LIEBERT-GP-POWER-MIB

File: LIEBERT-GP-POWER-MIB.mib (86358 bytes)

Imported modules

SNMPv2-SMI LIEBERT-GP-REGISTRATION-MIB

Imported symbols

MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE
Integer32 Unsigned32 lgpPower
liebertPowerModuleReg

Defined Objects

liebertGlobalProductsPowerModule 1.3.6.1.4.1.476.1.42.1.6.1
The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY    

lgpPwrBattery 1.3.6.1.4.1.476.1.42.3.5.1
This sub-tree is used to register Liebert Power Battery object identifiers.
OBJECT-IDENTITY    

lgpPwrNumberInstalledBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.1
The number of battery modules installed in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberFailedBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.2
The number of battery modules in the device that have failed.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberRedundantBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.3
The number of redundant battery modules in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberActiveBatteryModules 1.3.6.1.4.1.476.1.42.3.5.1.4
The number of active battery modules in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrConfigLowBatteryWarningTime 1.3.6.1.4.1.476.1.42.3.5.1.5
The value of the device's estimated minutes of remaining battery at which a lgpEventLowBatteryWarning notification will be sent.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberBatteryModuleWarnings 1.3.6.1.4.1.476.1.42.3.5.1.6
The number of battery modules in the device that have a warning.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryCount 1.3.6.1.4.1.476.1.42.3.5.1.7
The number of batteries installed.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryTestResult 1.3.6.1.4.1.476.1.42.3.5.1.8
The outcome of the previous battery test.
OBJECT-TYPE    
  INTEGER unknown(1), passed(2), failed(3), inProgress(4), systemFailure(5), inhibited(6)  

lgpPwrNominalBatteryCapacity 1.3.6.1.4.1.476.1.42.3.5.1.9
The nominal battery capacity of the system (in minutes) at full load.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryFloatVoltage 1.3.6.1.4.1.476.1.42.3.5.1.10
The battery float voltage of the system.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryEndOfDischargeVoltage 1.3.6.1.4.1.476.1.42.3.5.1.11
The battery voltage threshold at which the batteries are consided completely discharged.
OBJECT-TYPE    
  Integer32  

lgpPwrAutomaticBatteryTestInterval 1.3.6.1.4.1.476.1.42.3.5.1.12
The automatic battery test interval.
OBJECT-TYPE    
  Integer32  

lgpPwrAutomaticBatteryTestCountdown 1.3.6.1.4.1.476.1.42.3.5.1.13
The time remaining before the next battery test.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryChargeStatus 1.3.6.1.4.1.476.1.42.3.5.1.14
The present state of the system's battery charge. A value of 'charging' indicates the batteries are currently charging. A value of 'discharging' indicates the batteries are currently discharging. A value of 'fullycharged' indicates the batteries are charged to their full capacity. A value of 'notfullycharged' indicates the battery charge is neither fully charged, charging or discharging.
OBJECT-TYPE    
  INTEGER fullycharged(1), notfullycharged(2), charging(3), discharging(4)  

lgpPwrBatteryLifeEnhancer 1.3.6.1.4.1.476.1.42.3.5.1.15
The state of the battery life enhancer. When 'on', it will preserve battery life.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrBatteryCharger 1.3.6.1.4.1.476.1.42.3.5.1.16
The state of the battery charger.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrBatteryChargeMode 1.3.6.1.4.1.476.1.42.3.5.1.17
The mode of the battery charger: 'float' charging or 'equalize' charging.
OBJECT-TYPE    
  INTEGER float(1), equalize(2)  

lgpPwrBatteryTimeRemaining 1.3.6.1.4.1.476.1.42.3.5.1.18
An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryCapacity 1.3.6.1.4.1.476.1.42.3.5.1.19
The present percentage of battery capacity.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryCabinet 1.3.6.1.4.1.476.1.42.3.5.1.20
This sub-tree contains items related to battery cabinets.
OBJECT-IDENTITY    

lgpPwrBatteryCabinetCount 1.3.6.1.4.1.476.1.42.3.5.1.20.1
The number of battery cabinets installed with this device. Note some devices may not permit writing a value to this object.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryCabinetType 1.3.6.1.4.1.476.1.42.3.5.1.20.2
The type of battery cabinet(s) installed on this device. Enum definitions: notSpecified - The type has not been specified in the device's configuration. internal - Battery cabinets are internal to the device. external - Device has external battery cabinets installed. lrt - Long Run Time cabinets. Note some devices may not permit writing a value to this object.
OBJECT-TYPE    
  INTEGER notSpecified(1), internal(2), external(3), lrt(4)  

lgpPwrBatteryCabinetRatedCapacity 1.3.6.1.4.1.476.1.42.3.5.1.20.3
Battery cabinet rated capacity (tenths of AmpHour). This assumes that each cabinet is of the same type and capacity. This is not a sum of the rating for all attached cabinets. Note some devices may not permit writing a value to this object.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurements 1.3.6.1.4.1.476.1.42.3.5.2
This sub-tree registers Liebert Power Measurement object identifiers. The sub-tree contains tables and well known power measurement points.
OBJECT-IDENTITY    

lgpPwrWellKnownMeasurementPoints 1.3.6.1.4.1.476.1.42.3.5.2.1
This sub-tree registers well known Liebert Power Measurement Points. The object identifier names usually imply locations where the measurement is taken -- such as 'input', 'output' and 'bypass'.
OBJECT-IDENTITY    

lgpPwrSource1Input 1.3.6.1.4.1.476.1.42.3.5.2.1.1
This sub-tree is used to register a source 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource1Input' etc. may depend on the physical wiring of the system when it was installed.
OBJECT-IDENTITY    

lgpPwrSource2Input 1.3.6.1.4.1.476.1.42.3.5.2.1.2
This sub-tree is used to register a source 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 2. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource2Input' etc. may depend on the physical wiring of the system when it was installed.
OBJECT-IDENTITY    

lgpPwrSourcePdu1Input 1.3.6.1.4.1.476.1.42.3.5.2.1.3
This sub-tree is used to register a source PDU 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring of the system when it was installed.
OBJECT-IDENTITY    

lgpPwrSourcePdu2Input 1.3.6.1.4.1.476.1.42.3.5.2.1.4
This sub-tree is used to register a source PDU 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring of the system when it was installed.
OBJECT-IDENTITY    

lgpPwrOutputToLoad 1.3.6.1.4.1.476.1.42.3.5.2.1.5
This sub-tree is used to register the output to the critical load as a well known measurement point. It is intended that no sub-trees be created below this node.
OBJECT-IDENTITY    

lgpPwrMeasBattery 1.3.6.1.4.1.476.1.42.3.5.2.1.6
This sub-tree is used to register a battery as a well known measurement point. It is intended that no sub-trees be created below this node.
OBJECT-IDENTITY    

lgpPwrMeasBypass 1.3.6.1.4.1.476.1.42.3.5.2.1.7
This sub-tree is used to register a bypass as a well known measurement point. It is intended that no sub-trees be created below this node.
OBJECT-IDENTITY    

lgpPwrMeasDcBus 1.3.6.1.4.1.476.1.42.3.5.2.1.8
This sub-tree is used to register a DC bus as a well known measurement point. It is intended that no sub-trees be created below this node.
OBJECT-IDENTITY    

lgpPwrMeasSystemOutput 1.3.6.1.4.1.476.1.42.3.5.2.1.9
This sub-tree is used to register the output of a multi-module system as a well known measurement point. It is intended that no sub-trees be created below this node. This identifier represents the power related data of the system.
OBJECT-IDENTITY    

lgpPwrMeasurementPointTable 1.3.6.1.4.1.476.1.42.3.5.2.2
This table contains a list of AC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrMeasurementPointId' in the 'LgpPwrMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrMeasurementPointEntry for the particular row of the table.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpPwrMeasurementPointEntry

lgpPwrMeasurementPointEntry 1.3.6.1.4.1.476.1.42.3.5.2.2.1
This entry defines the measurements to be populated in the various columns of the 'lgpPwrMeasurementPointTable'.
OBJECT-TYPE    
  LgpPwrMeasurementPointEntry  

lgpPwrMeasurementPointIndex 1.3.6.1.4.1.476.1.42.3.5.2.2.1.1
This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrMeasurementPointId 1.3.6.1.4.1.476.1.42.3.5.2.2.1.2
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrMeasurementPointNumLines 1.3.6.1.4.1.476.1.42.3.5.2.2.1.3
The number of lines on the indicated power measurement point. (i.e. the number of phases on the power source being measured.)
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNomVolts 1.3.6.1.4.1.476.1.42.3.5.2.2.1.4
The magnitude of the nominal voltage on the power source being measured.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNomFrequency 1.3.6.1.4.1.476.1.42.3.5.2.2.1.5
The nominal or configured/expected frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointFrequency 1.3.6.1.4.1.476.1.42.3.5.2.2.1.6
The present (actual) frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointApparentPower 1.3.6.1.4.1.476.1.42.3.5.2.2.1.7
The present apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointTruePower 1.3.6.1.4.1.476.1.42.3.5.2.2.1.8
The present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.2.1.9
The present Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointWattHours 1.3.6.1.4.1.476.1.42.3.5.2.2.1.10
The present number of Watt Hours for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointVAPercent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.11
The percentage of the rated apparent AC power of the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNeutralCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.12
The present neutral current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointGroundCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.13
The present ground current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNomCurrent 1.3.6.1.4.1.476.1.42.3.5.2.2.1.14
The nominal or configured/expected current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNomPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.2.1.15
The nominal or configured/expected power factor of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointNomVA 1.3.6.1.4.1.476.1.42.3.5.2.2.1.16
The nominal or configured/expected apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrMeasurementPointPowerFactorTag 1.3.6.1.4.1.476.1.42.3.5.2.2.1.19
The present description of the Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
OBJECT-TYPE    
  INTEGER leading(1), lagging(2)  

lgpPwrLineMeasurementTable 1.3.6.1.4.1.476.1.42.3.5.2.3
A list of power measurements for each phase/line for a given power measurement point/location in the 'lgpPwrMeasurementPointTable'. The lgpPwrMeasurementPointIndex in this table corresponds to the index in the lgpPwrMeasurementPointTable and the This table contains zero, one, or many rows, depending upon the number of power line source objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpPwrLineMeasurementEntry

lgpPwrLineMeasurementEntry 1.3.6.1.4.1.476.1.42.3.5.2.3.1
This entry defines the contents of the columns for the table 'lgpPwrLineMeasurementTable'.
OBJECT-TYPE    
  LgpPwrLineMeasurementEntry  

lgpPwrMeasurementPtIndex 1.3.6.1.4.1.476.1.42.3.5.2.3.1.1
This is the index indicating the row of the table 'lgpPwrMeasurementPointTable' for a power measurement point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrLineMeasurementIndex 1.3.6.1.4.1.476.1.42.3.5.2.3.1.2
This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrMeasurementPoint 1.3.6.1.4.1.476.1.42.3.5.2.3.1.3
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID name usually implies a location of the measurement point such as 'input', 'output', 'bypass', etc.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrLineMeasurementVoltsLL 1.3.6.1.4.1.476.1.42.3.5.2.3.1.4
The present Line-to-Line voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA].
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementVoltsLN 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5
The present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.6
The present current measurement for the indicated source. The line being measured is given by the 'lgpPwrLineMeasurementIndex' where [1 = A, 2 = B, 3 = C].
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementCapacity 1.3.6.1.4.1.476.1.42.3.5.2.3.1.7
The percentage of the power capacity presently being used on this line.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementVA 1.3.6.1.4.1.476.1.42.3.5.2.3.1.8
The present apparent AC line power.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementTruePower 1.3.6.1.4.1.476.1.42.3.5.2.3.1.9
The present AC line power measured in watts.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementVoltageTHD 1.3.6.1.4.1.476.1.42.3.5.2.3.1.10
The present total harmonic distortion on the AC line voltage.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementCurrentTHD 1.3.6.1.4.1.476.1.42.3.5.2.3.1.11
The present total harmonic distortion on the AC line current.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementKFactorCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.12
The present line K Factor.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementCrestFactorCurrent 1.3.6.1.4.1.476.1.42.3.5.2.3.1.13
The present crest factor of the line current.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementPowerFactor 1.3.6.1.4.1.476.1.42.3.5.2.3.1.14
The present Power Factor for the line.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementPowerFactorTag 1.3.6.1.4.1.476.1.42.3.5.2.3.1.15
The present description of the Power Factor for the line. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
OBJECT-TYPE    
  INTEGER leading(1), lagging(2)  

lgpPwrLineMeasurementMaxVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.16
The maximum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementMinVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.17
The minimum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementVAR 1.3.6.1.4.1.476.1.42.3.5.2.3.1.18
The present reactive AC line power of the power source indicated by 'lgpPwrMeasurementPoint'.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementPercentLoad 1.3.6.1.4.1.476.1.42.3.5.2.3.1.19
The present percent load of the AC line power.
OBJECT-TYPE    
  Integer32  

lgpPwrLineMeasurementVolts 1.3.6.1.4.1.476.1.42.3.5.2.3.1.20
The present voltage measurement for the indicated source.
OBJECT-TYPE    
  Integer32  

lgpPwrDcMeasurementPointTable 1.3.6.1.4.1.476.1.42.3.5.2.4
This table contains a list of DC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrDcMeasurementPointId' in the 'LgpPwrDcMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrDcMeasurementPointEntry for the particular row of the table.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpPwrDcMeasurementPointEntry

lgpPwrDcMeasurementPointEntry 1.3.6.1.4.1.476.1.42.3.5.2.4.1
This entry defines the measurements to be populated in the various columns of the 'lgpPwrDcMeasurementPointTable'.
OBJECT-TYPE    
  LgpPwrDcMeasurementPointEntry  

lgpPwrDcMeasurementPointIndex 1.3.6.1.4.1.476.1.42.3.5.2.4.1.1
This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrDcMeasurementPointId 1.3.6.1.4.1.476.1.42.3.5.2.4.1.2
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrDcMeasurementPointSubID 1.3.6.1.4.1.476.1.42.3.5.2.4.1.3
The identifier used to differentiate between identical thresholds for a given point index and point ID in the DC measurements table.
OBJECT-TYPE    
  Integer32  

lgpPwrDcMeasurementPointVolts 1.3.6.1.4.1.476.1.42.3.5.2.4.1.4
The present DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrDcMeasurementPointCurrent 1.3.6.1.4.1.476.1.42.3.5.2.4.1.5
The present DC current for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrDcMeasurementPointNomVolts 1.3.6.1.4.1.476.1.42.3.5.2.4.1.6
The nominal(configured/expected) DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrDcMeasurementPointTruePower 1.3.6.1.4.1.476.1.42.3.5.2.4.1.7
The present DC power for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
OBJECT-TYPE    
  Integer32  

lgpPwrWellKnownMeasurementTypes 1.3.6.1.4.1.476.1.42.3.5.2.5
This sub-tree registers well known Liebert Power Measurement Types. The object identifier names usually encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAC', 'current', 'voltsDc', 'VoltsLL', etc.
OBJECT-IDENTITY    

lgpPwrVoltsAc 1.3.6.1.4.1.476.1.42.3.5.2.5.1
This identifier represents an AC voltage.
OBJECT-IDENTITY    

lgpPwrVoltsDc 1.3.6.1.4.1.476.1.42.3.5.2.5.2
This identifier represents an DC voltage.
OBJECT-IDENTITY    

lgpPwrStatus 1.3.6.1.4.1.476.1.42.3.5.3
This sub-tree registers Liebert Power Status object identifiers. This is the location of power related status information that does not fit into a more specific category such as the lgpPwrConversion sub-tree.
OBJECT-IDENTITY    

lgpPwrTransferCount 1.3.6.1.4.1.476.1.42.3.5.3.1
Number of times that the output load has been transferred between the available input sources.
OBJECT-TYPE    
  Integer32  

lgpPwrAutoTransferTimer 1.3.6.1.4.1.476.1.42.3.5.3.2
The required wait time between output load auto transfer attempts between available input sources.
OBJECT-TYPE    
  Integer32  

lgpPwrAutoReTransferEnabled 1.3.6.1.4.1.476.1.42.3.5.3.3
The ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system
OBJECT-TYPE    
  INTEGER no(0), yes(1)  

lgpPwrSyncPhaseAngle 1.3.6.1.4.1.476.1.42.3.5.3.4
The phase angle difference of source 1 in relation to source 2.
OBJECT-TYPE    
  Integer32 -2147483648..2147483647  

lgpPwrParallelSystemOutputToLoadSource 1.3.6.1.4.1.476.1.42.3.5.3.5
The source supporting the parallel system's load.
OBJECT-TYPE    
  INTEGER unknown(0), utility(1), battery(2), bypass(3), none(4)  

lgpPwrDcToDcConverter 1.3.6.1.4.1.476.1.42.3.5.3.6
The state of the DC to DC converter.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrOutputToLoadOnInverter 1.3.6.1.4.1.476.1.42.3.5.3.7
The present source of output power is the Inverter.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrBatteryChargeCompensating 1.3.6.1.4.1.476.1.42.3.5.3.8
The system is adjusting the battery charging algorithm to accommodate for the battery temperature.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrInverterReady 1.3.6.1.4.1.476.1.42.3.5.3.9
The ability of the inverter to support the output load of the system.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrOutputToLoadOnBypass 1.3.6.1.4.1.476.1.42.3.5.3.10
The present source of output power is the Bypass.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrBoost 1.3.6.1.4.1.476.1.42.3.5.3.11
The present state of the boost circuitry
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrBuck 1.3.6.1.4.1.476.1.42.3.5.3.12
The present state of the buck circuitry
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrShutdownOverTemperature 1.3.6.1.4.1.476.1.42.3.5.3.13
The system has previously shutdown due to an over temperature condition.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownOverload 1.3.6.1.4.1.476.1.42.3.5.3.14
The system has previously shutdown due to an over load condition.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownDcBusOverload 1.3.6.1.4.1.476.1.42.3.5.3.15
The system has previously shutdown due to a DC bus over load condition.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownOutputShort 1.3.6.1.4.1.476.1.42.3.5.3.16
The system has previously shutdown due to an ouput short condition.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownLineSwap 1.3.6.1.4.1.476.1.42.3.5.3.17
The system has previously shutdown due to a condition where the line and neutral were reversed.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownLowBattery 1.3.6.1.4.1.476.1.42.3.5.3.18
The system has previously shutdown due to a low battery condition.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownRemote 1.3.6.1.4.1.476.1.42.3.5.3.19
The system has previously shutdown due to a remote shutdown command.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownInputUnderVoltage 1.3.6.1.4.1.476.1.42.3.5.3.20
The system has previously shutdown due to an under voltage condition during startup.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownPowerFactorCorrectionFailure 1.3.6.1.4.1.476.1.42.3.5.3.21
The system has previously shutdown due to a power factor correction startup failure.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrShutdownHardware 1.3.6.1.4.1.476.1.42.3.5.3.22
The system has previously shutdown due external shutdown signal.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrRedundantSubModule 1.3.6.1.4.1.476.1.42.3.5.3.23
The system has a redundant battery module installed.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrBypassReady 1.3.6.1.4.1.476.1.42.3.5.3.24
The ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrGeneratorStatus 1.3.6.1.4.1.476.1.42.3.5.3.25
The state of the system generator.
OBJECT-TYPE    
  INTEGER connected(1), disconnected(2)  

lgpPwrRotaryBreakerStatus 1.3.6.1.4.1.476.1.42.3.5.3.26
The state of the system rotary breaker.
OBJECT-TYPE    
  INTEGER unknown(1), closed(2), test(3), normal(4), bypass(5), maintenance(6)  

lgpPwrPowerFactorCorrection 1.3.6.1.4.1.476.1.42.3.5.3.27
The state of the power factor correction circuitry of the system.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrSettings 1.3.6.1.4.1.476.1.42.3.5.4
This sub-tree registers Liebert Power Static Switch object identifiers.
OBJECT-IDENTITY    

lgpPwrPreferredSource 1.3.6.1.4.1.476.1.42.3.5.4.1
The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrLoadOnSource 1.3.6.1.4.1.476.1.42.3.5.4.2
The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load).
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrNominalVoltageDeviation 1.3.6.1.4.1.476.1.42.3.5.4.3
The nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
OBJECT-TYPE    
  Integer32  

lgpPwrNominalVoltageDeviationPercent 1.3.6.1.4.1.476.1.42.3.5.4.4
The percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
OBJECT-TYPE    
  Integer32  

lgpPwrPhaseDifferenceLimit 1.3.6.1.4.1.476.1.42.3.5.4.5
The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.
OBJECT-TYPE    
  Integer32  

lgpPwrFrequencyDeviationLimit 1.3.6.1.4.1.476.1.42.3.5.4.6
The maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permitted.
OBJECT-TYPE    
  Integer32  

lgpPwrThresholdTable 1.3.6.1.4.1.476.1.42.3.5.4.7
A list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table corresponds to the type of measurement the high and low thresholds applies to. This table contains zero, one, or many rows, depending upon the number of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpPwrThresholdEntry

lgpPwrThresholdEntry 1.3.6.1.4.1.476.1.42.3.5.4.7.1
This entry defines the contents of the columns for the table 'lgpPwrThresholdTable'.
OBJECT-TYPE    
  LgpPwrThresholdEntry  

lgpPwrThresholdIndex 1.3.6.1.4.1.476.1.42.3.5.4.7.1.1
This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrThresholdPoint 1.3.6.1.4.1.476.1.42.3.5.4.7.1.2
An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrThresholdSubID 1.3.6.1.4.1.476.1.42.3.5.4.7.1.3
This is a sub identifier for the 'lgpPwrThresholdPoint'. It indicates the instance number of the well known threshold point.
OBJECT-TYPE    
  Unsigned32  

lgpPwrThresholdType 1.3.6.1.4.1.476.1.42.3.5.4.7.1.4
An OID representing a well known measurement type. These object identifiers indicate the type of measurement referenced by the row of the table. These object identifiers can encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrThresholdHighWarning 1.3.6.1.4.1.476.1.42.3.5.4.7.1.5
The high warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
OBJECT-TYPE    
  Integer32  

lgpPwrThresholdHighFailure 1.3.6.1.4.1.476.1.42.3.5.4.7.1.6
The high failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
OBJECT-TYPE    
  Integer32  

lgpPwrThresholdLowWarning 1.3.6.1.4.1.476.1.42.3.5.4.7.1.7
The low warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
OBJECT-TYPE    
  Integer32  

lgpPwrThresholdLowFailure 1.3.6.1.4.1.476.1.42.3.5.4.7.1.8
The low failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification.
OBJECT-TYPE    
  Integer32  

lgpPwrUpsAutoRestart 1.3.6.1.4.1.476.1.42.3.5.4.8
The device will automatically restart when utility power is restored following a battery discharge.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrUpsAutoRestartDelay 1.3.6.1.4.1.476.1.42.3.5.4.9
The device will automatically delay a certain number of seconds and then restart after utility power is restored following a battery discharge. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
OBJECT-TYPE    
  Integer32  

lgpPwrAutoRestartBatteryChargeThreshold 1.3.6.1.4.1.476.1.42.3.5.4.10
The battery charge percentage required before the device can automatically restart.
OBJECT-TYPE    
  Integer32  

lgpPwrParallelModuleCount 1.3.6.1.4.1.476.1.42.3.5.4.11
The number of modules in the parallel system.
OBJECT-TYPE    
  Integer32  

lgpPwrParallelRedundancyCount 1.3.6.1.4.1.476.1.42.3.5.4.12
The number of redundant modules in the parallel system.
OBJECT-TYPE    
  Integer32  

lgpPwrLoadBusSyncMode 1.3.6.1.4.1.476.1.42.3.5.4.13
The configuration of Load Bus Synchronization (LBS) between independent systems.
OBJECT-TYPE    
  INTEGER master(1), slave(2), none(3)  

lgpPwrEconomicOperationMode 1.3.6.1.4.1.476.1.42.3.5.4.14
The configuration of the economic operation mode of the system.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrAutomaticBatteryTest 1.3.6.1.4.1.476.1.42.3.5.4.15
Automatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must be initiated by a battery test command. The interval at which a battery test is performed is defined by 'lgpPwrAutomaticBatteryTestInterval'.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrMinimumRedundantPowerModule 1.3.6.1.4.1.476.1.42.3.5.4.16
The minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there is no redundant power functionality.
OBJECT-TYPE    
  Integer32  

lgpPwrMinimumRedundantBatteryModule 1.3.6.1.4.1.476.1.42.3.5.4.17
The minimum number of redundant battery modules that before enunciating an alarm. If 0, the redundant battery module alarm is disabled.
OBJECT-TYPE    
  Integer32  

lgpPwrOutputToLoadUserOverloadLimit 1.3.6.1.4.1.476.1.42.3.5.4.18
This is the user specified maximum load the device can support without enunciating an alarm.
OBJECT-TYPE    
  Integer32  

lgpPwrNoLoadWarningLimit 1.3.6.1.4.1.476.1.42.3.5.4.19
The minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgpConditionWarningNoLoadDetected will be triggered if the output current falls below this value. If this value is '-1' then the lgpConditionNoLoadDetectedWarning condition is 'disabled'.
OBJECT-TYPE    
  Integer32  

lgpPwrNoLoadWarningDelay 1.3.6.1.4.1.476.1.42.3.5.4.20
The amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load falls below the threshold lgpPwrOutputNoLoadWarningLimit.
OBJECT-TYPE    
  INTEGER 0..10000  

lgpPwrConversion 1.3.6.1.4.1.476.1.42.3.5.5
This sub-tree is used to register Liebert Power Conversion object identifiers.
OBJECT-IDENTITY    

lgpPwrNumberInstalledPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.1
The number of power modules installed in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberFailedPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.2
The number of power modules in the device that have failed.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberRedundantPowerModules 1.3.6.1.4.1.476.1.42.3.5.5.3
The number of redundant power modules installed in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberActivePowerModules 1.3.6.1.4.1.476.1.42.3.5.5.4
The number of active power modules in the device.
OBJECT-TYPE    
  Integer32  

lgpPwrNumberPowerModuleWarnings 1.3.6.1.4.1.476.1.42.3.5.5.6
The number of power modules in the device that have a warning.
OBJECT-TYPE    
  Integer32  

lgpPwrUpsInverterStandby 1.3.6.1.4.1.476.1.42.3.5.5.7
The output to the load is supported by the bypass and the inverter is on standby.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

lgpPwrControl 1.3.6.1.4.1.476.1.42.3.5.6
This sub-tree is used to register Liebert Power Control object identifiers.
OBJECT-IDENTITY    

lgpPwrWellKnownControlPoints 1.3.6.1.4.1.476.1.42.3.5.6.1
This sub-tree registers well known Liebert Power Control Points. The object identifier names usually imply locations where control of a device is available -- such 'output' or 'load circuits'.
OBJECT-IDENTITY    

lgpPwrLoadCircuit 1.3.6.1.4.1.476.1.42.3.5.6.1.1
The managed device's controllable load circuit. Many power systems contain more than one load circuit. This identifier represents one load circuit for the system but does not necessarily represent the 'first' one. The load circuits' numbering with respect to 'lgpPwrLoadCircuit1' etc. may depend on the physical wiring of the system when it was installed.
OBJECT-IDENTITY    

lgpPwrLoadCircuitTable 1.3.6.1.4.1.476.1.42.3.5.6.2
A list of load circuits that can be controlled(opened or closed). The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
OBJECT-TYPE    
  SEQUENCE OF  
    LgpPwrLoadCircuitEntry

lgpPwrLoadCircuitEntry 1.3.6.1.4.1.476.1.42.3.5.6.2.1
This entry defines the contents of the columns for the table 'lgpPwrLoadCircuitTable'.
OBJECT-TYPE    
  LgpPwrLoadCircuitEntry  

lgpPwrLoadCircuitIndex 1.3.6.1.4.1.476.1.42.3.5.6.2.1.1
This is the index indicating the row of the table 'lgpPwrLoadCircuitTable'.
OBJECT-TYPE    
  Unsigned32  

lgpPwrLoadCircuitId 1.3.6.1.4.1.476.1.42.3.5.6.2.1.2
An OID representing a well known load circuit identifier. These load circuit identifiers indicate the name or type of load circuit reference in the table.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

lgpPwrLoadCircuitSubID 1.3.6.1.4.1.476.1.42.3.5.6.2.1.3
This is a sub identifier for the 'lgpPwrLoadCircuitId'. It indicates the hardware identifier of the load control circuit.
OBJECT-TYPE    
  Unsigned32  

lgpPwrLoadCircuitState 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4
This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the ciruit will transition to desired state.
OBJECT-TYPE    
  INTEGER on(1), off(2), default(3)  

lgpPwrAlarmSilence 1.3.6.1.4.1.476.1.42.3.5.6.3
Audible Alarm Silence Command. This command turns off the device's audible alarm. It will not affect the status of the alarm(s) that caused the audible alarm. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryTest 1.3.6.1.4.1.476.1.42.3.5.6.4
Battery Test Command. This command will initiate a battery test if one is not already in progress, or abort the current test if it is in progress.
OBJECT-TYPE    
  INTEGER start(1), abort(2)  

lgpPwrUpsAbortCommand 1.3.6.1.4.1.476.1.42.3.5.6.5
UPS Abort command. This command will abort the pending command on the device. There is no guarantee a client using the abort command will cancel a command sent moments before from the same client. Another client could initiate a command and change what command is actually pending on the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrTransferToBypass 1.3.6.1.4.1.476.1.42.3.5.6.6
Transfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrTransferToInverter 1.3.6.1.4.1.476.1.42.3.5.6.7
Transfer to Inverter Command. This command will initiate a transfer of the load to the inverter of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrOutputOnDelay 1.3.6.1.4.1.476.1.42.3.5.6.8
Output On Delay Command. This command will turn on the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
OBJECT-TYPE    
  Integer32  

lgpPwrOutputOffDelayWithRestart 1.3.6.1.4.1.476.1.42.3.5.6.9
Output Off Delay with Restart Command. This command will turn off the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will then turn the output on again after a specified amount of time.
OBJECT-TYPE    
  Integer32  

lgpPwrOutputOffDelayWithoutRestart 1.3.6.1.4.1.476.1.42.3.5.6.10
Output Off Delay without Restart Command. This command will turn off the output of the device after a specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will NOT automatically turn the output on following this command.
OBJECT-TYPE    
  Integer32  

lgpPwrTopology 1.3.6.1.4.1.476.1.42.3.5.7
This sub-tree is used to register Liebert Power Topology object identifiers.
OBJECT-IDENTITY    

lgpPwrUpsTopOffline 1.3.6.1.4.1.476.1.42.3.5.7.1
The UPS has a offline topology. Under normal operating conditions, AC power from the utility passes straight through the UPS to the critical load. The inverter is used to convert the DC power from the battery to create AC power to support the load when the utility fails. Normally the inverter is operating in the stand-by mode, keeping the batteries charged. Should the utility power go out of specification, the inverter will power the load by drawing energy from the battery.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrUpsTopLineInteractive 1.3.6.1.4.1.476.1.42.3.5.7.2
The UPS has a line-interactive topology. This topology resembles the offline product, but inserts a transformer or inductor in series between the utility power source and the load. This inline inductor enables the UPS inverter to interact with incoming power and provide a measure of power conditioning to the load. This buck-and-boost circuitry helps with high and low input voltage conditions.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrUPSTopDualInput 1.3.6.1.4.1.476.1.42.3.5.7.3
The system has separate input sources for the bypass and inverter.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrTopFrequencyConverter 1.3.6.1.4.1.476.1.42.3.5.7.4
The system has a freqency converter.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrTopVoltageConverter 1.3.6.1.4.1.476.1.42.3.5.7.5
The system has a voltage converter.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrTopMaximumFrameCapacity 1.3.6.1.4.1.476.1.42.3.5.7.6
The maximum device system capacity.
OBJECT-TYPE    
  Integer32  

lgpPwrTopRedundantControlModules 1.3.6.1.4.1.476.1.42.3.5.7.7
The device has a redundant control module installed.
OBJECT-TYPE    
  INTEGER yes(1), no(2)  

lgpPwrStatistic 1.3.6.1.4.1.476.1.42.3.5.8
This sub-tree is used to register Liebert Power Statistic object identifiers.
OBJECT-IDENTITY    

lgpPwrBrownOutCount 1.3.6.1.4.1.476.1.42.3.5.8.1
The number of occurrences where the input line voltage has fallen below a pre-determined threshold for an specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
OBJECT-TYPE    
  Integer32  

lgpPwrBlackOutCount 1.3.6.1.4.1.476.1.42.3.5.8.2
The number of occurrences where there is a total loss of electric power. This number resets when the command 'lgpPwrStatisticsReset' is executed.
OBJECT-TYPE    
  Integer32  

lgpPwrTransientCount 1.3.6.1.4.1.476.1.42.3.5.8.3
The number of occurrences where the input line voltage spikes above a pre-determined threshold for an specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryDischargeCount 1.3.6.1.4.1.476.1.42.3.5.8.4
The number of battery discharges since the last reset.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryDischargeTime 1.3.6.1.4.1.476.1.42.3.5.8.5
The total accumlated time spent on battery since the last reset.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryAmpHours 1.3.6.1.4.1.476.1.42.3.5.8.6
The total accumulated Amp-Hours removed from the battery since last reset.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryWattHours 1.3.6.1.4.1.476.1.42.3.5.8.7
The total accumulated Watt-Hours removed from the battery since last reset. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrBatteryStatisticsReset 1.3.6.1.4.1.476.1.42.3.5.8.8
Battery statistics clear command. The command to reset all battery statistics stored by the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrStatisticsReset 1.3.6.1.4.1.476.1.42.3.5.8.9
Reset Power Statistics Command. This command will reset the power statistics stored in the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
OBJECT-TYPE    
  Integer32  

lgpPwrConfig 1.3.6.1.4.1.476.1.42.3.5.9
This sub-tree is used to register Liebert Power Config object identifiers.
OBJECT-IDENTITY    

lgpPwrSysCapacity 1.3.6.1.4.1.476.1.42.3.5.9.1
The current device system capacity.
OBJECT-TYPE    
  Integer32  

lgpPwrUPSModuleMode 1.3.6.1.4.1.476.1.42.3.5.9.2
The module mode of the UPS.
OBJECT-TYPE    
  INTEGER single(1), parallel(2), hotmaster(3), hotslave(4)  

Defined Objects

LgpPwrMeasurementPointEntry  
SEQUENCE    
  Unsigned32 as lgpPwrMeasurementPointIndex  
  OBJECT IDENTIFIER as lgpPwrMeasurementPointId  
  Integer32 as lgpPwrMeasurementPointNumLines  
  Integer32 as lgpPwrMeasurementPointNomVolts  
  Integer32 as lgpPwrMeasurementPointNomFrequency  
  Integer32 as lgpPwrMeasurementPointFrequency  
  Integer32 as lgpPwrMeasurementPointApparentPower  
  Integer32 as lgpPwrMeasurementPointTruePower  
  Integer32 as lgpPwrMeasurementPointPowerFactor  
  Integer32 as lgpPwrMeasurementPointWattHours  
  Integer32 as lgpPwrMeasurementPointVAPercent  
  Integer32 as lgpPwrMeasurementPointNeutralCurrent  
  Integer32 as lgpPwrMeasurementPointGroundCurrent  
  Integer32 as lgpPwrMeasurementPointNomCurrent  
  Integer32 as lgpPwrMeasurementPointNomPowerFactor  
  Integer32 as lgpPwrMeasurementPointNomVA  
  INTEGER as lgpPwrMeasurementPointPowerFactorTag  

LgpPwrLineMeasurementEntry  
SEQUENCE    
  Unsigned32 as lgpPwrMeasurementPtIndex  
  Unsigned32 as lgpPwrLineMeasurementIndex  
  OBJECT IDENTIFIER as lgpPwrMeasurementPoint  
  Integer32 as lgpPwrLineMeasurementVoltsLL  
  Integer32 as lgpPwrLineMeasurementVoltsLN  
  Integer32 as lgpPwrLineMeasurementCurrent  
  Integer32 as lgpPwrLineMeasurementCapacity  
  Integer32 as lgpPwrLineMeasurementVA  
  Integer32 as lgpPwrLineMeasurementTruePower  
  Integer32 as lgpPwrLineMeasurementVoltageTHD  
  Integer32 as lgpPwrLineMeasurementCurrentTHD  
  Integer32 as lgpPwrLineMeasurementKFactorCurrent  
  Integer32 as lgpPwrLineMeasurementCrestFactorCurrent  
  Integer32 as lgpPwrLineMeasurementPowerFactor  
  INTEGER as lgpPwrLineMeasurementPowerFactorTag  
  Integer32 as lgpPwrLineMeasurementMaxVolts  
  Integer32 as lgpPwrLineMeasurementMinVolts  
  Integer32 as lgpPwrLineMeasurementVAR  
  Integer32 as lgpPwrLineMeasurementPercentLoad  
  Integer32 as lgpPwrLineMeasurementVolts  

LgpPwrDcMeasurementPointEntry  
SEQUENCE    
  Unsigned32 as lgpPwrDcMeasurementPointIndex  
  OBJECT IDENTIFIER as lgpPwrDcMeasurementPointId  
  Integer32 as lgpPwrDcMeasurementPointSubID  
  Integer32 as lgpPwrDcMeasurementPointVolts  
  Integer32 as lgpPwrDcMeasurementPointCurrent  
  Integer32 as lgpPwrDcMeasurementPointNomVolts  
  Integer32 as lgpPwrDcMeasurementPointTruePower  

LgpPwrLoadCircuitEntry  
SEQUENCE    
  Unsigned32 as lgpPwrLoadCircuitIndex  
  OBJECT IDENTIFIER as lgpPwrLoadCircuitId  
  Unsigned32 as lgpPwrLoadCircuitSubID  
  INTEGER as lgpPwrLoadCircuitState  

LgpPwrThresholdEntry  
SEQUENCE    
  Unsigned32 as lgpPwrThresholdIndex  
  OBJECT IDENTIFIER as lgpPwrThresholdPoint  
  Unsigned32 as lgpPwrThresholdSubID  
  OBJECT IDENTIFIER as lgpPwrThresholdType  
  Integer32 as lgpPwrThresholdHighWarning  
  Integer32 as lgpPwrThresholdHighFailure  
  Integer32 as lgpPwrThresholdLowWarning  
  Integer32 as lgpPwrThresholdLowFailure