S412-MIB

File: S412-MIB.mib (61005 bytes)

Imported modules

RFC1155-SMI RFC-1212 SNMPv2-TC
RFC-1215

Imported symbols

private internet mgmt
NetworkAddress IpAddress Counter
Gauge TimeTicks enterprises
OBJECT-TYPE DisplayString TRAP-TYPE

Defined Objects

asentria 1.3.6.1.4.1.3052
OBJECT IDENTIFIER    

s412 1.3.6.1.4.1.3052.41
OBJECT IDENTIFIER    

device 1.3.6.1.4.1.3052.41.1
OBJECT IDENTIFIER    

serialNumber 1.3.6.1.4.1.3052.41.1.1
8-character serial number
OBJECT-TYPE    
  DisplayString  

firmwareVersion 1.3.6.1.4.1.3052.41.1.2
Firmware version text string
OBJECT-TYPE    
  DisplayString  

siteID 1.3.6.1.4.1.3052.41.1.3
Site Identifier, up to 12 characters.
OBJECT-TYPE    
  DisplayString  

snmpManager 1.3.6.1.4.1.3052.41.1.4
This is snmp manager #1
OBJECT-TYPE    
  IpAddress  

forceTraps 1.3.6.1.4.1.3052.41.1.6
Any write non-zero forces set of traps to be send to the SNMP Manager
OBJECT-TYPE    
  INTEGER  

thisTrapText 1.3.6.1.4.1.3052.41.1.7
A text string included in all traps
OBJECT-TYPE    
  DisplayString  

alarmStatus 1.3.6.1.4.1.3052.41.1.8
A text status of all alarms
OBJECT-TYPE    
  DisplayString  

snmpManager1 1.3.6.1.4.1.3052.41.1.9
SNMP manager #1
OBJECT-TYPE    
  IpAddress  

snmpManager2 1.3.6.1.4.1.3052.41.1.10
SNMP manager #2
OBJECT-TYPE    
  IpAddress  

snmpManager3 1.3.6.1.4.1.3052.41.1.11
SNMP manager #3
OBJECT-TYPE    
  IpAddress  

snmpManager4 1.3.6.1.4.1.3052.41.1.12
SNMP manager #4
OBJECT-TYPE    
  IpAddress  

statusRepeatHours 1.3.6.1.4.1.3052.41.1.13
0=none, 1-24 Number of Hours between Status Traps being Sent
OBJECT-TYPE    
  INTEGER  

serialTimeout 1.3.6.1.4.1.3052.41.1.14
5-30, Minutes of non-activity timeout on serial setup
OBJECT-TYPE    
  INTEGER  

powerupTrapsend 1.3.6.1.4.1.3052.41.1.15
0-no, 1-yes, send traps for all sensors on powerup
OBJECT-TYPE    
  INTEGER  

netlossTrapsend 1.3.6.1.4.1.3052.41.1.16
0-no, 1-yes, send traps for detected netloss and back up
OBJECT-TYPE    
  INTEGER  

buildID 1.3.6.1.4.1.3052.41.1.17
5-chars max text for build identifier
OBJECT-TYPE    
  DisplayString  

contacts 1.3.6.1.4.1.3052.41.2
OBJECT IDENTIFIER    

contact1 1.3.6.1.4.1.3052.41.2.1
OBJECT IDENTIFIER    

contact1Name 1.3.6.1.4.1.3052.41.2.1.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact1State 1.3.6.1.4.1.3052.41.2.1.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact1AlarmEnable 1.3.6.1.4.1.3052.41.2.1.3
0-alarms disabled 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact1ActiveDirection 1.3.6.1.4.1.3052.41.2.1.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact1Threshold 1.3.6.1.4.1.3052.41.2.1.5
Number of seconds that the contact must remain in a state before generating a trap, range 0-255
OBJECT-TYPE    
  INTEGER  

contact1ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.1.6
0-return to normal traps not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact1TrapRepeat 1.3.6.1.4.1.3052.41.2.1.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps.
OBJECT-TYPE    
  INTEGER  

contact1Severity 1.3.6.1.4.1.3052.41.2.1.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

contact2 1.3.6.1.4.1.3052.41.2.2
OBJECT IDENTIFIER    

contact2Name 1.3.6.1.4.1.3052.41.2.2.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact2State 1.3.6.1.4.1.3052.41.2.2.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact2AlarmEnable 1.3.6.1.4.1.3052.41.2.2.3
0-no alarms 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact2ActiveDirection 1.3.6.1.4.1.3052.41.2.2.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact2Threshold 1.3.6.1.4.1.3052.41.2.2.5
Number of seconds must be in a state to be 'open' or 'closed'
OBJECT-TYPE    
  INTEGER  

contact2ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.2.6
0-not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact2TrapRepeat 1.3.6.1.4.1.3052.41.2.2.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps
OBJECT-TYPE    
  INTEGER  

contact2Severity 1.3.6.1.4.1.3052.41.2.2.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

contact3 1.3.6.1.4.1.3052.41.2.3
OBJECT IDENTIFIER    

contact3Name 1.3.6.1.4.1.3052.41.2.3.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact3State 1.3.6.1.4.1.3052.41.2.3.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact3AlarmEnable 1.3.6.1.4.1.3052.41.2.3.3
0-no alarms 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact3ActiveDirection 1.3.6.1.4.1.3052.41.2.3.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact3Threshold 1.3.6.1.4.1.3052.41.2.3.5
Number of seconds must be in a state to be 'open' or 'closed'
OBJECT-TYPE    
  INTEGER  

contact3ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.3.6
0-not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact3TrapRepeat 1.3.6.1.4.1.3052.41.2.3.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps
OBJECT-TYPE    
  INTEGER  

contact3Severity 1.3.6.1.4.1.3052.41.2.3.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

contact4 1.3.6.1.4.1.3052.41.2.4
OBJECT IDENTIFIER    

contact4Name 1.3.6.1.4.1.3052.41.2.4.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact4State 1.3.6.1.4.1.3052.41.2.4.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact4AlarmEnable 1.3.6.1.4.1.3052.41.2.4.3
0-no alarms 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact4ActiveDirection 1.3.6.1.4.1.3052.41.2.4.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact4Threshold 1.3.6.1.4.1.3052.41.2.4.5
Number of seconds must be in a state to be 'open' or 'closed'
OBJECT-TYPE    
  INTEGER  

contact4ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.4.6
0-not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact4TrapRepeat 1.3.6.1.4.1.3052.41.2.4.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps
OBJECT-TYPE    
  INTEGER  

contact4Severity 1.3.6.1.4.1.3052.41.2.4.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

contact5 1.3.6.1.4.1.3052.41.2.5
OBJECT IDENTIFIER    

contact5Name 1.3.6.1.4.1.3052.41.2.5.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact5State 1.3.6.1.4.1.3052.41.2.5.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact5AlarmEnable 1.3.6.1.4.1.3052.41.2.5.3
0-no alarms 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact5ActiveDirection 1.3.6.1.4.1.3052.41.2.5.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact5Threshold 1.3.6.1.4.1.3052.41.2.5.5
Number of seconds must be in a state to be 'open' or 'closed'
OBJECT-TYPE    
  INTEGER  

contact5ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.5.6
0-not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact5TrapRepeat 1.3.6.1.4.1.3052.41.2.5.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps
OBJECT-TYPE    
  INTEGER  

contact5Severity 1.3.6.1.4.1.3052.41.2.5.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

contact6 1.3.6.1.4.1.3052.41.2.6
OBJECT IDENTIFIER    

contact6Name 1.3.6.1.4.1.3052.41.2.6.1
Name for contact, up to 30 characters
OBJECT-TYPE    
  DisplayString  

contact6State 1.3.6.1.4.1.3052.41.2.6.2
Current State of Contact, 0-open 1-closed
OBJECT-TYPE    
  INTEGER  

contact6AlarmEnable 1.3.6.1.4.1.3052.41.2.6.3
0-no alarms 1-alarms enabled
OBJECT-TYPE    
  INTEGER  

contact6ActiveDirection 1.3.6.1.4.1.3052.41.2.6.4
0-alarm on open 1-alarm on closed
OBJECT-TYPE    
  INTEGER  

contact6Threshold 1.3.6.1.4.1.3052.41.2.6.5
Number of seconds must be in a state to be 'open' or 'closed'
OBJECT-TYPE    
  INTEGER  

contact6ReturnNormalTrap 1.3.6.1.4.1.3052.41.2.6.6
0-not sent, 1-sent
OBJECT-TYPE    
  INTEGER  

contact6TrapRepeat 1.3.6.1.4.1.3052.41.2.6.7
0-no repeats. 1-255 number of minutes between repeats of alarm traps.
OBJECT-TYPE    
  INTEGER  

contact6Severity 1.3.6.1.4.1.3052.41.2.6.8
1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

relays 1.3.6.1.4.1.3052.41.3
OBJECT IDENTIFIER    

relay1 1.3.6.1.4.1.3052.41.3.1
OBJECT IDENTIFIER    

relay1Name 1.3.6.1.4.1.3052.41.3.1.1
Name for relay, up to 30 characters
OBJECT-TYPE    
  DisplayString  

relay1CurrentState 1.3.6.1.4.1.3052.41.3.1.2
0-opened, 1-closed
OBJECT-TYPE    
  INTEGER  

relay1PowerupState 1.3.6.1.4.1.3052.41.3.1.3
0-opened, 1-closed
OBJECT-TYPE    
  INTEGER  

relay2 1.3.6.1.4.1.3052.41.3.2
OBJECT IDENTIFIER    

relay2Name 1.3.6.1.4.1.3052.41.3.2.1
Name for relay, up to 30 characters
OBJECT-TYPE    
  DisplayString  

relay2CurrentState 1.3.6.1.4.1.3052.41.3.2.2
0-opened, 1-closed
OBJECT-TYPE    
  INTEGER  

relay2PowerupState 1.3.6.1.4.1.3052.41.3.2.3
0-opened, 1-closed
OBJECT-TYPE    
  INTEGER  

tempsensor 1.3.6.1.4.1.3052.41.4
OBJECT IDENTIFIER    

tempValue 1.3.6.1.4.1.3052.41.4.1
Current Temperature Value, in C or F based on 1.3.6.1.4.1.3052.41.4.10
OBJECT-TYPE    
  INTEGER  

tempAlarmEnable 1.3.6.1.4.1.3052.41.4.2
0=alarms disabled, 1=alarms enabled
OBJECT-TYPE    
  INTEGER  

tempHighLevel 1.3.6.1.4.1.3052.41.4.3
Level at which the High alarm goes active
OBJECT-TYPE    
  INTEGER  

tempVeryHighLevel 1.3.6.1.4.1.3052.41.4.4
Level at which the Very High alarm goes active
OBJECT-TYPE    
  INTEGER  

tempLowLevel 1.3.6.1.4.1.3052.41.4.5
Level at which the Low alarm goes active
OBJECT-TYPE    
  INTEGER  

tempVeryLowLevel 1.3.6.1.4.1.3052.41.4.6
Level at which the Very Low alarm goes active
OBJECT-TYPE    
  INTEGER  

tempAlarmThreshold 1.3.6.1.4.1.3052.41.4.7
Seconds must be in a range to be an alarm
OBJECT-TYPE    
  INTEGER  

tempReturnNormalTrap 1.3.6.1.4.1.3052.41.4.8
0-not sent, 1-send trap on return to normal range
OBJECT-TYPE    
  INTEGER  

tempTrapRepeat 1.3.6.1.4.1.3052.41.4.9
0-no repeats. 1-255 number of minutes between repeats of alarm traps.
OBJECT-TYPE    
  INTEGER  

tempMode 1.3.6.1.4.1.3052.41.4.10
0=all temp readings and levels in degrees F, 1=in degrees C
OBJECT-TYPE    
  INTEGER  

tempHighSeverity 1.3.6.1.4.1.3052.41.4.11
High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

tempVeryHighSeverity 1.3.6.1.4.1.3052.41.4.12
Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

tempLowSeverity 1.3.6.1.4.1.3052.41.4.13
Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

tempVeryLowSeverity 1.3.6.1.4.1.3052.41.4.14
Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

tempName 1.3.6.1.4.1.3052.41.4.15
Name for temperature sensor, up to 30 characters
OBJECT-TYPE    
  DisplayString  

humiditysensor 1.3.6.1.4.1.3052.41.5
OBJECT IDENTIFIER    

humidityValue 1.3.6.1.4.1.3052.41.5.1
Current Relative Humidity Value (0-100%)
OBJECT-TYPE    
  INTEGER  

humidityAlarmEnable 1.3.6.1.4.1.3052.41.5.2
0=alarms disabled, 1=alarms enabled
OBJECT-TYPE    
  INTEGER  

humidityHighLevel 1.3.6.1.4.1.3052.41.5.3
Level at which the High alarm goes active
OBJECT-TYPE    
  INTEGER  

humidityVeryHighLevel 1.3.6.1.4.1.3052.41.5.4
Level at which the Very High alarm goes active
OBJECT-TYPE    
  INTEGER  

humidityLowLevel 1.3.6.1.4.1.3052.41.5.5
Level at which the Low alarm goes active
OBJECT-TYPE    
  INTEGER  

humidityVeryLowLevel 1.3.6.1.4.1.3052.41.5.6
Level at which the Very Low alarm goes active
OBJECT-TYPE    
  INTEGER  

humidityAlarmThreshold 1.3.6.1.4.1.3052.41.5.7
Seconds must be in a range to be an alarm
OBJECT-TYPE    
  INTEGER  

humidityReturnNormalTrap 1.3.6.1.4.1.3052.41.5.8
0-not sent, 1-send trap on return to normal range
OBJECT-TYPE    
  INTEGER  

humidityTrapRepeat 1.3.6.1.4.1.3052.41.5.9
0-no repeats. 1-255 number of minutes between repeats of alarm traps.
OBJECT-TYPE    
  INTEGER  

humidityHighSeverity 1.3.6.1.4.1.3052.41.5.10
High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

humidityVeryHighSeverity 1.3.6.1.4.1.3052.41.5.11
Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

humidityLowSeverity 1.3.6.1.4.1.3052.41.5.12
Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

humidityVeryLowSeverity 1.3.6.1.4.1.3052.41.5.13
Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

humidityName 1.3.6.1.4.1.3052.41.5.14
Name for humidity sensor, up to 30 characters
OBJECT-TYPE    
  DisplayString  

passthrough 1.3.6.1.4.1.3052.41.6
OBJECT IDENTIFIER    

ptNeedPassword 1.3.6.1.4.1.3052.41.6.1
0-no 1-yes, is password required for passthrough connection.
OBJECT-TYPE    
  INTEGER  

ptSayLoginText 1.3.6.1.4.1.3052.41.6.2
0-no 1-yes, is passthrough login text displayed on connection.
OBJECT-TYPE    
  INTEGER  

ptLoginText 1.3.6.1.4.1.3052.41.6.3
0-24 char string which may be displayed on socket connection. Requires that ptSayLoginText be enabled to display this string.
OBJECT-TYPE    
  DisplayString  

ptSaySiteID 1.3.6.1.4.1.3052.41.6.4
0-no 1-yes, is SiteID displayed on pass through connection.
OBJECT-TYPE    
  INTEGER  

ptUsername 1.3.6.1.4.1.3052.41.6.5
0-16 char string for Username used in serial passthrough connections
OBJECT-TYPE    
  DisplayString  

ptPassword 1.3.6.1.4.1.3052.41.6.6
0-16 char string for Password used in serial passthrough connections
OBJECT-TYPE    
  DisplayString  

ptTimeout 1.3.6.1.4.1.3052.41.6.7
number of minutes (1-255) of idle activity (both directions) which causes disconnect. 0-never
OBJECT-TYPE    
  INTEGER  

ptEscChar 1.3.6.1.4.1.3052.41.6.8
ASCII character code (e.g, Escape=27) which if entered on the tcp port three times in a row causes disconnect. 0-none
OBJECT-TYPE    
  INTEGER  

ptLfstripToPort 1.3.6.1.4.1.3052.41.6.9
0-no 1-yes linefeed characters received on TCP connection are removed from stream to serial port
OBJECT-TYPE    
  INTEGER  

ptLfstripFromPort 1.3.6.1.4.1.3052.41.6.10
0-no 1-yes linefeed characters received on serial port are removed from stream to TCP connection
OBJECT-TYPE    
  INTEGER  

ptSerialBaudrate 1.3.6.1.4.1.3052.41.6.11
300 600 1200 2400 4800 9600 19200 baud are allowed values
OBJECT-TYPE    
  INTEGER  

ptSerialWordlength 1.3.6.1.4.1.3052.41.6.12
7 or 8 bit word selection
OBJECT-TYPE    
  INTEGER  

ptSerialParity 1.3.6.1.4.1.3052.41.6.13
N E O are allowed values for parity (none, even, odd) [a single-character string]
OBJECT-TYPE    
  DisplayString  

ptTCPPortnumber 1.3.6.1.4.1.3052.41.6.14
IP port number for passthrough connection (range 1024-65534)
OBJECT-TYPE    
  INTEGER  

ftp 1.3.6.1.4.1.3052.41.7
OBJECT IDENTIFIER    

ftpUsername 1.3.6.1.4.1.3052.41.7.1
0-16 char string for Username used in ftp server for updates
OBJECT-TYPE    
  DisplayString  

ftpPassword 1.3.6.1.4.1.3052.41.7.2
0-16 char string for Password used in ftp server for updates
OBJECT-TYPE    
  DisplayString  

analog 1.3.6.1.4.1.3052.41.8
OBJECT IDENTIFIER    

analog1 1.3.6.1.4.1.3052.41.8.1
OBJECT IDENTIFIER    

analog1Value 1.3.6.1.4.1.3052.41.8.1.1
Value of current analog reading, in 1/100 volt, +- 9999 range
OBJECT-TYPE    
  INTEGER  

analog1AlarmEnable 1.3.6.1.4.1.3052.41.8.1.2
0=no alarms, 1=send alarms
OBJECT-TYPE    
  INTEGER  

analog1HighLevel 1.3.6.1.4.1.3052.41.8.1.3
Level at which the High alarm goes active
OBJECT-TYPE    
  INTEGER  

analog1VeryHighLevel 1.3.6.1.4.1.3052.41.8.1.4
Level at which the Very High alarm goes active
OBJECT-TYPE    
  INTEGER  

analog1LowLevel 1.3.6.1.4.1.3052.41.8.1.5
Level at which the Low alarm goes active
OBJECT-TYPE    
  INTEGER  

analog1VeryLowLevel 1.3.6.1.4.1.3052.41.8.1.6
Level at which the Very Low alarm goes active
OBJECT-TYPE    
  INTEGER  

analog1AlarmThreshold 1.3.6.1.4.1.3052.41.8.1.7
Seconds must be in a range to be an alarm
OBJECT-TYPE    
  INTEGER  

analog1ReturnNormalTrap 1.3.6.1.4.1.3052.41.8.1.8
0-not sent, 1-send trap on return to normal range
OBJECT-TYPE    
  INTEGER  

analog1TrapRepeat 1.3.6.1.4.1.3052.41.8.1.9
0-no repeats else number of minutes between repeats of trap
OBJECT-TYPE    
  INTEGER  

analog1HighSeverity 1.3.6.1.4.1.3052.41.8.1.10
High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog1VeryHighSeverity 1.3.6.1.4.1.3052.41.8.1.11
Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog1LowSeverity 1.3.6.1.4.1.3052.41.8.1.12
Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog1VeryLowSeverity 1.3.6.1.4.1.3052.41.8.1.13
Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog1Name 1.3.6.1.4.1.3052.41.8.1.14
Name for analog sensor 1, up to 30 characters
OBJECT-TYPE    
  DisplayString  

analog2 1.3.6.1.4.1.3052.41.8.2
OBJECT IDENTIFIER    

analog2Value 1.3.6.1.4.1.3052.41.8.2.1
Value of current analog reading, in 1/100 volt, +- 9999 range
OBJECT-TYPE    
  INTEGER  

analog2AlarmEnable 1.3.6.1.4.1.3052.41.8.2.2
0=no alarms, 1=send alarms
OBJECT-TYPE    
  INTEGER  

analog2HighLevel 1.3.6.1.4.1.3052.41.8.2.3
Level at which the High alarm goes active
OBJECT-TYPE    
  INTEGER  

analog2VeryHighLevel 1.3.6.1.4.1.3052.41.8.2.4
Level at which the Very High alarm goes active
OBJECT-TYPE    
  INTEGER  

analog2LowLevel 1.3.6.1.4.1.3052.41.8.2.5
Level at which the Low alarm goes active
OBJECT-TYPE    
  INTEGER  

analog2VeryLowLevel 1.3.6.1.4.1.3052.41.8.2.6
Level at which the Very Low alarm goes active
OBJECT-TYPE    
  INTEGER  

analog2AlarmThreshold 1.3.6.1.4.1.3052.41.8.2.7
Seconds must be in a range to be an alarm
OBJECT-TYPE    
  INTEGER  

analog2ReturnNormalTrap 1.3.6.1.4.1.3052.41.8.2.8
0-not sent, 1-send trap on return to normal range
OBJECT-TYPE    
  INTEGER  

analog2TrapRepeat 1.3.6.1.4.1.3052.41.8.2.9
0-no repeats else number of minutes between repeats of trap
OBJECT-TYPE    
  INTEGER  

analog2HighSeverity 1.3.6.1.4.1.3052.41.8.2.10
High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog2VeryHighSeverity 1.3.6.1.4.1.3052.41.8.2.11
Very High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog2LowSeverity 1.3.6.1.4.1.3052.41.8.2.12
Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog2VeryLowSeverity 1.3.6.1.4.1.3052.41.8.2.13
Very Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
OBJECT-TYPE    
  INTEGER  

analog2Name 1.3.6.1.4.1.3052.41.8.2.14
Name for analog sensor 2, up to 30 characters
OBJECT-TYPE    
  DisplayString  

eventSensorStatus 1.3.6.1.4.1.3052.41.10
OBJECT IDENTIFIER    

esPointTable 1.3.6.1.4.1.3052.41.10.1
This table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, relay 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point).
OBJECT-TYPE    
  SEQUENCE OF  
    ESPoint

esPointEntry 1.3.6.1.4.1.3052.41.10.1.1
Entry for EventSensor point table
OBJECT-TYPE    
  ESPoint  

esIndexES 1.3.6.1.4.1.3052.41.10.1.1.1
The part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 4, which refer to attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor.
OBJECT-TYPE    
  INTEGER  

esIndexPC 1.3.6.1.4.1.3052.41.10.1.1.2
The part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=relay
OBJECT-TYPE    
  INTEGER  

esIndexPoint 1.3.6.1.4.1.3052.41.10.1.1.3
The part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or relay) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3.
OBJECT-TYPE    
  INTEGER  

esPointName 1.3.6.1.4.1.3052.41.10.1.1.4
The name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as ''. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as ''. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name.
OBJECT-TYPE    
  DisplayString  

esPointInEventState 1.3.6.1.4.1.3052.41.10.1.1.5
A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures and relays the values of this object are: 1=point in event state 2=point in normal state For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its open state. Setting it to 2 puts the relay into its closed state.
OBJECT-TYPE    
  INTEGER  

esPointValueInt 1.3.6.1.4.1.3052.41.10.1.1.6
A number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. For any point class except relay, this object is read-only. For relays, setting this object to 1 closes the relay, while setting it to 0 opens it. This works regardless of the control mode of the relay.
OBJECT-TYPE    
  INTEGER -32768..32767  

esPointValueStr 1.3.6.1.4.1.3052.41.10.1.1.7
A string referring to the value of a point on an EventSensor. For contact closures and relays this object is either 'Open' or 'Closed'. For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in volts.
OBJECT-TYPE    
  DisplayString  

eventSensorConfig 1.3.6.1.4.1.3052.41.11
OBJECT IDENTIFIER    

esNumberEventSensors 1.3.6.1.4.1.3052.41.11.1
The number of EventSensors recognized by the s412 Range: 0-4
OBJECT-TYPE    
  INTEGER  

esTable 1.3.6.1.4.1.3052.41.11.2
The table of what EventSensors are attached to the unit
OBJECT-TYPE    
  SEQUENCE OF  
    ESExist

esEntry 1.3.6.1.4.1.3052.41.11.2.1
Table entry for EventSensor table
OBJECT-TYPE    
  ESExist  

esIndex 1.3.6.1.4.1.3052.41.11.2.1.1
This number refers to an EventSensor; it has the same meaning as the esIndexES object (see above), except that this object is used only within the esTable branch. This object's allowable values are 1 through 4, which refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time.
OBJECT-TYPE    
  INTEGER  

esID 1.3.6.1.4.1.3052.41.11.2.1.2
The factory-assigned ID of the EventSensor
OBJECT-TYPE    
  DisplayString  

esNumberTempSensors 1.3.6.1.4.1.3052.41.11.2.1.3
The number of temperature sensors on the EventSensor
OBJECT-TYPE    
  INTEGER  

esTempReportingMode 1.3.6.1.4.1.3052.41.11.2.1.4
Description of how temperature values should be interpreted.
OBJECT-TYPE    
  DisplayString  

esNumberCCs 1.3.6.1.4.1.3052.41.11.2.1.5
The number of contact closures on the EventSensor.
OBJECT-TYPE    
  INTEGER  

esCCReportingMode 1.3.6.1.4.1.3052.41.11.2.1.6
Description of how CC values should be interpreted.
OBJECT-TYPE    
  DisplayString  

esNumberHumidSensors 1.3.6.1.4.1.3052.41.11.2.1.7
The number of humidity sensors on the EventSensor.
OBJECT-TYPE    
  INTEGER  

esHumidReportingMode 1.3.6.1.4.1.3052.41.11.2.1.8
Description of how humidity sensor values should be interpreted.
OBJECT-TYPE    
  DisplayString  

esNumberAnalog 1.3.6.1.4.1.3052.41.11.2.1.13
The number of analog inputs on the EventSensor.
OBJECT-TYPE    
  INTEGER  

esAnalogReportingMode 1.3.6.1.4.1.3052.41.11.2.1.14
Description of how analog input values should be interpreted.
OBJECT-TYPE    
  DisplayString  

esNumberRelayOutputs 1.3.6.1.4.1.3052.41.11.2.1.15
The number of relay outputs on the EventSensor
OBJECT-TYPE    
  INTEGER  

esRelayReportingMode 1.3.6.1.4.1.3052.41.11.2.1.16
Description of how relay output values should be interpreted.
OBJECT-TYPE    
  DisplayString  

techsupport 1.3.6.1.4.1.3052.41.99
OBJECT IDENTIFIER    

techsupportIPAddress 1.3.6.1.4.1.3052.41.99.1
May read or Set IP Address, takes effect on restart
OBJECT-TYPE    
  IpAddress  

techsupportNetMask 1.3.6.1.4.1.3052.41.99.2
May read or Set NetMask, takes effect on restart
OBJECT-TYPE    
  IpAddress  

techsupportRouter 1.3.6.1.4.1.3052.41.99.3
May read or Set Router IP Address, takes effect on restart
OBJECT-TYPE    
  IpAddress  

techsupportRestart 1.3.6.1.4.1.3052.41.99.4
Reads as 0, any Write resets unit so new IP, Netmask, Router may be used
OBJECT-TYPE    
  INTEGER  

techsupportVersionNumber 1.3.6.1.4.1.3052.41.99.5
Version Number of Firmware
OBJECT-TYPE    
  DisplayString  

mibend 1.3.6.1.4.1.3052.41.100
OBJECT IDENTIFIER    

mibendObject 1.3.6.1.4.1.3052.41.100.1
An object after all active mib items, to help some managers compile
OBJECT-TYPE    
  INTEGER  

contact1ActiveTrap 1.3.6.1.4.1.3052.41.20001
Sent to show Contact 1 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact1Name  
  contact1State  

contact2ActiveTrap 1.3.6.1.4.1.3052.41.20002
Sent to show Contact 2 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact2Name  
  contact2State  

contact3ActiveTrap 1.3.6.1.4.1.3052.41.20003
Sent to show Contact 3 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact3Name  
  contact3State  

contact4ActiveTrap 1.3.6.1.4.1.3052.41.20004
Sent to show Contact 4 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact4Name  
  contact4State  

contact5ActiveTrap 1.3.6.1.4.1.3052.41.20005
Sent to show Contact 5 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact5Name  
  contact5State  

contact6ActiveTrap 1.3.6.1.4.1.3052.41.20006
Sent to show Contact 6 is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact6Name  
  contact6State  

tempHighTrap 1.3.6.1.4.1.3052.41.20010
Sent to show Temp exceeded High Temp Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  tempValue  

tempVeryHighTrap 1.3.6.1.4.1.3052.41.20011
Sent to show Temp exceeded Very High Temp Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  tempValue  

tempLowTrap 1.3.6.1.4.1.3052.41.20012
Sent to show Temp went below Low Temp Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  tempValue  

tempVeryLowTrap 1.3.6.1.4.1.3052.41.20013
Sent to show Temp went below Very Low Temp Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  tempValue  

humidityHighTrap 1.3.6.1.4.1.3052.41.20020
Sent to show humidity exceeded High humidity Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  humidityValue  

humidityVeryHighTrap 1.3.6.1.4.1.3052.41.20021
Sent to show humidity exceeded Very High humidity Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  humidityValue  

humidityLowTrap 1.3.6.1.4.1.3052.41.20022
Sent to show humidity went below Low humidity Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  humidityValue  

humidityVeryLowTrap 1.3.6.1.4.1.3052.41.20023
Sent to show humidity went below Very Low humidity Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  humidityValue  

analog1HighTrap 1.3.6.1.4.1.3052.41.20030
Sent to show analog1 exceeded High analog1 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog1Name  
  analog1Value  

analog1VeryHighTrap 1.3.6.1.4.1.3052.41.20031
Sent to show analog1 exceeded Very High analog1 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog1Name  
  analog1Value  

analog1LowTrap 1.3.6.1.4.1.3052.41.20032
Sent to show analog1 went below Low analog1 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog1Name  
  analog1Value  

analog1VeryLowTrap 1.3.6.1.4.1.3052.41.20033
Sent to show analog1 went below Very Low analog1 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog1Name  
  analog1Value  

analog2HighTrap 1.3.6.1.4.1.3052.41.20040
Sent to show analog2 exceeded High analog2 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog2Name  
  analog2Value  

analog2VeryHighTrap 1.3.6.1.4.1.3052.41.20041
Sent to show analog2 exceeded Very High analog2 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog2Name  
  analog2Value  

analog2LowTrap 1.3.6.1.4.1.3052.41.20042
Sent to show analog2 went below Low analog2 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog2Name  
  analog2Value  

analog2VeryLowTrap 1.3.6.1.4.1.3052.41.20043
Sent to show analog2 went below Very Low analog2 Threshold
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog2Name  
  analog2Value  

contactESActiveTrap 1.3.6.1.4.1.3052.41.20101
Sent to show EventSensor contact is in the alarm state
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

tempESHighTrap 1.3.6.1.4.1.3052.41.20110
Sent to show Temp exceeded High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

tempESVeryHighTrap 1.3.6.1.4.1.3052.41.20111
Sent to show Temp exceeded Very High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

tempESLowTrap 1.3.6.1.4.1.3052.41.20112
Sent to show Temp went below Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

tempESVeryLowTrap 1.3.6.1.4.1.3052.41.20113
Sent to show Temp went below Very Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

humidityESHighTrap 1.3.6.1.4.1.3052.41.20120
Sent to show humidity exceeded High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

humidityESVeryHighTrap 1.3.6.1.4.1.3052.41.20121
Sent to show humidity exceeded Very High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

humidityESLowTrap 1.3.6.1.4.1.3052.41.20122
Sent to show humidity went below Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

humidityESVeryLowTrap 1.3.6.1.4.1.3052.41.20123
Sent to show humidity went below Very Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

voltageESHighTrap 1.3.6.1.4.1.3052.41.20130
Sent to show voltage exceeded High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

voltageESVeryHighTrap 1.3.6.1.4.1.3052.41.20131
Sent to show voltage exceeded Very High Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

voltageESLowTrap 1.3.6.1.4.1.3052.41.20132
Sent to show voltage went below Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

voltageESVeryLowTrap 1.3.6.1.4.1.3052.41.20133
Sent to show voltage went below Very Low Threshold on an EventSensor
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

contact1NormalTrap 1.3.6.1.4.1.3052.41.21001
Sent to show Contact 1 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact1Name  
  contact1State  

contact2NormalTrap 1.3.6.1.4.1.3052.41.21002
Sent to show Contact 2 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact2Name  
  contact2State  

contact3NormalTrap 1.3.6.1.4.1.3052.41.21003
Sent to show Contact 3 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact3Name  
  contact3State  

contact4NormalTrap 1.3.6.1.4.1.3052.41.21004
Sent to show Contact 4 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact4Name  
  contact4State  

contact5NormalTrap 1.3.6.1.4.1.3052.41.21005
Sent to show Contact 5 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact5Name  
  contact5State  

contact6NormalTrap 1.3.6.1.4.1.3052.41.21006
Sent to show Contact 6 is in the normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  contact6Name  
  contact6State  

tempNormalTrap 1.3.6.1.4.1.3052.41.21010
Sent to show Temp went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  tempValue  

humidityNormalTrap 1.3.6.1.4.1.3052.41.21020
Sent to show Humidity went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  humidityValue  

analog1NormalTrap 1.3.6.1.4.1.3052.41.21030
Sent to show analog1 went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog1Name  
  analog1Value  

analog2NormalTrap 1.3.6.1.4.1.3052.41.21040
Sent to show analog2 went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  analog2Name  
  analog2Value  

contactESNormalTrap 1.3.6.1.4.1.3052.41.21101
Send to show EventSensor contact has returned to normal state
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

tempESNormalTrap 1.3.6.1.4.1.3052.41.21110
Sent to show EventSensor Temp went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

humidityESNormalTrap 1.3.6.1.4.1.3052.41.21120
Sent to show EventSensor Humidity went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

voltageESNormalTrap 1.3.6.1.4.1.3052.41.21130
Sent to show EventSensor voltage went back to Normal range
TRAP-TYPE    
  thisTrapText  
  siteID  
  esPointName  
  esPointValueInt  
  esIndexES  
  esIndexPoint  

testTrap 1.3.6.1.4.1.3052.41.22000
Sent for testing the SNMP interface
TRAP-TYPE    
  thisTrapText  
  siteID  

Defined Objects

ESPoint  
SEQUENCE    
  INTEGER as esIndexES  
  INTEGER as esIndexPC  
  INTEGER as esIndexPoint  
  DisplayString as esPointName  
  INTEGER as esPointInEventState  
  INTEGER as esPointValueInt  
  DisplayString as esPointValueStr  

ESExist  
SEQUENCE    
  INTEGER as esIndex  
  DisplayString as esID  
  INTEGER as esNumberTempSensors  
  DisplayString as esTempReportingMode  
  INTEGER as esNumberCCs  
  DisplayString as esCCReportingMode  
  INTEGER as esNumberHumidSensors  
  DisplayString as esHumidReportingMode  
  INTEGER as esNumberAnalog  
  DisplayString as esAnalogReportingMode  
  INTEGER as esNumberRelayOutputs  
  DisplayString as esRelayReportingMode