| SNMPv2-SMI | SNMPv2-CONF | SNMPv2-TC |
| RITTAL-SMI-MIB |
| MODULE-IDENTITY | NOTIFICATION-TYPE | OBJECT-TYPE |
| Integer32 | Unsigned32 | TimeTicks |
| MODULE-COMPLIANCE | OBJECT-GROUP | NOTIFICATION-GROUP |
| DisplayString | rittal |
| cmcIII | 1.3.6.1.4.1.2606.7 | ||
| The MIB module for representing cmcIII SNMP agent | |||
| MODULE-IDENTITY | |||
| cmcIIINotifications | 1.3.6.1.4.1.2606.7.0 | ||
| OBJECT IDENTIFIER | |||
| alarmSensorDevice | 1.3.6.1.4.1.2606.7.0.1 | ||
| Alarm of sensors of device | |||
| NOTIFICATION-TYPE | |||
| cmcIIIDevName | |||
| cmcIIIMsgText | |||
| cmcIIIMsgStatus | |||
| cmcIIIMsgStatusText | |||
| alarmDevice | 1.3.6.1.4.1.2606.7.0.2 | ||
| Alarm of device | |||
| NOTIFICATION-TYPE | |||
| cmcIIIDevName | |||
| cmcIIIDevAlias | |||
| cmcIIIDevStatus | |||
| cmcIIIDevStatusText | |||
| cmcIIIMibRev | 1.3.6.1.4.1.2606.7.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIMibMajRev | 1.3.6.1.4.1.2606.7.1.1 | ||
| The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIIMibMinRev | 1.3.6.1.4.1.2606.7.1.2 | ||
| The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 0..65535 | ||
| cmcIIIAgentRev | 1.3.6.1.4.1.2606.7.1.3 | ||
| The SNMP Agent Revision level. | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..20) | ||
| cmcIIIUnit | 1.3.6.1.4.1.2606.7.2 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIUnitStatus | 1.3.6.1.4.1.2606.7.2.1 | ||
| General Status of CMCIII PU unit itself (1) OK (2) failed (3) overload (current too high) | |||
| OBJECT-TYPE | |||
| INTEGER | ok(1), failed(2), overload(3) | ||
| cmcIIIUnitURL | 1.3.6.1.4.1.2606.7.2.2 | ||
| URL of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIIUnitHWRev | 1.3.6.1.4.1.2606.7.2.3 | ||
| Hardware Revision of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..12) | ||
| cmcIIIUnitFWRev | 1.3.6.1.4.1.2606.7.2.4 | ||
| Firmware Revision of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..12) | ||
| cmcIIIUnitOSRev | 1.3.6.1.4.1.2606.7.2.5 | ||
| Linux Revision of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..20) | ||
| cmcIIIUnitSerial | 1.3.6.1.4.1.2606.7.2.6 | ||
| Serial Number of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..7) | ||
| cmcIIIUnitProd | 1.3.6.1.4.1.2606.7.2.7 | ||
| Production Code of CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..20) | ||
| cmcIIIUnitType | 1.3.6.1.4.1.2606.7.2.8 | ||
| Type of CMCIII (1) Unit unknown (2) Processing Unit (3) Processing Unit Compact | |||
| OBJECT-TYPE | |||
| INTEGER | unknown(1), pu(2), compact(3) | ||
| cmcIIIUnitCurrentSource | 1.3.6.1.4.1.2606.7.2.9 | ||
| Current source of CMCIII PU (1) unknown (2) AC Adapter Power Supply (3) Terminal Strip (4) poe: Power Over Ethernet (5) usb: Universal Serial Bus | |||
| OBJECT-TYPE | |||
| INTEGER | unknown(1), acAdapter(2), terminalStrip(3), poe(4), usb(5) | ||
| cmcIIICan0CurrentConsumption | 1.3.6.1.4.1.2606.7.2.10 | ||
| Maximal current consumption required by CANopen fieldbus 1 | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIICan1CurrentConsumption | 1.3.6.1.4.1.2606.7.2.11 | ||
| Maximal current consumption required by CANopen fieldbus 2 | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIUnitUpTime | 1.3.6.1.4.1.2606.7.2.12 | ||
| Operating time of CMCIII PU | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIISetup | 1.3.6.1.4.1.2606.7.3 | ||
| OBJECT IDENTIFIER | |||
| cmcIIILastChangeSetup | 1.3.6.1.4.1.2606.7.3.1 | ||
| Last change of configuration according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIISetupGeneral | 1.3.6.1.4.1.2606.7.3.2 | ||
| OBJECT IDENTIFIER | |||
| cmcIIISetTempUnit | 1.3.6.1.4.1.2606.7.3.2.1 | ||
| Unit of all temperature values and setpoints | |||
| OBJECT-TYPE | |||
| INTEGER | celsius(1), fahrenheit(2) | ||
| cmcIIISetBeeper | 1.3.6.1.4.1.2606.7.3.2.2 | ||
| Audible alarm in CMCIII unit: (1) beeper is off (general) (2) beeper is on | |||
| OBJECT-TYPE | |||
| INTEGER | off(1), on(2) | ||
| cmcIIIQuitRelay | 1.3.6.1.4.1.2606.7.3.2.3 | ||
| Enable or disable acknowledging currently active alarm relay (with 'C' on CMCIII). | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIILogicRelay | 1.3.6.1.4.1.2606.7.3.2.4 | ||
| Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay disabled | |||
| OBJECT-TYPE | |||
| INTEGER | closeAtAlarm(1), openAtAlarm(2), disabled(3) | ||
| cmcIIIUnitMsgRelay | 1.3.6.1.4.1.2606.7.3.2.5 | ||
| Alarm relay in case of Device Messages (detect, lost, changed..): (1) Relay disabled, relay will not switch in case of a device message (2) Relay enabled, relay will switch in case of a unit message | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIIFunctionRelay | 1.3.6.1.4.1.2606.7.3.2.6 | ||
| Logic of alarm relay: (1) Relay will switch in case of a warning only (2) Relay will switch in case of an alarm only (3) Relay will switch in case of an alarm or warning | |||
| OBJECT-TYPE | |||
| INTEGER | warningOnly(1), alarmOnly(2), warningOrAlarm(3) | ||
| cmcIIITimeZone | 1.3.6.1.4.1.2606.7.3.2.7 | ||
| Time Zone 0 : (GMT-12:00) International Date Line West 1 : (GMT-11:00) Midway Island, Samoa 2 : (GMT-10:00) Hawaii 3 : (GMT-09:00) Alaska 4 : (GMT-08:00) Pacific Time (US and Canada), Tijuana 5 : (GMT-07:00) Arizona 6 : (GMT-07:00) Chihuahua, La Paz, Mazatlan 7 : (GMT-07:00) Mountain Time (US & Canada) 8 : (GMT-06:00) Central America 9 : (GMT-06:00) Central Time (US and Canada) 10 : (GMT-06:00) Guadalajara, Mexico City, Monterrey 11 : (GMT-06:00) Saskatchewan 12 : (GMT-05:00) Bogota, Lima, Quito 13 : (GMT-05:00) Eastern Time (Us and Canada) 14 : (GMT-05:00) Indiana (East) 15 : (GMT-04:00) Atlantic Time (Canada) 16 : (GMT-04:00) Caracas, La Paz 17 : (GMT-04:00) Santiago 18 : (GMT-03:30) Newfoundland 19 : (GMT-03:00) Brasilia 20 : (GMT-03:00) Buenos Aires, Georgetown 21 : (GMT-03:00) Greenland 22 : (GMT-02:00) Mid-Atlantic 23 : (GMT-01:00) Azores 24 : (GMT-01:00) Cape Verde Is. 25 : (GMT) Casablanca, Monrovia 26 : (GMT) Greenwich Mean Time : Dublin, Lisbon, London 27 : (GMT+01:00) Amsterdam, Berlin, Bern, Rome, Vienna 28 : (GMT+01:00) Belgrade, Bratislava, Budapest, Prague 29 : (GMT+01:00) Brussels, Copenhagen, Madrid, Paris 30 : (GMT+01:00) Sarajevo, Skopje, Warsaw, Zagreb 31 : (GMT+01:00) West Central Africa 32 : (GMT+02:00) Athens, Istanbul, Minsk 33 : (GMT+02:00) Bucharest 34 : (GMT+02:00) Harare, Pretoria 35 : (GMT+02:00) Helsinki, Kyiv, Sofia 36 : (GMT+02:00) Riga, Tallinn, Vilnius 37 : (GMT+02:00) Jerusalem 38 : (GMT+03:00) Baghdad 39 : (GMT+03:00) Kuwait, Riyadh 40 : (GMT+03:00) Moscow, St. Petersburg, Volgograd 41 : (GMT+03:00) Nairobi 42 : (GMT+03:30) Tehran 43 : (GMT+04:00) Abu Dhabi, Muscat 44 : (GMT+04:00) Baku, Tbilisi, Yerevan 45 : (GMT+04:30) Kabul 46 : (GMT+05:00) Ekaterinburg 47 : (GMT+05:00) Islamabad, Karachi, Tashkent 48 : (GMT+05:30) Chennai, Kolkata, Mumbai, New Delhi 49 : (GMT+05:45) Kathmandu 50 : (GMT+06:00) Almaty, Novosibirsk 51 : (GMT+06:00) Astana, Dhaka 52 : (GMT+06:00) Sri Jayawardenepura 53 : (GMT+06:30) Rangoon 54 : (GMT+07:00) Bangkok, Hanoi, Jakarta 55 : (GMT+07:00) Krasnoyarsk 56 : (GMT+08:00) Beijing, Chongqing, Hong Kong, Urumqi 57 : (GMT+08:00) Irkutsk, Ulaan Bataar 58 : (GMT+08:00) Kuala Lumpur, Singapore 59 : (GMT+08:00) Perth 60 : (GMT+08:00) Taipei 61 : (GMT+09:00) Osaka, Sapporo, Tokyo 62 : (GMT+09:00) Seoul 63 : (GMT+09:00) Yakutsk 64 : (GMT+09:30) Adelaide 65 : (GMT+09:30) Darwin 66 : (GMT+10:00) Brisbane 67 : (GMT+10:00) Canberra, Melbourne, Sydney 68 : (GMT+10:00) Guam, Port Moresby 69 : (GMT+10:00) Hobart 70 : (GMT+10:00) Vladivostok 71 : (GMT+11:00) Magadan, Solomon Is., New Caledonia 72 : (GMT+12:00) Auckland, Wellington 73 : (GMT+12:00) Fiji, Kamchatka, Marshall Is. 74 : (GMT+13:00) Nukualofa | |||
| OBJECT-TYPE | |||
| Integer32 | 0..74 | ||
| cmcIIISetupDate | 1.3.6.1.4.1.2606.7.3.2.8 | ||
| Actual date in format DD.MM.YYYY Use UTC date to set date. | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(10..10) | ||
| cmcIIISetupTime | 1.3.6.1.4.1.2606.7.3.2.9 | ||
| Actual time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59). Use UTC time to set time. | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(8..8) | ||
| cmcIIIWebAccess | 1.3.6.1.4.1.2606.7.3.2.10 | ||
| Web access status: (0) httpEnabled : http protocol is enabled (1) httpsEnabled : https protocol is enabled | |||
| OBJECT-TYPE | |||
| BITS | httpEnabled(0), httpsEnabled(1) | ||
| cmcIIIHttpPort | 1.3.6.1.4.1.2606.7.3.2.11 | ||
| TCP/IP port of HTTP daemon | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIIHttpsPort | 1.3.6.1.4.1.2606.7.3.2.12 | ||
| TCP/IP port of HTTPS daemon | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIIFtpAccess | 1.3.6.1.4.1.2606.7.3.2.13 | ||
| Ftp access: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIIFtpPort | 1.3.6.1.4.1.2606.7.3.2.14 | ||
| TCP/IP port of FTP daemon | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIISshAccess | 1.3.6.1.4.1.2606.7.3.2.15 | ||
| Ssh access: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISshPort | 1.3.6.1.4.1.2606.7.3.2.16 | ||
| TCP/IP port of SSH daemon | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIITelnetAccess | 1.3.6.1.4.1.2606.7.3.2.17 | ||
| Telnet access: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIITelnetPort | 1.3.6.1.4.1.2606.7.3.2.18 | ||
| TCP/IP port of telnet daemon | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIILanguage | 1.3.6.1.4.1.2606.7.3.2.19 | ||
| Language: (1) English, (2) other | |||
| OBJECT-TYPE | |||
| INTEGER | english(1), other(2) | ||
| cmcIIISetupTimer | 1.3.6.1.4.1.2606.7.3.3 | ||
| OBJECT IDENTIFIER | |||
| cmcIIINumberOfTimers | 1.3.6.1.4.1.2606.7.3.3.1 | ||
| Number of value table entries=number of outlets available on this unit | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIITimerTable | 1.3.6.1.4.1.2606.7.3.3.2 | ||
| Headline of Timer Table | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIITimerEntry | |||
| cmcIIITimerEntry | 1.3.6.1.4.1.2606.7.3.3.2.1 | ||
| Entries of Timer Table | |||
| OBJECT-TYPE | |||
| CmcIIITimerEntry | |||
| cmcIIITimerIndex | 1.3.6.1.4.1.2606.7.3.3.2.1.1 | ||
| Index for the list of timer entries. Its value ranges between 1 and the value of cmcIIINumberOfTimers. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIITimerStatus | 1.3.6.1.4.1.2606.7.3.3.2.1.2 | ||
| Actual status of the timer | |||
| OBJECT-TYPE | |||
| INTEGER | switchedOff(1), switchedOn(2), noTime(3) | ||
| cmcIIITimerDayOfWeek | 1.3.6.1.4.1.2606.7.3.3.2.1.3 | ||
| Selection of day of week for timer to switch | |||
| OBJECT-TYPE | |||
| INTEGER | sun(1), mon(2), tue(3), wed(4), thu(5), fri(6), sat(7), sat2sun(8), mon2fri(9), mon2sun(10) | ||
| cmcIIITimeOn | 1.3.6.1.4.1.2606.7.3.3.2.1.4 | ||
| Time to switch on current function, Format: HH:MM | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(5..5) | ||
| cmcIIITimeOff | 1.3.6.1.4.1.2606.7.3.3.2.1.5 | ||
| Time to switch off current function, Format: HH:MM | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(5..5) | ||
| cmcIIITimeControl | 1.3.6.1.4.1.2606.7.3.3.2.1.6 | ||
| Control via RTC | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIITimerFunction | 1.3.6.1.4.1.2606.7.3.3.2.1.7 | ||
| Function which is controlled via timer 1: Unlock of doors via keypad is disabled 2: Doors will be unlocked 3-6: sending traps to this trap receiver will be disabled 7-10: sending SMS to phone number 1..4 will be disabled 11-18: Scheduled alarm off | |||
| OBJECT-TYPE | |||
| INTEGER | disKeypads(1), unlDoors(2), disTrapRec1(3), disTrapRec2(4), disTrapRec3(5), disTrapRec4(6), disSMS1(7), disSMS2(8), disSMS3(9), disSMS4(10), schedule1(11), schedule2(12), schedule3(13), schedule4(14), schedule5(15), schedule6(16), schedule7(17), schedule8(18) | ||
| cmcIIISetupTrap | 1.3.6.1.4.1.2606.7.3.4 | ||
| OBJECT IDENTIFIER | |||
| cmcIIINumberOfTrapReceivers | 1.3.6.1.4.1.2606.7.3.4.1 | ||
| Number of TrapReceiverTable entries. The number of trap receivers | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIITrapReceiverTable | 1.3.6.1.4.1.2606.7.3.4.2 | ||
| A list of trap receiver entries | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIITrapReceiverEntry | |||
| cmcIIITrapReceiverEntry | 1.3.6.1.4.1.2606.7.3.4.2.1 | ||
| Entries of trapTable | |||
| OBJECT-TYPE | |||
| CmcIIITrapReceiverEntry | |||
| cmcIIITrapReceiverIndex | 1.3.6.1.4.1.2606.7.3.4.2.1.1 | ||
| Index for the trap receiver table. Its value ranges between 1 and the value of NumberOfTrapReceivers | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIITrapReceiverStatus | 1.3.6.1.4.1.2606.7.3.4.2.1.2 | ||
| Enable trap version or disable trap receiver | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), snmpv1(2), snmpv2c(3), snmpv3(4) | ||
| cmcIIITrapReceiverIpAddress | 1.3.6.1.4.1.2606.7.3.4.2.1.3 | ||
| IP address of trap receiver | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIISetupSMTP | 1.3.6.1.4.1.2606.7.3.5 | ||
| OBJECT IDENTIFIER | |||
| cmcIIISmtpStatus | 1.3.6.1.4.1.2606.7.3.5.1 | ||
| SMTP (email) usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISmtpServer | 1.3.6.1.4.1.2606.7.3.5.2 | ||
| IP address of SMTP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIISmtpPort | 1.3.6.1.4.1.2606.7.3.5.3 | ||
| TCP/IP port of SMTP server | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIISmtpAuth | 1.3.6.1.4.1.2606.7.3.5.4 | ||
| SMTP authentication usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISmtpUsername | 1.3.6.1.4.1.2606.7.3.5.5 | ||
| Username required to authenticate at the SMTP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..20) | ||
| cmcIIISmtpPassword | 1.3.6.1.4.1.2606.7.3.5.6 | ||
| Password required to authenticate at the SMTP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..20) | ||
| cmcIIISmtpSender | 1.3.6.1.4.1.2606.7.3.5.7 | ||
| Sender address (FROM:) of the SMTP message | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIISmtpReply | 1.3.6.1.4.1.2606.7.3.5.8 | ||
| Reply address (REPLY:) of the SMTP message | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIINumberOfSmtpReceivers | 1.3.6.1.4.1.2606.7.3.5.9 | ||
| Number of SmtpReceiverTable entries. The number of SMTP receivers | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIISmtpReceiverTable | 1.3.6.1.4.1.2606.7.3.5.10 | ||
| A list of SMTP receiver entries | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIISmtpReceiverEntry | |||
| cmcIIISmtpReceiverEntry | 1.3.6.1.4.1.2606.7.3.5.10.1 | ||
| Entries of SMTPTable | |||
| OBJECT-TYPE | |||
| CmcIIISmtpReceiverEntry | |||
| cmcIIISmtpReceiverIndex | 1.3.6.1.4.1.2606.7.3.5.10.1.1 | ||
| Index for the SMTP receiver table. Its value ranges between 1 and the value of NumberOfSmtpReceivers | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIISmtpReceiverStatus | 1.3.6.1.4.1.2606.7.3.5.10.1.2 | ||
| Enable or disable SMTP receiver | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISmtpReceiverAddress | 1.3.6.1.4.1.2606.7.3.5.10.1.3 | ||
| IP address of SMTP receiver | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIISetupSMS | 1.3.6.1.4.1.2606.7.3.6 | ||
| OBJECT IDENTIFIER | |||
| cmcIIISmsStatus | 1.3.6.1.4.1.2606.7.3.6.1 | ||
| SMS usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISmsPIN | 1.3.6.1.4.1.2606.7.3.6.2 | ||
| SMS PIN number | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..4) | ||
| cmcIIISmsService | 1.3.6.1.4.1.2606.7.3.6.3 | ||
| SMS service number | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIISmsMSN | 1.3.6.1.4.1.2606.7.3.6.4 | ||
| SMS MSN for ISDN | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIISmsPreDial | 1.3.6.1.4.1.2606.7.3.6.5 | ||
| SMS PreDial number | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..2) | ||
| cmcIIINumberOfSmsReceivers | 1.3.6.1.4.1.2606.7.3.6.6 | ||
| Number of SmsReceiverTable entries. The number of SMS receivers | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIISmsReceiverTable | 1.3.6.1.4.1.2606.7.3.6.7 | ||
| A list of SMS receiver entries | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIISmsReceiverEntry | |||
| cmcIIISmsReceiverEntry | 1.3.6.1.4.1.2606.7.3.6.7.1 | ||
| Entries of SMSTable | |||
| OBJECT-TYPE | |||
| CmcIIISmsReceiverEntry | |||
| cmcIIISmsReceiverIndex | 1.3.6.1.4.1.2606.7.3.6.7.1.1 | ||
| Index for the SMS receiver table. Its value ranges between 1 and the value of NumberOfSmsReceivers | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIISmsReceiverStatus | 1.3.6.1.4.1.2606.7.3.6.7.1.2 | ||
| Enable or disable SMS receiver | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISmsReceiverNumber | 1.3.6.1.4.1.2606.7.3.6.7.1.3 | ||
| Phone number of SMS receiver | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIISetupSysLog | 1.3.6.1.4.1.2606.7.3.7 | ||
| OBJECT IDENTIFIER | |||
| cmcIIISysLogStatus | 1.3.6.1.4.1.2606.7.3.7.1 | ||
| SysLog usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIISysLogFacility | 1.3.6.1.4.1.2606.7.3.7.2 | ||
| SysLog facility local0..7 | |||
| OBJECT-TYPE | |||
| INTEGER | local0(1), local1(2), local2(3), local3(4), local4(5), local5(6), local6(7), local7(8) | ||
| cmcIIISysLogServer1 | 1.3.6.1.4.1.2606.7.3.7.3 | ||
| IP address of first SysLog server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIISysLogServer2 | 1.3.6.1.4.1.2606.7.3.7.4 | ||
| IP address of second SysLog server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIISetupNTP | 1.3.6.1.4.1.2606.7.3.8 | ||
| OBJECT IDENTIFIER | |||
| cmcIIINtpStatus | 1.3.6.1.4.1.2606.7.3.8.1 | ||
| NTP usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIINtpTimeZone | 1.3.6.1.4.1.2606.7.3.8.2 | ||
| NTP time zone, see cmcIIITimeZone for valid time zones | |||
| OBJECT-TYPE | |||
| Integer32 | 0..74 | ||
| cmcIIINtpServer1 | 1.3.6.1.4.1.2606.7.3.8.3 | ||
| IP address of first NTP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIINtpServer2 | 1.3.6.1.4.1.2606.7.3.8.4 | ||
| IP address of second NTP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIISetupLDAP | 1.3.6.1.4.1.2606.7.3.9 | ||
| OBJECT IDENTIFIER | |||
| cmcIIILdapStatus | 1.3.6.1.4.1.2606.7.3.9.1 | ||
| LDAP usage: (1) disabled (2) enabled | |||
| OBJECT-TYPE | |||
| INTEGER | disabled(1), enabled(2) | ||
| cmcIIILdapServer | 1.3.6.1.4.1.2606.7.3.9.2 | ||
| IP address of LDAP server | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..15) | ||
| cmcIIIDevice | 1.3.6.1.4.1.2606.7.4 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIDevs | 1.3.6.1.4.1.2606.7.4.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIDevInfo | 1.3.6.1.4.1.2606.7.4.1.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIOverallDevStatus | 1.3.6.1.4.1.2606.7.4.1.1.1 | ||
| Overall status of all devices | |||
| OBJECT-TYPE | |||
| INTEGER | ok(1), warning(2), alarm(3) | ||
| cmcIIINumberOfDevs | 1.3.6.1.4.1.2606.7.4.1.1.2 | ||
| Number of devices available | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIILastChangeOverallDevStatus | 1.3.6.1.4.1.2606.7.4.1.1.3 | ||
| Timestamp of last status change of any device connected to CMCIII PU according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeNumberOfDevs | 1.3.6.1.4.1.2606.7.4.1.1.4 | ||
| Timestamp of last device number change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeDevSettings | 1.3.6.1.4.1.2606.7.4.1.1.5 | ||
| Timestamp of last setting change of any device connected to CMCIII PU according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeDevs | 1.3.6.1.4.1.2606.7.4.1.1.6 | ||
| Timestamp of last device change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIIDevTable | 1.3.6.1.4.1.2606.7.4.1.2 | ||
| Headline of device table | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIIDevEntry | |||
| cmcIIIDevEntry | 1.3.6.1.4.1.2606.7.4.1.2.1 | ||
| Entries of device table | |||
| OBJECT-TYPE | |||
| CmcIIIDevEntry | |||
| cmcIIIDevIndex | 1.3.6.1.4.1.2606.7.4.1.2.1.1 | ||
| Index of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..126 | ||
| cmcIIIDevName | 1.3.6.1.4.1.2606.7.4.1.2.1.2 | ||
| Name of the device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIIDevAlias | 1.3.6.1.4.1.2606.7.4.1.2.1.3 | ||
| Descriptional text for device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIIDevType | 1.3.6.1.4.1.2606.7.4.1.2.1.4 | ||
| Type of device chassis connected to CMCIII PU. The authoritative identification of the device contained in the entity is allocated within the SMI cmcIIIProducts subtree (1.3.6.1.4.1.2606.7.7) and provides an easy and unambiguous means for determining `what kind of box' is connected. E.g.: in cmcIIIProductChassis (1.3.6.1.4.1.2606.7.7.4.x) the placeholder x is used for 1 : Not Available 2 : Internal Device of Processing Unit 3 : Virtual Device 4 : Temperature Sensor 7030.110 5 : Temp/Humidity Sensor 7030.111 6 : Vandalism Sensor 7030.130 7 : Access Sensor 7030.120 8 : Door Lock Device 7030.200, .210 9 : Universal Sensor 7030.190 10: Sensor Gateway 7030.100 11: Power Unit 7030.050 12: Pressure Sensor 7030.150 20-25: Gateways to RS422, RS485 | |||
| OBJECT-TYPE | |||
| OBJECT IDENTIFIER | |||
| cmcIIIDevNodeID | 1.3.6.1.4.1.2606.7.4.1.2.1.5 | ||
| Node ID of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevStatus | 1.3.6.1.4.1.2606.7.4.1.2.1.6 | ||
| General Status of device connected to CMCIII PU (1) Device not available (2) OK (3) Device detected, confirmation required (4) Device lost (disconnected), confirmation required (5) Device changed (6) Error | |||
| OBJECT-TYPE | |||
| INTEGER | notAvail(1), ok(2), detect(3), lost(4), changed(5), error(6) | ||
| cmcIIIDevArtNr | 1.3.6.1.4.1.2606.7.4.1.2.1.7 | ||
| Article number of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..10) | ||
| cmcIIIDevLocation | 1.3.6.1.4.1.2606.7.4.1.2.1.8 | ||
| Location of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIIDevBus | 1.3.6.1.4.1.2606.7.4.1.2.1.9 | ||
| CAN bus of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| INTEGER | canBus1(1), canBus2(2), virtual(3) | ||
| cmcIIIDevPos | 1.3.6.1.4.1.2606.7.4.1.2.1.10 | ||
| Position (order) of device in CAN bus connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevFW | 1.3.6.1.4.1.2606.7.4.1.2.1.11 | ||
| FW version of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..12) | ||
| cmcIIIDevHW | 1.3.6.1.4.1.2606.7.4.1.2.1.12 | ||
| HW version of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..12) | ||
| cmcIIIDevSerial | 1.3.6.1.4.1.2606.7.4.1.2.1.13 | ||
| Serial number of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(8..8) | ||
| cmcIIIDevProductWeek | 1.3.6.1.4.1.2606.7.4.1.2.1.14 | ||
| Production week of device connected to CMCIII PU | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(8..8) | ||
| cmcIIIDevLastChange | 1.3.6.1.4.1.2606.7.4.1.2.1.15 | ||
| Timestamp of last change of device connected to CMCIII PU according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIIDevURL | 1.3.6.1.4.1.2606.7.4.1.2.1.16 | ||
| URL to device page of CMCIII PU (if available) | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIIDevNumberOfVars | 1.3.6.1.4.1.2606.7.4.1.2.1.17 | ||
| Number of variables available on this device. This variable will give the number of rows of the variable table cmcIIIVarTable belonging to this device | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevNumberOfMsgs | 1.3.6.1.4.1.2606.7.4.1.2.1.18 | ||
| Number of messages available in this device. This variable will give the number of rows of the message table cmcIIIMsgTable belonging to this device | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevStatusText | 1.3.6.1.4.1.2606.7.4.1.2.1.19 | ||
| Latest status of this device | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..160) | ||
| cmcIIIDevCurrentMinConsumption | 1.3.6.1.4.1.2606.7.4.1.2.1.20 | ||
| Standby power consumption of device in mA | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevCurrentMaxConsumption | 1.3.6.1.4.1.2606.7.4.1.2.1.21 | ||
| Maximal power consumption of device in mA | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIDevEntPhysicalIndex | 1.3.6.1.4.1.2606.7.4.1.2.1.22 | ||
| Corresponding entPhysicalIndex of this device. 0 if none exists. | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIVars | 1.3.6.1.4.1.2606.7.4.2 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIVarInfo | 1.3.6.1.4.1.2606.7.4.2.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIINumberOfVars | 1.3.6.1.4.1.2606.7.4.2.1.1 | ||
| Total number of variables available | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIILastChangeNumberOfVars | 1.3.6.1.4.1.2606.7.4.2.1.2 | ||
| Timestamp of last message number change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeVarSettings | 1.3.6.1.4.1.2606.7.4.2.1.3 | ||
| Timestamp of last setting change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeVars | 1.3.6.1.4.1.2606.7.4.2.1.4 | ||
| Timestamp of last variable change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIIVarTable | 1.3.6.1.4.1.2606.7.4.2.2 | ||
| Headline of variable table | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIIVariableEntry | |||
| cmcIIIVarEntry | 1.3.6.1.4.1.2606.7.4.2.2.1 | ||
| Entries of variable table | |||
| OBJECT-TYPE | |||
| CmcIIIVariableEntry | |||
| cmcIIIVarDeviceIndex | 1.3.6.1.4.1.2606.7.4.2.2.1.1 | ||
| Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIIVarIndex | 1.3.6.1.4.1.2606.7.4.2.2.1.2 | ||
| Index for the list of value entries. Its value ranges between 1 and the value of cmcIIINumberOfVars. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIIVarName | 1.3.6.1.4.1.2606.7.4.2.2.1.3 | ||
| Clear name of variable | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..30) | ||
| cmcIIIVarType | 1.3.6.1.4.1.2606.7.4.2.2.1.4 | ||
| Type of variable | |||
| OBJECT-TYPE | |||
| INTEGER | description(1), value(2), setHigh(3), setWarn(4), setLow(5), hysteresis(6), status(7), statusEnum(8), setWarnLow(9), unit(10), alarmDur(11), steps(12), configPar(13), category(14), logic(15), logicEnum(16), setCntrl(17), output(20), outputdelay(21), outputaction(22), outdelayExec(23), outputEnum(24), sensitivity(30), accessTime(31), accessLogic(32), outputPWM(40), rotation(41), productDate(50), orderNr(51), devName(52), devLocation(53), keycode(80), command(81), commandEnum(82), commandKeypad(83), commandService(84), unitType(90), swVersion(91), serialNumber(92), position(93), grouping(100), ignore(254), illegal(255) | ||
| cmcIIIVarUnit | 1.3.6.1.4.1.2606.7.4.2.2.1.5 | ||
| Unit of variable e. g. degree C | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..12) | ||
| cmcIIIVarDatatype | 1.3.6.1.4.1.2606.7.4.2.2.1.6 | ||
| Datatype of variable | |||
| OBJECT-TYPE | |||
| INTEGER | notAvail(1), int(2), string(3), enum(4) | ||
| cmcIIIVarScale | 1.3.6.1.4.1.2606.7.4.2.2.1.7 | ||
| Scaling factor of variable value, e. g. -100 -> value has to be divided by 100 +100 -> value has to be multiplied by 100 | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIVarConstraints | 1.3.6.1.4.1.2606.7.4.2.2.1.8 | ||
| Constraints of value, e. g. [-- a-zA-Z0-9]+ (if VariableDatatype is 'string') | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..64) | ||
| cmcIIIVarSteps | 1.3.6.1.4.1.2606.7.4.2.2.1.9 | ||
| Steps of variable value (resolution) | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIVarValueStr | 1.3.6.1.4.1.2606.7.4.2.2.1.10 | ||
| Value as string, including sign (+/-) and unit (deg C) | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIIVarValueInt | 1.3.6.1.4.1.2606.7.4.2.2.1.11 | ||
| Value as int | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIVarLastChange | 1.3.6.1.4.1.2606.7.4.2.2.1.12 | ||
| Timestamp of last update or change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIIVarAccess | 1.3.6.1.4.1.2606.7.4.2.2.1.13 | ||
| Access for value | |||
| OBJECT-TYPE | |||
| INTEGER | none(1), readonly(2), readwrite(3), readwriteswitch(4), readwriteextended(5) | ||
| cmcIIIVarQuality | 1.3.6.1.4.1.2606.7.4.2.2.1.14 | ||
| Quality of variable | |||
| OBJECT-TYPE | |||
| INTEGER | undefined(1), ok(2), warning(3), alarm(4), info(5), undefined-noValue(21), ok-noValue(22), warning-noValue(23), alarm-noValue(24), info-noValue(25) | ||
| cmcIIIVarEntPhysicalIndex | 1.3.6.1.4.1.2606.7.4.2.2.1.15 | ||
| Corresponding entPhysicalIndex of this variable. 0 if none exists. | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIMsgs | 1.3.6.1.4.1.2606.7.4.3 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIMsgInfo | 1.3.6.1.4.1.2606.7.4.3.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIOverallMsgStatus | 1.3.6.1.4.1.2606.7.4.3.1.1 | ||
| Overall message status of device | |||
| OBJECT-TYPE | |||
| INTEGER | ok(1), warning(2), alarm(3) | ||
| cmcIIINumberOfMsgs | 1.3.6.1.4.1.2606.7.4.3.1.2 | ||
| Number of messages. All status vars available in cmcIIIVarTable will cause a message in cmcIIIMsgTable. | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIILastChangeOverallMsgStatus | 1.3.6.1.4.1.2606.7.4.3.1.3 | ||
| Timestamp of last status change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeNumberOfMsgs | 1.3.6.1.4.1.2606.7.4.3.1.4 | ||
| Timestamp of last message number change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIILastChangeMsgSettings | 1.3.6.1.4.1.2606.7.4.3.1.5 | ||
| Timestamp of last setting change according to operating time cmcIIIUnitUpTime | |||
| OBJECT-TYPE | |||
| TimeTicks | |||
| cmcIIIMsgTable | 1.3.6.1.4.1.2606.7.4.3.2 | ||
| Headline of message table | |||
| OBJECT-TYPE | |||
| SEQUENCE OF | |||
| CmcIIIMsgEntry | |||
| cmcIIIMsgEntry | 1.3.6.1.4.1.2606.7.4.3.2.1 | ||
| Entries of message table | |||
| OBJECT-TYPE | |||
| CmcIIIMsgEntry | |||
| cmcIIIMsgDeviceIndex | 1.3.6.1.4.1.2606.7.4.3.2.1.1 | ||
| Index for the device. Its value ranges between 1 and the value of cmcIIINumberOfDevs. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIIMsgIndex | 1.3.6.1.4.1.2606.7.4.3.2.1.2 | ||
| Index for the list of message entries. Its value ranges between 1 and the value of cmcIIINumberOfMsgs. | |||
| OBJECT-TYPE | |||
| Unsigned32 | 1..65535 | ||
| cmcIIIMsgText | 1.3.6.1.4.1.2606.7.4.3.2.1.3 | ||
| Text for each message (entry in the table) | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..40) | ||
| cmcIIIMsgStatus | 1.3.6.1.4.1.2606.7.4.3.2.1.4 | ||
| Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached high warning threshold 7: analog value too low, value reached low threshold (Alarm) 8: analog value too high, value reached high threshold (Alarm) 9: warning of analog value, value reached low warning threshold 10: output is set to OFF 11: output is set to ON 12: door is open 13: door is closed 14: door is locked 15: door is unlocked by remote input, e.g. external card reader 16: door is unlocked by reader or keypad connected 17: door is unlocked by SNMP set command 18: door is unlocked by WEB 19: door is unlocked by timer 20: no access, wrong key code or card number 21: orientation of PSM unit is circuit 1 22: orientation of PSM unit is circuit 2 23: battery low, wireless sensor 24: sensor cable broken 25: sensor cable short 26: sensor calibration in progress 27: sensor is inactive 28: sensor is active 29: no Power (PSM) | |||
| OBJECT-TYPE | |||
| INTEGER | notAvail(1), configChanged(2), error(3), ok(4), alarm(5), highWarn(6), lowAlarm(7), highAlarm(8), lowWarn(9), setOff(10), setOn(11), open(12), closed(13), locked(14), unlRemote(15), doorOpen(16), unlSNMP(17), unlWEB(18), unlTimer(19), noAccess(20), circuit1(21), circuit2(22), lowbatt(23), probeopen(24), probeshort(25), calibration(26), inactive(27), active(28), noPower(29) | ||
| cmcIIIMsgRelay | 1.3.6.1.4.1.2606.7.4.3.2.1.5 | ||
| Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay | |||
| OBJECT-TYPE | |||
| INTEGER | disable(1), enable(2) | ||
| cmcIIIMsgBeeper | 1.3.6.1.4.1.2606.7.4.3.2.1.6 | ||
| Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm | |||
| OBJECT-TYPE | |||
| INTEGER | disable(1), enable(2) | ||
| cmcIIIMsgTrap | 1.3.6.1.4.1.2606.7.4.3.2.1.7 | ||
| Each bit is representing an entry of cmcIIITrapReceiverTable. If the corresponding cmcIIITrapReceiverStatus is enabled setting this bit enables sending messages to this receiver. | |||
| OBJECT-TYPE | |||
| BITS | receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15) | ||
| cmcIIIMsgSMTP | 1.3.6.1.4.1.2606.7.4.3.2.1.8 | ||
| Each bit is representing an entry of cmcIIISmtpReceiverTable. If the corresponding cmcIIISmtpReceiverStatus is enabled setting this bit enables sending messages to this receiver. | |||
| OBJECT-TYPE | |||
| BITS | receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15) | ||
| cmcIIIMsgSMS | 1.3.6.1.4.1.2606.7.4.3.2.1.9 | ||
| Each bit is representing an entry of cmcIIISmsReceiverTable. If the corresponding cmcIIISmsReceiverStatus is enabled setting this bit enables sending messages to this receiver. | |||
| OBJECT-TYPE | |||
| BITS | receiver1(0), receiver2(1), receiver3(2), receiver4(3), receiver5(4), receiver6(5), receiver7(6), receiver8(7), receiver9(8), receiver10(9), receiver11(10), receiver12(11), receiver13(12), receiver14(13), receiver15(14), receiver16(15) | ||
| cmcIIIMsgQuit | 1.3.6.1.4.1.2606.7.4.3.2.1.10 | ||
| Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key | |||
| OBJECT-TYPE | |||
| INTEGER | auto(1), manual(2) | ||
| cmcIIIMsgDelay | 1.3.6.1.4.1.2606.7.4.3.2.1.11 | ||
| Delay of alarm condition | |||
| OBJECT-TYPE | |||
| Unsigned32 | |||
| cmcIIIMsgSchedAlarmOff | 1.3.6.1.4.1.2606.7.4.3.2.1.12 | ||
| Alarm condition disabled by scheduler | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIMsgQuality | 1.3.6.1.4.1.2606.7.4.3.2.1.13 | ||
| Quality of variable | |||
| OBJECT-TYPE | |||
| INTEGER | undefined(1), ok(2), warning(3), alarm(4), info(5), undefined-noValue(21), ok-noValue(22), warning-noValue(23), alarm-noValue(24), info-noValue(25) | ||
| cmcIIIMsgVarIdx | 1.3.6.1.4.1.2606.7.4.3.2.1.14 | ||
| Index of variable 'Status' in variable table generating this message | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIMsgVarValueIdx | 1.3.6.1.4.1.2606.7.4.3.2.1.15 | ||
| Index of variable 'Value' in the variable table | |||
| OBJECT-TYPE | |||
| Integer32 | |||
| cmcIIIMsgStatusText | 1.3.6.1.4.1.2606.7.4.3.2.1.16 | ||
| Message status text | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..160) | ||
| cmcIIIControl | 1.3.6.1.4.1.2606.7.5 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIQuitUnit | 1.3.6.1.4.1.2606.7.5.1 | ||
| Command to quit (acknowledge) alarms of CMCIII unit. Setting to 'quit' (2) will have same result as pressing 'C' on CMCIII. Variable is automatically set back to 'noQuit' (1). | |||
| OBJECT-TYPE | |||
| INTEGER | noQuit(1), quit(2) | ||
| cmcIIISmsQueue | 1.3.6.1.4.1.2606.7.5.2 | ||
| Fast track to send a SMS message based on configuration of cmcIIISetupSMS. Message format: MessageText TabulatorAsSeparator ReceiverPhoneNumber e.g.: Hello World! 0123456789 | |||
| OBJECT-TYPE | |||
| DisplayString | SIZE(0..180) | ||
| cmcIIIConformance | 1.3.6.1.4.1.2606.7.6 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIMibCompliances | 1.3.6.1.4.1.2606.7.6.1 | ||
| OBJECT IDENTIFIER | |||
| cmcIIIMibCompliance | 1.3.6.1.4.1.2606.7.6.1.1 | ||
| The core compliance statement for all cmcIII implementations. | |||
| MODULE-COMPLIANCE | |||
| cmcIIIMibGroups | 1.3.6.1.4.1.2606.7.6.2 | ||
| OBJECT IDENTIFIER | |||
| cmcIIITrapGroup | 1.3.6.1.4.1.2606.7.6.2.1 | ||
| Conformance group for objects contained in cmcIII notifications. | |||
| OBJECT-GROUP | |||
| cmcIIINotificationGroup | 1.3.6.1.4.1.2606.7.6.2.2 | ||
| The cmcIII MIB notification group. | |||
| NOTIFICATION-GROUP | |||
| cmcIIIInfoMibGroup | 1.3.6.1.4.1.2606.7.6.2.3 | ||
| Conformance group for all cmcIII base information. | |||
| OBJECT-GROUP | |||
| cmcIIISetupMibGroup | 1.3.6.1.4.1.2606.7.6.2.4 | ||
| Conformance group for all cmcIII setup operations. | |||
| OBJECT-GROUP | |||
| cmcIIIDeviceMibGroup | 1.3.6.1.4.1.2606.7.6.2.5 | ||
| Conformance group for all cmcIII device information. | |||
| OBJECT-GROUP | |||
| cmcIIIControlMibGroup | 1.3.6.1.4.1.2606.7.6.2.6 | ||
| Conformance group for all cmcIII control operations. | |||
| OBJECT-GROUP | |||
| CmcIIITimerEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIITimerIndex | |||
| INTEGER as cmcIIITimerStatus | |||
| INTEGER as cmcIIITimerDayOfWeek | |||
| DisplayString as cmcIIITimeOn | |||
| DisplayString as cmcIIITimeOff | |||
| INTEGER as cmcIIITimeControl | |||
| INTEGER as cmcIIITimerFunction | |||
| CmcIIITrapReceiverEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIITrapReceiverIndex | |||
| INTEGER as cmcIIITrapReceiverStatus | |||
| DisplayString as cmcIIITrapReceiverIpAddress | |||
| CmcIIISmtpReceiverEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIISmtpReceiverIndex | |||
| INTEGER as cmcIIISmtpReceiverStatus | |||
| DisplayString as cmcIIISmtpReceiverAddress | |||
| CmcIIISmsReceiverEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIISmsReceiverIndex | |||
| INTEGER as cmcIIISmsReceiverStatus | |||
| DisplayString as cmcIIISmsReceiverNumber | |||
| CmcIIIDevEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIIDevIndex | |||
| DisplayString as cmcIIIDevName | |||
| DisplayString as cmcIIIDevAlias | |||
| OBJECT IDENTIFIER as cmcIIIDevType | |||
| Integer32 as cmcIIIDevNodeID | |||
| INTEGER as cmcIIIDevStatus | |||
| DisplayString as cmcIIIDevArtNr | |||
| DisplayString as cmcIIIDevLocation | |||
| INTEGER as cmcIIIDevBus | |||
| Integer32 as cmcIIIDevPos | |||
| DisplayString as cmcIIIDevFW | |||
| DisplayString as cmcIIIDevHW | |||
| DisplayString as cmcIIIDevSerial | |||
| DisplayString as cmcIIIDevProductWeek | |||
| TimeTicks as cmcIIIDevLastChange | |||
| DisplayString as cmcIIIDevURL | |||
| Integer32 as cmcIIIDevNumberOfVars | |||
| Integer32 as cmcIIIDevNumberOfMsgs | |||
| DisplayString as cmcIIIDevStatusText | |||
| Integer32 as cmcIIIDevCurrentMinConsumption | |||
| Integer32 as cmcIIIDevCurrentMaxConsumption | |||
| Integer32 as cmcIIIDevEntPhysicalIndex | |||
| CmcIIIVariableEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIIVarDeviceIndex | |||
| Unsigned32 as cmcIIIVarIndex | |||
| DisplayString as cmcIIIVarName | |||
| INTEGER as cmcIIIVarType | |||
| DisplayString as cmcIIIVarUnit | |||
| INTEGER as cmcIIIVarDatatype | |||
| Integer32 as cmcIIIVarScale | |||
| DisplayString as cmcIIIVarConstraints | |||
| Integer32 as cmcIIIVarSteps | |||
| DisplayString as cmcIIIVarValueStr | |||
| Integer32 as cmcIIIVarValueInt | |||
| TimeTicks as cmcIIIVarLastChange | |||
| INTEGER as cmcIIIVarAccess | |||
| INTEGER as cmcIIIVarQuality | |||
| Integer32 as cmcIIIVarEntPhysicalIndex | |||
| CmcIIIMsgEntry | |||
| SEQUENCE | |||
| Unsigned32 as cmcIIIMsgDeviceIndex | |||
| Unsigned32 as cmcIIIMsgIndex | |||
| DisplayString as cmcIIIMsgText | |||
| INTEGER as cmcIIIMsgStatus | |||
| INTEGER as cmcIIIMsgRelay | |||
| INTEGER as cmcIIIMsgBeeper | |||
| BITS as cmcIIIMsgTrap | |||
| BITS as cmcIIIMsgSMTP | |||
| BITS as cmcIIIMsgSMS | |||
| INTEGER as cmcIIIMsgQuit | |||
| Unsigned32 as cmcIIIMsgDelay | |||
| Integer32 as cmcIIIMsgSchedAlarmOff | |||
| INTEGER as cmcIIIMsgQuality | |||
| Integer32 as cmcIIIMsgVarIdx | |||
| Integer32 as cmcIIIMsgVarValueIdx | |||
| DisplayString as cmcIIIMsgStatusText | |||