NMS510-MIB

File: NMS510-MIB.mib (27869 bytes)

Imported modules

RFC-1212 RFC1213-MIB GDCMACRO-MIB
GDCCMN-MIB DDS-MIB

Imported symbols

OBJECT-TYPE DisplayString SCinstance
gdc dsu

Defined Objects

nms510 1.3.6.1.4.1.498.8.6
OBJECT IDENTIFIER    

nms510MIBversion 1.3.6.1.4.1.498.8.6.1
Identifies the version of the MIB. The format of the version is x.yzT, where 'x' identifies the major revision number, 'y' identifies the minor revision number, 'z' identifies the typographical revision, and T identifies the test revision. Acceptable values for the individual revision components are as follows: x: 1 - 9 y: 0 - 9 z: 0 - 9 T: A - Z Upon formal release, no designation for the test revision will be present.
OBJECT-TYPE    
  DisplayString SIZE(5)  

nms510UnitCfgTable 1.3.6.1.4.1.498.8.6.2
The NMS510 Unit Configuration table. This table augments the GDC SC5520 Unit Configuration table, providing unit level configuration for each NMS510 device installed. For each entry in the GDC SC Unit Configuration table that represents an NMS510, there is a corresponding entry here whereby the value of the gdcSCunitCfgIndex object is equivalent to the value of the nms510unitCfgIndex object.
OBJECT-TYPE    
  SEQUENCE OF  
    Nms510UnitCfgEntry

nms510UnitCfgEntry 1.3.6.1.4.1.498.8.6.2.1
The NMS510 Unit Configuration table entry. The information in this entry augments the information in the corresponding entry in the GDC SC Unit Configuration table and provides unit level configuration for the installed NMS510.
OBJECT-TYPE    
  Nms510UnitCfgEntry  

nms510UnitCfgIndex 1.3.6.1.4.1.498.8.6.2.1.1
The index value which uniquely identifies the NMS510 to which this entry is applicable. This has the form of a SCinstance which defines the slot, line, and drop of the NMS510 with no sub-identifier value.
OBJECT-TYPE    
  SCinstance  

nms510DteCtsDelay 1.3.6.1.4.1.498.8.6.2.1.2
RTS/CTS Delay options ctsOn(1) Forces both RTS and CTS On regardless of the state of the attached business equipment (the transmitter is On regardless of the status of the RTS interface lead). MIB object nms510DteCtsDelayExt is ignored. cts0mSec(2) Provides zero bits of delay between active RTS and CTS being set to active. MIB object nms510DteCtsDelayExt must be set to ext0mSec(1). ctsFix3Char(3) Provides three character bits of delay between active RTS and CTS being set to active. MIB object nms510DteCtsDelayExt must be set to ext0mSec(1).
OBJECT-TYPE    
  INTEGER ctsOn(1), cts0mSec(2), ctsFixed3Char(3)  

nms510DteCtsDelayExt 1.3.6.1.4.1.498.8.6.2.1.3
RTS/CTS Delay options extension ext0mSec(1) Used to enable options cts0mSec(2) or ctsFix3Char(3) from MIB object nms510DteCtsDelay. ext30mSec(2) Provides 30 msec of delay between active RTS and CTS being set to active. MIB object nms510DteCtsDelay must be set for either cts0mSec(2) or ctsFix3Char(3). ext60mSec(3) Provides 60 msec of delay between active RTS and CTS being set to active. MIB object nms510DteCtsDelay must be set for either cts0mSec(2) or ctsFix3Char(3). ext90mSec(4) Provides 90 msec of delay between active RTS and CTS being set to active. MIB object nms510DteCtsDelay must be set for either cts0mSec(2) or ctsFix3Char(3).
OBJECT-TYPE    
  INTEGER ext0mSec(1), ext30mSec(2), ext60mSec(3), ext90mSec(4)  

nms510FirmwareLevel 1.3.6.1.4.1.498.8.6.2.1.4
The version number of the firmware, to allow products to know which revision is installed. The released version number is sequenced from --, A-, ... AA, ... ZZ. Test versions are numerical from 01 to 99.
OBJECT-TYPE    
  DisplayString SIZE(2)  

nms510AlarmCfgCountWindow 1.3.6.1.4.1.498.8.6.2.1.5
The DDS Alarm Threshold Alarm Interval. It specifies the amount of time in minutes, 1 to 15 minutes, in which the threshold setting is to be exceeded for the alarm to occur. There is one Alarm Interval for all alarms that require thresholds: nms510FrameLossAlm.
OBJECT-TYPE    
  INTEGER 1..15  

nms510SoftReset 1.3.6.1.4.1.498.8.6.2.1.6
This object will cause software reset in dataset.
OBJECT-TYPE    
  INTEGER normal(1), reset(2)  

nms510FrontPanelInhibit 1.3.6.1.4.1.498.8.6.2.1.7
Inhibits front panel test switch. If a test switch is activated while inhibited it will simply be ignored. If enabled via the nms510FrontPanelEnable object the test switch will function as normal.
OBJECT-TYPE    
  INTEGER fpInhibited(1), fpEnabled(2), execute(3)  

nms510FrontPanelEnable 1.3.6.1.4.1.498.8.6.2.1.8
Enables front panel test switch. If a test switch is activated while inhibited, via the nms510FrontPanelInhibit object, it will simply be ignored. If enabled the test switch will function as normal.
OBJECT-TYPE    
  INTEGER fpInhibited(1), fpEnabled(2), execute(3)  

nms510HdlcInvert 1.3.6.1.4.1.498.8.6.2.1.9
Primary data invert option. Will enhance the quality of data when network does not provide B8Z5. Primarily used with DDS II 56k
OBJECT-TYPE    
  INTEGER normal(1), invert(2)  

nms510PiggyBackDetect 1.3.6.1.4.1.498.8.6.2.1.10
If set to 2 then either a Data Rate Adadaptor or 530 card is installed.
OBJECT-TYPE    
  INTEGER not-installed(1), installed(2)  

nms510ExtPortCtrlOut1 1.3.6.1.4.1.498.8.6.2.1.11
This option sets the external output state (on/off) of the current network element and displays the external output.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

nms510ExtPortCtrlOut2 1.3.6.1.4.1.498.8.6.2.1.12
This option sets the external output state (on/off) of the current network element and displays the external output.
OBJECT-TYPE    
  INTEGER on(1), off(2)  

nms510AlarmData 1.3.6.1.4.1.498.8.6.4
OBJECT IDENTIFIER    

nms510NoResponseAlm 1.3.6.1.4.1.498.8.6.4.1
OBJECT IDENTIFIER    

nms510DiagRxErrAlm 1.3.6.1.4.1.498.8.6.4.2
OBJECT IDENTIFIER    

nms510PowerUpAlm 1.3.6.1.4.1.498.8.6.4.3
OBJECT IDENTIFIER    

nms510EEChkSumErrAlm 1.3.6.1.4.1.498.8.6.4.4
OBJECT IDENTIFIER    

nms510StcLoopbackAlm 1.3.6.1.4.1.498.8.6.4.5
OBJECT IDENTIFIER    

nms510NoSignalAlm 1.3.6.1.4.1.498.8.6.4.6
OBJECT IDENTIFIER    

nms510FpTestAlm 1.3.6.1.4.1.498.8.6.4.7
OBJECT IDENTIFIER    

nms510StreamingAlm 1.3.6.1.4.1.498.8.6.4.8
OBJECT IDENTIFIER    

nms510DSRLossAlm 1.3.6.1.4.1.498.8.6.4.9
OBJECT IDENTIFIER    

nms510DTRLossAlm 1.3.6.1.4.1.498.8.6.4.10
OBJECT IDENTIFIER    

nms510DTPLossAlm 1.3.6.1.4.1.498.8.6.4.11
OBJECT IDENTIFIER    

nms510DCDLossAlm 1.3.6.1.4.1.498.8.6.4.12
OBJECT IDENTIFIER    

nms510RXDLossAlm 1.3.6.1.4.1.498.8.6.4.13
OBJECT IDENTIFIER    

nms510TXDLossAlm 1.3.6.1.4.1.498.8.6.4.14
OBJECT IDENTIFIER    

nms510DBURequestForScanAlm 1.3.6.1.4.1.498.8.6.4.15
OBJECT IDENTIFIER    

nms510DBUOnalm 1.3.6.1.4.1.498.8.6.4.16
OBJECT IDENTIFIER    

nms510DBUFailedAlm 1.3.6.1.4.1.498.8.6.4.17
OBJECT IDENTIFIER    

nms510ExtInputChangeAlm 1.3.6.1.4.1.498.8.6.4.18
OBJECT IDENTIFIER    

nms510ExtInputLowAlm 1.3.6.1.4.1.498.8.6.4.19
OBJECT IDENTIFIER    

nms510FrameLossAlm 1.3.6.1.4.1.498.8.6.4.20
OBJECT IDENTIFIER    

nms510DiagCfgTable 1.3.6.1.4.1.498.8.6.6
The NMS510 Unit Diagonostic table.
OBJECT-TYPE    
  SEQUENCE OF  
    Nms510DiagCfgEntry

nms510DiagCfgEntry 1.3.6.1.4.1.498.8.6.6.1
The NMS510 Unit Diagonostic table entry.
OBJECT-TYPE    
  Nms510DiagCfgEntry  

nms510DiagCfgIndex 1.3.6.1.4.1.498.8.6.6.1.1
The index value which uniquely identifies the NMS510 to which this entry is applicable. This has the form of a SCinstance which defines the slot, line, and drop of the NMS510 with no sub-identifier value.
OBJECT-TYPE    
  SCinstance  

nms510DiagSendCode 1.3.6.1.4.1.498.8.6.6.1.2
Configures the selftest pattern to be run during any diagonostic test involving selftest. If option SendOtherPattern is selected, then pattern will default to 15 bit if unit is set for 56k-DDS/sc-multi point else pattern will default to 511 bit for all other conditions
OBJECT-TYPE    
  INTEGER sendOtherPattern(1), send511Pattern(2), send2047Pattern(3), send15BitPattern(4)  

nms510DiagTestExceptions 1.3.6.1.4.1.498.8.6.6.1.3
Indicates exceptions that have occurred that may affect interpretation of the test results. The value of this object is a sum. This sum initially take the value zero. Then, for each exception, the value associated with the exception is added to the sum. The exception values are: value exception 0 No errors 1 bit over range 2 block over range 4 bit and block over range
OBJECT-TYPE    
  INTEGER noExceptions(1), blocksOutOfRange(2), bitsOutOfRange(3), blocksAndBitsOutOfRange(4)  

nms510DiagBitErrors 1.3.6.1.4.1.498.8.6.6.1.4
The bit errors of the last diagnostic test that involved a Selftest pattern. Reading bit errors while a diagnostic test in running will cause the unit to drop out of test and invalidate the bit errors. Bit errors should be read only after the test is completed. The valid range for bit errors is 0 to 1,023, 65535 will be returned if for any reason the test was terminated early.
OBJECT-TYPE    
  INTEGER 0..65535  

nms510DiagBlockErrors 1.3.6.1.4.1.498.8.6.6.1.5
The block errors of the last diagnostic test that involved a Selftest pattern. Reading block errors while a diagnostic test in running will cause the unit to drop out of test and invalidate the block errors. Block errors should be read only after the test is completed. The valid range for block errors is 0 to 1,023, 65535 will be returned if for any reason the test was terminated early.
OBJECT-TYPE    
  INTEGER 0..65535  

nms510DiagTestReset 1.3.6.1.4.1.498.8.6.6.1.6
This object will halt the execution of any and all diagnostic test that may be running with the exception of the Network Delay Test. This should only be used to terminate the test because reading this object will terminate the test.
OBJECT-TYPE    
  INTEGER normal(1), diagnostic(2), resetTest(3)  

nms510DiagExcTable 1.3.6.1.4.1.498.8.6.7
The NMS510 Unit Diagonostic table.
OBJECT-TYPE    
  SEQUENCE OF  
    Nms510DiagExcEntry

nms510DiagExcEntry 1.3.6.1.4.1.498.8.6.7.1
The NMS510 Unit Diagonostic table entry.
OBJECT-TYPE    
  Nms510DiagExcEntry  

nms510DiagExcIndex 1.3.6.1.4.1.498.8.6.7.1.1
The index value which uniquely identifies the NMS510 to which this entry is applicable. This has the form of a SCinstance which defines the slot, line, and drop of the NMS510 with no sub-identifier value.
OBJECT-TYPE    
  SCinstance  

nms510DiagIntLineloop 1.3.6.1.4.1.498.8.6.7.1.2
Lineloop (or Analoop) can be either a Bilaterial or Unilaterial loopback depending on option ddsDteTermaloop. To initiate a Lineloop with Selftest SET this object and specifiy a blocksize. The blocksize indicates the number of blocks the Selftest pattern generator will run. There are 1000 bits/block. Emuns 3 through 10 are write only. The only valid responses to a READ are lineloopOn(2) or lineloopOff(1). This test will terminate after the specified number of blocks have been run. Reading test results via the nms510DiagBitErrors or nms510DiagBlockErrors objects while the test is running will cause the test to terminate prematurely and render the results invalid. Test results should be only read after the test is completed. The current Test Status can be obtained by reading this object or the nms510DiagTestStatus object on the unit under test. This test can also be terminated by seting the nms510DiagTestReset object.
OBJECT-TYPE    
  INTEGER lineloopOff(1), lineloopOn(2), blocks1(3), blocks10(4), blocks100(5), blocks500(6), blocks1000(7), blocks5000(8), blocks10000(9), blocks50000(10)  

nms510DiagIntDataloop 1.3.6.1.4.1.498.8.6.7.1.3
To initiate a Dataloop with Selftest SET this object and specifiy a blocksize. The nms510 (the remote) unit will go into Dataloop and the master (the sc5520) unit will go into Selftest. The blocksize indicates the number of blocks the Selftest pattern generator will run. There are 1000 bits/block. Emuns 3 through 10 are write only. The only valid responses to a READ are dataloopOn(2) or dataloopOff(1). This test will terminate after the specified number of blocks have been run. Reading test results via the nms510DiagBitErrors or nms510DiagBlockErrors objects while the test is running will cause the test to terminate prematurely and render the results invalid. Test results should be read only after the test is completed and are available from the master (sc5520) unit. The current Test Status can be obtained by reading the sc5520DiagTestStatus object on the master unit, reading test status on the remote unit may interfere with the diagonostic test pattern and cause errors. This test can also be terminated by seting the nms510DiagTestReset object.
OBJECT-TYPE    
  INTEGER dataloopOff(1), dataloopOn(2), blocks1(3), blocks10(4), blocks100(5), blocks500(6), blocks1000(7), blocks5000(8), blocks10000(9), blocks50000(10)  

nms510DiagEndToEndSelftest 1.3.6.1.4.1.498.8.6.7.1.4
To initiate an End to End Selftest(Error Rate Test) SET this object and specifiy a blocksize. Both the remote (nms510) amd master (sc5520) units will go into Selftest. The blocksize indicates the number of blocks the Selftest pattern generator will run. There are 1000 bits/block. Emuns 3 through 10 are write only. The only valid responses to a READ are selftestOn(2) or selftestOff(1). This test will terminate after the specified number of blocks have been run. Reading test results via the nms510DiagBitErrors or nms510DiagBlockErrors objects while the test is running will cause the test to terminate prematurely and render the results invalid. Test results should be read only after the test is completed and are available from both the remote (nms510) and master (sc5520) units. The current Test Status can be obtained by reading the sc5520DiagTestStatus object on the master unit, reading test status on the remote unit may interfere with the diagonostic test patternand cause errors. This test can also be terminated by seting the nms510DiagTestReset object.
OBJECT-TYPE    
  INTEGER endToEndOff(1), endToEndOn(2), blocks1(3), blocks10(4), blocks100(5), blocks500(6), blocks1000(7), blocks5000(8), blocks10000(9), blocks50000(10)  

nms510DiagNetworkDelay 1.3.6.1.4.1.498.8.6.7.1.5
To initiate a Network Delay test SET this object and specifiy runDelayTest. Both the remote (nms510) and master (sc5520) units will go into a test to measure network delay. Emun 3 is write only. The only valid responses to a READ are delayTestOn(2) or delayTestOff(1). This test will terminate after 10 seconds. Test results should be read only after the test is completed and are available from the master (sc5520) unit. The current Test Status can be obtained by reading the sc5520DiagTestStatus object on the master unit, reading test status on the remote unit may interfere with the test and cause errors. This test can not be terminated early once it is started.
OBJECT-TYPE    
  INTEGER delayTestOff(1), delayTestOn(2), runDelayTest(3)  

nms510DiagTestStatus 1.3.6.1.4.1.498.8.6.7.1.6
This object gives the current diagonostic test status. noTest indicates that no diagonostic test is currently active. Reading this object while in a diagonostic test involing two units may interfere with a selftest pattern and invalidate the test results. Reading the sc5520DiagTestStatus (master unit) object during dagonostic tests involing two unit will not disrupt the test results.
OBJECT-TYPE    
  INTEGER noTest(1), internalLineloop(2), externalDataloop(3), internalDataloop(4), serviceTestCenterLoop(5), endToend(6)  

nms510DiagExtDataloop 1.3.6.1.4.1.498.8.6.7.1.7
To initiate a Dataloop test with no Selftest SET this object and specifiy external, this will allow the data from the DTE attached to the far end unit (sc5520) to looped back to itself. Emun external(3) is write only. The only valid response to a READ is dataloopOn(2) or dataloopOff(1). To halt this test you must SET the nms510DiagTestReset object. Reading test results via the nms510DiagBitErrors or nms510DiagBlockErrors objects while the test is running will also cause the test to terminate. There are no test results associated with this test. Reading test status on the remote unit via nms510DiagTestStatus may interfere with the diagonostic test pattern generated from the terminal equiptment.
OBJECT-TYPE    
  INTEGER dataloopOff(1), dataloopOn(2), external(3)  

nms510AlarmCfgTable 1.3.6.1.4.1.498.8.6.8
The GDC NMS510 Alarm Configuration Table.
OBJECT-TYPE    
  SEQUENCE OF  
    Nms510AlarmCfgEntry

nms510AlarmCfgEntry 1.3.6.1.4.1.498.8.6.8.1
An entry in the GDC NMS510 alarm Configuration table.
OBJECT-TYPE    
  Nms510AlarmCfgEntry  

nms510AlarmCfgIndex 1.3.6.1.4.1.498.8.6.8.1.1
This object is the index of the NMS510 Alarm Threshold Configuration table.
OBJECT-TYPE    
  SCinstance  

nms510AlarmCfgIdentifier 1.3.6.1.4.1.498.8.6.8.1.2
The unique alarm identifier assigned to this alarm type. The format of this identifier is an OBJECT IDENTIFIER that has the following format: {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) gdc(498) xxx(x) alarm(z) yyy(y) where xxx(x) is the administratively assigned family object identifier (z) is the object identifier for alarms in the family defined MIB and yyy(y) is the administratively assigned alarm type identifier for this alarm.
OBJECT-TYPE    
  OBJECT IDENTIFIER  

nms510AlarmCfgThreshold 1.3.6.1.4.1.498.8.6.8.1.3
This function sets/reads the alarm threashold settings criteria. This threshold is used along with the alarm window to determine the number of instances in a given time frame for a Frame Loss alarm to occur before the alarm is considered active. Frame Loss alarm only reported in DDS-2 line type. Alarm Table Entry Threshold Range Defaults ------------------ -------------------- -------------- -------- Frame Loss nms510FrameLossAlm 1 to 99 Count 10
OBJECT-TYPE    
  INTEGER 0..99  

Defined Objects

Nms510UnitCfgEntry  
SEQUENCE    
  SCinstance as nms510UnitCfgIndex  
  INTEGER as nms510DteCtsDelay  
  INTEGER as nms510DteCtsDelayExt  
  DisplayString as nms510FirmwareLevel  
  INTEGER as nms510AlarmCfgCountWindow  
  INTEGER as nms510SoftReset  
  INTEGER as nms510FrontPanelInhibit  
  INTEGER as nms510FrontPanelEnable  
  INTEGER as nms510HdlcInvert  
  INTEGER as nms510PiggyBackDetect  
  INTEGER as nms510ExtPortCtrlOut1  
  INTEGER as nms510ExtPortCtrlOut2  

Nms510AlarmCfgEntry  
SEQUENCE    
  SCinstance as nms510AlarmCfgIndex  
  OBJECT IDENTIFIER as nms510AlarmCfgIdentifier  
  INTEGER as nms510AlarmCfgThreshold  

Nms510DiagCfgEntry  
SEQUENCE    
  SCinstance as nms510DiagCfgIndex  
  INTEGER as nms510DiagSendCode  
  INTEGER as nms510DiagTestExceptions  
  INTEGER as nms510DiagBitErrors  
  INTEGER as nms510DiagBlockErrors  
  INTEGER as nms510DiagTestReset  

Nms510DiagExcEntry  
SEQUENCE    
  SCinstance as nms510DiagExcIndex  
  INTEGER as nms510DiagIntLineloop  
  INTEGER as nms510DiagIntDataloop  
  INTEGER as nms510DiagEndToEndSelftest  
  INTEGER as nms510DiagNetworkDelay  
  INTEGER as nms510DiagTestStatus  
  INTEGER as nms510DiagExtDataloop