 | ||
| The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassOverVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.38.6 | ||
| The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.7 | ||
| The system has detected a battery over voltage condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBusOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.8 | ||
| This system has detected a DC Bus over voltage condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus1OverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.1 | ||
| The system has detected an over voltage condition on DC Bus 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus2OverVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.2 | ||
| The system has detected an over voltage condition on DC Bus 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus1OverVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.3 | ||
| The system has detected an over voltage failure condition on DC Bus 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus2OverVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.38.8.4 | ||
| The system has detected an over voltage failure condition on DC Bus 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39 | ||
| This system has detected an under voltage condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1UnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.1 | ||
| The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2UnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.2 | ||
| The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.3 | ||
| The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1UnderVoltageRMS | 1.3.6.1.4.1.476.1.42.3.2.1.39.4 | ||
| The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2UnderVoltageRMS | 1.3.6.1.4.1.476.1.42.3.2.1.39.5 | ||
| The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.6 | ||
| The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.7 | ||
| The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassUnderVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.39.8 | ||
| The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.9 | ||
| The system has detected a battery under voltage condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBusUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.10 | ||
| This system has detected a DC bus under voltage condition | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus1UnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.1 | ||
| The system has detected an under voltage condition on DC Bus 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus2UnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.2 | ||
| The system has detected an under voltage condition on DC Bus 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus1UnderVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.3 | ||
| The system has detected an under voltage failure condition on DC Bus 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcBus2UnderVoltageFailure | 1.3.6.1.4.1.476.1.42.3.2.1.39.10.4 | ||
| The system has detected an under voltage failure condition on DC Bus 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOverload | 1.3.6.1.4.1.476.1.42.3.2.1.40 | ||
| This system has detected an overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1Overload | 1.3.6.1.4.1.476.1.42.3.2.1.40.1 | ||
| The system has detected a overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemOverload | 1.3.6.1.4.1.476.1.42.3.2.1.40.2 | ||
| The system has detected a overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1PeakCurrentOverLoad | 1.3.6.1.4.1.476.1.42.3.2.1.40.3 | ||
| The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for an specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2PeakCurrentOverLoad | 1.3.6.1.4.1.476.1.42.3.2.1.40.4 | ||
| The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for an specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOverLimit | 1.3.6.1.4.1.476.1.42.3.2.1.40.5 | ||
| The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOverload | 1.3.6.1.4.1.476.1.42.3.2.1.40.6 | ||
| The system has detected an output overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysOverload | 1.3.6.1.4.1.476.1.42.3.2.1.40.7 | ||
| The parallel system has detected an overload condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionScrShort | 1.3.6.1.4.1.476.1.42.3.2.1.41 | ||
| This system has detected a Silicon Controlled Rectifier (SCR) short condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1ScrShort | 1.3.6.1.4.1.476.1.42.3.2.1.41.1 | ||
| The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2ScrShort | 1.3.6.1.4.1.476.1.42.3.2.1.41.2 | ||
| The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassScrShort | 1.3.6.1.4.1.476.1.42.3.2.1.41.3 | ||
| The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionScrOpen | 1.3.6.1.4.1.476.1.42.3.2.1.42 | ||
| This system has detected a Silicon Controlled Rectifier (SCR) open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1ScrOpen | 1.3.6.1.4.1.476.1.42.3.2.1.42.1 | ||
| The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2ScrOpen | 1.3.6.1.4.1.476.1.42.3.2.1.42.2 | ||
| The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassScrOpen | 1.3.6.1.4.1.476.1.42.3.2.1.42.3 | ||
| The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFanFailure | 1.3.6.1.4.1.476.1.42.3.2.1.43 | ||
| This system has detected a fan failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFan1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.43.1 | ||
| The system has detected a fan 1 failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionTransferInhibited | 1.3.6.1.4.1.476.1.42.3.2.1.44 | ||
| The system is preventing a transfer of the load to the alternate source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAutoReTransferPrimed | 1.3.6.1.4.1.476.1.42.3.2.1.45 | ||
| The system is capable to retransfer to the preferred source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSourcesOutOfSync | 1.3.6.1.4.1.476.1.42.3.2.1.46 | ||
| The system has detected that the input sources are not within the specified phase difference (synchronization window). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSourceFailure | 1.3.6.1.4.1.476.1.42.3.2.1.47 | ||
| This system has detected an input source failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.47.1 | ||
| The system has detected source 1 has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2Failure | 1.3.6.1.4.1.476.1.42.3.2.1.47.2 | ||
| The system has detected source 2 has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAutoReTransferInhibited | 1.3.6.1.4.1.476.1.42.3.2.1.48 | ||
| The system is preventing a transfer of the load back to the prefered source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAutoReTransferFailed | 1.3.6.1.4.1.476.1.42.3.2.1.49 | ||
| The system is failing to automatically retransfer the load back to the preferred source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFuseOpen | 1.3.6.1.4.1.476.1.42.3.2.1.50 | ||
| This system has detected an open fuse condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlFuse1Open | 1.3.6.1.4.1.476.1.42.3.2.1.50.1 | ||
| The system has detected a control power fuse 1 open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlFuse2Open | 1.3.6.1.4.1.476.1.42.3.2.1.50.2 | ||
| The system has detected a control power fuse 2 open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierFuseOpen | 1.3.6.1.4.1.476.1.42.3.2.1.50.3 | ||
| The system has detected a rectifier fuse open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterFuseOpen | 1.3.6.1.4.1.476.1.42.3.2.1.50.4 | ||
| The system has detected a inverter fuse open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadFuseOpen | 1.3.6.1.4.1.476.1.42.3.2.1.50.5 | ||
| The system has detected an output to load fuse open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcCapacitorFuseOpen | 1.3.6.1.4.1.476.1.42.3.2.1.50.6 | ||
| The system has detected a DC capacitor fuse open condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDisconnect | 1.3.6.1.4.1.476.1.42.3.2.1.51 | ||
| This system has detected an open/close disconnect condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1DisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.1 | ||
| The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2DisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.2 | ||
| The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1PduDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.3 | ||
| The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2PduDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.4 | ||
| The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadDisconnect1Open | 1.3.6.1.4.1.476.1.42.3.2.1.51.5 | ||
| The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadDisconnect2Open | 1.3.6.1.4.1.476.1.42.3.2.1.51.6 | ||
| The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1BypassDisconnectClosed | 1.3.6.1.4.1.476.1.42.3.2.1.51.7 | ||
| The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2BypassDisconnectClosed | 1.3.6.1.4.1.476.1.42.3.2.1.51.8 | ||
| The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadNeutralDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.9 | ||
| The system has detected the the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.10 | ||
| The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.11 | ||
| The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.12 | ||
| The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.13 | ||
| The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionStaticSwitchDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.1.51.14 | ||
| The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.1.52 | ||
| This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1FrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.1.52.1 | ||
| The system has detected a frequency deviation condition on source 1. The frequency for source 1 is outside of the pre-determined thresholds for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2FrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.1.52.2 | ||
| The system has detected a frequency deviation condition on source 2. The frequency for source 2 is outside of the pre-determined thresholds for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.1.52.3 | ||
| The system has detected a input frequency deviation condition. The frequency for the input is outside of the pre-determined thresholds for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.1.52.4 | ||
| The system has detected a frequency deviation condition on the output. The frequency for the output is outside of the pre-determined thresholds for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53 | ||
| This system has detected an current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1OverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.1 | ||
| The system has detected a over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2OverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.2 | ||
| The system has detected a over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.3 | ||
| The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionGroundOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.4 | ||
| A ground source is experiencing a over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.5 | ||
| The system has detected a rectifier over current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.6 | ||
| The system has detected an inverter over current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryConverterOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.7 | ||
| The system has detected a over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryBalancerOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.8 | ||
| The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.53.9 | ||
| The system has detected a over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54 | ||
| This system has detected a sensor failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadVoltageSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.1 | ||
| The system had detected a output to load voltage sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1VoltageSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.2 | ||
| The system had detected a source 1 voltage sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2VoltageSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.3 | ||
| The system had detected a source 2 voltage sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1ScrSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.4 | ||
| The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2ScrSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.5 | ||
| The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1CurrentSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.6 | ||
| The system has detected a source 1 current sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2CurrentSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.7 | ||
| The system has detected a source 2 current sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRoomTempHumiditySensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.8 | ||
| The system has detected a device temperature and humidity sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionGlycolTempSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.9 | ||
| The system has detected a glycol temperature sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLocal1SensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.10 | ||
| The system has detected a local 1 sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor1SensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.11 | ||
| The system has detected a compressor 1 digital scroll sensor failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressor2SensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.12 | ||
| The system has detected a compressor 2 digital scroll sensor failure condtion. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSupplySensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.13 | ||
| The system has detected a supply sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCabinetTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.14 | ||
| The system has detected a cabinet temperature sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCabinetHumiditySensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.15 | ||
| The system has detected a cabinet humidity sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRoomTempSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.54.16 | ||
| The system has detected a room temperature sensor failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInternalCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.1.55 | ||
| This system has detected an internal communication failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionExternalCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.1.56 | ||
| This system has detected an external communication failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSourceGateDriveFailure | 1.3.6.1.4.1.476.1.42.3.2.1.57 | ||
| This system has detected a source gate drive failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1GateDriveFailure | 1.3.6.1.4.1.476.1.42.3.2.1.57.1 | ||
| The system has detected a source 1 gate drive failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2GateDriveFailure | 1.3.6.1.4.1.476.1.42.3.2.1.57.2 | ||
| The system has detected a source 2 gate drive failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDisconnectFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58 | ||
| This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadNeutralDisconnectFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58.1 | ||
| The system has detected the the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1DisconnectShuntTripFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58.2 | ||
| The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2DisconnectShuntTripFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58.3 | ||
| The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterDisconnectFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58.4 | ||
| The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryDisconnectFailure | 1.3.6.1.4.1.476.1.42.3.2.1.58.5 | ||
| The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). | |||
| OBJECT-IDENTITY | |||
| lgpConditionOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59 | ||
| This system has detected an over temperature condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHeatSink1OverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.1 | ||
| The system has detected a heat sink 1 over temperature condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAmbient1OverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.2 | ||
| The system has detected an ambient over temperature condition at location 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.3 | ||
| The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionTransformerOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.4 | ||
| The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.5 | ||
| The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.6 | ||
| The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.7 | ||
| The system has detected an inverter over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierInductorOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.8 | ||
| The system has detected an inverter inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterInductorOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.9 | ||
| The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryConverterOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.10 | ||
| The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryBalancerInductorOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.11 | ||
| The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for an specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionChilledWaterOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.12 | ||
| The system has detected a chilled water over temperature condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionElectricHeatersOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.1.59.13 | ||
| The system has detected a electric heater over temperature condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadOnAlternateSource | 1.3.6.1.4.1.476.1.42.3.2.1.60 | ||
| The system has detected that the load is being supplied by the alternate source. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.1.61 | ||
| This system has detected a phase rotation error condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource1PhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.1.61.1 | ||
| The system has detected a phase rotation error on source 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSource2PhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.1.61.2 | ||
| The system has detected a phase rotation error on source 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassPhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.1.61.3 | ||
| The system has detected a phase rotation error on the bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputPhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.1.61.4 | ||
| The system has detected a phase rotation error on the input. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlModuleFailure | 1.3.6.1.4.1.476.1.42.3.2.1.62 | ||
| This system has detected a control module failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlModule1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.62.1 | ||
| The system has detected a control module 1 failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHistoryLogFull | 1.3.6.1.4.1.476.1.42.3.2.1.63 | ||
| The system has detected the history log is full. | |||
| OBJECT-IDENTITY | |||
| lgpConditionConfigurationModified | 1.3.6.1.4.1.476.1.42.3.2.1.64 | ||
| The system has detected the configuration has been modified. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPasswordModified | 1.3.6.1.4.1.476.1.42.3.2.1.65 | ||
| The system has detected the password has been modified. | |||
| OBJECT-IDENTITY | |||
| lgpConditionTimeModified | 1.3.6.1.4.1.476.1.42.3.2.1.66 | ||
| The system has detected the time has been modified. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDateModified | 1.3.6.1.4.1.476.1.42.3.2.1.67 | ||
| The system has detected the date has been modified. | |||
| OBJECT-IDENTITY | |||
| lgpConditionEventLogCleared | 1.3.6.1.4.1.476.1.42.3.2.1.68 | ||
| The system has detected the event log has been cleared. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHistoryLogCleared | 1.3.6.1.4.1.476.1.42.3.2.1.69 | ||
| The system has detected the history log has been cleared. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUtilityFailure | 1.3.6.1.4.1.476.1.42.3.2.1.70 | ||
| The system has detected a utility failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryTestInProgress | 1.3.6.1.4.1.476.1.42.3.2.1.71 | ||
| The system is performing a battery test at this time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadOnBattery | 1.3.6.1.4.1.476.1.42.3.2.1.72 | ||
| The system load is being supported by the battery. | |||
| OBJECT-IDENTITY | |||
| lgpConditionReplaceBattery | 1.3.6.1.4.1.476.1.42.3.2.1.74 | ||
| The system has detected the batteries are due to be replaced. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUpsShutdownPending | 1.3.6.1.4.1.476.1.42.3.2.1.75 | ||
| The system is in a shutdown pending condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryChargerFailed | 1.3.6.1.4.1.476.1.42.3.2.1.76 | ||
| The system has detected the battery charger has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassVoltageUnqualified | 1.3.6.1.4.1.476.1.42.3.2.1.77 | ||
| The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for an specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCheckAirFilter | 1.3.6.1.4.1.476.1.42.3.2.1.78 | ||
| The system has detected it is time to check the air filter. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBrownOut | 1.3.6.1.4.1.476.1.42.3.2.1.79 | ||
| The system has detected a brown out condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMultipleTransferLockout | 1.3.6.1.4.1.476.1.42.3.2.1.80 | ||
| The system has locked out transfers to bypass. Too many transfers have occured over a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBypassPhaseLost | 1.3.6.1.4.1.476.1.42.3.2.1.81 | ||
| The system has detected one or more bypass phases are missing. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMaintenceBypassInhibited | 1.3.6.1.4.1.476.1.42.3.2.1.82 | ||
| The system is preventing a transfer of the load to maintence bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLoadLockedOnBypass | 1.3.6.1.4.1.476.1.42.3.2.1.83 | ||
| The system has detected an error and been put locked on bypass. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadShort | 1.3.6.1.4.1.476.1.42.3.2.1.84 | ||
| The system has detected an output to load short circuit condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionEmergencyTransferToInverter | 1.3.6.1.4.1.476.1.42.3.2.1.85 | ||
| The system has detected an emergency transfer of the load to inverter. | |||
| OBJECT-IDENTITY | |||
| lgpConditonEmergencyPowerOff | 1.3.6.1.4.1.476.1.42.3.2.1.86 | ||
| The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterBackFeed | 1.3.6.1.4.1.476.1.42.3.2.1.87 | ||
| The system has detected an inverter backfeed condition. The inverter is feeding power through the bypass back to the input. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDcGroundFault | 1.3.6.1.4.1.476.1.42.3.2.1.88 | ||
| The system has detected a DC ground fault. | |||
| OBJECT-IDENTITY | |||
| lgpConditionStaticTransferSwitchInhibited | 1.3.6.1.4.1.476.1.42.3.2.1.89 | ||
| The system is preventing the use of the static transfer switch. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryLogFullWarning | 1.3.6.1.4.1.476.1.42.3.2.1.90 | ||
| The system has detected the battery log is approaching the maximum record limit. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputCurrentUnbalanced | 1.3.6.1.4.1.476.1.42.3.2.1.91 | ||
| The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSelfTestFailed | 1.3.6.1.4.1.476.1.42.3.2.1.92 | ||
| The system has detected a self-test failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterOutOfSynchronization | 1.3.6.1.4.1.476.1.42.3.2.1.93 | ||
| The system has detected a Inverter out of sync condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionModuleAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.94 | ||
| This system has detected an alarm within the multi-module system. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit1Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.1 | ||
| The multi-module system has detected an alarm condition on unit 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit2Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.2 | ||
| The multi-module system has detected an alarm condition on unit 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit3Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.3 | ||
| The multi-module system has detected an alarm condition on unit 3. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit4Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.4 | ||
| The multi-module system has detected an alarm condition on unit 4. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit5Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.5 | ||
| The multi-module system has detected an alarm condition on unit 5. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit6Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.6 | ||
| The multi-module system has detected an alarm condition on unit 6. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit7Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.7 | ||
| The multi-module system has detected an alarm condition on unit 7. | |||
| OBJECT-IDENTITY | |||
| lgpConditioniModuleUnit8Alarm | 1.3.6.1.4.1.476.1.42.3.2.1.94.8 | ||
| The multi-module system has detected an alarm condition on unit 8. | |||
| OBJECT-IDENTITY | |||
| lgpConditionActiveModuleAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.95 | ||
| The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlFailure | 1.3.6.1.4.1.476.1.42.3.2.1.96 | ||
| This system has detected a control failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMainControlFailure | 1.3.6.1.4.1.476.1.42.3.2.1.96.1 | ||
| The system has detected a main control failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRedundantControlFailure | 1.3.6.1.4.1.476.1.42.3.2.1.96.2 | ||
| The system has detected a redundant control failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysControlFailure | 1.3.6.1.4.1.476.1.42.3.2.1.96.3 | ||
| The parallel system has detected a control failure condition with one of the controls. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlWarning | 1.3.6.1.4.1.476.1.42.3.2.1.97 | ||
| This system has detected a control warning conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMainControlWarning | 1.3.6.1.4.1.476.1.42.3.2.1.97.1 | ||
| The system has detected a main control warning condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRedundantControlWarning | 1.3.6.1.4.1.476.1.42.3.2.1.97.2 | ||
| The system has detected a redundant control warning condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUserInterfaceFailure | 1.3.6.1.4.1.476.1.42.3.2.1.98 | ||
| The system has detected a user interface control failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLostPowerRedundancy | 1.3.6.1.4.1.476.1.42.3.2.1.99 | ||
| The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting 'lgpPwrMinimumRedundantPowerModule'. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerModuleFailure | 1.3.6.1.4.1.476.1.42.3.2.1.100 | ||
| The system has detected a power module failure condition in the system. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryModuleFailure | 1.3.6.1.4.1.476.1.42.3.2.1.101 | ||
| The system has detected a battery module failure condition in the system. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOff | 1.3.6.1.4.1.476.1.42.3.2.1.102 | ||
| The system has detected that there is no power being supplied to the load. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemOff | 1.3.6.1.4.1.476.1.42.3.2.1.103 | ||
| The system is off. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierStartupFailure | 1.3.6.1.4.1.476.1.42.3.2.1.104 | ||
| The system has detected a rectifier under voltage start-up failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierFault | 1.3.6.1.4.1.476.1.42.3.2.1.105 | ||
| The system has detected a rectifier fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterShutdownLowDc | 1.3.6.1.4.1.476.1.42.3.2.1.106 | ||
| The system has shutdown the inverter due to a DC bus under voltage. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterFault | 1.3.6.1.4.1.476.1.42.3.2.1.107 | ||
| The system has detected an inverter fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterDcOffsetOverrun | 1.3.6.1.4.1.476.1.42.3.2.1.108 | ||
| The system has detected an over run of the inverter DC offset voltage. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysLowBatteryWarning | 1.3.6.1.4.1.476.1.42.3.2.1.109 | ||
| The parallel system has detected a low battery warning condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysLoadShareFault | 1.3.6.1.4.1.476.1.42.3.2.1.110 | ||
| The parallel system has detected a load share fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryFault | 1.3.6.1.4.1.476.1.42.3.2.1.111 | ||
| The system has detected a battery fault condition. The battery conductors are either reversed or disconnected. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryConverterFailure | 1.3.6.1.4.1.476.1.42.3.2.1.112 | ||
| The system has detected a battery converter failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryBalancerFault | 1.3.6.1.4.1.476.1.42.3.2.1.113 | ||
| The system has detected a battery balancer fault condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionpsUpsOperationFault | 1.3.6.1.4.1.476.1.42.3.2.1.114 | ||
| The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence. | |||
| OBJECT-IDENTITY | |||
| lgpConditionOutputToLoadOnJointMode | 1.3.6.1.4.1.476.1.42.3.2.1.115 | ||
| The system load is being supported by both the battery and rectifier. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInputNeutralLost | 1.3.6.1.4.1.476.1.42.3.2.1.116 | ||
| The system had detected the main input neutral is disconnected. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowBatteryWarning | 1.3.6.1.4.1.476.1.42.3.2.1.117 | ||
| The battery's remaining charge is less than or equal to the agent's configured low threshold 'lgpPwrConfigLowBatteryWarningTime'. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInternalFault | 1.3.6.1.4.1.476.1.42.3.2.1.118 | ||
| The system has detected an internal fault. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryTestFailed | 1.3.6.1.4.1.476.1.42.3.2.1.119 | ||
| The system has detected a battery self-test failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerModuleWarning | 1.3.6.1.4.1.476.1.42.3.2.1.120 | ||
| The system has detected an alarm condition on one, or more, power modules. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBatteryModuleWarning | 1.3.6.1.4.1.476.1.42.3.2.1.121 | ||
| The system has detected an alarm condition on one, or more, battery modules. | |||
| OBJECT-IDENTITY | |||
| lgpConditionControlModuleWarning | 1.3.6.1.4.1.476.1.42.3.2.1.122 | ||
| The system has detected a control module warning. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUpsOperationFault | 1.3.6.1.4.1.476.1.42.3.2.1.123 | ||
| The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence. | |||
| OBJECT-IDENTITY | |||
| lgpConditionActiveAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.124 | ||
| The system has detected an alarm condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRectifierCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.1.125 | ||
| The system has detected an internal communication failure condition with the rectifier. | |||
| OBJECT-IDENTITY | |||
| lgpConditionInverterCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.1.126 | ||
| The system has detected an internal communication failure condition with the inverter. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysConnectionFault | 1.3.6.1.4.1.476.1.42.3.2.1.127 | ||
| The parallel system has detected a connection fault. One or more of the devices are not properly connected. | |||
| OBJECT-IDENTITY | |||
| lgpConditionParallelSysCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.1.128 | ||
| The parallel system has detected a communication failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLostBatteryRedundancy | 1.3.6.1.4.1.476.1.42.3.2.1.129 | ||
| The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompPumpDownFailure | 1.3.6.1.4.1.476.1.42.3.2.1.130 | ||
| The system has detected that a compressor has failed to pump down. | |||
| OBJECT-IDENTITY | |||
| lgpConditionComp1PumpDownFailure | 1.3.6.1.4.1.476.1.42.3.2.1.130.1 | ||
| The system has detected that compressor 1 has failed to pump down. | |||
| OBJECT-IDENTITY | |||
| lgpConditionComp2PumpDownFailure | 1.3.6.1.4.1.476.1.42.3.2.1.130.2 | ||
| The system has detected that compressor 2 has failed to pump down. | |||
| OBJECT-IDENTITY | |||
| lgpConditionChilledWaterLowWaterFlow | 1.3.6.1.4.1.476.1.42.3.2.1.131 | ||
| The system has detected a chilled water low water flow condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAirFilterClogged | 1.3.6.1.4.1.476.1.42.3.2.1.132 | ||
| The system has detected a air filter clogged condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierFailure | 1.3.6.1.4.1.476.1.42.3.2.1.133 | ||
| The system has detected a humidifier failure condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRunHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134 | ||
| The system has detected a pre-determined run hours threshold has been exceeded. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.1 | ||
| The system has detected the system run hours has exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionComp1RunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.2 | ||
| The system has detected the compressor 1 run hours has exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionComp2RunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.3 | ||
| The system has detected the compressor 2 run hours has exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFreeCoolRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.4 | ||
| The system has detected the free cooling run hours has exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionElectricalHeater1RunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.5 | ||
| The system has detected the electrical heater's run hours have exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionElectricalHeater2RunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.6 | ||
| The system has detected the electrical heater's run hours have exceeded the pre-determined limit. | |||
| OBJECT-IDENTITY | |||
| lgpConditionElectricalHeater3RunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.7 | ||
| The system has detected the electrical heater's run hours have exceeded the pre-determined limit. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHotWaterRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.8 | ||
| The system has detected the hot water run hours have exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHotGasRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.9 | ||
| The system has detected the hot gas run hours have exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.10 | ||
| The system has detected the humidifier run hours have exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionDehumidiferRunHrsExceeded | 1.3.6.1.4.1.476.1.42.3.2.1.134.11 | ||
| The system has detected the dehumidifier run hours have exceeded the pre-determined threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarning | 1.3.6.1.4.1.476.1.42.3.2.1.135 | ||
| The system has detected a loss of communications between another module. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit1 | 1.3.6.1.4.1.476.1.42.3.2.1.135.1 | ||
| The system has detected a loss of communications with unit 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit2 | 1.3.6.1.4.1.476.1.42.3.2.1.135.2 | ||
| The system has detected a loss of communications with unit 2. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit3 | 1.3.6.1.4.1.476.1.42.3.2.1.135.3 | ||
| The system has detected a loss of communications with unit 3. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit4 | 1.3.6.1.4.1.476.1.42.3.2.1.135.4 | ||
| The system has detected a loss of communications with unit 4. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit5 | 1.3.6.1.4.1.476.1.42.3.2.1.135.5 | ||
| The system has detected a loss of communications with unit 5. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit6 | 1.3.6.1.4.1.476.1.42.3.2.1.135.6 | ||
| The system has detected a loss of communications with unit 6. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit7 | 1.3.6.1.4.1.476.1.42.3.2.1.135.7 | ||
| The system has detected a loss of communications with unit 7. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit8 | 1.3.6.1.4.1.476.1.42.3.2.1.135.8 | ||
| The system has detected a loss of communications with unit 8. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit9 | 1.3.6.1.4.1.476.1.42.3.2.1.135.9 | ||
| The system has detected a loss of communications with unit 9. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit10 | 1.3.6.1.4.1.476.1.42.3.2.1.135.10 | ||
| The system has detected a loss of communications with unit 10. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit11 | 1.3.6.1.4.1.476.1.42.3.2.1.135.11 | ||
| The system has detected a loss of communications with unit 11. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit12 | 1.3.6.1.4.1.476.1.42.3.2.1.135.12 | ||
| The system has detected a loss of communications with unit 12. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit13 | 1.3.6.1.4.1.476.1.42.3.2.1.135.13 | ||
| The system has detected a loss of communications with unit 13. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit14 | 1.3.6.1.4.1.476.1.42.3.2.1.135.14 | ||
| The system has detected a loss of communications with unit 14. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit15 | 1.3.6.1.4.1.476.1.42.3.2.1.135.15 | ||
| The system has detected a loss of communications with unit 15. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCommWarningUnit16 | 1.3.6.1.4.1.476.1.42.3.2.1.135.16 | ||
| The system has detected a loss of communications with unit 16. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitOn | 1.3.6.1.4.1.476.1.42.3.2.1.136 | ||
| The unit is on. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitOff | 1.3.6.1.4.1.476.1.42.3.2.1.137 | ||
| The unit is off. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSleepModeOff | 1.3.6.1.4.1.476.1.42.3.2.1.138 | ||
| The system sleep mode operation has been turned off. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerOn | 1.3.6.1.4.1.476.1.42.3.2.1.139 | ||
| The system power is on. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemOnStanby | 1.3.6.1.4.1.476.1.42.3.2.1.140 | ||
| The system is on standby. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPowerOff | 1.3.6.1.4.1.476.1.42.3.2.1.141 | ||
| The system power is off. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureGroup | 1.3.6.1.4.1.476.1.42.3.2.1.142 | ||
| The system has detected a high temperature condition. This group contains various high temperature conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureSensor1 | 1.3.6.1.4.1.476.1.42.3.2.1.142.1 | ||
| The temperature has exceeded the high temperature threshold for sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureDigitalScroll1 | 1.3.6.1.4.1.476.1.42.3.2.1.142.2 | ||
| The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureDigitalScroll2 | 1.3.6.1.4.1.476.1.42.3.2.1.142.3 | ||
| The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureUser1 | 1.3.6.1.4.1.476.1.42.3.2.1.142.4 | ||
| The temperature has exceeded the high temperature threshold for user configured temperature sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighTemperatureInternal | 1.3.6.1.4.1.476.1.42.3.2.1.142.5 | ||
| The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowTemperatureGroup | 1.3.6.1.4.1.476.1.42.3.2.1.143 | ||
| The system has detected a low temperature condition. This group contains various low temperature conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowTemperatureSensor1 | 1.3.6.1.4.1.476.1.42.3.2.1.143.1 | ||
| The temperature is below the low temperature threshold for sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowTemperatureInternal | 1.3.6.1.4.1.476.1.42.3.2.1.143.2 | ||
| The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighHumidityGroup | 1.3.6.1.4.1.476.1.42.3.2.1.144 | ||
| The system has detected a high humidity condition. This group contains various high humidity conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighHumiditySensor1 | 1.3.6.1.4.1.476.1.42.3.2.1.144.1 | ||
| The humidity has exceeded the high humidity threshold for sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowHumidityGroup | 1.3.6.1.4.1.476.1.42.3.2.1.145 | ||
| The system has detected a low humidity condition. This group contains various high humidity conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowHumiditySensor1 | 1.3.6.1.4.1.476.1.42.3.2.1.145.1 | ||
| The humidity is below the low humidity threshold for sensor 1. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPeerNetworkNoMaster | 1.3.6.1.4.1.476.1.42.3.2.1.146 | ||
| The system is unable to communicate with the master on the peer to peer network. | |||
| OBJECT-IDENTITY | |||
| lgpConditionNoOnOffPermissions | 1.3.6.1.4.1.476.1.42.3.2.1.147 | ||
| The system lacks the permissions to execute the on/off operation. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPeerNetworkFailure | 1.3.6.1.4.1.476.1.42.3.2.1.148 | ||
| The system has detected a communication failure on the peer to peer network. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitDisabled | 1.3.6.1.4.1.476.1.42.3.2.1.149 | ||
| The unit is disabled. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitShutdown | 1.3.6.1.4.1.476.1.42.3.2.1.150 | ||
| The system has shutdown. | |||
| OBJECT-IDENTITY | |||
| lgpConditionPeerNetworkDiscovered | 1.3.6.1.4.1.476.1.42.3.2.1.151 | ||
| The system has established communications on the peer to peer network. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLossOfWaterFlow | 1.3.6.1.4.1.476.1.42.3.2.1.152 | ||
| The system has detected a loss of water flow condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCondensatePumpHighWater | 1.3.6.1.4.1.476.1.42.3.2.1.153 | ||
| The system has detected high water in the condensate pump. | |||
| OBJECT-IDENTITY | |||
| lgpConditionGeneralAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.154 | ||
| The system has detected a general alarm condition. | |||
| OBJECT-IDENTITY | |||
| lgpConditionProductSpecific | 1.3.6.1.4.1.476.1.42.3.2.1.155 | ||
| The system has detected a product specific condition. This condition is not currently available via the agent card. | |||
| OBJECT-IDENTITY | |||
| lgpConditionReheatLockout | 1.3.6.1.4.1.476.1.42.3.2.1.156 | ||
| The system has locked out the electrical reheat operation for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierLockout | 1.3.6.1.4.1.476.1.42.3.2.1.157 | ||
| The system has locked out the humidifier operation for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCompressorsLockout | 1.3.6.1.4.1.476.1.42.3.2.1.158 | ||
| The system has locked out compressor operation for a specified amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCallService | 1.3.6.1.4.1.476.1.42.3.2.1.159 | ||
| The system has detected a condition that requires a service representative be contacted. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowMemoryGroup | 1.3.6.1.4.1.476.1.42.3.2.1.160 | ||
| This group contains various low memory conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionLowMemory1 | 1.3.6.1.4.1.476.1.42.3.2.1.160.1 | ||
| The system has detected a low memory condition. The control board is low in memory resources. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMemoryFailureGroup | 1.3.6.1.4.1.476.1.42.3.2.1.161 | ||
| This group contains various memory device failure conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMemory1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.161.1 | ||
| The system has detected a memory 1 module failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionMemory2Failure | 1.3.6.1.4.1.476.1.42.3.2.1.161.2 | ||
| The system has detected a memory 2 module failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCodeErrorGroup | 1.3.6.1.4.1.476.1.42.3.2.1.162 | ||
| This group contains various memory device failure conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCodeNotConfigured | 1.3.6.1.4.1.476.1.42.3.2.1.162.1 | ||
| The system has detected the unit code is not configured. The unit code must be configured before system start-up. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode01OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.2 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode02OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.3 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode03OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.4 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode04OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.5 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode05OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.6 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode06OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.7 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode07OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.8 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode08OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.9 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode09OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.10 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode10OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.11 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode11OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.12 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode12OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.13 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode13OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.14 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode14OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.15 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode15OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.16 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode16OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.17 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode17OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.18 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnitCode18OutOfRange | 1.3.6.1.4.1.476.1.42.3.2.1.162.19 | ||
| The system has detected a unit code error. This digit of the unit code value is out of range. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHighExternalDewPoint | 1.3.6.1.4.1.476.1.42.3.2.1.163 | ||
| The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHcbDisconnected | 1.3.6.1.4.1.476.1.42.3.2.1.164 | ||
| The system has detected the humidifier control board is disconnected or not installed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionBmsResetTimerExpired | 1.3.6.1.4.1.476.1.42.3.2.1.165 | ||
| The BMS fan speed control reset counter has timed out. | |||
| OBJECT-IDENTITY | |||
| lgpConditionAgentFirmwareCorrupt | 1.3.6.1.4.1.476.1.42.3.2.1.166 | ||
| The firmware update to the agent card has failed and the firmware is now corrupt. | |||
| OBJECT-IDENTITY | |||
| lgpConditionSystemAccessGroup | 1.3.6.1.4.1.476.1.42.3.2.1.175 | ||
| This group contains various system access conditions. An examples is an open access panel. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFrontAccessOpen | 1.3.6.1.4.1.476.1.42.3.2.1.175.1 | ||
| The system has detected the front access panel/door is open. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRearAccessOpen | 1.3.6.1.4.1.476.1.42.3.2.1.175.2 | ||
| The system has detected the rear access panel/door is open. | |||
| OBJECT-IDENTITY | |||
| lgpConditionsDamperFailure | 1.3.6.1.4.1.476.1.42.3.2.1.176 | ||
| This group contains various damper failure conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionEmergencyDamperFailure | 1.3.6.1.4.1.476.1.42.3.2.1.176.1 | ||
| The system has detected an emergency damper failure. The damper is in the wrong position. | |||
| OBJECT-IDENTITY | |||
| lgpConditionRemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.1.177 | ||
| A remote shutdown occurred. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFireAlarm | 1.3.6.1.4.1.476.1.42.3.2.1.178 | ||
| Fire Alarm. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHeatersOverheated | 1.3.6.1.4.1.476.1.42.3.2.1.179 | ||
| Heaters Overheated. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCondenserFailureGroup | 1.3.6.1.4.1.476.1.42.3.2.1.180 | ||
| This group contains condenser failure conditions. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCondenser1Failure | 1.3.6.1.4.1.476.1.42.3.2.1.180.1 | ||
| Condenser 1 Failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionCondenser2Failure | 1.3.6.1.4.1.476.1.42.3.2.1.180.2 | ||
| Condenser 2 Failure. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierCyclinderWorn | 1.3.6.1.4.1.476.1.42.3.2.1.181 | ||
| The system has detected the humidifier cylinder is worn. | |||
| OBJECT-IDENTITY | |||
| lgpConditionUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.182 | ||
| The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHumidifierUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.1.182.1 | ||
| The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHeatRejectorGroup | 1.3.6.1.4.1.476.1.42.3.2.1.183 | ||
| This group contains failure conditions for the heat rejection unit. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHeatRejectorFanFailure | 1.3.6.1.4.1.476.1.42.3.2.1.183.1 | ||
| The heat rejector fan has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionHeatRejectorVoltageSuppressionFailure | 1.3.6.1.4.1.476.1.42.3.2.1.183.2 | ||
| The heat rejector voltage suppression has failed and is no longer able to protect the unit from power fluctuations. | |||
| OBJECT-IDENTITY | |||
| lgpConditionFreeCoolLockout | 1.3.6.1.4.1.476.1.42.3.2.1.184 | ||
| The free cooling capability has been disabled. | |||
| OBJECT-IDENTITY | |||
| lgpConditionWaterLeakSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.1.185 | ||
| The sensor used to detect water leaks is not connected or has failed. | |||
| OBJECT-IDENTITY | |||
| lgpConditionNoLoadDetectedWarning | 1.3.6.1.4.1.476.1.42.3.2.1.186 | ||
| There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit' | |||
| OBJECT-IDENTITY | |||
| lgpConditionsPresent | 1.3.6.1.4.1.476.1.42.3.2.2 | ||
| The present number of conditions. | |||
| OBJECT-TYPE | |||
| Gauge32 | |||
| lgpConditionsTable | 1.3.6.1.4.1.476.1.42.3.2.3 | ||
| A list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'. | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| LgpConditionEntry | |||
| lgpConditionEntry | 1.3.6.1.4.1.476.1.42.3.2.3.1 | ||
| This entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table. | |||
| OBJECT-TYPE | |||
| LgpConditionEntry | |||
| lgpConditionId | 1.3.6.1.4.1.476.1.42.3.2.3.1.1 | ||
| A unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'. | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| lgpConditionDescr | 1.3.6.1.4.1.476.1.42.3.2.3.1.2 | ||
| A reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description. | |||
| OBJECT-TYPE | |||
| OBJECT IDENTIFIER | |||
| lgpConditionTime | 1.3.6.1.4.1.476.1.42.3.2.3.1.3 | ||
| The value of sysUpTime when the condition occurred. | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| lgpConditionControl | 1.3.6.1.4.1.476.1.42.3.2.4 | ||
| OBJECT IDENTIFIER | |||
| lgpConditionControlEventReset | 1.3.6.1.4.1.476.1.42.3.2.4.1 | ||
| Event Reset Command. This command will reset all of the device's events. | |||
| OBJECT-TYPE | |||
| INTEGER | noAction(1), resetAll(2) | ||
| lgpConditionControlEventAck | 1.3.6.1.4.1.476.1.42.3.2.4.2 | ||
| Event Acknowledge Command. This command will acknowledge all of the device's events. | |||
| OBJECT-TYPE | |||
| INTEGER | noAction(1), ackAll(2) | ||
| lgpConditionDescription | 1.3.6.1.4.1.476.1.42.3.2.5 | ||
| The ascii text description for the condition. | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(255) | ||
| lgpNetworkName | 1.3.6.1.4.1.476.1.42.3.2.6 | ||
| The network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information. | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(255) | ||
| LgpConditionEntry | |||
| SEQUENCE | |||
| Unsigned32 as lgpConditionId | |||
| OBJECT IDENTIFIER as lgpConditionDescr | |||
| TimeTicks as lgpConditionTime | |||