LIEBERT-SERIES-300-UPS-MIB
File:
LIEBERT-SERIES-300-UPS-MIB.mib (33074 bytes)
Imported modules
Imported symbols
Defined Objects
| emerson |
1.3.6.1.4.1.476 |
| OBJECT IDENTIFIER |
|
|
|
| luCore |
1.3.6.1.4.1.476.1.1.1.1 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsIdent |
1.3.6.1.4.1.476.1.1.1.1.1 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsIdentSpecific |
1.3.6.1.4.1.476.1.1.1.1.1.4 |
| A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value. |
| OBJECT-TYPE |
|
|
|
| |
OBJECT IDENTIFIER |
|
|
| lcUpsBatTimeRemaining |
1.3.6.1.4.1.476.1.1.1.1.2.1 |
| The estimated time to depletion of battery charge. (Unit of measure: Minute) |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..65535 |
|
| lcUpsBatVoltage |
1.3.6.1.4.1.476.1.1.1.1.2.3 |
| The current battery voltage. (Unit of measure: volt) |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
-32768..32767 |
|
| lcUpsBatCurrent |
1.3.6.1.4.1.476.1.1.1.1.2.4 |
| The current battery discharging/charging current. (Unit of measure: Amp) |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
-32768..32767 |
|
| lcUpsOutput |
1.3.6.1.4.1.476.1.1.1.1.4 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsOutputNumLines |
1.3.6.1.4.1.476.1.1.1.1.4.3 |
| The number of output lines utilized in this device. This entry indicates the number of rows in the output table. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
1..3 |
|
| lcUpsInverterStatus |
1.3.6.1.4.1.476.1.1.1.1.5.1 |
| The state of the inverter. Unknown is returned if the state can not be determined. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), on(2), off(3) |
|
| lcUpsInverterTemp |
1.3.6.1.4.1.476.1.1.1.1.5.2 |
| The temperature of the inverter. (Unit of measure: degree, Centigrade) |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
-32768..32767 |
|
| lcUpsAlarm |
1.3.6.1.4.1.476.1.1.1.1.6 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsAlarmId |
1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 |
| A unique identifier for an alarm condition. This value must remain constant between agent initializations. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsAlarmDescr |
1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 |
| A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
| OBJECT-TYPE |
|
|
|
| |
OBJECT IDENTIFIER |
|
|
| lcUpsTest |
1.3.6.1.4.1.476.1.1.1.1.7 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsTestBattery |
1.3.6.1.4.1.476.1.1.1.1.7.1 |
| Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), start(2), abort(3) |
|
| lcUpsTestBatteryStatus |
1.3.6.1.4.1.476.1.1.1.1.7.2 |
| The status of the battery test. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7) |
|
| lcUpsTestDiag |
1.3.6.1.4.1.476.1.1.1.1.7.3 |
| Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), start(2), abort(3) |
|
| lcUpsTestDiagStatus |
1.3.6.1.4.1.476.1.1.1.1.7.4 |
| The status of the diagnostics test. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7) |
|
| lcUpsControlOutputOffDelay |
1.3.6.1.4.1.476.1.1.1.1.8.1 |
| Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlOutputOnDelay |
1.3.6.1.4.1.476.1.1.1.1.8.2 |
| Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlOutputOffTrapDelay |
1.3.6.1.4.1.476.1.1.1.1.8.3 |
| When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlOutputOnTrapDelay |
1.3.6.1.4.1.476.1.1.1.1.8.4 |
| When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlUnixShutdownDelay |
1.3.6.1.4.1.476.1.1.1.1.8.5 |
| Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlUnixShutdownTrapDelay |
1.3.6.1.4.1.476.1.1.1.1.8.6 |
| When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsControlCancelCommands |
1.3.6.1.4.1.476.1.1.1.1.8.7 |
| Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), cancel(2) |
|
| lcUpsControlRebootAgentDelay |
1.3.6.1.4.1.476.1.1.1.1.8.8 |
| Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
0..2147483647 |
|
| lcUpsTraps |
1.3.6.1.4.1.476.1.1.1.1.11 |
| OBJECT IDENTIFIER |
|
|
|
| lcUpsOverloadWarningTrap |
1.3.6.1.4.1.476.1.1.1.1.11.1 |
| An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity. |
| TRAP-TYPE |
|
|
|
| |
sysUpTime |
|
|
| lcUpsOutputOnTrap |
1.3.6.1.4.1.476.1.1.1.1.11.14 |
| An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay. |
| TRAP-TYPE |
|
|
|
| |
sysUpTime |
|
|
| lsUpsIdent |
1.3.6.1.4.1.476.1.1.1.2.1 |
| OBJECT IDENTIFIER |
|
|
|
| lsUpsAlarm |
1.3.6.1.4.1.476.1.1.1.2.6 |
| OBJECT IDENTIFIER |
|
|
|
| lsUpsTraps |
1.3.6.1.4.1.476.1.1.1.2.11 |
| OBJECT IDENTIFIER |
|
|
|
| lsUpsConfig |
1.3.6.1.4.1.476.1.1.1.2.12 |
| OBJECT IDENTIFIER |
|
|
|
| lsUpsBypass |
1.3.6.1.4.1.476.1.1.1.2.13 |
| OBJECT IDENTIFIER |
|
|
|
| lsUpsOnBypass |
1.3.6.1.4.1.476.1.1.1.2.13.1 |
| Indicates that the UPS is currently on bypass. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
unknown(1), yes(2), no(3) |
|
| lsUpsBypassNumLines |
1.3.6.1.4.1.476.1.1.1.2.13.3 |
| The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| OBJECT-TYPE |
|
|
|
| |
INTEGER |
1..3 |
|
| luPrivate |
1.3.6.1.4.1.476.1.1.3 |
| OBJECT IDENTIFIER |
|
|
|
Defined Objects
| LcUpsInputEntry |
|
| SEQUENCE |
|
|
|
| |
INTEGER as lcUpsInputLine |
|
|
| |
INTEGER as lcUpsInputVoltage |
|
|
| |
INTEGER as lcUpsInputCurrent |
|
|
| |
INTEGER as lcUpsInputVA |
|
|
| LcUpsOutputEntry |
|
| SEQUENCE |
|
|
|
| |
INTEGER as lcUpsOutputLine |
|
|
| |
INTEGER as lcUpsOutputVoltage |
|
|
| |
INTEGER as lcUpsOutputCurrent |
|
|
| |
INTEGER as lcUpsOutputVA |
|
|
| LcUpsAlarmEntry |
|
| SEQUENCE |
|
|
|
| |
INTEGER as lcUpsAlarmId |
|
|
| |
OBJECT IDENTIFIER as lcUpsAlarmDescr |
|
|
| |
TimeTicks as lcUpsAlarmTime |
|
|
| LsUpsBypassEntry |
|
| SEQUENCE |
|
|
|
| |
INTEGER as lsUpsBypassLine |
|
|
| |
INTEGER as lsUpsBypassVoltage |
|
|
| |
INTEGER as lsUpsBypassCurrent |
|
|